Allen-Bradley 193 E200 / E300 Control Module Installation Instructions
The Allen-Bradley 193 E200 / E300 Control Module is a versatile device designed for industrial applications. This module provides various input/output capabilities, enabling you to control and monitor various processes. It features expansion bus connectors for scalability, relay and ground fault terminals for reliable operation, power/PTC terminals for managing power supply and thermal protection, and communication module latch for secure connection. The module is compatible with a range of AC and DC power supplies, ensuring flexibility in your system setup.
advertisement
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of
malfunction or damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.
Features
Installation
193-EIOGP-42- _ _ _
193-EIOGP-22- _ _ _
Installation Instructions
E300 / E200 Control Module
(Cat 193-EIO-_ _-_ _ _; 193-EIOGP-_ _-_ _ _)
Sensing Module
Latch
Power / PTC
Terminals
Input / Output
Terminals
Communication
Module Latch
Expansion Bus
Connector
Relay / Ground
Fault Terminals
2
3
1
Additional Resources:
1) Go to http://www.literature.rockwellautomation.com; 2) Go to Search. Type in publication number: 193-UM015
R13R14 S1 S2
A1 A1 A2 IN2 IN3 IT1 IT2
R13R14 S1 S2
193-EIO-63- _ _ _
193-EIO-43- _ _ _
R13R14
R23 R24
A1 A1 A2 IN2 IN3 IN4 IN5
R13R14
R23 R24
A1 A1 A2 IN2IN3
A1 A1 A2 IT1 IT2
IN1 IN0 A2
A1
R04 R03
193-EIO-22-24D
193-EIO-22-120 and
193-EIO-22-240
R13R14
A1 A1 A2
R13R14
A1 A1 A2
IMPORTANT - Tightening screws
while the 6 position connector is
plugged in could result in damage
to the connector.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of
malfunction or damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.
Features
Installation
193-EIOGP-42- _ _ _
193-EIOGP-22- _ _ _
Installation Instructions
E300 / E200 Control Module
(Cat 193-EIO-_ _-_ _ _; 193-EIOGP-_ _-_ _ _)
Sensing Module
Latch
Power / PTC
Terminals
Input / Output
Terminals
Communication
Module Latch
Expansion Bus
Connector
Relay / Ground
Fault Terminals
2
3
1
Additional Resources:
1) Go to http://www.literature.rockwellautomation.com; 2) Go to Search. Type in publication number: 193-UM015
R13R14 S1 S2
A1 A1 A2 IN2 IN3 IT1 IT2
R13R14 S1 S2
193-EIO-63- _ _ _
193-EIO-43- _ _ _
R13R14
R23 R24
A1 A1 A2 IN2 IN3 IN4 IN5
R13R14
R23 R24
A1 A1 A2 IN2IN3
A1 A1 A2 IT1 IT2
IN1 IN0 A2
A1
R04 R03
193-EIO-22-24D
193-EIO-22-120 and
193-EIO-22-240
R13R14
A1 A1 A2
R13R14
A1 A1 A2
IMPORTANT - Tightening screws
while the 6 position connector is
plugged in could result in damage
to the connector.
PN-510351
DIR 10000518534 (Version 04)
Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Publication 193-IN058E-EN-P - July 2018
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Wiring Diagrams
Power Requirements
Input / Output Ratings
R24R23
RELAY 2RELAY 1
R14R13IN3IN2
Additional Inputs for 193-EIO-63-24D
IN0 IN1
A2 PEA1A1
A1 R03 R04 A2
IN5IN4
(+) (-)
RELAY 0
S2S1
RELAY 1
R14R13IN3IN2
IN0 IN1
A2A1A1
A1 R03 R04 A2
IT2IT1
(+) (-)
RELAY 0
193-EIOGP-_ _-_ _ _193-EIO-_ _-_ _ _
PE
Ground
FaultPTC
Additional Inputs for 193-EIOGP-42-24D
Nominal Supply Voltage (Us)
193-EIO-22-24D, 193-EIO-63-24D, 193-EIOGP-42-24D
193-EIO-22-120, 193-EIO-43-120, 193-EIOGP-22-120
193-EIO-22-240, 193-EIO-43-240, 193-EIOGP-22-240
24V DC
Operating Range 11 - 30V DC
Rated Supply Current 725mA @ 11V DC derated to 267mA @ 30V DC
Maximum Surge Current at Power-Up 6A for 1.25ms
Maximum Power Consumption 6W
Maximum Power Interruption Time @ 25 V DC 10ms at all environmental conditions
Rated Supply Voltage (Us) 120V AC
Operating Range 85 - 132V AC
Rated Supply Current 118mA @ 85V AC derated to 65mA @ 132V AC
Maximum Surge Current at Power-Up 5.2A for 1.00ms
Maximum Power Consumption 6W
Maximum Power Interruption Time @ 120V AC 10ms at all environmental conditions
Rated Supply Voltage (Us) 240V AC
Operating Range 184 - 265V AC
Rated Supply Current 58mA @ 172V AC derated to 33mA @ 310V AC
