RADSON Tempco Digital 51022 User manual

Add to My manuals
46 Pages

advertisement

RADSON Tempco Digital 51022 User manual | Manualzz
DIGITAL
230V -230V
24V
DIGITAL
GB
Digital thermostat 230V
3 -12
F
Thermostat digital 230V
13 -24
D
25 -35
Gebruiksaanwijzing
Nl
UFH – 230VAC Digitale thermostaat
Instrukcja Użytkowania
36-46
Pl
230VAC Termostat z wyświetlaczem
Manualul utilizatorului
47-57
Ro
Termostat digital UFH – 230VAC
58-68
Инструкция по эксплуатации
UFH0051002 – 230VAC Термостат с дисплеем
1
Ru
69-80
2
Installation and Operation Manual
IMPORTANT!
Before starting work the installer should carefully read this Installation
& Operation Manual, and make sure all instructions contained therein
are understood and observed.
- The Main zone digital programmer should be mounted, operated
and maintained by specially trained personnel only. Personnel in the
course of training are only allowed to handle the product under the
supervision of an experienced fitter. Subject to observation of the
above terms, the manufacture shall assume the liability for the
equipment as provided by legal stipulations.
- All instructions in this Installation & Operation manual should be
observed when working with the controller. Any other application shall
not comply with the regulations. The manufacturer shall not be liable
in case of incompetent use of the control. Any modifications and
amendments are not allowed for safety reasons. The maintenance
may be performed by service shops approved by the manufacturer
only.
- The functionality of the controller depends on the model and
equipment. This installation leaflet is part of the product and has to be
obtained.
APPLICATION
- The Main zone digital programmer is developed to control and
manage all installations of water floor heating and cooling equipped
with our UFH range thermostat. The temperature in each room is
managed the control of actuators mounting on the manifold.
- The controller is normally used in conjunction with a complete
connecting box “UFH-MASTER” with or without “Heating & Cooling
module” to connect all electrical & hydraulic components of the
installation like a circulation pump, actuators...
- The controllers have been designed for use in residential rooms,
office spaces and industrial facilities.
Verify that the installation complies with existing regulations before
operation to ensure proper use of the installation.
SAFETY INSTRUCTIONS
Before starting work disconnect power supply!
- All installation and wiring work related to the controller must be
carried out only when de-energized. The appliance should be
connected and commissioned by qualified personnel only. Make sure
to adhere to valid safety regulations.
- The connecting boxes are neither splash- nor drip-proof. Therefore,
they must be mounted at a dry place.
- Do not interchange the connections of the thermostats and the 230V
connections under any circumstances! Interchanging these
connections may result in life endangering electrical hazards or the
destruction of the appliance and the connected sensors and other
appliances.
3
1 User Guide
UFH – 230VAC Digital thermostat
Wired Digital thermostat (230VAC) specially designed to control your
Under Floor Heating and cooling managed by actuator.
Flush Mounting version, standard fixing with 60mm axes.
Pilot wire for NSB function (-2°C)
Possibility to regulate on:
o
Air sensor only
o
Floor sensor only
o
Air & Floor combined with different possibilities
Amber Backlight
Temporary override function (2H)
Silent (Triac output),
- Optional external sensor 10K at 25°C
2 Technical characteristics
Measured temperature
precision
0.1°C
Operating temperature
0°C - 50°C
Setting temperature range
5°C - 35°C by 0.5°C step
Regulation characteristics
hysteresis (ON/OFF) or
adjustable Proportional
Integral (PWM)
Electrical Protection
Class II - IP30
Power Supply
Consumption
230VAC 50Hz
~ 3,5W
TRIAC
230VAC 75W Max (4
actuators)
Displayed during the init
