VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-RA1212P For main and standby power supplies.
Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm)
Terminal type: Faston 187 or Faston 250
0.534±0.3
(13.5±0.75)
5.945
-
-
+
1.5
0.5
0.059
0.020
151
-
-
+
0.059
0.020
(98 )
0.394
+ 0.039
0.059 0.020
Specifications
Nominal Voltage
Rated Capacity (20 hour rate)
Length
Dimensions
Width
Height
Total Height*
Approx. mass
UL94HB Faston 187
Standard Terminals and Resin
UL94HB Faston 250
* The total height with #250 teminal is 101.5mm.
Characteristics
Photo/Label for reference only.
12V
12Ah
5.945 inches (151.0 mm)
3.860 inches (98.0 mm)
3.702 inches (94.0 mm)
3.937 inches (100.0 mm)
8.36 lbs. (3.8 kg)
LC-RA1212P
LC-RA1212P1
Capacity
(note)
77˚F (25˚C)
Internal Resistance
Temperature dependency of capacity
(20 hour rate)
Self discharge
77˚F (25˚C)
20 hour rate (600mA)
10 hour rate (1130mA)
5 hour rate (2080mA)
1 hour rate (8100mA)
1.5 hour rate discharge
Cut-off voltage 10.5 V
Fully charged battery
77˚F (25˚C)
104˚F (40˚C)
77˚F (25˚C)
32˚F (0˚C)
5˚F (-15˚C)
Residual capacity after standing 3 months
Residual capacity after standing 6 months
Residual capacity after standing 12 months
12Ah
11.3Ah
10.4Ah
8.1Ah
5.8A
Approx. 30m
102%
100%
85%
65%
91%
82%
64%
Ω
Charge
Method
(Constant
Voltage)
Cycle use
(Repeating use)
Trickle use
Initial current
Control voltage
Initial current
Control voltage
4.8 A or smaller
14.5V to 14.9V
(per 12V cell 25˚C)
1.8 A or smaller
13.6V to 13.8V
(per 12V cell 25˚C)
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
Battery case resin: Standard (UL94HB) Color is black.
Discharge characteristics 77°F (25°C) (Note)
14.4
13.8
13.2
12.6
12.0
11.4
10.8
10.2
9.6
9.0
8.4
7.8
24A
12A
6A
3A
1.2A 0.6A
0 1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 40
(Minute) (Hour)
Duration of discharge
Duration of discharge vs. Discharge current (Note)
30
20
15
10
104˚F (40˚C)
1
50
40
30
5
4
3
2
1.5
20
32˚F (0˚C)
5˚F (-15˚C)
77˚F (25˚C)
10
5
3
300 500 1 3 5 10 30 50 100
(mA) (A)
Discharge current
VRLA BATTERIES AUGUST 2005