HEME GEO 30
Operating Instructions /
Gebrauchsanleitung /
Manuel d’utilisation /
Guida all‘uso /
Manual de instrucciones
GROUND LOOP TESTER /
ERDSCHLEIFENMESSGERÄT /
APPAREIL DE TEST DE BOUCLE
DE TERRE /
TESTER DI TERRA A TENAGLIA /
MISURATORE DI TERRA
HEME GEO 30
LEM HEME
1 Penketh Place
Skelmersdale
Lancs, UK
Tel:
+44 (0) 1695 720 535
Fax:
+44 (0) 1695 507 29
HEME GEO 30
Scope of delivery
1 battery 9V alkaline (type IEC LR6, installed)
1 Resistance test/check loop
1 Users manual E/G/F/I/ES
1 Professional carrying case
SE 8130 Z
Unpacking: Check delivery for damage during transport.
Keep the packing material for later transport and check scope of delivery.
Contents
Contents
1
Safety Regulations...................................................................................... 5
2
Description of Instrument........................................................................... 6
3
Ground Loop Measurements...................................................................... 9
4
Continuity Loop Test ................................................................................ 11
5
Ground Leakage Current Measurement ................................................... 12
6
Memory and Alarm Functions .................................................................. 13
6.1
6.2
6.3
6.4
6.5
6.6
) ............................................................. 13
High and Low Alarm (
Setting the Sampling Interval ............................................................ 15
Data Logging ................................................................................... 15
Read the Data Stored in Memory...................................................... 16
Clear Data Memory .......................................................................... 16
Cancel the Auto Power Off ............................................................... 16
7
Principle of Operation............................................................................... 17
8
Specification ............................................................................................. 19
9
Maintenance, Service................................................................................ 22
10
Other products.......................................................................................... 23
HEME GEO 30
SO8130Z Rev. B
3
Contents
4
HEME GEO 30
SO8130Z Rev. B
Safety Regulations
1
Safety Regulations
General
This measuring device is only to be installed and operated by qualified personnel
and according to the technical data in compliance with the safety precautions
and regulations set forth below. Additionally, the use of this equipment requires
compliance with all legal and safety regulations pertaining to each specific
application. Similar regulations apply to the use of accessories.
Operating electrical devices implies that parts of the device carry dangerous
voltages. Disregarding warning notices may lead to serious physical injury and
material damage.
It can be assumed that safe operation is no longer possible if the device
•
shows visible damage,
•
has been exposed to unfavourable conditions (e.g. storage beyond the
permissible climatic limits without adaptation to the ambient climate, dewing etc.)
or
•
has been exposed to major strain during transport (e.g. been dropped from
some height without visible external damage etc.).
No measurements must be performed on unprotected measuring circuits.
Qualified Personnel
Are persons familiar with the setting up, installation, starting of and operation of the
device and possess an appropriate qualification required for such activities.
Special warnings
•
Use of rubber gloves is a good safety practice even if the equipment is properly
operated and grounded.
•
Safety is the responsibility of the operator.
•
Use extreme caution when using the instrument around energized electrical
equipment.
•
Do not attempt to use the ground tester to twist or pry the ground electrode or
ground wire away from the equipment being grounded.
•
All metal objects or wires connected to the electrical system should be assumed
to be lethal until tested. Grounding systems are no exception.
HEME GEO 30
SO8130Z Rev. B
5
Description of Instrument
2
Description of Instrument
The compliance with the actual EMC-regulations is documented by the attached CE-sign.
The clamp-on ground resistance tester enables the user to measure ground resistance of
the ground rod without the use of auxiliary ground rods. Clamp-on ground resistance
testers are used in multi-grounded systems without disconnecting the ground under test.
Applications:
•
earth resistance of various installations (high voltage pylons, buildings, cell phone
substations, RF transmitters etc.)
inspection of lightning protection systems
•
Instrument description:
H
O
F U
c
d
e
f
g
6
R
Jaws: To enclose electrode or ground wire. No air gap is allowed
between the two halves of the jaws.
HOLD button: Press this button to hold the displayed value
Rotary switch: Power on and function selection
Display unit, liquid crystal display (LCD)
REC button: When one of the functions is selected by FUNC button, it is
used to increment value. If no function is selected, it is used to start data
logging, or record one data.
