Allen-Bradley ASEM 6300P DC Powered Panel PCs Installation Instructions
Allen-Bradley ASEM 6300P DC Powered Panel PCs are robust industrial panel PCs designed for demanding environments like food processing and life sciences. IP65 rating makes it suitable for wash-down applications, while fanless construction ensures low maintenance and extended lifespan. The integrated DC-DC converter board provides noise immunity and features reverse polarity protection, overvoltage protection, and a 12A soldered fuse for input power security. The 6300P integrates seamlessly with Rockwell Automation's FactoryTalk View SE and ME software for smooth HMI integration.
advertisement
Installation Instructions
Original Instructions
ASEM 6300P DC Powered Panel PCs
Bulletin Number 6300P
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Product Overview
The ASEM™ 6300P DC powered panel PC family is available in various display sizes and resolutions with either standard or low profile bezel units. IP65 environmental
protection makes the 6300P DC powered panel PC an excellent match for wash-down applications such as food processing and life sciences. Fanless construction helps to
deliver low maintenance operation and enhance longevity. An internal power supply, galvanically isolated DC-DC converter board, provides increased electrical noise
immunity, reverse polarity circuitry, overvoltage, and a 12 A soldered fuse provide input power protection.
6300P DC powered panel PCs are ideal for applications that require a high-performance Human Machine Interface (HMI). This product family integrates completely with our
FactoryTalk® View SE and FactoryTalk View® ME software for smooth assimilation within your facility.
Compliance
UL/cUL Mark Compliance
Equipment with the UL/cUL mark complies with the requirements of UL 61010-1, UL 61010-2-201, CSA C22.2 No. 61010-1, and CSA C22.2 No. 61010-2-201. A copy of the
certificate of compliance is available at rok.auto/certifications.
European Union Directive Compliance
This equipment meets the European Union Directive requirements when installed within the European Union or EEA regions and have the CE marking. A copy of the
declaration of the conformity is available at rok.auto/certifications.
Topic Page
Summary of Changes 1
Product Overview 1
Compliance 1
Environment and Enclosure Information 2
Installation Requirements 2
Install the Panel PC 4
Prepare the DC Power Connection 5
Install the DC Power Connector Assembly 6
Connect the Peripheral Cables and DC Power 7
Additional Resources 7
ATTENTION: Read this document and the documents that are listed in the Additional Resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with
installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by
suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner that is not specified by the
manufacturer, the protection that is provided by the equipment can be impaired.
Topic Page
Removed incorrect catalog number from IMPORTANT table within Peripheral Connection Requirements 4
ATTENTION: This equipment is intended to operate in an industrial or control room environment, which uses some form of power isolation from the
public low-voltage mains. Some computer configurations cannot comply with the EN 61000-3-2 Harmonic Emissions standard as specified by the EMC
Directive of the European Union.
All I/O cables must be used only indoors.
Original Instructions
ASEM 6300P DC Powered Panel PCs
Bulletin Number 6300P
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Product Overview
The ASEM™ 6300P DC powered panel PC family is available in various display sizes and resolutions with either standard or low profile bezel units. IP65 environmental
protection makes the 6300P DC powered panel PC an excellent match for wash-down applications such as food processing and life sciences. Fanless construction helps to
deliver low maintenance operation and enhance longevity. An internal power supply, galvanically isolated DC-DC converter board, provides increased electrical noise
immunity, reverse polarity circuitry, overvoltage, and a 12 A soldered fuse provide input power protection.
6300P DC powered panel PCs are ideal for applications that require a high-performance Human Machine Interface (HMI). This product family integrates completely with our
FactoryTalk® View SE and FactoryTalk View® ME software for smooth assimilation within your facility.
Compliance
UL/cUL Mark Compliance
Equipment with the UL/cUL mark complies with the requirements of UL 61010-1, UL 61010-2-201, CSA C22.2 No. 61010-1, and CSA C22.2 No. 61010-2-201. A copy of the
certificate of compliance is available at rok.auto/certifications.
