Contrel MR-DI16 Extension module Owner's Manual
The Contrel MR-DI16 Extension module is a modular DIN-rail device with 16 isolated digital inputs. It's designed to expand the input capabilities of Contrel electronic devices equipped with RS485 communication. Each input can be configured as normally open or normally closed using dip switches, allowing for versatile applications. The MR-DI16 utilizes Modbus RTU protocol for seamless integration with supervision systems.
advertisement
pag. 1 / 4
MANUALE OPERATIVO / INSTRUCTION MANUAL
IM1302-IU v0.1
MR-DI16
Modulo di espansione
16 ingressi digitali
MR-DI16
Expansion unit
16 digital inputs
MANUALE OPERATIVO / INSTRUCTION MANUAL
IM1302-IU v0.1
MR-DI16
Modulo di espansione
16 ingressi digitali
MR-DI16
Expansion unit
16 digital inputs
pag. 2 / 4
ATTENZIONE!!!
Leggere attentamente il manuale prima dell’utilizzo e l’installazione.
Questi strumenti devono essere installati da personale qualificato, nel
rispetto delle vigenti normative impiantistiche, allo scopo di evitare danni
a persone o cose.
Prima di qualsiasi intervento sullo strumento, togliere tensione dagli
ingressi di alimentazione e dalle uscite relè dove presenti.
Il costruttore non si assume responsabilità in merito alla sicurezza
elettrica in caso di utilizzo improprio del dispositivo.
I prodotti descritti in questo documento sono suscettibili in qualsiasi
momento di evoluzioni o di modifiche.
Introduzione
Il modulo MR-DI16 include 16 ingressi digitali isolati. Questo modulo può
essere inoltre collegato ad apparecchi Contrel elettronica provvisti di
interfaccia di comunicazione RS485 dove si necessita di un numero
maggiore di ingressi.
E’ possibile configurare ogni ingresso come normalmente aperto o
normalmente chiuso, attraverso i relativi dip-switch.
Il modulo MR-DI16 è dotato di un'interfaccia RS-485 con protocollo Modbus
per consentire l'integrazione nei sistemi di supervisione. Le impostazioni dei
parametri di comunicazione vengono definiti attraverso il relativo dip switch di
configurazione.
Descrizione
Esecuzione modulare, 6 moduli per guida DIN
16 ingressi digitali configurabili NA o NC
1 LED verde di segnalazione alimentazione
16 LED rossi di indicazione dello stato degli ingressi
1 LED giallo di segnalazione comunicazione dati
Dip switch di programmazione
Interfaccia di comunicazione RS485 integrata (Modbus RTU)
Operatori
Dip switch di programmazione
Configurazione contatti ingressi N.O. – N.C.
N.O. = contatto normalmente aperto; in questa condizione significa che “in
stato di riposo” il circuito rimane aperto.
N.C. = contatto normalmente chiuso; in questa condizione significa che “in
stato di riposo” il circuito rimane chiuso.
Porta seriale
SW1-2 = impostazione baud rate comunicazione: 38,4 K-19,2 K-9,6 K-4,8 K
SW1 SW2 Baud rate (Kbps)
OFF OFF 4,8
OFF ON 9,6
ON OFF 19,2
ON ON 38,4
WARNING!
Carefully read the manual before the installation or use.
This device is to be installed by qualified personnel, complying to current
standards, to avoid damages.
Before any maintenance operation on the device, remove supply inputs.
The manufacturer cannot be held responsible for electrical safety in case
of improper use of the equipment.
Products illustrated herein are subject to alteration and changes without
prior notice.
Introduction
The MR-DI16 module includes 16 isolated digital inputs. This module can
also be connected to Contrel elettronica devices equipped with an
RS485 communication interface where a greater number of inputs is
required.
It is possible to configure each input as normally open or normally closed,
through the relative dip-switches.
The MR-DI16 is also provided with a RS-485 interface with Modbus protocol
to consent the integration in supervision systems.