HEME GEO 30
SO8130Z Rev. B
Description of Instrument
h
i
j
k
button: to decrement value, press this button
Jaws trigger
button: to increment a value press this button
FUNC button: press to select HI (hi alarm), LO (low alarm), SEC (seconds), or no.
(of reading)
HEME GEO 30
SO8130Z Rev. B
7
Description of Instrument
Display
c
Function
Display of current selected function or current record
number
d
Digits
Display value from 0 to 9999 with decimal point.
e
Ohm
Symbol will be shown in Ω and alarm functions
f
mA
Display ground leakage current in mA or A
g
8
This symbol is displayed if the rotary switch is in the alarm
position
h
NOISE:
Noise present in ground electrode or ground rod.
i
Jaw Open
If the jaw is not properly closed during measurement, this
symbol and the word ”OPEN” will be shown on the LCD.
j
Low Battery
k
l
NO.
REC
When the battery voltage is lower than required,
this symbol will be shown in LCD. Replace the
battery.
Indicate the READ function
Indicates data logging is in progress
11
AP
Indicate Autopower off will operate in 4 to 6 minutes
HEME GEO 30
SO8130Z Rev. B
Ground Loop Measurements
3
Ground Loop Measurements
n
Open the jaws and make sure the jaw mating surfaces are clean and free of dust,
dirt or any foreign substances.
o
p
Snap (open and close) the jaws a few times to ensure the jaws mate properly.
Turn the power on, and set the rotary switch to the Ω position.
Do not clamp on to any conductor or open the jaws at this moment or
during self-calibration.
q At powering on, the clamp-on ground tester will self-calibrate for better accuracy.
Users should wait for the self-calibration to finish before making measurements.
During the self-calibration, the LCD will show CAL7, CAL6,..., CAL2, CAL1.
r
s
t
When the ground tester is ready, a beep sound will be heard.
Clamp on to the electrode or ground rod to be measured.
Read the value of Rg (ground loop resistance) from LCD.
Note: For better measurement:
Snap (open and close) the jaws a few times before powering on.
Do not clamp on to any conductor at the moment of powering on.
Note: If self-calibration does not stop:
This is because the self-calibration is not complete. The ground tester will
continue the process until a proper self-calibration is complete.
Check the jaw mating surfaces. If there is any dirt, dust, or any foreign
substance, clean the surface and power up again.
Note: Noise present in the electrode or ground rod:
If there exists over 3A current or 30V in ground rod, the symbol ”NOISE” will be
shown in LCD. Under the presence of noise, the reading is no longer accurate.
Note: If the jaw assembly is open during measurement, a symbol and the word
”OPEN” will be displayed on LCD.
HEME GEO 30
SO8130Z Rev. B
9
Ground Loop Measurements
Ground resistance measurements principle:
Equivalent circuit diagram:
R1
R2
......Rn
Rg
Rg
10
HEME GEO 30
SO8130Z Rev. B
Continuity Loop Test
4
Continuity Loop Test
The testing procedures are the same as ground resistance measurement:
n
Open the jaws and make sure the jaw mating surfaces are clean and free of
dust, dirt or any foreign substances.
o
p
Snap (open and close) the jaws a few times to ensure the jaws mate properly.
Turn the power on, and set the rotary switch to the “Continuity” position.
Do not clamp on to any conductor or open the jaws at this moment or
during self-calibration.
q At powering on, the clamp-on ground tester will self-calibrate for better accuracy.
r
s
t
Users should wait for the self-calibration to finish before making measurements.
During the self-calibration, the LCD will show CAL7, CAL6,..., CAL2, CAL1.
When the ground tester is ready, a beep sound will be heard.
Clamp on to the electrode or ground rod to be measured.
A beep sound will be heard if resistance Rg is less than 40 Ω.
Rg
HEME GEO 30
SO8130Z Rev. B
11
Ground Leakage Current Measurement
5
n
o
p
12
Ground Leakage Current Measurement
Turn the power on, set the rotary switch at the mA~ or A~ position.
Clamp on to the electrode or ground rod.
Read the value of leakage current displayed on LCD.
HEME GEO 30
SO8130Z Rev. B
Memory and Alarm Functions
6
Memory and Alarm Functions
6.1
High and Low Alarm (
1. Set the rotary switch at the
)
position.
2. Press the FUNC button to select “HI“ or “LO” alarm. The current value of High or
Low alarm will be shown in the upper row of LCD.
