Solas ONE6 Owner's Manual
Solas ONE6 is a self-calibrating direct vent gas fireplace. It features powerful vent systems to deliver efficient heating performance and a visually appealing flame aesthetic. Its unique venting configuration allows for flexibility in installation, and the system includes the necessary components for easy setup and maintenance.
advertisement
THIS POWER VENT KIT IS ONLY FOR USE WITH THE FOLLOWING SÓLAS MODELS:
SL-16N, SL-16P, SL-26N, SL-26P, ST-46N, ST-46P, FS-16N-RV, FS-16P-RV, FS-16N-TV, FS-16P-TV, BI-38N-C, BI-38P-C, BI-38N-T, BI-38P-T,
46N-BICZ, 26N-BICZ, 16N-BICZ, BI-48-SSL, BI-48-SSR, BI-48-ST, BI-60-SSL, BI-60-SSR, BI-60-ST, BI-72-SSL, BI-72-SSR, BI-72-ST
SELF-CALIBRATING
POWER VENT CONTROL
AND TERMINATION KIT
Ce manual est disponsible en Francais sur demande.
SCPV-900C SHOWN
SÓLAS STRONGLY SUGGESTS THAT YOU READ THIS
MANUAL THOROUGHLY BEFORE BEGINNING THE
INSTALLATION OF THE SÓLAS POWER VENT KIT. THIS
SPECIFIC PRODUCT HAS ITS OWN UNIQUE SET-UP AND
INSTALLATION REQUIREMENTS THAT MUST BE
FOLLOWED EXACTLY. PLAN YOUR INSTALLATION IN
ADVANCE BY CAREFULLY RE-VIEWING ALL THE
INFORMATION CONTAINED IN THIS MANUAL.
WARNING: ALL INSTALLATION, SERVICING, AND
TROUBLESHOOTING MUST BE PERFORMED BY A
QUALIFIED GAS TECHNICIAN.
SL-16N, SL-16P, SL-26N, SL-26P, ST-46N, ST-46P, FS-16N-RV, FS-16P-RV, FS-16N-TV, FS-16P-TV, BI-38N-C, BI-38P-C, BI-38N-T, BI-38P-T,
46N-BICZ, 26N-BICZ, 16N-BICZ, BI-48-SSL, BI-48-SSR, BI-48-ST, BI-60-SSL, BI-60-SSR, BI-60-ST, BI-72-SSL, BI-72-SSR, BI-72-ST
SELF-CALIBRATING
POWER VENT CONTROL
AND TERMINATION KIT
Ce manual est disponsible en Francais sur demande.
SCPV-900C SHOWN
SÓLAS STRONGLY SUGGESTS THAT YOU READ THIS
MANUAL THOROUGHLY BEFORE BEGINNING THE
INSTALLATION OF THE SÓLAS POWER VENT KIT. THIS
SPECIFIC PRODUCT HAS ITS OWN UNIQUE SET-UP AND
INSTALLATION REQUIREMENTS THAT MUST BE
FOLLOWED EXACTLY. PLAN YOUR INSTALLATION IN
ADVANCE BY CAREFULLY RE-VIEWING ALL THE
INFORMATION CONTAINED IN THIS MANUAL.
WARNING: ALL INSTALLATION, SERVICING, AND
TROUBLESHOOTING MUST BE PERFORMED BY A
QUALIFIED GAS TECHNICIAN.
2
TABLE OF CONTENTS
SÓLAS Power Vent Components 3
SÓLAS Power Vent Terminations 4
Flush-mount Termination specifications 6
Surface-mount Termination specifications 7
Power Vent Clearances 8
Venting Configurations 9
Flush Mount (side wall) Installation 10
Surface Mount (side wall) Installation 11
Vertical (thru the roof) Installation 12
Installation Instructions 14
Electrical Instructions 16
Calibration and Operation 17
Troubleshooting 20
Replacement Parts List 22
Warranty Information 23
WARNING:
This installation manual covers the functional
requirements for optimal performance of your
fireplace with power vent installation, consult with a
professional architect, civil engineer, or home
builder regarding the building code, aesthetic and
functional finishing requirements of the home.
