NJS5
Series Time Relay
1. Scope of application
NJS5 series time relay mainly used as time control component for control circuit with AC 50Hz/60Hz, rated control power supply voltage to 380V, make or break the circuit at a preset time.
Relay
Control Relay
2. Model and meaning
N JS 5 - □ □ / □
Rated control supply voltage
Delay specifications
A: Power on delay
B: Interval delay
Y: Star - Delta Starters delay
Design number
Time relay
Enterprise features of the code
3. Main parameters and technical performance
Product Model
Work mode
Rated control supply voltage
Number of Contacts
Star - delta conversion time
Contact capacity
Electrical life
Mechanical life
Delay specifications
Ambient temperature
Installation
NJS5-A
Power on delay
NJS5-B
Interval delay
AC220V,AC380V
Delay 1 CO
Ue/Ie:AC-15 220V/0.75A, 380V/0.47A; DC-13 220V/0.27A; Ith:5A
3×10 4
1×10 6
5s,10s,30s,60s,2min,3min,5min,10min,20min
-5℃~+40℃
Guide rail
NJS5-Y
Star - Delta Starters delay
AC380V
Delay 2 NO
20ms ~ 300ms (adjustable)
67 > >>
Relay
Control Relay
4. Wiring diagram
NJS5-A wiring diagram NJS5-B wiring diagram NJS5-Y wiring diagram
18.5max
R
ON
3
5
100
1
200
7
9
10
20 300ms
延时 10 s
时间继电器
NJS5-Y
5. Outside shape and mounting dimensions
65max
18.5max
R
ON
延时 10 s
5
3
1
7
9
10
时间继电器
NJS5-A
65max
NJS5-A,NJS5-B outside dimensions
NJS5-Y outside dimensions
> >> 68