3. Press the ▲ button or ▼ button to increment/decrement the value by 1 ohm. As
users hold the button longer, the speed of incrementing/decrementing will become
faster. The value can be increment from 0 ohm to 1510 ohm and then OL. Or the
value can be decrement from OL to 1510 ohm to o ohm. The value will roll over to
OL/0 if the current value is 0/OL.
4. Once the value is set, press the FUNC button several times until the upper row LCD
show no letters.
position. The unit will compare the current
5. When the rotary switch is set at the
value with the high and low values. If the current measurement is larger than HI
value, the unit will beep and show HI -- in the upper row of LCD. If the current
measurement is smaller than the LO value, the unit will beep and show LO – in the
upper row of LCD.
HEME GEO 30
SO8130Z Rev. B
13
Memory and Alarm Functions
HO
OF LD
F
FU
N
C
R
E
C
NOTE: If the HI value is set at OL, or the LO value is set at 0, the ALARM
function will not be performed. So they are method to disable one of the HI or
LO alarm.
NOTE: The HI value can’t be smaller than the low value. And the LO value can’t
be larger than the HI value. HI value will be adjusted to LO value plus 1 when
rollover occurs. The maximum value of LO value is HI value minus 1.
NOTE: If data logging is progressing, sound of beeping will be disabled to save
battery power. But the LCD still shows the warning letters of “HI—“ or “LO—“.
NOTE: The values for the high and low alarm are stored in the memory. They
are restored when the power is turned on.
14
HEME GEO 30
SO8130Z Rev. B
Memory and Alarm Functions
6.2
Setting the Sampling Interval
1. Press the FUNC button until letters of “SEC” are shown in the upper row of LCD.
2. The unit shows the current sampling interval in seconds.
3. Press the ▲ or ▼ button to increment/decrement the value by 1 second. As users
hold the button longer, the speed of incrementing/decrementing will become faster.
The value can be incremented/decremented from 0 to 255 / 255 to 0 seconds.
Value will roll over when the value of maximum 255/minimum 0 seconds is reached.
4. Press the FUNC button several times until the upper row LCD show no letters.
6.3
Data Logging
The unit will start data logging if the REC button is pressed, and a symbol of REC will
be shown in LCD. Data will be recorded at the specified sampling interval.
Data logging will be stopped if the memory is full, or the unit detects the condition of low
battery, or the REC button is pressed again.
NOTE: If the sampling interval is set at 0 seconds, only one data is recorded. To
record next data, users can press the REC button again. The record number is
also displayed for about 1 seconds.
HEME GEO 30
SO8130Z Rev. B
15
Memory and Alarm Functions
6.4
Read the Data Stored in Memory
1. Press the FUNC button until a symbol of “NO.” is shown in LCD. The
current record number is shown in the upper row of LCD. And the data is
shown in the lower row of LCD.
2. Press the ▲ or ▼ button to read the next/previous data,
3. If the users hold the ▲ or ▼ button longer, the record number will be
incremented/decremented faster. The record number will roll over when the
last/first record is reached.
6.5
Clear Data Memory
Press and hold the REC button, then turn the power on. Letters of “CL” will be shown to
indicate that memory is cleared.
6.6
Cancel the Auto Power Off
When the unit is turned on, a symbol of AP is displayed in LCD. That means the unit
will turn itself off in about 4 to 6 minutes. To cancel this function, user can hold the
FUNC button, then turn the power on. Symbol of AP will not be displayed in LCD.
16
HEME GEO 30
SO8130Z Rev. B
Principle of Operation
7
Principle of Operation
The following diagram (fig. 1) shows a simplified typical grounded distribution system.
Its equivalent circuit (fig. 2) is shown below. If R1, R2, R3, ... Rn is combined as Req,
then only Rg and Req are left in the circuit (see figure). If a constant voltage is applied
to the circuit, the following equation is valid:
U
= Rg + Req
I
where
Req =
1
1
∑R
i
, i = 1,2,...n
If Rg and R1, R2, ... Rn are about the same, and n is a large number (such as 200),
then Req will be much less than Rg and maybe approach zero.
Rg >> ( Req → 0)
Example:
If Rg and R1, R2, ... Rn are all 10 Ω, respectively and n = 200, then Req by calculation
equals
Req =
1
1
1
1
+ + ... +
10
10 10
= 0,05Ω
In this example, we can see that as long as the number of multiple electrodes is large
enough, the equivalent resistance is negligible with respect to the ground resistance to
be measured.