(after power supplying)
1.x x
Output
Software version
4
3 Presentation
1
2
3
4
10
5
6
0
7
B
A
C
1:
2:
3:
4:
5:
6:
7:
10:
Water circulation in the room.
Key lock function.
Parameters menu.
Parameters number or sensor message indication.
Sensor used indication
Ambient, setting temperature or parameter if 3 displayed.
Heating or cooling mode indication.
Operating mode. (The active mode is framed)
A:
B:
C:
Minus key. (-)
Validation key or Mode key. (OK)
Plus key. (+)
5
4 How to use your thermostat
Use the (OK) key to change the mode in the Operating mode menu
OFF mode: (Manual mode)
Use this mode if you want to stop the Heating or Cooling function in
the room.
The ambient temperature will be displayed all the time.
Press once on the (OK) to turn on the backlight only and a second
time to change the operating mode.
Simple installation without main zone programmer:
The antifreeze temperature (7°C) will be maintained in the room all
the time.
Installation with main zone programmer: (with or without Heating
and Cooling function)
In heating mode: (Winter)
The antifreeze temperature (7°C) will be maintained in the room all
the time.
In cooling mode: (Summer)
The thermostat will be switched Off.
COMFORT operating mode: (Manual mode)
By pressing the keys (-) or (+), the actual comfort setting temperature
is now displayed, then press the desired key 1 sec to start the
increment or decrement of the setting temperature.
The ambient room temperature reappears after a few seconds.
Press once on the (OK) to turn on the backlight only and a second
time to change operating the mode.
The comfort temperature will be followed all the time in accordance
with these descriptions:
Simple installation without main zone programmer:
The comfort temperature will be followed all the time. (Default setting
20°C)
Installation with main zone programmer: (with or without Heating
and Cooling function)
Your thermostat is equipped with 2 comfort settings temperature (1
for heating and 1 for cooling)
6
In heating mode: (Winter)
The comfort temperature will be followed all the time. (Default setting
20°C)
You can adjust this setting only when the system will work in heating
mode.
In cooling mode: (Summer)
The comfort temperature will be followed all the time. (Default setting
22°C)
You can adjust this setting only when the system will work in cooling
mode.
REDUCED operating mode: (Manual mode)
By pressing the keys (-) or (+), the actual reduced setting temperature
is now displayed, then press the desired key 1 sec to start the
increment or decrement of the setting temperature.
The ambient room temperature reappears after a few seconds.
Press once on the (OK) to turn on the backlight only and a second
time to change operating the mode.
The reduced temperature will be followed all the time in accordance
with these descriptions:
Simple installation without main zone programmer:
The reduced temperature will be followed all the time. (Default setting
18°C)
Installation with main zone programmer: (with or without Heating
and Cooling function)
Your thermostat is equipped with 2 reduced settings temperature (1
for heating and 1 for cooling)
In heating mode: (Winter)
The reduced temperature will be followed all the time. (Default setting
18°C)
You can adjust this setting only when the system will work in heating
mode.
In cooling mode: (Summer)
The reduced temperature will be followed all the time. (Default setting
24°C)
You can adjust this setting only when the system will work in cooling
mode.
7
Automatic operating mode:
Simple installation without main zone programmer:
The comfort temperature will be maintained in the room all the time.
Installation with main zone programmer: (with or without Heating
and Cooling function)
In this mode your thermostat will follow the program (Comfort or
reduced) and order (Heating, cooling, Anti freeze, holiday…) of the
main zone programmer.
The ambient temperature will be displayed all the time.
