Below you will find brief information for CamCon DC92/I, CamCon DC50, CamCon DC90, CamCon DC115, CamCon DC91, CamCon DC91/IO, CamCon DC1756-DIAM.. CamCon DC92/I is an input extension module that allows for the expansion of the CamCon series electronic cam switch unit. It features 32 high active inputs and is connected via the external interface of the CamCon DC50, 90, and 115 -DICAM. By connecting multiple modules, the total number of inputs can be increased to a maximum of 200. The CamCon DC92/I module is a modular, flexible, and reliable solution for industrial automation systems and can be used in various applications, and industrial equipment, including PLC systems, process control, and machinery automation.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

CamCon DC92/I User Manual - Input Extension for CamCon Series | Manualzz
Input - extension
CamCon DC92/I
Digitronic Automationsanlagen GmbH
Steinbeisstraße 3 • D - 72636 Frickenhausen • Tel. (+49)7022/40590-0 • Fax -10
Auf der Langwies 1 • D - 65510 Hünstetten-Wallbach • Tel.(+49)6126/9453-0 • Fax -42
Internet: http://www.digitronic.com • E-Mail: [email protected]
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Input - extension
CamCon DC92/I
For your attention
This instruction manual relates to the CamCon DC92/I from 8/1997. The company Digitronic
Automationsanlagen GmbH reserves the right to make changes which present an improvement of the
quality or functionality of the device without prior notice. The instruction manual was created with great
care, although it may not be error-proof. We would be grateful for any communication relating to any
errors you may have found.
UP-date
You can also obtain this instruction manual on the Internet at http://www.digitronic.com in the latest
version as PDF file.
Qualified personnel
This device may only be started and operated by qualified staff. By qualified we mean personnel who
are entitled to handle, to earth and to lable devices, systems and power circuits in accordance with the
technology safety standards.
Liability
(1) The supplier is liable for damages caused by himself or by the owner of the rights up to the sum of
the sales price. He is not liable for loss of profits, forfeited savings, intermediate and successive
damages.
(2) The above mentioned limits to liability do not apply to insurance of named characteristics and
damages which were caused deliberately or through negligence.
Protection
The CamCon DC92/I and this instruction manual are protected by copyright. All rights are reserved.
Neither the CamCon DC92/I, nor this document may be copied as a whole or partially, photocopied,
reproduced, translated or transferred to electronic media of any kind or into machine readable format
without prior written permission by the company Digitronic Automationsanlagen GmbH.
Note:
Note:
Note:
We have examined the devices of the CamCon series for year 2000 compatibility and
have not found any adverse effects on any functions.
CamCon is a registered trademark of the company Firma Digitronic
Automationsanlagen GmbH.
The devices of the CamCon series comply with the standards for electromagnetic
compatibility: EN 55011, EN 55022, EN 55024 Part 2, EN 50082 Part 2, ENV 50140,
VDE 0843 Part 2,
VDE 0843 Part 4,
VDE 0871,
VDE 0875 Part 3 ("N"),
VDE 0875 Part 11, VDE 0877 Part 2, IEC 801 Part 3, IEC 801 Part 2, IEC 801 Part 4,
IEC 801 Part 5.
(c) Copyright 1992 - 2004 / File: DC92E.DOC
Digitronic Automationsanlagen GmbH
Auf der Langwies 1
D-65510 Hünstetten - Wallbach
Tel. (+49)6126/9453-0 Fax. (+49)6126/9453-42
Internet: http://www.digitronic.com
E-Mail: [email protected]
Version: 11.08.04
Page: 2
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Input - extension
CamCon DC92/I
Content
1. Introduction .......................................................................................................................................... 3
2. Assembling .......................................................................................................................................... 4
3. Status LED........................................................................................................................................... 4
4. Dimensions .......................................................................................................................................... 4
5. Electrical connections .......................................................................................................................... 5
5.1. Clamp allocation ............................................................................................................................... 5
5.1.1. Clamp allocation of power supply .................................................................................................. 5
5.1.2. Clamp allocation of the inputs........................................................................................................ 5
5.1.3. Pin allocation of the external interface........................................................................................... 6
5.2. The Inputs ......................................................................................................................................... 6
6. Technical data...................................................................................................................................... 7
1. Introduction
The CamCon DC92/I module is used as an input extension for the electronic cam-switch unit of the
CamCon series. Each CamCon DC92 module has got 32 inputs, it can be connected by means of the
external interface of the CamCon DC50, 90 and 115 -DICAM. By a series connection of several
CamCon DC92 modules it is possible to increase the total number of inputs at one Camcon to at
maximum 200 inputs. Thus, at a CamCon DC51 having 16 inputs another 5 CamCon DC92 modules
could be connected. With 5 CamCon DC91/IO modules, for instance, you have got additionally 160
inputs at your disposal.
Version: 11.08.04
Page: 3
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Input - extension
CamCon DC92/I
2. Assembling
The CamCon DC92 input extension module is locked on an EN carrier bar in the switch cabinet. The
earthing clamps shall be connected to the central earth connection point of the mounting panel on the
shortest possible way. All cable connections shall be established in a dead condition! Each CamCon
DC9X module shall be connected with the supply voltage which amounts to 24VDC +/-20 %. The
external interface of the CamCon DC50,90,115 and/or 1756-DIAM becomes connected via a cable of