HEME GEO 30
SO8130Z Rev. B
17
Principle of Operation
Fig. 1: Typical grounded distribution systems
I
U
Rg
~
I
Req
U
~
R1
R2
R3
R4 .....Rn
Rg
Fig. 2: Equivalent circuit diagram
18
HEME GEO 30
SO8130Z Rev. B
Specification
8
Specification
Electrical Specification
Display:
9999 digit LC-display with special symbols
Temperature ranges:
Operating humidity: Less than 85% RH
Storage
temperature:
-20 °C ... +60 °C (-4 °F ... +140 °F)
Storage humidity:
Less than 75% RH
Reference temp.:
+23 °C
±. 5 °C (+73 °F ± 9 °F)
Temperature coeff.: 0,1% o. rdg. / Kelvin
Operating error:
Refers to the operating temperature range
Protective type:
IP20 according to IEC 529 / EN 60529
Safety:
300V, installation CAT III / pollution degree 2
(according to EN 61010-1:1992)
EMC (Emission):
IEC 1000-4-2, IEC 61326-1 class B
EMC (Immunity):
IEC 61000-4-2 8 kV (air) perf. criteria B,
IEC 61000-4-3 3 V/m perf. criteria A
Range selection:
Auto
Overload indication: OL
Measuring time:
0,4 sec
1.667KHz
Auxiliary power:
9V alkaline (type IEC 6 LR 61)
Power consumption: 40 mA
Low battery
indication:
Symbol
Mechanical Specification
Conductor size:
Dimensions:
257 mm (L) x 100 mm (W) x 47 mm (H)
10" (L) x 3.9"(W) x 1.9"(H)
640 g (1,4 lbs)
Weight:
HEME GEO 30
SO8130Z Rev. B
19
Specification
Ground Loop Resistance (Autorange):
Operating temp.:
Range
(1)
0 °C ... +50 °C (+24 °F ... +122 °F)
Resolution
Operating error(1)
0.025 - 0.250 Ω
0.002 Ω
±1.5%rdg ± 0.05 Ω
0.250 - 9.999 Ω
0.02 Ω
±1.5%rdg ± 0.1 Ω
10.00 - 99.99 Ω
0.04 Ω
±2.0%rdg ± 0.3 Ω
100.0 - 199.9 Ω
0.4 Ω
±3.0%rdg ± 1.0 Ω
200.0 - 400.0 Ω
2Ω
±5.0%rdg ± 5 Ω
400.0 - 600.0 Ω
5Ω
±10%rdg ± 10 Ω
±20%
600.0 - 1500 Ω
20 Ω
Loop resistance with no inductance, external field < 50 A/m, external electrical field
< 1 V/m, conductor centered.
Continuity
Operating temp.:
0 °C ... +50 °C (+24 °F ... +122 °F)
Beep if resistance < approximately 40.00 Ω
Ground/Leakage Current mA~
Operating temp.:
-10 °C ... +50 °C (+14 °F ... +122 °F)
(Autorange, 50/60 Hz, True RMS, crest factor CF< 3.0)
Range
Resolution
Operating error
0.200 - 1.000 mA
0.001 mA
±2.5%rdg ± 0.05 mA
1.00 - 10.00 mA
0.01 mA
±2.5%rdg ± 0.05 mA
10.0 - 100.0 mA
0.1 mA
±2.0%rdg ± 0.3 mA
100 - 1000 mA
1 mA
±2.0%rdg ± 3 mA
Ground/Leakage Current A~ (50/60 Hz, True RMS, crest factor CF< 3.0)
Operating temp.:
-10 °C ... +50 °C (+14 °F ... +122 °F)
Range
Resolution
Operating error
0.20 - 15.00 A
0.01 A
±2.0%rdg ± 0.03 A
15.00 - 30.00 A
0.01 A
±3.0%rdg ± 0.03 A
Max. Current Protection: 100A continuous, 200A (< 60 sec.) 50/60Hz.
Current Overload Protection: 100A Continuous, 200A ( < 60 seconds) 50/60Hz.
20
HEME GEO 30
SO8130Z Rev. B
Specification
Battery Replacement
When the low battery symbol is displayed in LCD, replace the battery.