Press once on the (OK) to turn on the backlight only and a second
time to change the operating mode.
Override mode:
Use this mode to override the automatic mode during 2 hours.
You can choose another setting temperature for this duration.
By pressing the keys (-) or (+), the override setting temperature is
now displayed, then press the desired key 1 sec to start the
increment or decrement of the setting temperature.
When the duration is finished the thermostat will come back in
Automatic mode
.
The ambient temperature will be displayed all the time.
Press once on the (OK) to turn on the backlight only and a second
time to change operating the mode.
Lock and unlock keypads:
Use this function to avoid change on your thermostat. (Available in all
modes)
- To lock the keypad, maintains the keys (-) & (+) pressed and press
the (OK) key in the same time, then the symbol “
“appears.
- To unlock the key pads repeat this procedure, (the symbol “
will disappear)
“
Sensor messages:
Main errors: (the regulation will be stopped)
Error on the internal sensor => Err in position “6” in the display with
the
logo blinks.
Error on the External (Floor) sensor
display with the
=> Err in position “6” in the
logo blinks.
8
Indications:
Error on the limiter (floor) sensor
display with the
=> Err in position “4” in the
logo blinks.
Lower limitation (floor sensor)
display with the
=> Lo in position “4” in the
logo blinks.
Higher limitation (floor sensor)
display with the
=> Hi in position “4” in the
logo blinks.
Special display:
If your installation works with a main zone programmer, the residual
humidity is monitored, to avoid risk of residual humidity in the house.
If the residual humidity is detected in cooling mode the thermostat will
be advised to active the dry function.
During the dry function the thermostat will stop the water circulation
on the room.
The cooling logo
will be blink to show the function.
5 Installation parameters menu
Your thermostat has 1 advanced installer menus.
- In order to enter in this menu, use the (OK) key and go to the
automatic mode
5 sec.
, then press the (-) & (+) in the same time during
- The first parameter is displayed 01 “Deg”.
How to change the value of a parameter:
- Once the parameter is displayed, press the (OK) key to start to
blink the value, then you can adjust it with (-) or (+) keys. Press (OK)
or wait few seconds to valid your adjustments.
To exit the parameter menu, go to the parameter number 09 “End”
and press (OK).
9
Parameters
N°
00
Names
XXx
01
Deg
02
Out
03
04
Sen
AiC
FlC
Other possibility
Sofware version
Type of degrees displayed
Actuator type
Selection of the sensor which will be
used for the regulation.
The listing of the following
parameters will be different in
function of this parameter.
Calibration of the internal sensor
(The calibration must be done after
12Hours working with the same
setting temperature)
Calibration of the Floor sensor
05
Default setting
(The calibration must be done after
12Hours working with the same
setting temperature)
°C: Celsius degrees.
°F: Fahrenheit degrees.
NC: Normally closed actuator.
NO: Normally open actuator.
Air: ambient sensor only
Flr: External (floor) sensor only.
FL.1: ambient sensor with lower and upper floor limitation.
FL.2: ambient sensor with intelligent lower floor limitation.
- To check the temperature in the room, put a thermometer at
1.5M distance to the floor in the concerned room and wait 1 hour
to be sure that the thermometer show the correct temperature.
Then you can enter the value saw on the thermometer with (-) or
(+) keys.
- When a calibration is made the message “Yes” will be displayed.
- To erase the calibration press simultaneity (-) and (+) keys when
“Yes” is displayed. Now the message “no” should be displayed.
The calibration must be done same as described above if the
external sensor is connected and used like an external ambiance
sensor.
If the external sensor is used as floor sensor, the thermometer
