Contrel MR-R8 Extension module Owner's Manual

Contrel MR-R8 Extension module Owner's Manual

The Contrel MR-R8 Extension module is a powerful and versatile device designed to expand the capabilities of your Contrel system. This module allows you to add 8 independent relay outputs to your system. Each output is configurable as normally open (NO) or normally closed (NC), providing flexibility in your applications. The MR-R8 module is equipped with a RS-485 interface with Modbus protocol, enabling seamless integration with supervision systems. The communication settings are easily configured using the integrated DIP switch. The MR-R8 module has a compact modular design suitable for DIN rail mounting.

advertisement

pag. 1 / 4
MANUALE OPERATIVO / INSTRUCTION MANUAL

IM1300-IU v0.1

MR-R8

Scheda ripetizione relè

MR-R8

Relais output board
pag. 2 / 4
ATTENZIONE!!!

Leggere attentamente il manuale prima dell’utilizzo e l’installazione.

Questi strumenti devono essere installati da personale qualificato, nel

rispetto delle vigenti normative impiantistiche, allo scopo di evitare danni
a persone o cose.

Prima di qualsiasi intervento sullo strumento, togliere tensione dagli
ingressi di alimentazione e dalle uscite relè dove presenti.

Il costruttore non si assume responsabilità in merito alla sicurezza
elettrica in caso di utilizzo improprio del dispositivo.

I prodotti descritti in questo documento sono suscettibili in qualsiasi
momento di evoluzioni o di modifiche.

Introduzione

Il modulo MRR include 8 uscite a relè indipendenti tra loro. Questo modulo
può essere inoltre collegato ad apparecchi Contrel elettronica provvisti di
interfaccia di comunicazione RS485.

Le funzionalità delle uscite vengono definiti attraverso i relativi menu di
configurazione dello strumento base.

L‘MRR
è dotato di un'interfaccia RS-485 con protocollo Modbus per
consentire l'integrazione nei sistemi di supervisione. Le impostazioni dei
parametri di comunicazione vengono definiti attraverso il relativo dip switch
di configurazione.

Descrizione

Esecuzione modulare, 6 moduli per guida DIN

8 uscite a relè con contatto in scambio configurabile NA o NC

1 LED verde di segnalazione alimentazione

8 LED rossi di indicazione dello stato del relè

Dip switch di programmazione

Interfaccia di comunicazione RS485 integrata (Modbus RTU)

Dip switch di programmazione

Relay Fail Safe N F.S.

F.S. = sicurezza positiva attivata; in questa condizione il relè di uscita è
normalmente eccitato

N = sicurezza positiva disattivata. Relè di uscita normalmente diseccitato.

Serial Ports

SW1-2 = impostazione baud rate comunicazione: 38,4 K-19,2 K-9,6 K-4,8 K

SW2
SW1 Baud rate (Kbps)
OFF
OFF 4,8
ON
OFF 9,6
OFF
ON 19,2
ON
ON 38,4
SW3-8 = impostazione indirizzo nodo seriale: 1...32

SW8
SW7 SW6 SW5 SW4 SW3 Nodo seriale
ON
OFF OFF OFF OFF OFF 1
OFF
ON OFF OFF OFF OFF 2
ON
ON OFF OFF OFF OFF 3
OFF
OFF ON OFF OFF OFF 4
…………………………………………
…..
ON
ON ON ON ON ON 32
OFF
OFF OFF OFF OFF OFF Impostazioni interne
Funzione dei LED frontali

NOME
COLORE DESCRIZIONE
ON
Verde Acceso:
Presenza alimentazione

Spento: Il modulo non è alimentato o è
guasto

DATA
Giallo Spento: Assenza di comunicazione sulla
linea seriale RS485

Lampeggio: Traffico dati sulla seriale
RS485

OUTn

(n=1..8)

Rosso
Spento: Uscita relè non attiva
Acceso: Uscità relè attiva

WARNING!

Carefully read the manual before the installation or use.

This device is to be installed by qualified personnel, complying to current
standards, to avoid damages.

Before any maintenance operation on the device, remove supply inputs.

The manufacturer cannot be held responsible for electrical safety in case
of improper use of the equipment.

Products illustrated herein are subject to alteration and changes without

prior notice.

Introduction

The MRR module includes 8 relay outputs independent of each other. This
module can also be connected to Contrel elettronica devices equipped with
RS485 communication interface.

The outputs functionalities are done directly from the proper instrument
menu in an easy way.

The MRR is also provided with a RS-485 interface with Modbus protocol to
consent the integration in supervision systems. The communication set-up is
done directly from the proper setting dip switch.

Description

Modular DIN-rail housing, 6 modules

8 output relay with changeover contact configurable as NO or NC

1 green LED indicator for power supply

8 red LED indicator for output relay status

Dip switch settings

Built-in RS485 interface (Modbus RTU)

Dip switch settings

Relay Fail Safe N F.S.

F.S. = positive safety activated; in this condition the output realy is normally
energised.