type: KK91/IO-XX with the 9pol. D Sub pin plug "external inter. in" at the CamCon DC92 module
connected. Each further CamCon DC92 oder DC91 module is attached with a cable of the same type
to the plug "external inter out". The data line of the CamCon DC9X/IO modules are connected to
each other via optical-couplers, thus being free of potentials.
For monitoring the data exchange you should program the safety output of the CamCon at the last
CamCon DC91/IO module, because this will switch off in the case of an interruption of the cable
connection.
3. Status LED
The CamCon DC91 module has got 2 additional status LED (see chapter 4. Dimensions).
LED 1
LED 2
Indicates to supply voltage.
indicates that for the moment no data exchange via CamCon and the DC92 is aktiv. The
possible causes are: the cable length stopped at the CamCon exceeds the permissible
border of 300 meters, the CamCon is switched off, and/or data exchange is interrupted
(cable broken).
4. Dimensions
LED 1
LED 2
The following carrier rails may be used to adjust the case:
Version: 11.08.04
Page: 4
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Input - extension
CamCon DC92/I
5. Electrical connections
.
5.1. Clamp allocation
5.1.1. Clamp allocation of power supply
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
11:
12:
13:
14:
15:
16:
Earth connection/shielding
Earth connection/shielding
0V
0V
+24V DC Power supply
+24V DC Power supply
5.1.2. Clamp allocation of the inputs
Clamp
17 + 35:
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
18:
19:
20:
21:
22:
23:
24:
25:
26:
27:
28:
29:
30:
31:
32:
33:
Clamp
34 + 52:
Note:
0V of the input, connected to Clamp 13 and 14.
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
Clamp
36:
37:
38:
39:
40:
41:
42:
43:
44:
45:
46:
47:
48:
49:
50:
51:
Input 17
Input 18
Input 19
Input 20
Input 21
Input 22
Input 23
Input 24
Input 25
Input 26
Input 27
Input 28
Input 29
Input 30
Input 31
Input 32
+24V DC for power supply of external inputs connected to Clamp 15 and 16.
Clamp 15, 16, 34 and 52 are connected with each other.
Clamp 13, 14, 17 and 35 are connected with each other.
Clamp 11 and 12 are connected with each other.
Version: 11.08.04
Page: 5
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Input - extension
CamCon DC92/I
5.1.3. Pin allocation of the external interface
The CamCon DC91 module has an external interface via which the data exchange with the camswitch
is processed. Via the interfaceinput also the data exchange with the CamCon DC 50 i.e. DC 90 or
DC115 is done. The interface output is used for the data exchange with another CamCon DC91
module. By this way of switching it is possible to switch up tio 7 CamCon DC91 module to a CamCon
DC50 i.e. DC90 or DC115. A shielded 6 pole data cable with pairly wired cores is required for this
purpose. the maximum wiring distance is 300 meters. As an option, distances up to 100 meters are
possible. the data exchange is realised by optical couplers and therefore free of potentials. For the
monitoring of the data exchange you should program the safety output of the CamCon DC50, DC90 or
DC115 at the last CamCon DC91, for it will switch of if the wire is broken.
DSUB 9 male and female plug:
Pin 1,4,7
Pin 2
Pin 6
GND
TxD +
TxD -
CamCon DC50
external
Pin 8
Pin 3
CLK +
CLK -
CamCon DC92/I
external
external
Pin 5
Pin 9
RxD +
RxD CamCon DC91
external
5.2. The Inputs
The CamCon DC92 Modul has got 32 inputs. These inputs function with highly active 24 V signals and
are not free of potentials. For each input one Status LED shows the status.
The input resistance amounts to approx. 5.7 KOhm.
Input circuit:
Version: 11.08.04
Page: 6
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Input - extension
CamCon DC92/I
6. Technical data
Display ................................................................ 32 yellow LED for each input.
1 red LED for error messages.
1 yellow LED for power supply.
Number of inputs................................................. 32
Length of the connecting cable
between CamCon and CamCon DC91/IO.......... max. 300 m (optionally up to 1000 meters)
Supply voltage..................................................... 24VDC ±20 %
Current consumption........................................... approx. 100mA.
Input resistance................................................... ca. 5.7kOhm
Connections for:
Voltage supply..................................................... via plug-in screw clamps IP20
Inputs ................................................................. via plug-in screw clamps IP20
Assembly............................................................. convenient snap-on assembly; carrier bar according to
EN 50 022, may be set in rows.
Dismantling ......................................................... by pulling back the snap lock.
Dimensions ......................................................... Please, refer to chapter 4. Dimensions at page 4.
International protection........................................ The housing fulfils IP20.
Operation temperature........................................ 0°C ... + 55° C
Weight.................................................................approx. 500 g
Version: 11.08.04
Page: 7
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com

advertisement

Key Features

  • 32 high active inputs
  • Extends CamCon series input capability
  • Modular design for scalability
  • 24V DC power supply
  • External interface for connectivity
  • Data exchange via optical couplers
  • Status LEDs for monitoring

Frequently Answers and Questions

What is the maximum number of inputs that can be added using CamCon DC92/I?
With the use of multiple CamCon DC92/I modules, the total number of inputs can be increased to a maximum of 200 inputs.
How is the CamCon DC92/I connected to other CamCon modules?
It utilizes both an external interface for connecting to the CamCon DC50, 90, and 115 -DICAM modules, also connecting multiple DC92 modules for input expansion.
What is the maximum permissible wiring distance for the CamCon DC92/I?
The maximum wiring distance is 300 meters, but an optional extended distance of up to 1000 meters is available.
Does the CamCon DC92/I have any specific requirements for the power supply?
The CamCon DC92/I requires a 24VDC ±20% power supply.
How does the CamCon DC92/I module monitor the data exchange?
The module features status LEDs that indicate the supply voltage and data exchange status, and the safety output feature of the CamCon can monitor for cable interruptions.