MILLENIUM NTR 735 A Simple Automation Control Module INSTALLATION MANUAL

MILLENIUM NTR 735 A Simple Automation Control Module INSTALLATION MANUAL
Show PDF Add to My manuals

MILLENIUM NTR 735 A is a Simple Automation Control Module designed for use in domestic, office and industrial applications. It can manage all the sensors and actuators in the installation and features a display on the front panel to check the system's status. It offers ease of programming, WINDOWS-based software, compact size, EEPROM module backup, real-time clock, and high breaking capacity outputs. It can be used for various applications such as lighting, air conditioning, irrigation, doors, barriers, simple safety systems, greenhouses, and ventilation.

advertisement

MILLENIUM
INSTALLATION MANUAL
NTR 735 A
Simple Automation Control Module (MAS)
MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_ installation_ manual.doc 07/1999 - 1/8
Table of contents
1. INTRODUCTION 1
2. HARDWARE DESCRIPTION 2
3. INSTALLATION 5
4. CONNECTION 6
5. USER SAFETY AND PROTECTION OF EQUIPMENT 8
1. Introduction
The MILLENIUM series has been designed for use in domestic, office and industrial applications. Each module
can be used to manage all the sensors and actuators in the installation. A display on the front panel can be used
to check the state of your system at any time.
The MILLENIUM series is characterised by :
• Ease of programming and parameter entry
• WINDOWS-based programming software
• Compact size
• EEPROM module backup
• Realtime clock as standard
• Output with high breaking capacity
The MILLENIUM series has been designed for simple automation control modules (examples : lighting, air
conditioning, irrigation, doors, barriers, simple safety systems, greenhouses, ventilation). The realtime clock
allows equipment to be programmed in hours or minutes.
MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_ installation_ manual.doc 07/1999 - 2/8
2. Hardware description
2.1 Part numbers
Codes Part numbers Power supply Inputs Outputs Dimensions Weight
Type No. Type No. mm kg
89 750 001 MAS 6 RCA 100 - 240V AC 100 - 240V AC 4 RELAY 2
89 750 002 MAS 10 RCA 100 - 240V AC 100 - 240V AC 6 RELAY 4 71.2 x 90 x 55 0.2
89 750 003 MAS 10 RCD 24V DC 24V DC 6 RELAY 4
89 750 004 MAS 20 RCA* 100 - 240V AC 100 - 240V AC 12 RELAY 8 124.6 x 90 x 55
89 750 005 MAS 20 RCD* 24V DC 24V DC 12 RELAY 8
* Available from Q4/1999.
2.2 Description of power supplies
Description Code Specification
Power supply MAS x RCA 100 - 240V AC, +10% -15%, 50/60 Hz
MAS x RCD 24V DC, +20% -15%
Micro-cuts MAS x RCA 10ms
MAS x RCD 5ms
Current peak 240V AC 1.5 A t < 0.3 ms
24 V DC 7 A t < 0.2 ms
MAS 6 RCA, 264V AC 3 VA
Maximum consumption MAS 10 RCA, 264V AC 4 VA
MAS 10 RCD, 28.8V DC 3 W
MAS 6 RCA, 240V AC active I/O : 2.5 VA, deactivated I/O : 1.5 VA
MAS 6 RCA, 120V AC active I/O : 2 VA, deactivated I/O : 1.2 VA
MAS 10 RCA, 240V AC active I/O : 3 VA, deactivated I/O : 1.5 VA
Typical consumption MAS 10 RCA, 120V AC active I/O : 2 VA, deactivated I/O : 1.2 VA
MAS 10 RCD, 24V DC active I/O : 2 W, deactivated I/O : 0.3 W
MAS 20 RCA, 240V AC
MAS 20 RCA, 120V AC
MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_ installation_ manual.doc 07/1999 - 3/8
2.3 Description of inputs
Description Description of AC inputs
Input voltage 100 - 240V AC, +10% -15%, 50/60 Hz
Input impedance 800 k Ohms
Level 0 40V AC
Level 1 80V AC
Response time 25 ms min, 130 ms max.
Galvanic isolation No
Status indication LCD display
Description Description of DC inputs
Input voltage 24V DC +20% -15%
Current consumption 5 mA
Level 0 4V
Level 1 18V
Response time 15 ms
Galvanic isolation No
Status indication LCD display
Description Description of analogue inputs
MAS 10 RCD 6 Inputs: I 01 – I 06
MAS 20 RCD 8 Inputs: I 01 – I 08
Number of bits 8
Resolution (10000 / 250) mV
Conversion time 15 +/- 5ms
Input voltage 0 - 10V DC
Input impedance 150 k Ohms max.
Precision +/- 5%
Default Offset/ Gain Offset = 0
Gain = 1
These values can be changed by the program
Temp. dependent derating +/- 3 LSB on the authorised range
2.4 Description of relay outputs
Description Description of relay outputs
Max. operating voltage 250V AC, 30V DC
Max. operating current 8A / point
Minimum load 10mA at 5V DC
Response time 10ms
Type of contact Gold-plated silver
Status indication LCD display
Category
of use
Max. operating
voltage
Power consumption
in steady state
Durability
(number of operations)
Max. ops /
hour
AC15 (electromagnet) 250V AC 450 VA 100000 600
DC13 (electromagnet)
(L/R = 150 ms)
30V DC 10 W 100000 360
AC14 (electromagnet) 250V AC 750 VA 100000 600
AC12 (resistive) 250V AC 2000 VA 100000 1800
DC12 (resistive) 30V DC 192 W 100000 1800
5
6
7
8
9
  • Page 1
  • Page 2
  • Page 3
  • Page 4
  • Page 5
  • Page 6
  • Page 7
  • Page 8
  • Page 9
/

advertisement

Key Features

  • Ease of programming
  • WINDOWS-based software
  • Compact size
  • EEPROM module backup
  • Real-time clock
  • High breaking capacity outputs
  • Front panel display

Related manuals

Frequently Answers and Questions

What is the intended use of the MILLENIUM NTR 735 A?
The MILLENIUM NTR 735 A is designed for use as a simple automation control module for various applications such as lighting, air conditioning, irrigation, doors, barriers, simple safety systems, greenhouses, and ventilation.
What are the key features of the MILLENIUM NTR 735 A?
The MILLENIUM NTR 735 A offers ease of programming, WINDOWS-based software, compact size, EEPROM module backup, real-time clock, and high breaking capacity outputs. It also features a front panel display for checking the system's status.
What are the input and output capabilities of the MILLENIUM NTR 735 A?
The MILLENIUM NTR 735 A offers various input and output options, including AC and DC inputs, analog inputs, and relay outputs. More detailed information about the specific input and output capabilities can be found in the manual.
What are the mounting options for the MILLENIUM NTR 735 A?
The MILLENIUM NTR 735 A can be mounted on a 35 mm DIN rail or panel mounted using M4 screws.