NOTE:
SÓLAS advises that the appliance installation should
be calibrated, tested, and the fireplace burned to
ensure optimal performance and desired flame
aesthetics BEFORE the vent system or fireplace are
enclosed and walls or ceilings are finished.
TABLE OF CONTENTS
SÓLAS Power Vent Components 3
SÓLAS Power Vent Terminations 4
Flush-mount Termination specifications 6
Surface-mount Termination specifications 7
Power Vent Clearances 8
Venting Configurations 9
Flush Mount (side wall) Installation 10
Surface Mount (side wall) Installation 11
Vertical (thru the roof) Installation 12
Installation Instructions 14
Electrical Instructions 16
Calibration and Operation 17
Troubleshooting 20
Replacement Parts List 22
Warranty Information 23
WARNING:
This installation manual covers the functional
requirements for optimal performance of your
fireplace with power vent installation, consult with a
professional architect, civil engineer, or home
builder regarding the building code, aesthetic and
functional finishing requirements of the home.
NOTE:
SÓLAS advises that the appliance installation should
be calibrated, tested, and the fireplace burned to
ensure optimal performance and desired flame
aesthetics BEFORE the vent system or fireplace are
enclosed and walls or ceilings are finished.
3
SÓLAS POWER VENT COMPONENTS
SCPV-900C - Self-Calibrating Power Vent Control
Module, required for all power vent installations.
SCPV-905PS - Self-Calibrating Power Vent Pressure
Switch, required for all power vent installations. Only
use the pressure switch certified by SÓLAS with the
SÓLAS Self-Calibrating Power Vent Control. Connect
to pressure port using the 12ft length of ¼” ID silicon
tubing (not shown) supplied with the Self-Calibrating
Powervent control kit.
SCPV-914GS - Self-Calibrating Power Vent Gas
Solenoid, required for all power vent installations.
Only gas solenoids certified for use by SÓLAS are to be
used with the SÓLAS Self-Calibrating Power Vent
Control.
SCPV-TWH-XX - Self-Calibrating Power Vent
termination wire harness, required for all power vent
installations. The termination wire harness is available
in 25, 50, 100, and 150 lengths.
Harness Part # Description
SCPV-TWH-25 Termination Wire Harness, 25FT long
SCPV-TWH-50 Termination Wire Harness, 50FT long
SCPV-TWH-100 Termination Wire Harness, 100FT long
SCPV-TWH-150 Termination Wire Harness, 150FT long
SÓLAS POWER VENT COMPONENTS
SCPV-900C - Self-Calibrating Power Vent Control
Module, required for all power vent installations.
SCPV-905PS - Self-Calibrating Power Vent Pressure
Switch, required for all power vent installations. Only
use the pressure switch certified by SÓLAS with the
SÓLAS Self-Calibrating Power Vent Control. Connect
to pressure port using the 12ft length of ¼” ID silicon
tubing (not shown) supplied with the Self-Calibrating
Powervent control kit.
SCPV-914GS - Self-Calibrating Power Vent Gas
Solenoid, required for all power vent installations.
Only gas solenoids certified for use by SÓLAS are to be
used with the SÓLAS Self-Calibrating Power Vent
Control.
SCPV-TWH-XX - Self-Calibrating Power Vent
termination wire harness, required for all power vent
installations. The termination wire harness is available
in 25, 50, 100, and 150 lengths.
Harness Part # Description
SCPV-TWH-25 Termination Wire Harness, 25FT long
SCPV-TWH-50 Termination Wire Harness, 50FT long
SCPV-TWH-100 Termination Wire Harness, 100FT long
SCPV-TWH-150 Termination Wire Harness, 150FT long
4
SÓLAS POWER VENT TERMINATIONS
SCPV-946DVA – Self-Calibrating Power Vent Pressure
Port Vent Adapter, required with terminations SCPV-
130-FLUSH, SCPV-130-SURFACE, and SCPV-130-
VERTICAL.
NOTE: This adapter, based on M&G Duravent’s 46DVA-
06 directvent pipe, should be installed immediately on
the starter collar of the fireplace. For SÓLAS fireplaces
requiring a 45° elbow immediately following the
starter, this adapter should be installed immediately
following the 45° elbow.