European Union Directive Compliance
This equipment meets the European Union Directive requirements when installed within the European Union or EEA regions and have the CE marking. A copy of the
declaration of the conformity is available at rok.auto/certifications.
Topic Page
Summary of Changes 1
Product Overview 1
Compliance 1
Environment and Enclosure Information 2
Installation Requirements 2
Install the Panel PC 4
Prepare the DC Power Connection 5
Install the DC Power Connector Assembly 6
Connect the Peripheral Cables and DC Power 7
Additional Resources 7
ATTENTION: Read this document and the documents that are listed in the Additional Resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with
installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by
suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner that is not specified by the
manufacturer, the protection that is provided by the equipment can be impaired.
Topic Page
Removed incorrect catalog number from IMPORTANT table within Peripheral Connection Requirements 4
ATTENTION: This equipment is intended to operate in an industrial or control room environment, which uses some form of power isolation from the
public low-voltage mains. Some computer configurations cannot comply with the EN 61000-3-2 Harmonic Emissions standard as specified by the EMC
Directive of the European Union.
All I/O cables must be used only indoors.
2 Rockwell Automation Publication 6300P-IN001F-EN-P - February 2024
6300P DC Powered Panel PCs Installation Instructions
Environment and Enclosure Information
Environment Requirements
Follow these environment requirements to make sure that your 6300P DC powered panel PC provides service with excellent reliability.
• Your installation site:
- must have sufficient power,
- must be indoors and non-hazardous,
- must not expose your 6300P DC powered panel PC to direct sunlight, and
- must be placed in an industrial or control room environment, which uses some form of power isolation from the public, low voltage mains.
• The surrounding air temperature must not exceed the maximum temperature for your 6300P DC powered panel PC, especially when mounted in an enclosure.
• The ambient air temperature range is 0…+50 °C (+32…+122 °F)
• The surrounding air temperature range for storage is -10…+60 °C (-14…+140 °F).
• The relative humidity of the ambient air must be 20…90% noncondensing at 0…+40 °C (+32…+104 °F), and 20…80% noncondensing at +41…+50 °C (+105…+122 °F).
Enclosure Requirements
Follow these enclosure requirements:
• Never allow air passages to become obstructed. The enclosure must provide sufficient space around air inlets and outlets to provide the circulation necessary for
cooling. See Table 3 on page 4 for minimum clearances.
• Hot air rises. The temperature at the top of the enclosure is often higher than the temperature in other parts of the enclosure, especially if air is not circulating.
Consider a user-supplied fan, heat exchanger, or air conditioner for heat generated by other devices in the enclosure. See Environment Requirements for the
acceptable temperature ranges for your 6300P DC powered panel PC .
Installation Requirements
Observe all installation requirements listed below.
DC Power Supply Requirements
Follow these requirements to select the DC power supply for your 6300P DC powered panel PC.
• Your 6300 DC powered panel PC must be powered with a voltage of 24V DC (18…32V DC SELV input voltage range).
• Power consumption is rated at 156 W maximum/38 W typical for 24V DC.
• The nominal output power must be 25% larger than the rated power of your 6300P DC powered panel PC.
• The output voltage rise time has to be less than 100 ms.
• Consider the working temperature and the thermal derating of the power supply.
• The inrush current impulse of a 6300P DC powered panel PC is shown below.
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in
IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/EN 61326-1. Without appropriate precautions, there can be
potential difficulties with electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is considered open equipment, which means it must be mounted in an enclosure where the equipment can be operated from the front
panel.
The enclosure in which this equipment is installed must be accessed only with a key or tool, and only by trained and authorized personnel.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 , for more installation requirements.
• UL 50, CSA C22.2 No. 94.1, and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
IMPORTANT All 6300P DC powered panel PCs require a safety extra low voltage (SELV) power supply per UL. The power supply is internally protected against
reverse polarity. To minimize ground loop currents and noise, all 6300P DC powered panel PCs should use only one grounded connection.
lpk: Load peak
t: Time
t (2 ms)
lpk
(<13 A)
In Rush Current Impulse
6300P DC Powered Panel PCs Installation Instructions
Environment and Enclosure Information
Environment Requirements
Follow these environment requirements to make sure that your 6300P DC powered panel PC provides service with excellent reliability.
