Allen-Bradley 193 E100, O.L. RELAY, EXT CT is an external current transformer overload relay designed for use with separately mounted current transformers. This device provides protection against overloads and short circuits in motor circuits, ensuring safe operation. The 193 E100 features adjustable trip settings, selectable trip classes, and automatic or manual reset modes. It can be mounted on DIN rails and is suitable for a wide range of industrial applications.
advertisement
Installation Instructions
Bulletin 193 E100 External Current Transformer Overload Relay
Application and Installation
(Cat 193-1EF_Z)
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free from contaminants.
Follow NFPA70E requirements.
WARNING: Do not use automatic reset mode in applications where unexpected automatic restart of the motor can cause injury to persons or damage to equipment.
WARNING: The improper selection of a current transformer can result in the overload relay not properly protecting the motor and possible motor damage. The selected
current transformer must be rated for protective relaying applications.
At the end of its life, this
equipment should be
collected separately from
any unsorted municipal
waste.
25
= FLA
1.73
S.F. < 1.15
S.F. _ _ FLA _ _
S.F. > 1.15
Y
= .9 X FLA
= 1 X FLA
= FLA
1.73
STAR DELTA (Y )
= 1 X FLADOL
FLA _ _
Settings
Installation
DIN Rail Mount
Selectable Trip Class
Automatic/Manual Reset Mode
Push to test
Push to reset
Push to stop
Trip Indicator Window
Red indicator not visible: Not Tripped
Red indicator visible: Tripped
To adjust trip current, turn
dial until the desired current is
aligned with the pointer.
Trip rating is 120% of dial setting.
193-1EF*
Ø .18 in
[4.8] mm
CLICK
Bulletin 193 E100 External Current Transformer Overload Relay
Application and Installation
(Cat 193-1EF_Z)
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free from contaminants.
Follow NFPA70E requirements.
WARNING: Do not use automatic reset mode in applications where unexpected automatic restart of the motor can cause injury to persons or damage to equipment.
WARNING: The improper selection of a current transformer can result in the overload relay not properly protecting the motor and possible motor damage. The selected
current transformer must be rated for protective relaying applications.
At the end of its life, this
equipment should be
collected separately from
any unsorted municipal
waste.
25
= FLA
1.73
S.F. < 1.15
S.F. _ _ FLA _ _
S.F. > 1.15
Y
= .9 X FLA
= 1 X FLA
= FLA
1.73
STAR DELTA (Y )
= 1 X FLADOL
FLA _ _
Settings
Installation
DIN Rail Mount
Selectable Trip Class
Automatic/Manual Reset Mode
Push to test
Push to reset
Push to stop
Trip Indicator Window
Red indicator not visible: Not Tripped
Red indicator visible: Tripped
To adjust trip current, turn
dial until the desired current is
aligned with the pointer.
Trip rating is 120% of dial setting.
193-1EF*
Ø .18 in
[4.8] mm
CLICK
2
Publication 193-IN084F-EN-E - March 2022 PN-562589 DIR 10004184713 (Version 05)
Table 1: E100 UL Standard Fault Ra�ngs, Type I
E100 Overload
Cat No Amp Range
Max. Available
Fault Current Max. Voltage
1EFHZ 30-150 A
1EFJZ 40-200 A
1EFKZ 60-300 A
1EFWZ 80-400 A 18 kA
1EFLZ 100-500 A
1EFMZ 120-600 A
1EFNZ 160-800 A
193- 600 V
30 kA
10 kA
Table 3: Type I per EN/IEC 60947-4-1
E100 Overload
Cat No Amp Range
Standard Fault,
Prospec�ve S. C.
current , Ir (kA)
High Fault,
Condi�onal S. C.
current , Iq (kA)
Max
Voltage (V)
1EFHZ 30-150 A
1EFJZ 40-200 A
1EFKZ 60-300 A
1EFWZ 80-400 A
1EFLZ 100-500 A
1EFMZ 120-600 A
1EFNZ 160-800 A 30 kA
193- 100 kA 600 V
10 kA
18 kA
Main Connections
Rated Insulation Voltage (Ui): 690V AC Rated Operating Frequency: 50 / 60 Hz
Rated Operational Voltage (Ue) IEC/UL: 690V AC / 600V AC
Short Circuit Ratings, per UL60947-4-1 and CSA 22.2 No. 60947-4-1
Branch circuit protection may be fuses or circuit breakers sized per NEC/CEC.
Wiring Diagram
*FOR MULTIPLE CONDUCTOR APPLICATIONS
THE SAME SIZE AND STYLE WIRE MUST BE USED.