should be put on the floor.
10
FLl
06
FLo
07
08
09
FLh
Cld
End
Lower limitation of the floor
temperature.
Only effective if the parameter 02 is
adjusted on (FLr or Fl.1)
Offset added or subtracted to the
actual setting temperature, to define
the value of the lower floor limitation.
Only effective if the parameter 02 is
adjusted on (FL.2)
Example:
Comfort (Day) setting: 20°C
Reduced (Night) setting: 18°C
Floor limitation offset: -1°C
Upper limit of the floor temperature.
Only effective if the external sensor is
connected and selected. (FLr or FL.1)
Cooling function in the room.
Example:
Cooling function should be deactivated
for room with residual humidity
(Bathroom, kitchen...)
Default: 18°C
Adjustable: From 5°C to ”FLh”
Default: 0°C
Adjustable: From - 5°C to + 5°C
Example:
Value of the lower limitation during the day: 19°C
Value of the lower limitation during the Night: 17°C
Default: 35°C
Adjustable: From ”FLl” to 50°C
Yes: Cooling function is activated
no: Cooling function is deactivated
Press (OK) on this parameter to exit the parameters menu end come back to the main display.
11
6 Notes
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
12
13
14
Protection
Class II - IP30
Alimentation
Consommation
Sortie
Version logiciel
15
10
5
6
0
7
B
A
C
A:
B:
C:
16
18
clignotant.
clignotant.
19
er
20
N°
Noms
00
XXx
Version logiciel
01
Deg
02
Out
03
04
Sen
AiC
21
N°
Noms
05
FLC
FLl
06
FLo
22
N°
Names
07
FLh
08
Cld
09
End
23
6 Notes
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
24
und
die
25
o
o
o
0.1°C
Betriebstemperatur
0°C - 50°C
Regelungsart
Class II - IP30
Software Version
26
10
5
6
0
7
B
A
C
1:
2:
3:
4:
5:
6:
7:
10:
A:
B:
C:
27
blinkt
blinkt
blinkt
30
31
Nr.
00
Name
XXx
01
Deg
02
Out
03
Sen
04
AiC
32
Nr.
Name
05
FlC
FLl
06
FLo
33
Nr.
Name
07
FLh
08
Cld
09
End
34
Inbouwversie met standaard 60 mm as aansluiting.
-
o
o
o
-
Parti afwijking (2H)
-
-
-
Externe voeler in optie10K à 25°C
2 Technische kenmerken
Meetnauwkeurigheid
0.1°C
Werkingstemperatuur
Omgevingstemperatuur
instelling
0°C - 50°C
hystérèse (ON/OFF) of
proportioneel integraal (PWM)
Class II - IP30
Voedingsspanning
Vermogen
Uitgang
Software versie
5°C - 35°C by 0.5°C step
37
3 Indicatie
1
2
3
4
10
5
6
0
7
B
A
C
38
40
knippert.
knippert.
41
42
Parameters
N°
Noms
01
Deg
02
Out
03
Sen
04
AiC
43
Parameters
N°
Noms
05
FLC
FLl
06
FLo
Fabrieksinstellingen
44
Noms
07
FLh
Fabrieksinstellingen
Fabrieksinstelling: 35°C
Instelling: Van ”FLl” tot 45°C
Funkcja functie.
Chłodzenia
Koeling
08
Cld
09
End
Przykład:
Voorbeeld:
Funkcja chłodzenia powinna być
In vochtige ruimtes dient men de koeling
nieaktywna w pomieszczeniach o
uit
te schakelenwilgotności
om condens
te
podwyższonej
(Łazienka,
voorkomen.
kuchnia...)
Yes : Funkcja
Koeling Chłodzenia
actief
OFF:
nieaktywna
No : Koeling uitgeschakeld
ON: Funkcja Chłodzenia aktywna
45
6 Nota’s
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
46

advertisement

Key Features

  • Precise temperature control with 0.1°C precision
  • Choice of air or floor temperature sensing
  • Adjustable proportional-integral (PWM) regulation for energy efficiency
  • Temporary override function for quick adjustments
  • Easy-to-use interface with amber backlight and clear display
  • Silent operation for a peaceful environment

Related manuals

Frequently Answers and Questions

How do I change the operating mode?
Press the (OK) key to change the mode in the Operating mode menu.
What is the default comfort temperature?
The default comfort temperature is 20°C in heating mode.
Can I use an external sensor with this thermostat?
Yes, you can use an optional external sensor (10K at 25°C).
What is the maximum output power of this thermostat?
The maximum output power is 75W (4 actuators).
What type of electrical protection does this thermostat have?
The thermostat has Class II - IP30 electrical protection.
What is the power consumption of this thermostat?
The power consumption is ~3.5W.