• Your installation site:
- must have sufficient power,
- must be indoors and non-hazardous,
- must not expose your 6300P DC powered panel PC to direct sunlight, and
- must be placed in an industrial or control room environment, which uses some form of power isolation from the public, low voltage mains.
• The surrounding air temperature must not exceed the maximum temperature for your 6300P DC powered panel PC, especially when mounted in an enclosure.
• The ambient air temperature range is 0…+50 °C (+32…+122 °F)
• The surrounding air temperature range for storage is -10…+60 °C (-14…+140 °F).
• The relative humidity of the ambient air must be 20…90% noncondensing at 0…+40 °C (+32…+104 °F), and 20…80% noncondensing at +41…+50 °C (+105…+122 °F).
Enclosure Requirements
Follow these enclosure requirements:
• Never allow air passages to become obstructed. The enclosure must provide sufficient space around air inlets and outlets to provide the circulation necessary for
cooling. See Table 3 on page 4 for minimum clearances.
• Hot air rises. The temperature at the top of the enclosure is often higher than the temperature in other parts of the enclosure, especially if air is not circulating.
Consider a user-supplied fan, heat exchanger, or air conditioner for heat generated by other devices in the enclosure. See Environment Requirements for the
acceptable temperature ranges for your 6300P DC powered panel PC .
Installation Requirements
Observe all installation requirements listed below.
DC Power Supply Requirements
Follow these requirements to select the DC power supply for your 6300P DC powered panel PC.
• Your 6300 DC powered panel PC must be powered with a voltage of 24V DC (18…32V DC SELV input voltage range).
• Power consumption is rated at 156 W maximum/38 W typical for 24V DC.
• The nominal output power must be 25% larger than the rated power of your 6300P DC powered panel PC.
• The output voltage rise time has to be less than 100 ms.
• Consider the working temperature and the thermal derating of the power supply.
• The inrush current impulse of a 6300P DC powered panel PC is shown below.
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in
IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/EN 61326-1. Without appropriate precautions, there can be
potential difficulties with electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is considered open equipment, which means it must be mounted in an enclosure where the equipment can be operated from the front
panel.
The enclosure in which this equipment is installed must be accessed only with a key or tool, and only by trained and authorized personnel.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 , for more installation requirements.
• UL 50, CSA C22.2 No. 94.1, and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
IMPORTANT All 6300P DC powered panel PCs require a safety extra low voltage (SELV) power supply per UL. The power supply is internally protected against
reverse polarity. To minimize ground loop currents and noise, all 6300P DC powered panel PCs should use only one grounded connection.
lpk: Load peak
t: Time
t (2 ms)
lpk
(<13 A)
In Rush Current Impulse
Rockwell Automation Publication 6300P-IN001F-EN-P - February 2024 3
6300P DC Powered Panel PCs Installation Instructions
Panel Consumption
Panel Cutout Requirements
Observe these requirements to plan your panel cutout area:
• The mounting panel material must be 2…6 mm (0.08…0.24 in.) thick.
• The roughness of the panel surface must not exceed 120 microns (Rz 120) to allow for a uniform gasket seal.
• The area around the panel cutout must be clear of obstructions and free of debris.
• See Table 2 for panel cutout dimensions for your particular display size.
IMPORTANT The operating system (OS) can become corrupt if insufficient power is supplied on initial power on.
IMPORTANT Total system power consumption cannot exceed 120 watts (W). Exceeding this limit can cause damage to components. The values listed in Table 1
exclude an externally connected USB device
Table 1 - Power Consumption, Maximum Watts (1)
(1) The values listed exclude an externally connected USB device.
Monitor PC Component PC Ports and Slots
Display Size Aspect Ratio Power Consumption
Maximum Watts Component Description Power Consumption
Maximum Watts Port or Slot Description Power Consumption
Maximum Watts
12.1 in. (4:3) 12
Processor (2)
(2) Power consumption values include the motherboard and 1 x 4 GB RAM.