Maximum Surge Current at Power-Up 5.8A for 1.25ms
Maximum Power Consumption 6W
Maximum Power Interruption Time @ 240V AC 10ms at all environmental conditions
Rated Operating
Current (Ie)
Cat No
Outputs
5A @ 250V AC
0.25A @ 220V DC
5A @ 250V AC
5A @ 5-30V DC
2A @ 250V AC
2A @ 5-30V DC
Output Current
Rating
Resistive (P.F. = 1.0) Inductive
Cat No
Inputs
193-EIO-22-24D
193-EIO-63-24D
193-EIOGP-42-24D
193-EIO-22-120
193-EIO-43-120
193-EIOGP-22-120
ALL
11 - 30V DC
74 - 132V AC
193-EIO-22-240
193-EIO-43-240
193-EIOGP-22-240
159 - 265V AC
Operating Voltage Range
+t
Additional Inputs for 193-EIO-43-_ _ _
and 193-EIO-63-24D
Additional Outputs for
193-EIO-43-_ _ _ and
193-EIO-63-24D
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/about-us/sustainability-ethics/product-environmental-compliance.page
DIR 10000518534 (Version 04)
Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Publication 193-IN058E-EN-P - July 2018
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Wiring Diagrams
Power Requirements
Input / Output Ratings
R24R23
RELAY 2RELAY 1
R14R13IN3IN2
Additional Inputs for 193-EIO-63-24D
IN0 IN1
A2 PEA1A1
A1 R03 R04 A2
IN5IN4
(+) (-)
RELAY 0
S2S1
RELAY 1
R14R13IN3IN2
IN0 IN1
A2A1A1
A1 R03 R04 A2
IT2IT1
(+) (-)
RELAY 0
193-EIOGP-_ _-_ _ _193-EIO-_ _-_ _ _
PE
Ground
FaultPTC
Additional Inputs for 193-EIOGP-42-24D
Nominal Supply Voltage (Us)
193-EIO-22-24D, 193-EIO-63-24D, 193-EIOGP-42-24D
193-EIO-22-120, 193-EIO-43-120, 193-EIOGP-22-120
193-EIO-22-240, 193-EIO-43-240, 193-EIOGP-22-240
24V DC
Operating Range 11 - 30V DC
Rated Supply Current 725mA @ 11V DC derated to 267mA @ 30V DC
Maximum Surge Current at Power-Up 6A for 1.25ms
Maximum Power Consumption 6W
Maximum Power Interruption Time @ 25 V DC 10ms at all environmental conditions
Rated Supply Voltage (Us) 120V AC
Operating Range 85 - 132V AC
Rated Supply Current 118mA @ 85V AC derated to 65mA @ 132V AC
Maximum Surge Current at Power-Up 5.2A for 1.00ms
Maximum Power Consumption 6W
Maximum Power Interruption Time @ 120V AC 10ms at all environmental conditions
Rated Supply Voltage (Us) 240V AC
Operating Range 184 - 265V AC
Rated Supply Current 58mA @ 172V AC derated to 33mA @ 310V AC
Maximum Surge Current at Power-Up 5.8A for 1.25ms
Maximum Power Consumption 6W
Maximum Power Interruption Time @ 240V AC 10ms at all environmental conditions
Rated Operating
Current (Ie)
Cat No
Outputs
5A @ 250V AC
0.25A @ 220V DC
5A @ 250V AC
5A @ 5-30V DC
2A @ 250V AC
2A @ 5-30V DC
Output Current
Rating
Resistive (P.F. = 1.0) Inductive
Cat No
Inputs
193-EIO-22-24D
193-EIO-63-24D
193-EIOGP-42-24D
193-EIO-22-120
193-EIO-43-120
193-EIOGP-22-120
ALL
11 - 30V DC
74 - 132V AC
193-EIO-22-240
193-EIO-43-240
193-EIOGP-22-240
159 - 265V AC
Operating Voltage Range
+t
Additional Inputs for 193-EIO-43-_ _ _
and 193-EIO-63-24D
Additional Outputs for
193-EIO-43-_ _ _ and
193-EIO-63-24D
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/about-us/sustainability-ethics/product-environmental-compliance.page
advertisement
Key Features
- Input/Output capabilities
- Expansion Bus Connectors
- Relay and Ground Fault Terminals
- Power/PTC Terminals
- Communication Module Latch
- AC/DC Power Supply Compatibility
Related manuals
Frequently Answers and Questions
What are the installation requirements for the Allen-Bradley 193 E200 / E300 Control Module?
The module should be installed in a suitable enclosure, kept free from contaminants, and installed by trained personnel following applicable code of practice. Disconnect the power source before installation or servicing.
What are the power requirements for the Allen-Bradley 193 E200 / E300 Control Module?
The power requirements vary depending on the specific model. Please refer to the document for power supply specifications for your particular module.
How do I troubleshoot malfunctions or damage to the Allen-Bradley 193 E200 / E300 Control Module?
Do not attempt repairs yourself. Return the product to the manufacturer for repair. Do not dismantle the product.