Allen-Bradley 284D ArmorStart Base and Control Module is a device that provides a reliable and efficient solution for motor control applications. Featuring a user-friendly interface, it offers a wide range of configurable settings to adapt to various motor types and operating conditions. This base and control module can be used in various industrial settings, including manufacturing, processing, and infrastructure.
advertisement
ArmorStart Base and Control Module Replacement
1) Remove and lockout power sources feeding the unit.
2) Turn unit disconnect switch to the “OFF” position.
3) Remove all of the quick connect cables from the Control Module.
4) Loosen the four mounting screws on the Control Module.
5) Unplug the Control Module from the Base Module by slowly pulling straight forward.
WARNING To prevent electrical shock, disconnect from power source before installing or servicing.
WARNING The drive contains high voltage capacitors which take time to discharge after removal of main supply. Before working on drive, ensure
isolation of main supply from line inputs (R, S, T [L1, L2, L3]). Wait three minutes for capacitors to discharge to safe voltage levels. Failure
to do so may result in personal injury or death. Darkened display LEDs are not an indication that capacitors have discharged to safe
voltage levels.
Removal of Control Module
*The removal of the Base Module is only required for Base Module Replacement. If only the Control Module is being replaced, skip to Step 18.
6) Remove communications, input, and output cables from the Base Module.
7) Loosen the four mounting screws on the
Terminal Access Cover Plate.
8) Remove cover plate.
9) Loosen terminal screws.
10) Remove all wires from terminal
block.
11) Remove conduit fittings.
Removal of Base Module
With Conduit / Cable With ArmorConnect Media
Motor
Cable
Terminal Access
Cover Plate
6
1
3
7
8
9
10
5
4
2
Control
Module
CAUTION Verify that power is removed to motor, inputs, and outputs before replacing any module.
Control
Module
Base
Module
Disconnect SM
wire connection
between Control and
Base Modules
6) Remove all low power quick disconnect cables from the Base
Module.
7) Unplug and remove the ArmorConnect power media from the
gland plate.
Skip to Step 12.
12) Loosen unit mounting screws and remove the Base Module.
12
3-Phase
Control
Voltage
-Bulletin 284D shown-
When Safety version used, internal cable
connection needs to be disconnected.
Base
Module
Note if the existing base module
includes guide pins.
Guide pins
7
1) Remove and lockout power sources feeding the unit.
2) Turn unit disconnect switch to the “OFF” position.
3) Remove all of the quick connect cables from the Control Module.
4) Loosen the four mounting screws on the Control Module.
5) Unplug the Control Module from the Base Module by slowly pulling straight forward.
WARNING To prevent electrical shock, disconnect from power source before installing or servicing.
WARNING The drive contains high voltage capacitors which take time to discharge after removal of main supply. Before working on drive, ensure
isolation of main supply from line inputs (R, S, T [L1, L2, L3]). Wait three minutes for capacitors to discharge to safe voltage levels. Failure
to do so may result in personal injury or death. Darkened display LEDs are not an indication that capacitors have discharged to safe
voltage levels.
Removal of Control Module
*The removal of the Base Module is only required for Base Module Replacement. If only the Control Module is being replaced, skip to Step 18.
6) Remove communications, input, and output cables from the Base Module.
7) Loosen the four mounting screws on the
Terminal Access Cover Plate.
8) Remove cover plate.
9) Loosen terminal screws.
10) Remove all wires from terminal
block.
11) Remove conduit fittings.
Removal of Base Module
With Conduit / Cable With ArmorConnect Media
Motor
Cable
Terminal Access
Cover Plate
6
1
3
7
8
9
10
5
4
2
Control
Module
CAUTION Verify that power is removed to motor, inputs, and outputs before replacing any module.
Control
Module
Base
Module
Disconnect SM
wire connection
between Control and
Base Modules
6) Remove all low power quick disconnect cables from the Base
Module.
7) Unplug and remove the ArmorConnect power media from the
gland plate.
