East EA900 User Manual
The EAST EA900 is a reliable uninterruptible power supply (UPS) designed for protecting sensitive electronics from power outages. It offers a range of features to ensure continuous operation, including backup time, overload protection, and communication capabilities. The EA900 comes with a user-friendly LCD display that shows key system parameters and provides alerts in case of any issues. It is suitable for various applications, including home offices, small businesses, and critical equipment requiring uninterrupted power.
advertisement
Table of Contents
1 Safety Information ................................................................................. 1
1.1 UPS safety information ........................................................................ 1
1.2 Battery safety information .................................................................... 1
2 Product Overview .................................................................................. 3
2.1 Specifications ...................................................................................... 3
2.2 Rear panel features ............................................................................. 5
3 Installation.............................................................................................. 7
3.1 Unpacking inspection .......................................................................... 7
3.2 Installation information......................................................................... 7
3.3 Installation and output connection ....................................................... 8
4 Network Functions ................................................................................ 9
4.1 Communication port ............................................................................ 9
4.2 EPO port(optional) .......................................................................... 9
4.3 Intelligent card (optional) ................................................................... 10
5 Operation.............................................................................................. 11
5.1 Button operation ................................................................................ 11
5.2 Display interface ................................................................................ 11
5.3 UPS On/Off operation ........................................................................ 13
5.4 UPS Settings ..................................................................................... 14
5.5 Parameters inquiring operation ......................................................... 15
5.6 Operation mode ................................................................................. 16
6 Fault Messages .................................................................................... 18
7 Troubleshooting .................................................................................. 22
8 Software Download & Installation ..................................................... 24
1 Safety Information ................................................................................. 1
1.1 UPS safety information ........................................................................ 1
1.2 Battery safety information .................................................................... 1
2 Product Overview .................................................................................. 3
2.1 Specifications ...................................................................................... 3
2.2 Rear panel features ............................................................................. 5
3 Installation.............................................................................................. 7
3.1 Unpacking inspection .......................................................................... 7
3.2 Installation information......................................................................... 7
3.3 Installation and output connection ....................................................... 8
4 Network Functions ................................................................................ 9
4.1 Communication port ............................................................................ 9
4.2 EPO port(optional) .......................................................................... 9
4.3 Intelligent card (optional) ................................................................... 10
5 Operation.............................................................................................. 11
5.1 Button operation ................................................................................ 11
5.2 Display interface ................................................................................ 11
5.3 UPS On/Off operation ........................................................................ 13
5.4 UPS Settings ..................................................................................... 14
5.5 Parameters inquiring operation ......................................................... 15
5.6 Operation mode ................................................................................. 16
6 Fault Messages .................................................................................... 18
7 Troubleshooting .................................................................................. 22
8 Software Download & Installation ..................................................... 24
1
1 Safety Information
1.1 UPS safety information
Read all safety information and operating instructions carefully before attempting to
install, service or maintain the UPS. Save this manual properly for reuse.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with fluids, or where there is
excessive dust or humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space against
the wall for proper ventilation.
Do not open the UPS case as you will, there is a high risk of electric shocks inside.
All connection/wiring/servicing must be performed by a qualified electrician.
Do not connect to the equipment like hair dryer or electric heater.
Do not use liquid extinguisher if there is a fire, a dry powder extinguisher is
recommended.
CAUTION
UPS has high voltage inside, do not repair it by yourself. If any questions, please
contact local service center or dealer.
1.2 Battery safety information
Environmental factors impact battery life. Elevated ambient temperatures, poor
quality utility power, and frequent short duration discharges will shorten battery life.
Replacing battery periodically can help to keep UPS in normal state and assure
backup time required.
Battery installing or replacing should be performed by a qualified electrician. If you
want to replace the battery cable, please purchase it from our local service center
or distributors to avoid fever and lighter which can cause fire by inadequate power
capacity.
Batteries may cause electric shocks and have a high short circuit current, follow
below requirements before installing or replacing the batteries.
A. Remove wristwatches, rings, jewelry and other conductive materials.
B. Only use tools with insulated grips and handles.
C. Wear insulated shoes and gloves.
D. Do not put the metal tools or parts on the batteries.
E. Before disconnecting the terminals from the batteries, cut off all the loads
to the batteries first.
1 Safety Information
1.1 UPS safety information
Read all safety information and operating instructions carefully before attempting to
install, service or maintain the UPS. Save this manual properly for reuse.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with fluids, or where there is
excessive dust or humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space against
the wall for proper ventilation.
Do not open the UPS case as you will, there is a high risk of electric shocks inside.
All connection/wiring/servicing must be performed by a qualified electrician.
Do not connect to the equipment like hair dryer or electric heater.
Do not use liquid extinguisher if there is a fire, a dry powder extinguisher is
recommended.
CAUTION
UPS has high voltage inside, do not repair it by yourself. If any questions, please
contact local service center or dealer.
1.2 Battery safety information
Environmental factors impact battery life. Elevated ambient temperatures, poor
quality utility power, and frequent short duration discharges will shorten battery life.
Replacing battery periodically can help to keep UPS in normal state and assure
backup time required.
Battery installing or replacing should be performed by a qualified electrician. If you
want to replace the battery cable, please purchase it from our local service center
or distributors to avoid fever and lighter which can cause fire by inadequate power
capacity.