Intel® Celeron® 43 CFast Slot (3)
(3) Power consumption value applies only when the port or slot is loaded.
SATA III, MLC 1.3
12.1 in. (16:10) 8 Intel Core™ i3 43 SATA III, 3D TLC 1.3
15 in. (4:3) 13 Intel Core i5 61 Expansion Slot (3) PCI half-size or PCIe x4 5
15.6 in. (16:9) 24 Intel Core i7 65 USB Ports 2.0 Type A, each port 2.5
17 in. (5:4) 17 Solid-state Drive 2.5 in., SATA III, 3D TLC 3 3.0 Type A, each port 4.5
18.5 in. (16:9) 24 mSATA, SATA III, 3D TLC 3
19 in. (5:4) 17
RAM
8 GB 1
21.5 in. (16:9) 22 16 GB 2
24 in. (16:9) 16 32 GB 2
ATTENTION: Failure to follow the panel cutout requirements can result in personal injury or damage to the panel components.
Take precautions so any metal fragments during the panel cutout do not enter components that are installed already in the panel.
Table 2 - Panel Cutout Dimensions
Display Size Format (1)
(1) Standard format is offered with an analog resistive touch screen. Widescreen format is offered with analog resistive and projective capacitive (PCAP) touch screens.
Dimensions [mm (in.)] (2)
(2) All dimensions are ± 1 mm (0.04 in.).
A B
12.1 Standard 315 (12.4) 250 (9.84)
Widescreen 313 (12.3) 216 (8.5)
15.0 Standard 370 (14.57) 295 (11.61)
15.6 Widescreen 388 (15.28) 238 (9.37)
17.0 Standard 435 (17.13) 335 (13.19)
18.5 Widescreen 453 (17.83) 274 (10.79)
19.0 Standard 470 (18.5) 368 (14.49)
21.5 Widescreen 520 (20.47) 312 (12.28)
24.0 Widescreen 577 (22.71) 344 (13.54)
A
B A
B
Panel Cutout Area
Standard Widescreen
6300P DC Powered Panel PCs Installation Instructions
Panel Consumption
Panel Cutout Requirements
Observe these requirements to plan your panel cutout area:
• The mounting panel material must be 2…6 mm (0.08…0.24 in.) thick.
• The roughness of the panel surface must not exceed 120 microns (Rz 120) to allow for a uniform gasket seal.
• The area around the panel cutout must be clear of obstructions and free of debris.
• See Table 2 for panel cutout dimensions for your particular display size.
IMPORTANT The operating system (OS) can become corrupt if insufficient power is supplied on initial power on.
IMPORTANT Total system power consumption cannot exceed 120 watts (W). Exceeding this limit can cause damage to components. The values listed in Table 1
exclude an externally connected USB device
Table 1 - Power Consumption, Maximum Watts (1)
(1) The values listed exclude an externally connected USB device.
Monitor PC Component PC Ports and Slots
Display Size Aspect Ratio Power Consumption
Maximum Watts Component Description Power Consumption
Maximum Watts Port or Slot Description Power Consumption
Maximum Watts
12.1 in. (4:3) 12
Processor (2)
(2) Power consumption values include the motherboard and 1 x 4 GB RAM.
Intel® Celeron® 43 CFast Slot (3)
(3) Power consumption value applies only when the port or slot is loaded.
SATA III, MLC 1.3
12.1 in. (16:10) 8 Intel Core™ i3 43 SATA III, 3D TLC 1.3
15 in. (4:3) 13 Intel Core i5 61 Expansion Slot (3) PCI half-size or PCIe x4 5
15.6 in. (16:9) 24 Intel Core i7 65 USB Ports 2.0 Type A, each port 2.5
17 in. (5:4) 17 Solid-state Drive 2.5 in., SATA III, 3D TLC 3 3.0 Type A, each port 4.5
18.5 in. (16:9) 24 mSATA, SATA III, 3D TLC 3
19 in. (5:4) 17
RAM
8 GB 1
21.5 in. (16:9) 22 16 GB 2
24 in. (16:9) 16 32 GB 2
ATTENTION: Failure to follow the panel cutout requirements can result in personal injury or damage to the panel components.