N = postive safety deactivated. Output relay normally deenergised.

Serial Ports

SW1-2 = setting communication baud rate: 38,4 K-19,2 K-9,6 K-4,8 K

SW2
SW1 Baud rate (Kbps)
OFF
OFF 4,8
ON
OFF 9,6
OFF
ON 19,2
ON
ON 38,4
SW3-8 = setting serial node address: 1..32

SW8
SW7 SW6 SW5 SW4 SW3 Node address
ON
OFF OFF OFF OFF OFF 1
OFF
ON OFF OFF OFF OFF 2
ON
ON OFF OFF OFF OFF 3
OFF
OFF ON OFF OFF OFF 4
…………………………………………
…..
OFF
OFF OFF OFF OFF ON 32
OFF
OFF OFF OFF OFF OFF Internal settings
Front LED functions

NAME
COLOUR DESCRIPTION
ON
Green Switched ON: Power supply present on
the unit

Switched OFF: MRR is not powered or it
is broken

DATA
Yellow Switched OFF: No communication on
the RS485

Blinking: Data traffic on the RS485
interface

OUTn

(n=1..8)

Red
Switched OFF: Relay output not active
Switched ON: Relay output active
pag. 3 / 4
Schema di connessione

Dimensioni meccaniche (mm)

Caratteristiche tecniche

Alimentazione ausiliaria

Tensione nominale
90 250 VCA/CC
Frequenza
50 60 Hz
Potenza assorbita/dissipata
<10VA / <3W
Uscite relè

Uscite
8
Tipo di uscita
1 contatto in scambio
Tensione nominale di lavoro
250 VCA
Corrente nominale
6A
Tempo di intervento:
eccitazione/diseccitazione
6 ms / 4 ms
Vita meccanica
20x106 operazioni
Interfaccia seriale RS485

Indirizzo nodo seriale
01-247
Baud-rate
Programmabile 4800 115200 bps
Formati dati
8-none-1, 8-odd, 8-even
Stop bits
1-2
Protocollo
Modbus RTU
Isolamento

Tensione d‘isolamento
3.5kV per 1 minuto
Contenitore

Esecuzione
6 moduli DIN
Grado di protezione
IP40 sul fronte
IP20 connessioni

Peso
315g
Condizioni ambientali

Temperatura d’impiego
0…+60 °C
Temperatura di stoccaggio
-10…+70 °C
Umidità relativa
5…95%
Conformità

Conformità a norme
EN 50081-2, 1992 - EN 55022-
CLASSE B CISPR 22,
EN 50082-1,
1992 - EN 61000-6-2
, EN61010-2
Wiring connection

Mechanical dimensions (mm)

Technical characteristics

Auxiliary supply

Rated voltage
90 250 VAC/DC
Frequency
50 60 Hz
Power consumption/dissapation
<10VA / <3W
Output relays

Number of outputs
8
Type of output
1 changeover contact
Rated operating voltage
250 VAC
Rated current
6A
Operated/release

time
6 ms / 4 ms
Mechanical file
20x106 ops
RS485 Serial interface

Serial node address
01-247
Baud-rate
Programmable 4800 115200 bps
Data format
8-none-1, 8-odd, 8-even
Stop bits
1-2
Protocol
Modbus RTU
Insulation

Insulation voltage
3.5kV for 1 minute
Housing

Mouting
6 modules DIN
Protection degree
IP40 on front
IP20 terminals

Weight
315g
Ambient conditions

Operating temperature
0…+60 °C
Storage temperature
-10…+70 °C
Relative humidity
5…95%
Compliance

Reference standards

EN 50081-2, 1992 - EN 55022-
CLASSE B CISPR 22,
EN 50082-1,
1992 - EN 61000-6-2
, EN61010-2
pag. 4 / 4
Per ulteriori informazioni contattare:

Contrel elettronica s.r.l.

Via San Fereolo, 9

I-26900 Lodi

Tel: +39 0371 30207 / 30761 / 35386

E-Mail: [email protected]

www.contrel.it

For further details please contact:
  • Page 1
  • Page 2
  • Page 3
  • Page 4
/

advertisement

Key Features

  • 8 relay outputs
  • configurable NO/NC
  • RS-485 interface
  • Modbus protocol
  • DIN rail mounting
  • LED indicators
  • Fail-Safe option

Related manuals

Frequently Answers and Questions

What type of outputs does the MR-R8 module have?
The MR-R8 module provides 8 relay outputs with changeover contact configurable as NO or NC.
How do I configure the communication settings for the MR-R8 module?
The communication settings are configured using the integrated DIP switch on the module.
What communication protocol does the MR-R8 module support?
The MR-R8 module supports the Modbus RTU protocol.
Can I use the MR-R8 module with other Contrel devices?
Yes, the MR-R8 module can be connected to Contrel devices equipped with RS485 communication interface. The specific functionality is defined through the configuration menus of the base instrument.

advertisement