Batteries may cause electric shocks and have a high short circuit current, follow
below requirements before installing or replacing the batteries.
A. Remove wristwatches, rings, jewelry and other conductive materials.
B. Only use tools with insulated grips and handles.
C. Wear insulated shoes and gloves.
D. Do not put the metal tools or parts on the batteries.
E. Before disconnecting the terminals from the batteries, cut off all the loads
to the batteries first.
2
Do not dispose of the batteries with fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte inside is harmful to the skin
and eyes, and maybe toxic.
Do not connect the positive pole and negative pole directly, otherwise it will cause
electric shocks or will be on fire.
The battery circuit is not isolated from the input voltage, high voltage may occur
between the battery terminals and ground, check if there is no voltage there before
touching.
Note:Symbol instructions:
Symbol Significations Symbol Significations
Caution Protective earth
Danger! High Voltage!
Disable/mute audible
alarm
Turn on Overload
Turn off Battery inspection
Standby or Shutdown Repeat
AC Display screen repeat key
DC Battery
Do not dispose of the batteries with fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte inside is harmful to the skin
and eyes, and maybe toxic.
Do not connect the positive pole and negative pole directly, otherwise it will cause
electric shocks or will be on fire.
The battery circuit is not isolated from the input voltage, high voltage may occur
between the battery terminals and ground, check if there is no voltage there before
touching.
Note:Symbol instructions:
Symbol Significations Symbol Significations
Caution Protective earth
Danger! High Voltage!
Disable/mute audible
alarm
Turn on Overload
Turn off Battery inspection
Standby or Shutdown Repeat
AC Display screen repeat key
DC Battery
3
2 Product Overview
2.1 Specifications
Model 1kVAS 2kVAS 3kVAS
Rated Capacity 1 kVA / 900W 2 kVA / 1800W 3 kVA / 2700W
Input
Rated input voltage 110 Vac / 115 Vac / 120 Vac / 127Vac
Rated input
frequency
50 Hz / 60 Hz (auto-sense)
Input voltage range
50 ~ 80Vac (power derating linearly between 50% and 100% load);
80 ~ 150Vac (no derating);
Input frequency
range
40~70 Hz
PFC ≥ 0.99
THDI ≤ 6%
Bypass voltage range -25% ~ +15% (settable)
Output
Output voltage 110 Vac / 115 Vac / 120 Vac / 127 Vac(settable)
Voltage accuracy ± 1%
Output PF 0.9
Inverter overload
capability
108% ~ 127% load: transfer to bypass in 1 min;
127% ~ 150% load: transfer to bypass in 30 s;
> 150% load: transfer to bypass in 100 ms
From mains mode to
BAT mode
0ms (transfer time)
From mains mode to
bypass
4 ms (typical)
Output
frequency
Line mode Same as input frequency
BAT mode (50 / 60 ± 0.1) Hz
Total voltage
harmonic distortion
≤ 2% (linear load); ≤ 5% (non-linear load)
Batteries
Battery type Sealed lead acid maintenance free battery
2 Product Overview
2.1 Specifications
Model 1kVAS 2kVAS 3kVAS
Rated Capacity 1 kVA / 900W 2 kVA / 1800W 3 kVA / 2700W
Input
Rated input voltage 110 Vac / 115 Vac / 120 Vac / 127Vac
Rated input
frequency
50 Hz / 60 Hz (auto-sense)
Input voltage range
50 ~ 80Vac (power derating linearly between 50% and 100% load);
80 ~ 150Vac (no derating);
Input frequency
range
40~70 Hz
PFC ≥ 0.99
THDI ≤ 6%
Bypass voltage range -25% ~ +15% (settable)
Output
Output voltage 110 Vac / 115 Vac / 120 Vac / 127 Vac(settable)
Voltage accuracy ± 1%
Output PF 0.9
Inverter overload
capability
108% ~ 127% load: transfer to bypass in 1 min;
127% ~ 150% load: transfer to bypass in 30 s;
> 150% load: transfer to bypass in 100 ms
From mains mode to
BAT mode
0ms (transfer time)
From mains mode to
bypass
4 ms (typical)
Output
frequency
Line mode Same as input frequency
BAT mode (50 / 60 ± 0.1) Hz
Total voltage
harmonic distortion
≤ 2% (linear load); ≤ 5% (non-linear load)
Batteries
Battery type Sealed lead acid maintenance free battery
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
advertisement
Key Features
- Uninterruptible power supply
- Backup time
- Overload protection
- LCD display
- Communication port
- Battery management
- Automatic voltage regulation
- Bypass mode
- ECO mode
- CUCF mode
Related manuals
Frequently Answers and Questions
How do I turn on and off the EAST EA900?
To turn on the UPS, press the "ON" button for more than half a second. To turn it off, press the "OFF" button for more than half a second. See the user manual for detailed instructions on turning on and off the UPS in different modes.
What does the 'ECO' mode do?
ECO mode allows the UPS to operate more efficiently by drawing power directly from the mains when the power is stable. This helps to conserve energy and minimize noise.
What does the 'CUCF' mode do?
The CUCF (Constant Voltage and Constant Frequency) mode ensures stable output voltage and frequency, making it suitable for applications that require precision equipment. While in CUCF mode, the UPS operates at 70% of its normal capacity and cannot be set to bypass mode.