Take precautions so any metal fragments during the panel cutout do not enter components that are installed already in the panel.
Table 2 - Panel Cutout Dimensions
Display Size Format (1)
(1) Standard format is offered with an analog resistive touch screen. Widescreen format is offered with analog resistive and projective capacitive (PCAP) touch screens.
Dimensions [mm (in.)] (2)
(2) All dimensions are ± 1 mm (0.04 in.).
A B
12.1 Standard 315 (12.4) 250 (9.84)
Widescreen 313 (12.3) 216 (8.5)
15.0 Standard 370 (14.57) 295 (11.61)
15.6 Widescreen 388 (15.28) 238 (9.37)
17.0 Standard 435 (17.13) 335 (13.19)
18.5 Widescreen 453 (17.83) 274 (10.79)
19.0 Standard 470 (18.5) 368 (14.49)
21.5 Widescreen 520 (20.47) 312 (12.28)
24.0 Widescreen 577 (22.71) 344 (13.54)
A
B A
B
Panel Cutout Area
Standard Widescreen
4 Rockwell Automation Publication 6300P-IN001F-EN-P - February 2024
6300P DC Powered Panel PCs Installation Instructions
Mounting Requirements
Follow these mounting requirements to mount your 6300P DC powered panel PC.
• Choose a suitable, ergonomic mounting height.
• To help prevent overheating and to provide access to the I/O ports for cable connections, mount your 6300P DC powered panel PC with the minimum clearances on
all four sides of the outer frame and the back of the chassis as shown in Table 3.
• For optimal performance, mount your 6300P DC powered panel PC horizontally in a 0° vertical (upright) position with the I/O ports facing downward as shown in
Table 3.
Peripheral Connection Requirements
Required Tools and Hardware
You need the following tools to install and connect your 6300P DC powered panel PC.
Install the Panel PC
Follow these steps to install your 6300P DC powered panel PC
Create the Panel Cutout
1. Disconnect all electrical power before you make the cutout.
2. Be sure all requirements have been met within Panel Cutout Requirements on page 3.
3. Cut an opening in the mounting material according to the dimensions specified for your model shown in Table 2 on page 3.
4. Clean the panel area of all debris and metal fragments.
IMPORTANT The vertical position can be tilted up to 20° forward or 20° backward from the upright position. However, this acceptable tilt angle range
decreases the maximum operating air temperature to 45 °C (113 °F).
Table 3 - Minimum Clearance for Mounting Placement
Dimension X Dimension Y Dimension Z
7 cm (2.75 cm) 10 cm (3.94 in) 7 cm (2.75 cm)
IMPORTANT To comply with EN 61326-1, all cable types must be shielded and must be used only indoors, and USB cables must be less than 3 m (9.84 ft) in length.
IMPORTANT Before connecting or disconnecting peripheral cables from I/O ports, verify that you are in a non-hazardous location before you connect or
disconnect any peripheral connections.
The front USB port on your 6300P DC powered panel PC is not for use in hazardous locations. Only use the front USB port for installation and
maintenance purposes.
Table 4 - I/O Port Locations
Note No. Cable Type Required Attribute
1 LAN
Shielded
2 USB 2.0
3 USB 3.0
4 RS-232 DB9M
5 DVI-D
For Panel Cutout For Mounting For DC Power Connection For Peripheral and DC Power Connection
• Level
• Pencil
• Ruler
• Safety Glasses
• Cutting tool appropriate for
mounting material
• Mounting clips (supplied)
• Torque limiting screwdriver
• 1.5 mm hex key bit
• Wire stripper, cutter, and crimper tool
• Small screwdriver
• Uninterruptible power supply (UPS)
(recommended)
• Various peripheral cables
(see for Peripheral Connection Requirements for compliance and types)
• DC power supply
(see DC Power Supply Requirements on page 2 for requirements)
0°
20° 20°
I/O Ports
Facing Downward
I/O Ports
Facing Downward
ZXX
Y
Rear View Side View
Horizontal Orientation Vertical Upright Position
Y
Preferred
1
2 3
5
14
6300P DC Powered Panel PCs Installation Instructions
Mounting Requirements
Follow these mounting requirements to mount your 6300P DC powered panel PC.