The communication set-up is done directly from the proper setting
dip switch.
Description
Modular DIN-rail housing, 6 modules
16 digital inputs configurable as NO or NC
1 green LED indicator for power supply
16 red LED indicator for digital inputs status
1 yellow LED indicator for data communication
Dip switch settings
Built-in RS485 interface (Modbus RTU)
Operators
Dip switch settings
Inputs setting N.O. – N.C.
N.O. = normally open contact; in this condition it means that “in the idle state”
the circuit remains open.
N.C. = normally closed contact; in this condition it means that “in the idle
state” the circuit remains closed.
Serial Ports
SW1-2 = setting communication baud rate: 38,4 K-19,2 K-9,6 K-4,8 K
SW1 SW2 Baud rate (Kbps)
OFF OFF 4,8
OFF ON 9,6
ON OFF 19,2
ON ON 38,4
LED presenza
alimentazione
LED traffico dati
comunicazione RS485
LED power
supply present
LED Data traffic
on the RS485
Dip switch serial port
settings
Dip switch input 9..16
setting
Dip switch input 1..8
setting
LED
stato ingressi (1..16) LED
inputs status (1..16)
Dip switch config.
porta seriale
Dip switch config.
ingressi 9..16
Dip switch config.
ingressi 1..8
ATTENZIONE!!!
Leggere attentamente il manuale prima dell’utilizzo e l’installazione.
Questi strumenti devono essere installati da personale qualificato, nel
rispetto delle vigenti normative impiantistiche, allo scopo di evitare danni
a persone o cose.
Prima di qualsiasi intervento sullo strumento, togliere tensione dagli
ingressi di alimentazione e dalle uscite relè dove presenti.
Il costruttore non si assume responsabilità in merito alla sicurezza
elettrica in caso di utilizzo improprio del dispositivo.
I prodotti descritti in questo documento sono suscettibili in qualsiasi
momento di evoluzioni o di modifiche.
Introduzione
Il modulo MR-DI16 include 16 ingressi digitali isolati. Questo modulo può
essere inoltre collegato ad apparecchi Contrel elettronica provvisti di
interfaccia di comunicazione RS485 dove si necessita di un numero
maggiore di ingressi.
E’ possibile configurare ogni ingresso come normalmente aperto o
normalmente chiuso, attraverso i relativi dip-switch.
Il modulo MR-DI16 è dotato di un'interfaccia RS-485 con protocollo Modbus
per consentire l'integrazione nei sistemi di supervisione. Le impostazioni dei
parametri di comunicazione vengono definiti attraverso il relativo dip switch di
configurazione.
Descrizione
Esecuzione modulare, 6 moduli per guida DIN
16 ingressi digitali configurabili NA o NC
1 LED verde di segnalazione alimentazione
16 LED rossi di indicazione dello stato degli ingressi
1 LED giallo di segnalazione comunicazione dati
Dip switch di programmazione
Interfaccia di comunicazione RS485 integrata (Modbus RTU)
Operatori
Dip switch di programmazione
Configurazione contatti ingressi N.O. – N.C.
N.O. = contatto normalmente aperto; in questa condizione significa che “in
stato di riposo” il circuito rimane aperto.
N.C. = contatto normalmente chiuso; in questa condizione significa che “in
stato di riposo” il circuito rimane chiuso.
Porta seriale
SW1-2 = impostazione baud rate comunicazione: 38,4 K-19,2 K-9,6 K-4,8 K
SW1 SW2 Baud rate (Kbps)
OFF OFF 4,8
OFF ON 9,6
ON OFF 19,2
ON ON 38,4
WARNING!
Carefully read the manual before the installation or use.
This device is to be installed by qualified personnel, complying to current
standards, to avoid damages.
Before any maintenance operation on the device, remove supply inputs.
The manufacturer cannot be held responsible for electrical safety in case
of improper use of the equipment.