M
OVERLOAD
RELAY
L1/1
L1/1
T1/2 T2/4 T3/6
L2/3 L3/5
L2/3 L3/5
H1(Dot) H1(Dot) H1(Dot)
H2 H2 H2
X1 X1 X1
X2X2X2
CT1
T1/2 T2/4 T3/6
CT2 CT3
Wire Type # Wires Range Torque
1 Wire
2 Wires*
1 Wire
2 Wires*
Stranded / Solid 0.75...4.0 mm²
(18...12 AWG)
1.4 N•m
(12 lb-in)
Flexible Stranded
w/ Ferrule 0.75...2.5 mm² 1.4 N•m
ClosedOpenOpen
OpenOpenClosed
Test TrippedStop PressedNormal
95
97 98
96
97 95
98 96
97 95
98 96
97 95
98 96
Contact Status
Contact Ratings: N.O. C600 / N.C. B600 (AC)
N.O. / N.C. R300 (DC)
Table 2: Panel Mount, Standalone Overload, High Fault, Type I
E100 Overload
Cat No Amp Range
Max. Available
Fault Current Max. Voltage
1EFHZ 30-150 A
1EFJZ 40-200 A
1EFKZ 60-300 A
1EFWZ 80-400 A
1EFLZ 100-500 A
1EFMZ 120-600 A
1EFNZ 160-800 A
193- 100 kA 600 V
Publication 193-IN084F-EN-E - March 2022 PN-562589 DIR 10004184713 (Version 05)
Table 1: E100 UL Standard Fault Ra�ngs, Type I
E100 Overload
Cat No Amp Range
Max. Available
Fault Current Max. Voltage
1EFHZ 30-150 A
1EFJZ 40-200 A
1EFKZ 60-300 A
1EFWZ 80-400 A 18 kA
1EFLZ 100-500 A
1EFMZ 120-600 A
1EFNZ 160-800 A
193- 600 V
30 kA
10 kA
Table 3: Type I per EN/IEC 60947-4-1
E100 Overload
Cat No Amp Range
Standard Fault,
Prospec�ve S. C.
current , Ir (kA)
High Fault,
Condi�onal S. C.
current , Iq (kA)
Max
Voltage (V)
1EFHZ 30-150 A
1EFJZ 40-200 A
1EFKZ 60-300 A
1EFWZ 80-400 A
1EFLZ 100-500 A
1EFMZ 120-600 A
1EFNZ 160-800 A 30 kA
193- 100 kA 600 V
10 kA
18 kA
Main Connections
Rated Insulation Voltage (Ui): 690V AC Rated Operating Frequency: 50 / 60 Hz
Rated Operational Voltage (Ue) IEC/UL: 690V AC / 600V AC
Short Circuit Ratings, per UL60947-4-1 and CSA 22.2 No. 60947-4-1
Branch circuit protection may be fuses or circuit breakers sized per NEC/CEC.
Wiring Diagram
*FOR MULTIPLE CONDUCTOR APPLICATIONS
THE SAME SIZE AND STYLE WIRE MUST BE USED.
M
OVERLOAD
RELAY
L1/1
L1/1
T1/2 T2/4 T3/6
L2/3 L3/5
L2/3 L3/5
H1(Dot) H1(Dot) H1(Dot)
H2 H2 H2
X1 X1 X1
X2X2X2
CT1
T1/2 T2/4 T3/6
CT2 CT3
Wire Type # Wires Range Torque
1 Wire
2 Wires*
1 Wire
2 Wires*
Stranded / Solid 0.75...4.0 mm²
(18...12 AWG)
1.4 N•m
(12 lb-in)
Flexible Stranded
w/ Ferrule 0.75...2.5 mm² 1.4 N•m
ClosedOpenOpen
OpenOpenClosed
Test TrippedStop PressedNormal
95
97 98
96
97 95
98 96
97 95
98 96
97 95
98 96
Contact Status
Contact Ratings: N.O. C600 / N.C. B600 (AC)
N.O. / N.C. R300 (DC)
Table 2: Panel Mount, Standalone Overload, High Fault, Type I
E100 Overload
Cat No Amp Range
Max. Available
Fault Current Max. Voltage
1EFHZ 30-150 A
1EFJZ 40-200 A
1EFKZ 60-300 A
1EFWZ 80-400 A
1EFLZ 100-500 A
1EFMZ 120-600 A
1EFNZ 160-800 A
193- 100 kA 600 V
3
Publication 193-IN084F-EN-E - March 2022 PN-562589 DIR 10004184713 (Version 05)
Current Transformer Selection and Application
E100 overload relays (Cat. No. 193-1EF_Z) are designed for use with separately mounted, customer-supplied current transformers (CTs) as required in
higher-current applications. CTs must be kept at least six times the wire gauge from the overload relay.