Skip to Step 12.
12) Loosen unit mounting screws and remove the Base Module.
12
3-Phase
Control
Voltage
-Bulletin 284D shown-
When Safety version used, internal cable
connection needs to be disconnected.
Base
Module
Note if the existing base module
includes guide pins.
Guide pins
7
13) Mount Base Module with four Mounting Screws.
14) Re-Install conduit fittings and wires onto terminal block.
15) Tighten the terminal screws.
16) Install terminal cover plate.
17) Tighten the four mounting screws on
the terminal access cover plate to
12-14 lb-in.
With Conduit / Cable With ArmorConnect Media
Terminal Access
Cover Plate
PN-78269
DIR 10000125790 (Version 01)
Printed in U.S.A.
Control
Module
Base Module
Motor
Cable
17
16
15
Control
Module
20
18
19
14
Base
Module
Control
Module
13) Mount Base Module with four mounting screws.
14) Install the low power cables and ArmorConnect Media by
plugging the media in and tightening the fastener.
Skip to Step 18
Installation of Control Module
Installation of Base Module
NOTE: Verify that the new Control Module has the same node address as the
old module. Default setting is ‘99’
For the Safety version, re-connect the wire connection
between the Control and Base Modules
18) Install the Control Module by pushing straight toward the base with proper orientation
19) Tighten the four mounting screws to 30-40 lb-in.
20) Install motor and brake cables to the Control Module.
14
13
13
12-14 in-lbs
30-40 in-lbs
Line Voltage
16-20 in-lbsControl Voltage
5-7 in-lbs
Connect SM
wire connection
between Control and
Base Modules
Input / Output
Cables
14) Re-Install conduit fittings and wires onto terminal block.
15) Tighten the terminal screws.
16) Install terminal cover plate.
17) Tighten the four mounting screws on
the terminal access cover plate to
12-14 lb-in.
With Conduit / Cable With ArmorConnect Media
Terminal Access
Cover Plate
PN-78269
DIR 10000125790 (Version 01)
Printed in U.S.A.
Control
Module
Base Module
Motor
Cable
17
16
15
Control
Module
20
18
19
14
Base
Module
Control
Module
13) Mount Base Module with four mounting screws.
14) Install the low power cables and ArmorConnect Media by
plugging the media in and tightening the fastener.
Skip to Step 18
Installation of Control Module
Installation of Base Module
NOTE: Verify that the new Control Module has the same node address as the
old module. Default setting is ‘99’
For the Safety version, re-connect the wire connection
between the Control and Base Modules
18) Install the Control Module by pushing straight toward the base with proper orientation
19) Tighten the four mounting screws to 30-40 lb-in.
20) Install motor and brake cables to the Control Module.
14
13
13
12-14 in-lbs
30-40 in-lbs
Line Voltage
16-20 in-lbsControl Voltage
5-7 in-lbs
Connect SM
wire connection
between Control and
Base Modules
Input / Output
Cables
advertisement
Key Features
- Modular design
- Quick connect cables
- Configurable settings
- High voltage capacitors
- Safety version
- Terminal block
- Conduit/Cable and ArmorConnect Media connections
- ArmorConnect Media Support
Related manuals
Frequently Answers and Questions
How do I remove the Control Module?
1. Remove and lockout power sources feeding the unit.
2. Turn unit disconnect switch to the “OFF” position. Verify that power is removed to motor, inputs, and outputs before replacing any module.
3. Remove all of the quick connect cables from the Control Module.
4. Loosen the four mounting screws on the Control Module.
5. Unplug the Control Module from the Base Module by slowly pulling straight forward.
How do I install the Control Module?
18) Install the Control Module by pushing straight toward the base with proper orientation
19) Tighten the four mounting screws to 30-40 lb-in.
20) Install motor and brake cables to the Control Module.
What should I do before working on the drive?
Ensure isolation of the main supply from line inputs (R, S, T [L1, L2, L3]). Wait three minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal injury or death.