• Choose a suitable, ergonomic mounting height.
• To help prevent overheating and to provide access to the I/O ports for cable connections, mount your 6300P DC powered panel PC with the minimum clearances on
all four sides of the outer frame and the back of the chassis as shown in Table 3.
• For optimal performance, mount your 6300P DC powered panel PC horizontally in a 0° vertical (upright) position with the I/O ports facing downward as shown in
Table 3.
Peripheral Connection Requirements
Required Tools and Hardware
You need the following tools to install and connect your 6300P DC powered panel PC.
Install the Panel PC
Follow these steps to install your 6300P DC powered panel PC
Create the Panel Cutout
1. Disconnect all electrical power before you make the cutout.
2. Be sure all requirements have been met within Panel Cutout Requirements on page 3.
3. Cut an opening in the mounting material according to the dimensions specified for your model shown in Table 2 on page 3.
4. Clean the panel area of all debris and metal fragments.
IMPORTANT The vertical position can be tilted up to 20° forward or 20° backward from the upright position. However, this acceptable tilt angle range
decreases the maximum operating air temperature to 45 °C (113 °F).
Table 3 - Minimum Clearance for Mounting Placement
Dimension X Dimension Y Dimension Z
7 cm (2.75 cm) 10 cm (3.94 in) 7 cm (2.75 cm)
IMPORTANT To comply with EN 61326-1, all cable types must be shielded and must be used only indoors, and USB cables must be less than 3 m (9.84 ft) in length.
IMPORTANT Before connecting or disconnecting peripheral cables from I/O ports, verify that you are in a non-hazardous location before you connect or
disconnect any peripheral connections.
The front USB port on your 6300P DC powered panel PC is not for use in hazardous locations. Only use the front USB port for installation and
maintenance purposes.
Table 4 - I/O Port Locations
Note No. Cable Type Required Attribute
1 LAN
Shielded
2 USB 2.0
3 USB 3.0
4 RS-232 DB9M
5 DVI-D
For Panel Cutout For Mounting For DC Power Connection For Peripheral and DC Power Connection
• Level
• Pencil
• Ruler
• Safety Glasses
• Cutting tool appropriate for
mounting material
• Mounting clips (supplied)
• Torque limiting screwdriver
• 1.5 mm hex key bit
• Wire stripper, cutter, and crimper tool
• Small screwdriver
• Uninterruptible power supply (UPS)
(recommended)
• Various peripheral cables
(see for Peripheral Connection Requirements for compliance and types)
• DC power supply
(see DC Power Supply Requirements on page 2 for requirements)
0°
20° 20°
I/O Ports
Facing Downward
I/O Ports
Facing Downward
ZXX
Y
Rear View Side View
Horizontal Orientation Vertical Upright Position
Y
Preferred
1
2 3
5
14
5
6
7
8
advertisement
Key Features
- IP65 rated
- Fanless
- DC-DC converter
- FactoryTalk integration
- Wash-down applications
- Various display sizes
- High performance HMI
Related manuals
Frequently Answers and Questions
What are the environmental requirements for the ASEM 6300P?
The 6300P is designed for an industrial environment with a temperature range of 0…+50 °C (+32…+122 °F) and humidity of 20…90% noncondensing at 0…+40 °C (+32…+104 °F). The enclosure must be indoors and non-hazardous, with sufficient clearance for airflow.
What are the recommended power supply specifications for the ASEM 6300P?
The ASEM 6300P requires a 24V DC SELV power supply with a nominal output power of 25% larger than the panel's rated power, which is 156W maximum/38W typical. The output voltage rise time should be less than 100ms. Refer to the manual for inrush current impulse details.
How do I install the DC power connector assembly?
The DC power connector assembly must be assembled. You'll need to strip the DC power wires to the specified length, insert them into the terminal block, and tighten the screws securely. Ensure the connector halves are properly aligned and locked into place. Refer to the specific instructions in the manual for detailed steps.