Products illustrated herein are subject to alteration and changes without
prior notice.
Introduction
The MR-DI16 module includes 16 isolated digital inputs. This module can
also be connected to Contrel elettronica devices equipped with an
RS485 communication interface where a greater number of inputs is
required.
It is possible to configure each input as normally open or normally closed,
through the relative dip-switches.
The MR-DI16 is also provided with a RS-485 interface with Modbus protocol
to consent the integration in supervision systems.
The communication set-up is done directly from the proper setting
dip switch.
Description
Modular DIN-rail housing, 6 modules
16 digital inputs configurable as NO or NC
1 green LED indicator for power supply
16 red LED indicator for digital inputs status
1 yellow LED indicator for data communication
Dip switch settings
Built-in RS485 interface (Modbus RTU)
Operators
Dip switch settings
Inputs setting N.O. – N.C.
N.O. = normally open contact; in this condition it means that “in the idle state”
the circuit remains open.
N.C. = normally closed contact; in this condition it means that “in the idle
state” the circuit remains closed.
Serial Ports
SW1-2 = setting communication baud rate: 38,4 K-19,2 K-9,6 K-4,8 K
SW1 SW2 Baud rate (Kbps)
OFF OFF 4,8
OFF ON 9,6
ON OFF 19,2
ON ON 38,4
LED presenza
alimentazione
LED traffico dati
comunicazione RS485
LED power
supply present
LED Data traffic
on the RS485
Dip switch serial port
settings
Dip switch input 9..16
setting
Dip switch input 1..8
setting
LED
stato ingressi (1..16) LED
inputs status (1..16)
Dip switch config.
porta seriale
Dip switch config.
ingressi 9..16
Dip switch config.
ingressi 1..8
pag. 3 / 4
SW3-8 = impostazione indirizzo nodo seriale: 1...32
SW3 SW4 SW5 SW6 SW7 SW8 Nodo seriale
OFF OFF OFF OFF OFF ON 1
OFF OFF OFF OFF ON OFF 2
OFF OFF OFF OFF ON ON 3
OFF OFF OFF ON OFF OFF 4
………………………………………… …..
ON ON ON ON ON ON 32
OFF OFF OFF OFF OFF OFF Impostazioni interne
Funzione dei LED frontali
NOME COLORE DESCRIZIONE
ON Verde Acceso:
Presenza alimentazione
Spento: Il modulo MR-DI16 non è
alimentato o è guasto
DATA Giallo Spento: Assenza di comunicazione sulla
linea seriale RS485
Lampeggio: Traffico dati sulla seriale
RS485
INn
(n=1..16)
Rosso Spento: Ingresso a riposo
Acceso: Ingresso impegnato
Disposizione morsetti
Dimensioni meccaniche (mm)
SW3-8 = setting serial node address: 1..32
SW3 SW4 SW5 SW6 SW7 SW8 Node address
OFF OFF OFF OFF OFF ON 1
OFF OFF OFF OFF ON OFF 2
OFF OFF OFF OFF ON ON 3
OFF OFF OFF ON OFF OFF 4
…………………………………………
ON ON ON ON ON ON 32
OFF OFF OFF OFF OFF OFF Internal settings
Front LED functions
NAME COLOUR DESCRIPTION
ON Green Switched ON: Power supply present on
the unit
Switched OFF: MR-DI16 is not powered
or it is broken
DATA Yellow Switched OFF: No communication on
the RS485
Blinking: Data traffic on the RS485
interface
INn
(n=1..16)
Red Switched OFF: Input not active
Switched ON: Input active
Terminals position
Mechanical dimensions (mm)
SW3-8 = impostazione indirizzo nodo seriale: 1...32
SW3 SW4 SW5 SW6 SW7 SW8 Nodo seriale
OFF OFF OFF OFF OFF ON 1
OFF OFF OFF OFF ON OFF 2
OFF OFF OFF OFF ON ON 3
OFF OFF OFF ON OFF OFF 4
………………………………………… …..
