TOSHIBA BMS-IFDD01E Digital Input/Output Relay Interface Installation Manual
Below you will find brief information for Digital Input/Output Relay Interface BMS-IFDD01E. This device is used to control air conditioners by interlocking them with electric lock signals and fire alarm signals, and to transmit air conditioner failures to other devices. It is designed to connect non-voltage contact signals, transmit their input status to the Intelligent Server, and output signals from the contacts (open collector) according to the command from the Intelligent Server. The interface has 8 digital input points and 4 digital output points and can be used to control up to 4 air conditioners.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
INSTALLATION MANUAL
DIGITAL INPUT/OUTPUT
RELAY INTERFACE
BMS-IFDD01E
• Thank you very much for purchasing this TOSHIBA Digital Input/Output Relay Interface.
• Please read this manual carefully beforehand for proper installation of the relay interface.
CONTENTS
Precautions for Safety .................................................................................................................... 1
Introduction ..................................................................................................................................... 2
Before Installation .......................................................................................................................... 3
1 Installation .................................................................................................................................... 4
2 Conection of Power cables/Earth wires/Singl wires ............................................................... 5
3 Setting .......................................................................................................................................... 8
4 Trial Operation Check ................................................................................................................. 9
Precautions for Safety
• Read these “Precautions for Safety” carefully before installation.
• The precautions described below include important items regarding safety. Observe them without fail.
• After the installation work, perform a trial operation to check for any problem. Follow the Owner's
Manual to explain how to use and maintain the unit to the customer. Ask the customer to keep this
Installation Manual together with the Owner’s Manual.
WARNING
• Ask an authorized dealer or qualified installation professional to install or reinstall the relay interface.
Improper installation may result in electric shock or fire.
• Perform installation work properly according to this Installation Manual.
Improper installation may result in electric shock or fire.
• Do not modify the unit.
Any modification may cause a malfunction, resulting in overheating or fire.
CAUTION
• Perform wiring correctly in accordance with specified the current capacity.
Failure to do so may result in short-circuiting, overheating, or fire.
• Connect the specified cables for the terminals securely to prevent external forces from affecting them.
Failure to do so may result in disconnection, overheating, or fire.
1
Introduction
• Applications
The Digital Input/Output Relay Interface is used to control air conditioners by interlocking them with electric lock signals and fire alarm signals, and to transmit air conditioner failures to other devices.
•
Functions
The Digital Input/Output Relay Interface connects non-voltage contact signals, transmits their input status to the Intelligent Server, and outputs signals from the contacts (open collector) according to the command from the Intelligent Server.
• Specifications
Power supply
Power consumption
Operating temperature/ humidity
Storage temperature
Chassis material
Dimensions
Mass
220 - 240 V, AC 50/60 Hz
6.5 W
0 to 40 °C, 10 to 90% RH
-20 to +60 °C
Galvanized sheet metal 0.8t
(no coating)
66(H) x 193(W) x 246(D) mm
1.65 kg
Digital input
Digital output
Input type
Input points
Input registance
Input "ON" current
Output type
Output points
Output current
Output voltage
External power supply for
Input/Output
Photo-coupler insulation
8 points
9 k ohm
1 mA
Open collector
4 points
Max. 35 mA (per point)
Less than DC 24V
DC 12 V, 120 mA
External View
234
Grommet for power input
Grommet for
Digital Inputs
Grommet for
RS485
Grommet for
Digital Outputs
220
246
2
Before Installation
Check the following package contents.
No.
1
2
3
4
Item
DIGITAL INPUT/OUTPUT RELAY INTERFACE
Installation Manual
Screw
Pin terminal
Quantity
1
1
4
2
Remarks
M4 x 12mm tapping screws
Use the following wiring materials to connect signal lines. (Procured on site.)
No.
1
2
Signaling line
For RS-485
For digital Input/Output connection
Type
Wire size
Length
Description
2-core shield wire
1.25mm
2
, 500m max. (total length)
Type
Wire size
Length
2-core wire, 0.3mm
2
, 100m max.
3
1
Installation
Digital Input/Output Relay Interface Installation Method and Orientation
There are five installation methods for this relay interface as shown below, surface mount or wall mount.