•
•
•
•
•
•
Turn the power off.
Remove the bottom case screws.
Lift and remove the bottom case.
Remove the old battery.
Install new 9V battery.
Replace the bottom case and secure the screws.
HEME GEO 30
SO8130Z Rev. B
21
Maintenance, Service
9
Maintenance, Service
If the instrument is operated and handled properly it does not require specific
maintenance and service. Maintenance work must only be undertaken by trained and
qualified staff and during the warranty period only by authorised service centres.
Calibration
As an additional service we offer a regular inspection and calibration of your instrument.
Upon request and for a fee we supply company test certificates or test certificates from
national calibration services.
Storage
In case the instrument is either not used or stored for a longer period, remove the
battery and keep it separately to avoid possible damage from leaking battery lectrolyte.
Service
This instrument has been manufactured and tested according to the latest
technological innovations and in compliance with the quality assurance system DIN
ISO 9001.
If there should still be reason for complaint please refer to your nearest service centre,
giving a detailed description of the defect by using the enclosed service card and
including a copy of the invoice or the delivery note. If the instrument is operated as
agreed we guarantee fault free function of the instrument for a period of TWO (2) years
after the date of the first end-user purchase.
This warranty does not apply to any damage caused by improper treatment or
operation or by impermissible overload.
Packing
Use for shipping the original packing only. The manufacturer doesn't accept any
charges for damage that may have been caused by inappropriate packing.
1 year warranty entitlement to repairs free of charge in case of malfunction of the
instrument excluding damage caused by misuse.
Note:
22
For reasons of clarity this manual does not contain detailed
information about all models and applications, modes of operation
and maintenance.
HEME GEO 30
SO8130Z Rev. B
Other Products
10 Other products
LEM offers a comprehensive range of electrical test products to ensure the safe and
efficient operation of electrical equipment and installations including:
Earth/ground testers:
Installation testers:
Insulation testers:
Clamp-on meters:
Current probes:
Multimeters:
Power Quality
Analysers
HANDY GEO, SATURN GEO, UNILAP GEO (X)
SATURN 100, UNILAP 100, UNILAP 100 (X)E
HANDY ISO, SATURN ISO, UNILAP ISO X, UNILAP ISO 5kV
LH Series and Analyst 2050/60
PR Series and LEM~Flex
Unigor Series
Analyst 3Q – Three and Four phase analyser
Analyst 3P – Three phase energy analyser
A full range of accessories is available including: interfaces (RS232, IrDA), data
memory and PC-software for report generation.
Other products from the LEM group include systems and analysers for power and
power quality monitoring and transducers for current and voltage measurement. LEM
provides complete measurement solutions in current, voltage and power quality please, contact our sales partners worldwide for more information.
LEM policy is one of continuous product improvement and the company
reserves the right to revise the above specifications without notice.
HEME GEO 30
SO8130Z Rev. B
23
2
3
4
5
6
7
8
9
10
Andere Produkte .................................................................................21
HEME GEO 30
SO8130Z Rev. B
1
2
HEME GEO 30
SO8130Z Rev. B
1
•
•
•
•
•
HEME GEO 30
SO8130Z Rev. B
3
2
H
O
F U
c
d
e
f
g
4
R
h
i
j
k
HEME GEO 30
SO8130Z Rev. B
5
c
d
e
Ohm
f
mA
g
h
NOISE:
i
Zange offen
j
k
l
NO.
REC
11 AP
6
HEME GEO 30
SO8130Z Rev. B
3
t Der
HEME GEO 30
SO8130Z Rev. B
7
R1
R2
......Rn
Rg
Rg
8
HEME GEO 30
SO8130Z Rev. B
4
p
Rg
HEME GEO 30
SO8130Z Rev. B
9
5
n
o
p
10
HEME GEO 30
SO8130Z Rev. B
6
6.1
)
.