ON ON ON ON ON ON 32
OFF OFF OFF OFF OFF OFF Impostazioni interne
Funzione dei LED frontali
NOME COLORE DESCRIZIONE
ON Verde Acceso:
Presenza alimentazione
Spento: Il modulo MR-DI16 non è
alimentato o è guasto
DATA Giallo Spento: Assenza di comunicazione sulla
linea seriale RS485
Lampeggio: Traffico dati sulla seriale
RS485
INn
(n=1..16)
Rosso Spento: Ingresso a riposo
Acceso: Ingresso impegnato
Disposizione morsetti
Dimensioni meccaniche (mm)
SW3-8 = setting serial node address: 1..32
SW3 SW4 SW5 SW6 SW7 SW8 Node address
OFF OFF OFF OFF OFF ON 1
OFF OFF OFF OFF ON OFF 2
OFF OFF OFF OFF ON ON 3
OFF OFF OFF ON OFF OFF 4
…………………………………………
ON ON ON ON ON ON 32
OFF OFF OFF OFF OFF OFF Internal settings
Front LED functions
NAME COLOUR DESCRIPTION
ON Green Switched ON: Power supply present on
the unit
Switched OFF: MR-DI16 is not powered
or it is broken
DATA Yellow Switched OFF: No communication on
the RS485
Blinking: Data traffic on the RS485
interface
INn
(n=1..16)
Red Switched OFF: Input not active
Switched ON: Input active
Terminals position
Mechanical dimensions (mm)
pag. 4 / 4
Caratteristiche tecniche
Alimentazione ausiliaria
Tensione nominale 90 – 250 VCA/CC
Frequenza 50 – 60 Hz
Potenza assorbita/dissipata <10VA / <3W
Ingressi digitali
Numero di ingressi 16
Tipo di ingresso Configurabile N.O. / N.C.
Corrente di ingresso 5 mA max
Tensione presente sui morsetti 24 o 48 o 115 o 230 VCA/CC
(specificare in fase d’ordine)
Interfaccia seriale RS485
Indirizzo nodo seriale 01-247
Baud-rate Programmabile 4800 – 115200 bps
Formati dati 8 bit, no parità
8 bit, dispari
8 bit, pari
Stop bits 1-2
Protocollo Modbus RTU
Isolamento
Tensione d‘isolamento 3.5kV per 1 minuto
Contenitore
Esecuzione 6 moduli DIN
Grado di protezione IP40 sul fronte
IP20 connessioni
Peso 300g
Condizioni ambientali
Temperatura d’impiego 0…+60 °C
Temperatura di stoccaggio -10…+70 °C
Umidità relativa 5…95%
Conformità
Conformità a norme EN 50081-2, 1992 - EN 55022-
CLASSE B CISPR 22, EN 50082-1,
1992 - EN 61000-6-2, EN61010-2
Per ulteriori informazioni contattare:
Contrel elettronica s.r.l.
Via San Fereolo, 9
I-26900 Lodi
Tel: +39 0371 30207 / 30761 / 35386
Fax: +39 0371 32819
E-Mail: [email protected]
www.contrel.it
Technical characteristics
Auxiliary supply
Rated voltage 90 – 250 VAC/DC
Frequency 50 – 60 Hz
Power consumption/dissapation <10VA / <3W
Digital inputs
Number of inputs 16
Input type Programmable N.O. / N.C.