Use the attached screws.
No good
REQUIREMENT
Do not install the unit in any of the following places.
• Humid or wet place
• Dusty place
• Place exposed to direct sunlight
• Place where there is a TV set or radio within one meter
• Place exposed to rain (outdoors, under eaves, etc.)
Installation Space and Maintenance Space
A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation.
The other sides can be adjacent to surrounding objects.
100mm
100mm
100mm
4
Connection of Power cables/Earth wires/
2
Signal wires
CAUTION
The RS-485 signal wire has polarity. Connect A to A, and B to B. If connected with incorrect polarity, the unit will not work.
REQUIREMENT
Install a breaker at the primary side of the power supply.
Power cables/Earth wires/Signal wires
Connect power cables, earth wires, and signal wires to the specified terminals on the terminal block.
Secure each cable with a cable clamp.
SW1
SW4 SW7
SW2
ON
SW3
1 2 3 4
Connect the earth wire to the earth terminal on the chassis.
Secure each cable with a cable clamp.
Power cable
Digital input contacts
Intelligent server
DO1
DO2
DO3
DO4
GND
+12V
Digital output load
Length of stripped digital
Input/Output connector wire
35 6
Length of stripped power cable
35 10
Length of stripped communication wire
35 6
55 10
Insert the wire by pushing the lever with a screwdriver. Check that the wire is inserted securely.
When inserting two RS-485 communication cables into a single terminal for connection to another interface, crimp them using the attached pin terminal.
5
Connection of Power cables/Earth wires/
2
Signal wires
(continued)
Wiring Connection
CAUTION
If an inductive load (relay coil) or a bulb is connected, a surge voltage or rush current will be generated. Take adequate measures against surge voltage or rush current.
The following describes wiring connections of the Digital Input/Output Relay Interface when it is used in the air conditioner control system.
• Terminator resistor setting
Set the RS-485 terminator resistor by the TCS-NET Relay Interface.
Do not set it by the Digital Input/Output Relay Interface.
• Shield earthing
The shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on the
Intelligent Server.
Other shield lines should be closed, and the terminal end should be open and insulated.
• Connection of external digital inputs
Input circuit examples are shown below (electrically isolated using a photo-coupler).
(1) Example of contact input connection
(2) Example of current sink connection
12V
12V
Input terminal
DI-1 to DI-8
Contact
Input terminal
DI-1 to DI-8
Current sink
• Connection of external digital outputs
Output circuit examples are shown below (open collector output electrically isolated using a photocoupler).
(1) Example of load connection
(2) Example of load connection
12V
12V
Output terminal
DO1 to DO4
Load
+12V
External power supply
GND
Output terminal
DO1 to DO4
6
Connection of Power cables/Earth wires/
2
Signal wires
(continued)
Connection diagram
Connect the shield wire of the two wires
The shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on the
Intelligent Server.
Set the Digital Input/Output Relay
Interface address with SW1. Assign
1 to 4 to each address to avoid duplication. You can set the digital
Input/Output Relay Interface address independently from the TCC-LINK
Relay Interface address or the
Energy Monitoring Relay Interface address.
CAUTION: The SW1 setting is read when the power is turned on. Push the reset switch (SW7) after changing the address.
CAUTION: Set the RS-485 terminator resistor on the TCS-NET
Relay Interface. No terminator resistor setting switch is provided on the Digital Input/Output Relay
Interface.
TCS-NET RELAY
INTERFACE
SW1
4
ADDRESS
DIGITAL I/O
INTERFACE
(BMS-IFDD01E)
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
DIGITAL I/O
INTERFACE
(BMS-IFDD01E)
SW1
1
ADDRESS
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
DO 1
DO 2
DO 3
DO 4
GND
+12V
DO 1
DO 2
DO 3
DO 4
GND
+12V
Input contact 1
Input contact 2
Input contact 3
Input contact 4
Input contact 5
Input contact 6
Input contact 7
Input contact 8
The RS-485 signal wire has polarity A and B. Be careful when connecting the wire.
