Bul. 140G2
DIR 1002011A1803 Version 01 - 140G2-K-EXS3, 140G2-K-EXS4
Spreader Terminals for 140G2-K, 140G2-L, 140MG2-K, 140MG2-L
Terminali prolungati divaricati
Vorderseitige verlängerte V-förmige Anschlüsse
Prises avant prolongées écartées
Terminales frontales prolongados separados
扩展前终端
140G2-K, 140MG2-K
Installation - Installazione - Installation - Installation Instalación - Instalação -
140G2-L, 140MG2-L
WARNING: To prevent electrical shock, disconnect from power source before
installing or servicing. Install in suitable enclosure. Keep free from contaminants.
70E requirements
Per prevenire infortuni, togliere tensione prima dell'installazione o
manutenzione. Installare in custodia idonea. Tenere lontano da contaminanti.
WARNUNG: Vor Installations- oder Servicearbeiten Stromversorgung zur
Vermeidung von elektrischen Unfällen trennen. Die Geräte müssen in einem
passenden Gehäuse eingebaut und gegen Verschmutzung geschützt werden.
AVERTISSEMENT: Avant le montage et la mise en service, couper l'alimentation
secteur pour éviter toute décharge. Prévoir une mise en coffret ou armoire
appropriée. Protéger le produit contre les environnements agressifs.
ADVERTENCIA: Desconéctese de la corriente eléctrica, antes de la instalación o
del servicio, a fin de impedir sacudidas eléctricas. Instálelo en una caja apropiada.
Manténgalo libre de contaminantes.
ATENÇÃO: Para evitar choques, desconectar da corrente elétrica antes de fazer a
instalação ou a manutenção. Instalar em caixa apropriada. Manter livre de
contaminantes.
警告:感電事故防止のため、取付けまたは修理の際は電源から取り外してく
ださい。適切なケース内に取付けてください。また、汚染物質がないことを
確認してください。
警告 为了防止触电,在安装或维修之前必须先切断电源。安装在合适的设备
箱内。防止接触污染物。
A
B
C
D
Clack!
1
E
F
G
H
I
J
Required Tools
Phase
Barriers
M
M4
xx lb-in
xx Nm
L 0.394"
(10mm)
CH 8
3p Spreader 4p Spreader
Back Shield Back Shield
3p140G2-K-PB3L
Terminals
4p140G2-K-PB4L
140G2-K-EXS3 3p
1
-
3
1
-
1
-
1
2
3
140G2-K-EXS4 4p
-
1
4
1
1
-
1
1
3
4
Publication 140G-IN222B-EN-P - April 2022
TX 25
Spreader Terminals for 140G2-K, 140G2-L, 140MG2-K, 140MG2-L
2
1
2
140G2-K-EXS3
3
H
CH 8
36 Nm
319 lb in
2
F
1
B
D
1
4
140G2-K-EXS3
H
5
36 Nm
319 lb in
TX 25
2
G
140G2-K-EXS4
CH 8
1
1.2 Nm
10.6 lb in
E
D
6
140G2-K-EXS4
7
I
TX 25
1
2
1.2 Nm
10.6 lb in
Publication 140G-IN222B-EN-P - April 2022
DIR 1002011A1803 (Version 01)
Spreader Terminals for 140G2-K, 140G2-L, 140MG2-K, 140MG2-L
8
140G2-K-EXS3
9
140G2-K-EXS4
Publication 140G-IN222B-EN-P - April 2022
DIR 1002011A1803 (Version 01)
3
4
Spreader Terminals for 140G2-K, 140G2-L, 140MG2-K, 140MG2-L
10
PH 1
140G2-K-EXS3, 140G2-K-EXS4: ≥500V AC (≥250V DC) or REVERSE FEED Insulation Requirements
≥500V AC *
(≥250V DC)*
B
3
4.4 lb-in
0.5 Nm
REQUIRED: 140G2-K-TC3S, 140G2-K-TC4S
Ordered separately
Refer to the IN233 for installation requirements
3
*Breakers and accessories are tested for conformance
to governing body standards with insulated cable or
busbar. Any other configuration must be tested in the
installation at the cost of the customer
For Technical Support, visit rok.auto/support.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Product certificates are located in the Rockwell Automation Literature Library: rok.auto/certifications.
EEE Yönetmeliğine Uygundur.
TM
expanding human possibility
AMERICAS
EUROPE/MIDDLE EAST/AFRICA
ASIA PACIFIC
Publication 140G-IN222B-EN-P - April 2022
Copyright © 2022 Rockwell Automation, Inc. Al l Rights Reserved. Printed in USA.
DIR 1002011A1803 (Version 01)
(ECN000231036) - ECN000231036
">