HEME GEO 30
SO8130Z Rev. B
11
HO
OF LD
F
FU
N
C
R
E
C
12
HEME GEO 30
SO8130Z Rev. B
6.2
6.3
Datenprotokollierung
HEME GEO 30
SO8130Z Rev. B
13
6.4
6.5
6.6
14
HEME GEO 30
SO8130Z Rev. B
7
Req =
1
1
∑R
i
, i = 1,2,...n
Req =
1
1
1
1
+ + ... +
10 10
10
= 0,05Ω
U
= Rg + Req = 10 + 0,05 = 10,05 → R g
I
HEME GEO 30
SO8130Z Rev. B
15
I
U
Rg
~
I
U
Req
~
R1
R2
R3
R4 .....Rn
Rg
16
HEME GEO 30
SO8130Z Rev. B
8
ca. 23mm (0.9")
257 mm (L) x 100 mm (W) x 47 mm (H)
10" (L) x 3.9"(W) x 1.9"(H)
640 g (1,4 lbs)
HEME GEO 30
SO8130Z Rev. B
17
Betriebsmessabweichung(1)
±1.5% v. MW ± 0.05 Ω
±1.5% v. MW ± 0.1 Ω
±2.0% v. MW ± 0.3 Ω
±3.0% v. MW ± 1.0 Ω
±5.0% v. MW ± 5 Ω
±10% v. MW ± 10 Ω
±20%
18
HEME GEO 30
SO8130Z Rev. B
•
•
•
•
•
•
HEME GEO 30
SO8130Z Rev. B
19
9
20
HEME GEO 30
SO8130Z Rev. B
Andere Produkte
HEME GEO 30
SO8130Z Rev. B
21
No de commande
SE 8130 Z
2
3
4
5
6
6.1
6.2
6.3
6.4
6.5
6.6
7
8
9
10
HEME GEO 30
SO8130Z Rev. B
1
2
HEME GEO 30
SO8130Z Rev. B
1
•
•
•
•
•
•
HEME GEO 30
SO8130Z Rev. B
3
2
H
O
O L
F U
c
d
e
f
g
4
R
Sert
à
mettre
l’instrument
sous
tension
et
à
h
i
j
k
HEME GEO 30
SO8130Z Rev. B
5
Ecran
c
Fonction
d
Chiffres
e
Ohm
f
mA
g
h
NOISE:
i
j
k
l
NO.
REC
AP
11
6
HEME GEO 30
SO8130Z Rev. B
3
n
o
p
q
r
s
t
HEME GEO 30
SO8130Z Rev. B
7
R1
R2
......Rn
Rg
Rg
8
HEME GEO 30
SO8130Z Rev. B
4
r
s
t
Rg
HEME GEO 30
SO8130Z Rev. B
9
5
n
o
p
10
HEME GEO 30
SO8130Z Rev. B
6
6.1
)
..
HEME GEO 30
SO8130Z Rev. B
11
FU
N
C
R
E
C
12
HEME GEO 30
SO8130Z Rev. B
6.2
6.3
HEME GEO 30
SO8130Z Rev. B
13
6.4
6.5
6.6
14
HEME GEO 30
SO8130Z Rev. B
7
U
= Rg + Req
I
où
Req =
1
1
∑R
i
, i = 1,2,...n
Req =
1
1
1
1
+ + ... +
10 10
10
= 0,05Ω
HEME GEO 30
SO8130Z Rev. B
15
I
U
Rg
~
I
U
Req
~
R1
R2
R3
R4 .....Rn
Rg
16
HEME GEO 30
SO8130Z Rev. B
8
HEME GEO 30
SO8130Z Rev. B
17
0.002 Ω
0.02 Ω
0.04 Ω
0.4 Ω
2Ω
5Ω
20 Ω
18
HEME GEO 30
SO8130Z Rev. B
HEME GEO 30
SO8130Z Rev. B
19
9
Note:
20
HEME GEO 30
SO8130Z Rev. B
HEME GEO 30
SO8130Z Rev. B
21
Numero ordine
SE 8130 Z
Indice
Indice
1
2
3
4
5
6
7
8
9
10
HEME GEO 30
SO8130Z Rev. B
1
Indice
2
HEME GEO 30
SO8130Z Rev. B
1
•
•
•
•
•
HEME GEO 30
SO8130Z Rev. B
3
2
H
O
O
F U
R
g
h
i
j
k
Pulsante REC:
HEME GEO 30
SO8130Z Rev. B
5
Display
c
d
Cifre
e
f
Ohm
mA
h
NOISE:
i
j
k
l
11
AP
g
6
3
HEME GEO 30
SO8130Z Rev. B
7
R1
R2
......Rn
Rg
Rg
8
HEME GEO 30
SO8130Z Rev. B
4
Rg
HEME GEO 30
SO8130Z Rev. B
9
5
n
o
p
10
HEME GEO 30
SO8130Z Rev. B
6
6.1
)
.