Current input 5 mA max
Voltage presents on terminals 24 or 48 or 115 or 230 VAC/DC
(specify when ordering)
RS485 Serial interface
Serial node address 01-247
Baud-rate Programmable 4800 – 115200 bps
Data format 8 bit, no parity
8 bit, odd
8 bit, even
Stop bits 1-2
Protocol Modbus RTU
Insulation
Insulation voltage 3.5kV for 1 minute
Housing
Mouting 6 modules DIN
Protection degree IP40 on front
IP20 terminals
Weight 300g
Ambient conditions
Operating temperature 0…+60 °C
Storage temperature -10…+70 °C
Relative humidity 5…95%
Compliance
Reference standards EN 50081-2, 1992 - EN 55022-
CLASSE B CISPR 22, EN 50082-1,
1992 - EN 61000-6-2, EN61010-2
For further details please contact:
Caratteristiche tecniche
Alimentazione ausiliaria
Tensione nominale 90 – 250 VCA/CC
Frequenza 50 – 60 Hz
Potenza assorbita/dissipata <10VA / <3W
Ingressi digitali
Numero di ingressi 16
Tipo di ingresso Configurabile N.O. / N.C.
Corrente di ingresso 5 mA max
Tensione presente sui morsetti 24 o 48 o 115 o 230 VCA/CC
(specificare in fase d’ordine)
Interfaccia seriale RS485
Indirizzo nodo seriale 01-247
Baud-rate Programmabile 4800 – 115200 bps
Formati dati 8 bit, no parità
8 bit, dispari
8 bit, pari
Stop bits 1-2
Protocollo Modbus RTU
Isolamento
Tensione d‘isolamento 3.5kV per 1 minuto
Contenitore
Esecuzione 6 moduli DIN
Grado di protezione IP40 sul fronte
IP20 connessioni
Peso 300g
Condizioni ambientali
Temperatura d’impiego 0…+60 °C
Temperatura di stoccaggio -10…+70 °C
Umidità relativa 5…95%
Conformità
Conformità a norme EN 50081-2, 1992 - EN 55022-
CLASSE B CISPR 22, EN 50082-1,
1992 - EN 61000-6-2, EN61010-2
Per ulteriori informazioni contattare:
Contrel elettronica s.r.l.
Via San Fereolo, 9
I-26900 Lodi
Tel: +39 0371 30207 / 30761 / 35386
Fax: +39 0371 32819
E-Mail: [email protected]
www.contrel.it
Technical characteristics
Auxiliary supply
Rated voltage 90 – 250 VAC/DC
Frequency 50 – 60 Hz
Power consumption/dissapation <10VA / <3W
Digital inputs
Number of inputs 16
Input type Programmable N.O. / N.C.
Current input 5 mA max
Voltage presents on terminals 24 or 48 or 115 or 230 VAC/DC
(specify when ordering)
RS485 Serial interface
Serial node address 01-247
Baud-rate Programmable 4800 – 115200 bps
Data format 8 bit, no parity
8 bit, odd
8 bit, even
Stop bits 1-2
Protocol Modbus RTU
Insulation
Insulation voltage 3.5kV for 1 minute
Housing
Mouting 6 modules DIN
Protection degree IP40 on front
IP20 terminals
Weight 300g
Ambient conditions
Operating temperature 0…+60 °C
Storage temperature -10…+70 °C
Relative humidity 5…95%
Compliance
Reference standards EN 50081-2, 1992 - EN 55022-
CLASSE B CISPR 22, EN 50082-1,
1992 - EN 61000-6-2, EN61010-2
For further details please contact:
advertisement
Key Features
- 16 isolated digital inputs
- Modular DIN-rail housing
- NO/NC configurable inputs
- RS485 interface with Modbus RTU protocol
- LED indicators for power, inputs, and communication
- Dip switch configuration
Related manuals
Frequently Answers and Questions
How many digital inputs does the MR-DI16 module have?
The MR-DI16 module offers 16 isolated digital inputs.
Can I configure the inputs as normally open or normally closed?
Yes, each input can be configured as either normally open (NO) or normally closed (NC) using the dip switches on the module.
What communication protocol does the MR-DI16 use?
The MR-DI16 module uses the Modbus RTU protocol for communication over RS485.
What is the purpose of the LED indicators?
The LED indicators provide visual feedback on the module's status. The green LED indicates power supply, the red LEDs show the status of each input, and the yellow LED indicates data communication activity.
advertisement