Allen-Bradley DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual
The Allen-Bradley DC/DC Converter - 48V/48V, 5 A, 240 W is a DIN rail mountable DC/DC converter providing a floating, stabilized, and galvanically isolated SELV/PELV output voltage. This unit is suited for nearly every situation with features like high efficiency, small size, wide operational temperature range, and power reserve.
advertisement
DC/DC Converter - 48V/48V,
5 A, 240 W
Catalog Number 1606-XLDF240F
Reference Manual Original Instructions
5 A, 240 W
Catalog Number 1606-XLDF240F
Reference Manual Original Instructions
2 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021
DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Labels may also be on or inside the equipment to provide specific precautions.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which
may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).
DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Labels may also be on or inside the equipment to provide specific precautions.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which
may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).
Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 3
Table of Contents
Terminology and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Requirements for the Supplying Source. . . . . . . . . . . . . . . . . . . . . . . . . 7
Input Inrush Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Soft Start Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Hold-up Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Efficiency and Power Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Functional Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Front Side and User Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Connection Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Daisy Chaining of Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Lifetime Expectancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mean Time Between Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electromagnetic Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Safety and Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dielectric Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Approved, Fulfilled, or Tested Standards . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Regulatory Product Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Physical Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wall/Panel Mount Bracket (Cat. No. 1606-XLC) . . . . . . . . . . . . . . . . . 17
Side Mount Bracket (Cat. No. 1606-XLA-S44) . . . . . . . . . . . . . . . . . . . 17
48V DC Redundancy Module (Cat. No. 1606-XLERED) . . . . . . . . . . 18
Buffer Module (Cat. No. 1606-XLSBUFFER) . . . . . . . . . . . . . . . . . . . . 18
Peak Current Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Output Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Battery Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Series Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Parallel Use to Increase Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Parallel Use for Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1+1 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
N+1 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Use In a Tightly Sealed Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Mounting Orientations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table of Contents
Terminology and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Requirements for the Supplying Source. . . . . . . . . . . . . . . . . . . . . . . . . 7
Input Inrush Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Soft Start Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Hold-up Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Efficiency and Power Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Functional Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Front Side and User Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Connection Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Daisy Chaining of Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Lifetime Expectancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mean Time Between Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electromagnetic Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Safety and Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dielectric Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Approved, Fulfilled, or Tested Standards . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Regulatory Product Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Physical Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wall/Panel Mount Bracket (Cat. No. 1606-XLC) . . . . . . . . . . . . . . . . . 17
Side Mount Bracket (Cat. No. 1606-XLA-S44) . . . . . . . . . . . . . . . . . . . 17
48V DC Redundancy Module (Cat. No. 1606-XLERED) . . . . . . . . . . 18
Buffer Module (Cat. No. 1606-XLSBUFFER) . . . . . . . . . . . . . . . . . . . . 18
Peak Current Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Output Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Battery Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Series Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Parallel Use to Increase Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Parallel Use for Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1+1 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
N+1 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Use In a Tightly Sealed Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Mounting Orientations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021
Table of Contents
Notes:
Table of Contents
Notes:
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
advertisement
Key Features
- DIN rail mountable
- Floating SELV/PELV output
- High efficiency
- Wide operational temperature range
- Power reserve
- Compact size
- Soft start
- Low inrush current
- Reverse polarity protection
- Overload, no-load, and short-circuit protection
Related manuals
Frequently Answers and Questions
What is the output voltage range of this DC/DC converter?
The output voltage range is 48…56V with a factory setting of 48.0V.
What is the maximum output current for this DC/DC converter?
The maximum output current is 7A peak, but the continuous current depends on the ambient temperature: 6A below 45 °C (113 °F), 5A at 60 °C (140 °F), and 3.8A at 70 °C (158 °F).
What is the efficiency of this DC/DC converter?
The efficiency is up to 95.1% at 48V, 5A output.