HEME GEO 30
SO8130Z Rev. B
11
FU
N
C
R
E
C
12
HEME GEO 30
SO8130Z Rev. B
6.2
6.3
HEME GEO 30
SO8130Z Rev. B
13
6.4
6.5
6.6
14
HEME GEO 30
SO8130Z Rev. B
7
Req =
1
1
∑R
i
, i = 1,2,...n
Req =
1
1
1
1
+ + ... +
10
10 10
= 0,05Ω
HEME GEO 30
SO8130Z Rev. B
15
I
U
Rg
~
~
R1
R2
R3
R4 .....Rn
Rg
16
HEME GEO 30
SO8130Z Rev. B
8
ca. 23 mm
Dimensioni:
257 mm (L) x 100 mm (B) x 47 mm (A)
10" (L) x 3,9" (B) x 1,9" (A)
640 g
Peso:
HEME GEO 30
SO8130Z Rev. B
17
0,025 - 0,250 Ω
0,250 - 9,999 Ω
10,00 - 99,99 Ω
100,0 - 199,9 Ω
200,0 - 400,0 Ω
400,0 - 600,0 Ω
600,0 - 1500 Ω
0,002 Ω
0,02 Ω
0,04 Ω
0,4 Ω
2Ω
5Ω
20 Ω
Deviazione di misura in
esercizio(1)
±1,5% val. mis. ± 0,05 Ω
±1,5% val. mis. ± 0,1 Ω
±2,0% val. mis. ± 0,3 Ω
±3,0% val. mis. ± 1,0 Ω
±5,0% val. mis. ± 5 Ω
±10% val. mis. ± 10 Ω
±20%
(1)
18
HEME GEO 30
SO8130Z Rev. B
•
HEME GEO 30
SO8130Z Rev. B
19
9
20
HEME GEO 30
SO8130Z Rev. B
HEME GEO 30
SO8130Z Rev. B
21
Nº de pedido
SE 8130 Z
Índice de materias
1
Normas de seguridad............................................................................... 3
2
3
4
5
6
Memory and Alarm Functions................................................................ 11
6.1
High and Low Alarm (
)............................................................ 11
6.2
Setting the Sampling Interval ......................................................... 13
6.3
Data Logging................................................................................. 13
6.4
Read the Data Stored in Memory ................................................... 14
6.5
Clear Data Memory ....................................................................... 14
6.6
Cancel the Auto Power Off............................................................. 14
7
8
9
10
HEME GEO 30
SO8130Z Rev. B
1
2
HEME GEO 30
SO8130Z Rev. B
Normas de seguridad
1
Normas de seguridad
•
•
•
•
•
•
HEME GEO 30
SO8130Z Rev. B
3
2
H
O
O L
F
F U
!
"
#
$
%
4
R
&
'
(
)
botón:
botón:
HEME GEO 30
SO8130Z Rev. B
5
6
!
"
Dígitos
#
$
%
Ohmio
mA
&
NOISE:
'
(
Batería baja
)
*
NO.
REC
11
AP
3
n
o
p
q
r
s
t
HEME GEO 30
SO8130Z Rev. B
7
Diagrama de circuito equivalente:
R1
R2
......Rn
Rg
Rg
8
HEME GEO 30
SO8130Z Rev. B
4
n
o
p
q
r
s
t
Rg
HEME GEO 30
SO8130Z Rev. B
9
5
n
o
p
10
HEME GEO 30
SO8130Z Rev. B
6
6.1
Alarma alta y baja (
)
.
HEME GEO 30
SO8130Z Rev. B
11
F
U
N
C
R
E
C
12
HEME GEO 30
SO8130Z Rev. B
6.2
2.
3.
6.3
Registro de datos
HEME GEO 30
SO8130Z Rev. B
13
6.4
6.5
2.
3.