Load 1
Load 2
Load 3
Load 4
Input contact 1
Input contact 2
Input contact 3
Input contact 4
Input contact 5
Input contact 6
Input contact 7
Input contact 8
Load 1
Load 2
Load 3
Load 4
7
3
Setting
SW4
SW1
SW7
SW2
ON
SW3
1 2 3 4
SW1
SW2
SW3
SW4
SW7
LED1
LED2
LED3
LED4
LED5
LED14 -
LED17
Address set switch
1 - 4
0,5 - F
Address
Not used
Operating mode set switch (0 usually)
Test switch (all OFF usually)
Test switch
Reset switch
Power indicator
RS-485 communication status indicator
Not used
Test indicator
Test indicator
Digital output indicator
LED17
LED16
LED15
LED14
DO1
DO2
DO3
DO4
GND
+12V
The following settings are necessary to use Digital Input/Output Relay Interfaces.
• SW1 Address set switch
When two or more Digital Input/Output Relay Interfaces are used, set a different address for each unit to avoid address duplication.
Assign addresses in ascending order.
CAUTION
• Set relay interface addresses according to the air conditioner address table.
• When the SW1 setting has been changed, push the reset switch SW7. The new address setting is read.
• SW2 Operation mode set switch
• SW3 Test switch
These switches are not used during normal operation. Set zero (0) or “all OFF”.
• SW4 Test switch
• SW7 Reset switch
When performing address setting with SW1, push this reset switch after address setting to read the set value.
8
4
Trial Operation Check
Before starting trial operation
Turn on the power of the Digital Input/Output Relay Interface after all cable connections and settings are completed. Turn on power of the air conditioning control system.
Trial operation
• Confirming external input connection
In the test mode, when the external inputs connected to the input terminals DI-1 to DI-8 are ON, the respective LEDs will goes on so you can confirm the connection.
Confirming procedure:
Set the operation mode switch SW2 to “3”, and push the reset switch SW7 to enter the test mode.
Unless SW4 is pushed, the respective input status of DI-1 to DI-4 is indicated by LED2 to LED5.
When SW4 is pushed, the respective input status of DI-5 to DI-8 is indicated by LED2 to LED5.
(*) To return to the normal operation, reset SW2 to “zero (0)” and push SW7.
SW4 OFF
SW4 ON
LED2
Displays DI-1 input status.
Displays DI-5 input status.
LED3
Displays DI-2 input status.
Displays DI-6 input status.
Input ON: LED lights
Input OFF: LED turns off
LED4
Displays DI-3 input status.
Displays DI-7 input status.
LED5
Displays DI-4 input status.
Displays DI-8 input status.
• Checking external output connection
In the test mode, you can set output terminals DO1 to DO4 to ON or OFF with the test switch. Their output status is indicated by each LED.
Checking procedure:
Set the operation mode switch SW2 to “3” in the same way as the external input check, and then push the reset switch SW7 to enter the test mode.
When the bit of the test switch SW3 is set to ON, the external output turns ON; when set to OFF, the external output turns OFF.
Bits 1 to 4 of SW3 correspond to output terminals DO1 to DO4.
The respective output status of output terminals DO1 to DO4 is indicated by LED14 to LED17.
The LEDs light with the output ON, and goes off with the output OFF.
(*)To return to normal operation, reset SW2 to “zero (0)” and push SW7.
LED14
Displays DO1 output status.
Output ON: LED lights
Output OFF: LED turns off
LED15
Displays DO2 output status.
LED16
Displays DO3 output status.
LED17
Displays DO4 output status.
• Checking the RS-485 communication status
Use LED2 for checking the RS-485 communication status.
When RS-485 communication with Intelligent Server is normal, LED2 will blink.
LED1
LED2
LED3
LED4
LED5
Power indicator
RS-485 communication status indicator
Not used
Test indicator
Test indicator
Normal
ON
Blinking
OFF
OFF
OFF
Abnormal
OFF
OFF
OFF
OFF
OFF
9
Memo
10
DH69409101
advertisement
Key Features
- Control air conditioners
- Interlock with electric lock signals and fire alarm signals
- Transmit air conditioner failures
- Connect non-voltage contact signals
- Transmit input status to Intelligent Server
- Output signals from contacts (open collector)
- 8 digital inputs
- 4 digital outputs