SCPV-130-FLUSH – Self-Calibrating Power Vent
Flush-Mount Termination, for use with vent runs over
10 feet in length, regardless of the number of elbows
in the vent configuration. This termination requires
the use of SCPV-946DVA - Self-Calibrating Power Vent
Pressure Port Vent Adapter.
SCPV-130-SURFACE – Self-Calibrating Power Vent
Surface-Mount Termination, for use with vent runs
over 10 feet in length, regardless of the number of
elbows in the vent configuration. This termination
requires the use of SCPV-946DVA - Self-Calibrating
Power Vent Pressure Port Vent Adapter.
SCPV-10-SRSM – Self-Calibrating Power Vent
Surface-Mount Termination, for use with vent runs
under 10 feet in length, regardless of the number of
elbows in the vent configuration. This termination is
Not to be used with SCPV-946DVA - Self-Calibrating
Power Vent Pressure Port Vent Adapter.
NOTE: This termination can be differentiated from
SCPV-130-SURFACE by the addition of the pressure
port on the rear top-left corner of the termination.
PRESSURE PORT
SÓLAS POWER VENT TERMINATIONS
SCPV-946DVA – Self-Calibrating Power Vent Pressure
Port Vent Adapter, required with terminations SCPV-
130-FLUSH, SCPV-130-SURFACE, and SCPV-130-
VERTICAL.
NOTE: This adapter, based on M&G Duravent’s 46DVA-
06 directvent pipe, should be installed immediately on
the starter collar of the fireplace. For SÓLAS fireplaces
requiring a 45° elbow immediately following the
starter, this adapter should be installed immediately
following the 45° elbow.
SCPV-130-FLUSH – Self-Calibrating Power Vent
Flush-Mount Termination, for use with vent runs over
10 feet in length, regardless of the number of elbows
in the vent configuration. This termination requires
the use of SCPV-946DVA - Self-Calibrating Power Vent
Pressure Port Vent Adapter.
SCPV-130-SURFACE – Self-Calibrating Power Vent
Surface-Mount Termination, for use with vent runs
over 10 feet in length, regardless of the number of
elbows in the vent configuration. This termination
requires the use of SCPV-946DVA - Self-Calibrating
Power Vent Pressure Port Vent Adapter.
SCPV-10-SRSM – Self-Calibrating Power Vent
Surface-Mount Termination, for use with vent runs
under 10 feet in length, regardless of the number of
elbows in the vent configuration. This termination is
Not to be used with SCPV-946DVA - Self-Calibrating
Power Vent Pressure Port Vent Adapter.
NOTE: This termination can be differentiated from
SCPV-130-SURFACE by the addition of the pressure
port on the rear top-left corner of the termination.
PRESSURE PORT
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
advertisement
Key Features
- Self-Calibrating Power Vent Control
- Multiple vent configurations
- Flush and surface mount options
- Easy installation and maintenance
- Powerful vent system
- Attractive flame aesthetic
Related manuals
Frequently Answers and Questions
What models can be used with the Solas Power Vent Kit?
The kit is designed for use with specific Solas models listed on page 5 of the manual. These models include SL-16N, SL-16P, SL-26N, SL-26P, ST-46N, ST-46P, FS-16N-RV, FS-16P-RV, FS-16N-TV, FS-16P-TV, BI-38N-C, BI-38P-C, BI-38N-T, BI-38P-T, BI-48-SSL, BI-48-SSR, BI-48-ST, BI-60-SSL, BI-60-SSR, BI-60-ST, BI-72-SSL, BI-72-SSR, BI-72-ST.
What are the maximum venting lengths and configurations?
The maximum vent length is 130 ft, including up to eight 90° elbows or a combination of other elbows. Each 90° elbow reduces the maximum vent length by 3 ft. The vent can be installed with any combination of rise and run, including up to 6 ft of downward venting. See page 9 for diagram and details of the configuration.
What are the clearance requirements for the power vent termination?
The location of the Power Vent termination must be in accordance with page 8 of the manual. It outlines the clearances needed to combustible materials and electrical wiring.
advertisement