Allen-Bradley ArmorBlock MaXum I/O Cable Bases Series B are designed to mate with 4 or 8 point modules, offering plug-and-play upgrade capability. These bases provide easy field replacement and are compatible with both flat and round media cable types. They are intended for industrial environments and offer IP67 sealing integrity.
advertisement
Publication 1792D-IN009B-EN-P - September 2000
Installation Instructions
ArmorBlock MaXum I/O Cable Bases
Series B
(Series 1792D-CBXXX)
The ArmorBlock MaXum™ Ι/Ο Cable Bases mate with 4 or 8 point
modules depending on your installation requirements. No
modification is required. Modules are interchangeable whether flat or
round media cable bases are used. This interchangeability provides
plug and play block upgrade capability and easy field replacement.
The completely assembled ArmorBlock module and base requires no
enclosure.
These instructions describe the installation of each cable base. The
catalog numbers for the cable bases are:
• 1792D-CB12 for 12mm drop cable installation, see page 3
• 1792D-CBFM for flat media installation using KwikLink™
cabling, see page 7
(Please note: ArmorBlock MaXum modules and flat or round media
cables are ordered and shipped separately.)
CB12 CBFM 41528
41529
Installation Instructions
ArmorBlock MaXum I/O Cable Bases
Series B
(Series 1792D-CBXXX)
The ArmorBlock MaXum™ Ι/Ο Cable Bases mate with 4 or 8 point
modules depending on your installation requirements. No
modification is required. Modules are interchangeable whether flat or
round media cable bases are used. This interchangeability provides
plug and play block upgrade capability and easy field replacement.
The completely assembled ArmorBlock module and base requires no
enclosure.
These instructions describe the installation of each cable base. The
catalog numbers for the cable bases are:
• 1792D-CB12 for 12mm drop cable installation, see page 3
• 1792D-CBFM for flat media installation using KwikLink™
cabling, see page 7
(Please note: ArmorBlock MaXum modules and flat or round media
cables are ordered and shipped separately.)
CB12 CBFM 41528
41529
2 ArmorBlock MaXum I/O Cable Bases Series B
Publication 1792D-IN009B-EN-P - September 2000
European Union Directive Compliance
If this product has the CE mark it is approved for installation within
the European Union and EEA regions. It has been designed and
tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 -
Industrial Environment
• EN 50082-2 EMC - Generic Immunity Standard, Part 2 -
Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation Wiring and Grounding Guidelines For
Noise Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B113
Package Contents for 1792D-CB12
Your package contains:
• 1 ArmorBlock 12mm cable base
• installation instructions
(Please note: ArmorBlock MaXum modules are ordered and shipped
separately.)
Publication 1792D-IN009B-EN-P - September 2000
European Union Directive Compliance
If this product has the CE mark it is approved for installation within
the European Union and EEA regions. It has been designed and
tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 -
Industrial Environment
• EN 50082-2 EMC - Generic Immunity Standard, Part 2 -
Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation Wiring and Grounding Guidelines For
Noise Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B113
Package Contents for 1792D-CB12
Your package contains:
• 1 ArmorBlock 12mm cable base
• installation instructions
(Please note: ArmorBlock MaXum modules are ordered and shipped
separately.)
ArmorBlock MaXum I/O Cable Bases Series B 3
Publication 1792D-IN009B-EN-P - September 2000
Install Your ArmorBlock 1792D-CB12
To install the cable base:
• Mount the cable base
• Attach the module to the base
• Attach the cables
These steps are described in more detail in the following
sections.
Mount the Cable Base
The cable base can be mounted either vertically or horizontally, using
3 screws. Cable bases accommodate 4 or 8 point ArmorBlock MaXum
modules. You must allow additional space for installation of 8 point
ArmorBlock MaXum modules. They are longer than the 4 point
modules.
41537
When
installing a
cable base
with an 8
connector
module, allow
for the
additional
length.
1.90in.