6.6
14
HEME GEO 30
SO8130Z Rev. B
7
U
= Rg + Req
I
donde
Req =
1
1
∑R
i
, i = 1,2,...n
Req =
1
1
1
1
+ + ... +
10 10
10
= 0,05Ω
U
= Rg + Req = 10 + 0,05 = 10,05 → R g
I
HEME GEO 30
SO8130Z Rev. B
15
I
U
Rg
~
I
U
Req
~
R1
R2
R3
R4 .....Rn
Rg
Fig. 2: Diagrama de circuito equivalente
16
HEME GEO 30
SO8130Z Rev. B
8
CEI 61000-4-2 8 kV (air) criterio de rendim. A
CEI 61000-4-3 3 V/m criterio de rendim. A
Automático
OL
0,4 s
1.667 KHz
Pila alcalina 9 V (tipo CEI 6 LR 61)
40 mA
Símbolo
23 mm (0.9”) aprox.
257 mm (largo) x 100 mm (ancho) x 47 mm (alto)
10” (largo) x 3.9” (ancho) x 1.9” (alto)
640 g (1,4 lb)
17
0.025 - 0.250 Ω
0.250 - 9.999 Ω
10.00 - 99.99 Ω
100.0 - 199.9 Ω
200.0 - 400.0 Ω
400.0 - 600.0 Ω
600.0 - 1500 Ω
0.002 Ω
0.02 Ω
0.04 Ω
0.4 Ω
2Ω
5Ω
20 Ω
18
HEME GEO 30
SO8130Z Rev. B
HEME GEO 30
SO8130Z Rev. B
19
9
Nota:
20
HEME GEO 30
SO8130Z Rev. B
HEME GEO 30
SO8130Z Rev. B
21
22
HEME GEO 30
SO8130Z Rev. B
EC-Certificate of conformity
EG-Konformitätserklärung
CE-Certificat de conformité
Document No. / month / year:
Dokument Nr. / Monat / Jahr:
N° de document / Mois / Année:
Manufacturer:
Hersteller:
Fabricant:
Adress:
Anschrift:
Adresse:
Kind of product:
Produktart:
Type de produit:
Name of product:
Produktname:
Nom du produit:
CE001/10/04C
HEME GEO 30
the product meets the regulations of the following EC-directives
das Produkt erfüllt die Bestimmungen der folgenden EG-Richtlinien:
le produit est conforme aux normes des directives de l'Union Européenne suivantes:
73/23/EEC
" D i r e c t i v e o n t h e a p p r o x i m a t i o n o f t h e l a w s o f t h e Memb e r S ta t es r el at in g t o
e l e c t r i c a l e q u i p m e n t d e s i g n e d f o r u s e w it h i n c e r t a i n v o l t a g e l i m i t s a m e n d e d b y t h e
d i r ec ti ve 93 /6 8/E EC "
89/336/EEC
"D ir e ct iv e o n th e ap p r ox ima t i o n o f t h e l a w s o f t h e Me m b e r St a t e s r e l a t i n g t o
e le ct r o ma g n et ic co m p at ib ili ty a men d e d b y th e d ir ec tiv es 9 1/2 63 /E EC , 9 2/ 31 /EE C ,
93 /6 8/EEC a nd 93 /9 7/EEC "
die Übereinstimmung wird nachgewiesen durch die vollständige Einhaltung folgender Normen:
the accordance is proved by the observance of the following standards:
la conformité estprouvée par le respect des normes suivantes:
L
V
IEC/EN 61010-1:2001
E
Emission
Emissions
Émission
IEC/EN 61326 : 1997
+A2 :2001
M
Immunity
Imission
Susceptibilité
IEC/EN 61010-2-032:2002
2004
EN 61010-1:2001
300 V CATIII Pol. Degree 2
IEC 1010-2-032:2002
IEC/EN 61326, EN 55011 Class B
IEC/EN 61326, EN 55011 Klasse B
IEC/EN 61326, EN 55011 Classe B
IEC/EN 61326 : 1997
+A1 :1998+A2 :2001
EN 61000-4-2
EN 61000-4-3
4 kV air (A)
10 V/m (A)
DI Ronald Steuer, authorized signatory
Name, Position / Name, Funktion / Nom, Position
Printed in EU / Gedruckt in EU / Imprimé en EU / Stampato in EU / Impreso en EU
LEM HEME
1 Penketh Place
Skelmersdale,
Lancs, UK
Tel: +44 (0) 1695 720 535
Fax: +44 (0) 1695 50729
SO8130Z REV B
Right to change specification reserved /
Technische Änderungen vorbehalten /
Sous réserve de modifications /
Tutti i diritti di variazione tecnica riservat /
Nos reservamos el derecho a
modificaciones técnicas sin previo aviso