NOTIFIER FRM-1 Relay Control Module Installation Guide
Notifier FRM-1 is a relay control module designed for use in intelligent, two-wire systems. It allows a compatible control panel to switch discrete contacts by code command. The relay contains two isolated sets of Form-C contacts, which operate as a DPDT switch and are rated for a variety of loads. The module also has a panel controlled LED indicator. This module can be used to replace a CMX-2 module that has been configured for Form-C operation.
advertisement
NO-460-006 1 I56-3502-003
FRM-1 Relay Control Module
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate Notifier control panel installation manual for detailed system
information. If the modules will be installed in an existing operational sys-
tem, inform the operator and local authority that the system will be tempo-
rarily out of service. Disconnect power to the control panel before installing
the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FRM-1 Relay Control Module is intended for use in intelligent, two-wire
systems where the individual address of each module is selected using the
built-in rotary switches. It allows a compatible control panel to switch discrete
contacts by code command. The relay contains two isolated sets of Form-C
contacts, which operate as a DPDT switch and are rated in accordance with
the table in the manual. Circuit connections to the relay contacts are not su-
pervised by the module. The module also has a panel controlled LED indi-
cator. This module can be used to replace a CMX-2 module that has been
configured for Form-C operation.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panel (list available from Notifier).
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5 mA (LED on)
Average Operating Current: 230µA direct poll; 255µA group poll
EOL Resistance: Not used
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4.675˝ H x 4.275˝ W x 1.4˝ D (Mounts to a 4˝ square by 21
/8˝ deep box.)
Accessories: SMB500 Electrical Box; CB500 Barrier
I56-3502-003
INSTALLATION AND MAINTENANCE INSTRUCTIONS
FIGURE 1. CONTROLS AND INDICATORS:
C1071-00
MOUNTING
The FRM-1 mounts directly to 4-inch square electrical boxes (see Figure 2A).
The box must have a minimum depth of 21/8 inches. Surface mounted electri-
cal boxes (SMB500) are available from Notifier. The module can also mount to
the DNR(W) duct housing.
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
RELAY CONTACT RATINGS:
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
FRM-1 Relay Control Module
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate Notifier control panel installation manual for detailed system
information. If the modules will be installed in an existing operational sys-
tem, inform the operator and local authority that the system will be tempo-
rarily out of service. Disconnect power to the control panel before installing
the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FRM-1 Relay Control Module is intended for use in intelligent, two-wire
systems where the individual address of each module is selected using the
built-in rotary switches. It allows a compatible control panel to switch discrete
contacts by code command. The relay contains two isolated sets of Form-C
contacts, which operate as a DPDT switch and are rated in accordance with
the table in the manual. Circuit connections to the relay contacts are not su-
pervised by the module. The module also has a panel controlled LED indi-
cator. This module can be used to replace a CMX-2 module that has been
configured for Form-C operation.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panel (list available from Notifier).
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5 mA (LED on)
Average Operating Current: 230µA direct poll; 255µA group poll
EOL Resistance: Not used
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4.675˝ H x 4.275˝ W x 1.4˝ D (Mounts to a 4˝ square by 21
/8˝ deep box.)
Accessories: SMB500 Electrical Box; CB500 Barrier
I56-3502-003
INSTALLATION AND MAINTENANCE INSTRUCTIONS
FIGURE 1. CONTROLS AND INDICATORS:
C1071-00
MOUNTING
The FRM-1 mounts directly to 4-inch square electrical boxes (see Figure 2A).
The box must have a minimum depth of 21/8 inches. Surface mounted electri-
cal boxes (SMB500) are available from Notifier. The module can also mount to
the DNR(W) duct housing.
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
RELAY CONTACT RATINGS:
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
NO-460-006 2 I56-3502-003
©2011 Notifier
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
FIGURE 3. RELAY MODULE WIRING DIAGRAM:
MODULE
FROM PANEL OR
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
CONTROL
CONNECT MODULES TO LISTED COMPATIBLE
RELAY COMMON 1
RELAY COMMON 2
NORMALLY CLOSED 1
NORMALLY OPEN 2
NORMALLY CLOSED 2
MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS
NORMALLY OPEN 1
CONTROL PANELS ONLY
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
UNUSED
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
IF ANY WIRING TO TERMINALS 4 – 10 IS NONPOWER
LIMITED, THE CB500 BARRIER IS REQUIRED. THE CB500
INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST
BE PLACED OVER THE POWER LIMITED TERMINAL
INFORMATION ON THE NAMEPLATE LABEL.
C0946-00
FIGURE 2A. MODULE MOUNTING FIGURE 2B:
WITH BARRIER:
C1070-00
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
CB500 Module Barrier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and wiring. The barrier
must be inserted into a 4˝ × 4˝ × 21/8˝ junction box, and the control module
must be placed into the barrier and attached to the junction box (Figure 2A).
The power-limited wiring must be placed into the isolated quadrant of the
module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), see Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length
is 1/4“ to 3/8”). Exposed conductor should be secured under the clamping plate
and should not protrude beyond the terminal block area. Caution: Do not loop
wire under terminals. Break wire run to provide supervision of connections.
©2011 Notifier
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
FIGURE 3. RELAY MODULE WIRING DIAGRAM:
MODULE
FROM PANEL OR
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
CONTROL
CONNECT MODULES TO LISTED COMPATIBLE
RELAY COMMON 1
RELAY COMMON 2
NORMALLY CLOSED 1
NORMALLY OPEN 2
NORMALLY CLOSED 2
MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS
NORMALLY OPEN 1
CONTROL PANELS ONLY
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
UNUSED
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
IF ANY WIRING TO TERMINALS 4 – 10 IS NONPOWER
LIMITED, THE CB500 BARRIER IS REQUIRED. THE CB500
INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST
BE PLACED OVER THE POWER LIMITED TERMINAL
INFORMATION ON THE NAMEPLATE LABEL.
C0946-00
FIGURE 2A. MODULE MOUNTING FIGURE 2B:
WITH BARRIER:
C1070-00
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
CB500 Module Barrier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and wiring. The barrier
must be inserted into a 4˝ × 4˝ × 21/8˝ junction box, and the control module
must be placed into the barrier and attached to the junction box (Figure 2A).
The power-limited wiring must be placed into the isolated quadrant of the
module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), see Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length
is 1/4“ to 3/8”). Exposed conductor should be secured under the clamping plate
and should not protrude beyond the terminal block area. Caution: Do not loop
wire under terminals. Break wire run to provide supervision of connections.
advertisement
Key Features
- Compatible with Notifier system control panels
- Two isolated sets of Form-C contacts
- Panel controlled LED indicator
- Can replace a CMX-2 module configured for Form-C operation
- Can be used to switch discrete contacts by code command
- Mounts to a 4" square by 21/8" deep box
- Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
- Humidity: 10% to 93% Non-condensing
Related manuals
Frequently Answers and Questions
What is the maximum current draw for the FRM-1?
6.5 mA (LED on)
What is the average operating current for the FRM-1?
230µA direct poll; 255µA group poll
What is the temperature range for the FRM-1?
32˚F to 120˚F (0˚C to 49˚C)
What is the humidity range for the FRM-1?
10% to 93% Non-condensing
What are the dimensions of the FRM-1?
4.675˝ H x 4.275˝ W x 1.4˝ D