48.18mm 2.70in.
68.5mm
1.42in.
36.0mm
0.26in.
6.5mm
4.21in.
107mm
5.71in.
145mm
1.35in.
34.18mm
1.10in.
28mm
2.05in.
52mm
0.18in.
04.6mm
1.10in.
28mm
0.60in.
15.3mm
5.71in.
145mm
4 connector
pins
1.24in.
31.5mm
7.84in.
199mm
7 connector
module
12mm
Publication 1792D-IN009B-EN-P - September 2000
Install Your ArmorBlock 1792D-CB12
To install the cable base:
• Mount the cable base
• Attach the module to the base
• Attach the cables
These steps are described in more detail in the following
sections.
Mount the Cable Base
The cable base can be mounted either vertically or horizontally, using
3 screws. Cable bases accommodate 4 or 8 point ArmorBlock MaXum
modules. You must allow additional space for installation of 8 point
ArmorBlock MaXum modules. They are longer than the 4 point
modules.
41537
When
installing a
cable base
with an 8
connector
module, allow
for the
additional
length.
1.90in.
48.18mm 2.70in.
68.5mm
1.42in.
36.0mm
0.26in.
6.5mm
4.21in.
107mm
5.71in.
145mm
1.35in.
34.18mm
1.10in.
28mm
2.05in.
52mm
0.18in.
04.6mm
1.10in.
28mm
0.60in.
15.3mm
5.71in.
145mm
4 connector
pins
1.24in.
31.5mm
7.84in.
199mm
7 connector
module
12mm
4 ArmorBlock MaXum I/O Cable Bases Series B
Publication 1792D-IN009B-EN-P - September 2000
Attach the Module to the Base
1. Position the module over the mounted cable base. Align the
three captive screws in the module with the accepting
receptacles in the base.
2. Tighten the screws with a torque of 8 inch-pounds to secure
the module to the base.
ArmorBlock MaXum I/O modules are described in the following
publications:
• 1792D series of ArmorBlock MaXum Installation Instructions
• 1792-TD001B-EN-P ArmorBlock Technical Data
The DeviceNet™ Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at
http://www.ab.com/networks for producer/consumer technology
information and updates.
IMPORTANT Make sure you properly align the screws to
complete the connections between the module
contacts and the cable contacts.
30834-M
Screws must be
aligned properly to
complete contact
connections.
Contact
connections
Publication 1792D-IN009B-EN-P - September 2000
Attach the Module to the Base
1. Position the module over the mounted cable base. Align the
three captive screws in the module with the accepting
receptacles in the base.
2. Tighten the screws with a torque of 8 inch-pounds to secure
the module to the base.
ArmorBlock MaXum I/O modules are described in the following
publications:
• 1792D series of ArmorBlock MaXum Installation Instructions
• 1792-TD001B-EN-P ArmorBlock Technical Data
The DeviceNet™ Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at
http://www.ab.com/networks for producer/consumer technology
information and updates.
IMPORTANT Make sure you properly align the screws to
complete the connections between the module
contacts and the cable contacts.
30834-M
Screws must be
aligned properly to
complete contact
connections.
Contact
connections
5
6
7
8
9
10
11
12
13
14
15
16
advertisement
Key Features
- Interchangeable modules
- Plug and play upgrades
- IP67 sealing
- Flat and round media cable compatibility
- Vertical or horizontal mounting
- Industrial environment rated
Related manuals
Frequently Answers and Questions
What types of cables can be used with the ArmorBlock MaXum I/O Cable Bases Series B?
These cable bases can accommodate both flat and round media cables. For flat media installations, the KwikLink™ cabling system is recommended.
How many points can the cable base handle?
The cable base can accommodate either 4 or 8 point ArmorBlock MaXum modules, but you'll need to consider additional space if using the 8 point modules as they are longer.
What are the mounting options for the cable base?
The cable base can be mounted either vertically or horizontally, using 3 screws.