Allen-Bradley ArmorBlock MaXum 2 Input Installation Instructions

PDF
Document
Allen-Bradley ArmorBlock MaXum 2 Input Installation Instructions | Manualzz
Publication 1792D-IN015B-EN-P - September 2000
Installation Instructions
ArmorBlock MaXum 2 Input with Alarm/
2 Output Module Series B
(Cat. No. 1792D-2BVA2D)
This ArmorBlock MaXum I/O module (Cat. No. 1792D-2BVA2D) is a
stand-alone 24V dc I/O product which communicates via a
DeviceNet network. The sealed housing of this module requires no
enclosure.
This model has 2 inputs with alarm and 2 outputs. Inputs are 24V dc
automatically configured for PNP (sourcing) or NPN (sinking)
devices. Outputs are also configured for sourcing. Two self-protected
24V dc outputs can provide up to 1.0 amp each. Diagnostic features
included are short circuit, open wire, and no load detection reported
to the point level. Local logic control has been added to the Series B
version of this product.
41453
2 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B
Publication 1792D-IN015B-EN-P - September 2000
Package Contents
Your package contains:
1 ArmorBlock MaXum Module
Installation Instructions
(Please note: Cable bases are ordered and shipped separately.)
European Union Directive Compliance
If this product has the CE mark it is approved for installation within
the European Union and EEA regions. It has been designed and
tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
EN 50081-2 EMC - Generic Emission Standard, Part 2 -
Industrial Environment
EN 50082-2 EMC - Generic Immunity Standard, Part 2 -
Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
Industrial Automation Wiring and Grounding Guidelines For
Noise Immunity, publication 1770-4.1
Automation Systems Catalog, publication B113
ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 3
Publication 1792D-IN015B-EN-P - September 2000
Install Your ArmorBlock MaXum I/O Module
To install the module:
Set the node address
Mount the module to the cable base
Connect the cord sets
Communicate with the module
Each of these steps is explained in more detail in the following
procedures.
Set the Node Address
Valid node addresses are 00 to 63.
Set the node address using the rotary switches, RSNetWorx for
DeviceNet, DeviceNetManager, or other software configuration
tool. Setting the switches between 64 to 99 lets the software have
address control.
Each module is shipped set for node address 63. The switches are
located on the underside of the module. The two switches are:
MSD (most significant digit)
LSD (least significant digit)
To reset the node address, use a small blade screwdriver to rotate the
switches. Line up the small black dot on the switch with the number
setting you wish to use.
The rotary switches are read at module power up only. Settings
between 64 and 99 cause the module to use the last valid node
address stored internally. Example: The last setting was 40. If a
change is made to 68, and then you power up, the address will
default to 40.
4 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B
Publication 1792D-IN015B-EN-P - September 2000
Refer to the illustration of the node address below.
The module is equipped with AutoBaud detect. AutoBaud lets the
module read the settings already in use on your DeviceNet network
and automatically adjusts to follow those settings.
Install the Module
This module mounts to the following cable bases:
1792D-CBFM for KwikLink flat media installation
1792D-CB12 for 12mm drop cable installation
1792D-CB18P for round media DeviceNet and output power
1792D-CB18PT for 4 connector blocks needing round media
DeviceNet and output power
or other optional cable base assembly
IMPORTANT The cable base should already be installed. See
publication 1792D-IN009B-EN-P for more
information on installing the cable base.
30703-MExample: Node address is set at 62, see small black dots.
5
6
7
8
9
10
11
12
13
14
15
16
/
Preparing document for printing…
0%