Rating: Protective Relaying
Secondary Current: 5 A
Secondary Load: 0.1VA (Overload Relay Only)
Accuracy: 2% Over Operating Range
ANSI (USA): Class C57.13,BO.1
CSA (Canada): Class 10L5
IEC (Europe): 5VA Class, 5P10
Current Transformer Specification (One Per Motor Phase)
Primary
Current
Transformers
E100 Cat. No. 193-1EFHZ 193-1EFJZ 193-1EFKZ 193-1EFWZ 193-1EFLZ 193-1EFMZ 193-1EFNZ
FLA (A) 30-150 40-200 60-300 80-400 100-500 120-600 160-800
C.T. Ra�o 150:5 200:5 300:5 400:5 500:5 600:5 800:5
CT 1411-*-151 1411-*-201 1411-*-301 1411-*-401 1411-*-501 1411-*-601 1411-*-801
Multiple of FLA
Trip Curves
Time (s)
1
10
100
1000
1 8
Cold Trip Curves
Class 30
Class 20
Class 15
Class 10
1
10
100
1000
1 8
Hot Trip Curves
Class 30
Class 20
Class 15
Class 10
Multiple of FLA
Publication 193-IN084F-EN-E - March 2022 PN-562589 DIR 10004184713 (Version 05)
Current Transformer Selection and Application
E100 overload relays (Cat. No. 193-1EF_Z) are designed for use with separately mounted, customer-supplied current transformers (CTs) as required in
higher-current applications. CTs must be kept at least six times the wire gauge from the overload relay.
Rating: Protective Relaying
Secondary Current: 5 A
Secondary Load: 0.1VA (Overload Relay Only)
Accuracy: 2% Over Operating Range
ANSI (USA): Class C57.13,BO.1
CSA (Canada): Class 10L5
IEC (Europe): 5VA Class, 5P10
Current Transformer Specification (One Per Motor Phase)
Primary
Current
Transformers
E100 Cat. No. 193-1EFHZ 193-1EFJZ 193-1EFKZ 193-1EFWZ 193-1EFLZ 193-1EFMZ 193-1EFNZ
FLA (A) 30-150 40-200 60-300 80-400 100-500 120-600 160-800
C.T. Ra�o 150:5 200:5 300:5 400:5 500:5 600:5 800:5
CT 1411-*-151 1411-*-201 1411-*-301 1411-*-401 1411-*-501 1411-*-601 1411-*-801
Multiple of FLA
Trip Curves
Time (s)
1
10
100
1000
1 8
Cold Trip Curves
Class 30
Class 20
Class 15
Class 10
1
10
100
1000
1 8
Hot Trip Curves
Class 30
Class 20
Class 15
Class 10
Multiple of FLA
4
PN-562589
DIR 10004184713 (Version 05)
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
For Technical Support, visit ROK.AUTO/SUPPORT.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza ĺş Merkezi E Blok Kat:6 34752 ĺçerenkÖy, ĺstanbul, Tel: +90 (216) 5698400
Allen-Bradley, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
EEE YÖnetmeliğine Uygundur
Publication 193-IN084F-EN-E - March 2022 | Supersedes 193-IN084C-EN-E - October 2021
Copyright ©2022 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
(Cat 193-1ERA)
Overload Relay Reset Adapter
(Cat 193-1BC8)
Overload Relay Anti-Tamper Shield
0.8 x 2.5 mm MAX
1
1
2 3
2 3 4
Accessories
CLICK
PN-562589
DIR 10004184713 (Version 05)
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
For Technical Support, visit ROK.AUTO/SUPPORT.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza ĺş Merkezi E Blok Kat:6 34752 ĺçerenkÖy, ĺstanbul, Tel: +90 (216) 5698400
Allen-Bradley, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
EEE YÖnetmeliğine Uygundur
Publication 193-IN084F-EN-E - March 2022 | Supersedes 193-IN084C-EN-E - October 2021
Copyright ©2022 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
(Cat 193-1ERA)
Overload Relay Reset Adapter
(Cat 193-1BC8)
Overload Relay Anti-Tamper Shield
0.8 x 2.5 mm MAX
1
1
2 3
2 3 4
Accessories
CLICK
advertisement
Key Features
- External CT
- Adjustable trip
- Selectable trip class
- Auto/Manual reset
- DIN rail mount
- Short circuit protection
- Overload protection
- Motor protection
Related manuals
Frequently Answers and Questions
What type of current transformers are compatible with the 193 E100?
The 193 E100 is designed for use with separately mounted, customer-supplied current transformers (CTs). The CTs must be rated for protective relaying applications and have a secondary current of 5A. Refer to the document for specific CT recommendations based on the motor's full load amperage (FLA).
How do I adjust the trip current on the 193 E100?
To adjust the trip current, turn the dial until the desired current is aligned with the pointer. The trip rating is 120% of the dial setting.
What are the different trip classes available on the 193 E100?
The 193 E100 features selectable trip classes, allowing users to customize the protection characteristics based on the application. Trip classes refer to different time-current curves, affecting how quickly the relay trips in response to an overload. The document provides information about different trip classes and their applications.
advertisement