Robert S.
What are the parameters for static tuning?
The parameter for static tuning on the device is "Static Tune 2."
Allen-Bradley PowerFlex 755 is a versatile AC drive designed for various industrial applications. It offers features like embedded EtherNet/IP communication, making it suitable for integration into automated systems. This drive also allows for easy motor setup with its simple parameter configuration. With its flexibility, it is ideal for applications like fans, pumps, conveyors, and compressors.
Advertisement
Advertisement
These topics are included to provide more detail about the tasks required to start up and configure your drive.
Topic
Identify Option Modules and Compatible Ports
Typical Speed Reference Examples
Acceleration and Deceleration Time
Disable the HIM Start Function
If You Have to Contact Technical Support
Page
Reference Section
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
21
Reference Section
There are three easy ways to determine which drive you are working with.
1. Look at the label on the drive cover. (The label is located behind the HIM.) If the cover is not installed on the drive, use one of the following methods.
2. Locate Nameplate 1 on the drive chassis. The first three characters of the catalog number indicate the drive type.
Nameplate 1 : Specifications and Custom Catalog Number representing options installed at factory.
See Nameplate 2 (Located behind HIM) for equivalent base catalog number and separate options
Cat No. 20F11 N G 011 AA0NNNNN
UL Open Type/IP20 - without Debris Hood and Conduit Plate
UL Type 1 - only with Debris Hood and Conduit Plate
400V Class
Series: A
480V Class
20F = PowerFlex 753
Nameplate 1 : Specifications and Custom Catalog Number representing options installed at factory.
See Nameplate 2 (Located behind HIM) for equivalent base catalog number and separate options
Cat No. 20G11 N G 011 AA0NNNNN
UL Open Type/IP20 - without Debris Hood and Conduit Plate
UL Type 1 - only with Debris Hood and Conduit Plate
400V Class
Series: A
480V Class
20G = PowerFlex 755
3. Look at the main control board that is installed in the drive.
PowerFlex 753 has a 14-point I/O terminal block.
PowerFlex 755 has three EtherNet/IP address selectors.
22
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Wall Mount Frame 1
Wall Mount Frame 2
(3)
(3)
(2)
(1)
L1
R
L2
S
L3
T
BR
1
BR
2
+
DC
-
DC
T1
U
T2
V
T3
W
(2)
Wall Mount Frame 3
(3)
(1)
L1
R
L2
S
L3
T
BR
1
BR
2
+
DC
-
DC
T1
U
T2
V
T3
W
(2)
No.
Name
(1) Power Terminal Block
(2) PE Grounding Studs
(3) PE-A and PE-B
Description
R/L1, S/L2, T/L3, BR1, BR2, +DC, -DC, U/T1, V/T2, W/T3
Terminating point to chassis ground for incoming AC line and motor shields.
MOV and CMC Jumpers
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
23
Reference Section
Wall Mount Frame 4
(1)
(3)
(2)
Wall Mount Frame 5
24
(1)
(3)
No.
Name
(1) Power Terminal Block
(2) PE Grounding Studs
(3) PE-A and PE-B
(2)
Description
R/L1, S/L2, T/L3, BR1, BR2, +DC, -DC, U/T1, V/T2, W/T3
Terminating point to chassis ground for incoming AC line and motor shields.
MOV and CMC Jumpers
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Wall Mount Frame 6 Wall Mount Frame 7
(4)
(5)
(4)
(3)
(1)
(4)
(2)
400/480V drives shown.
(5)
(3)
(1)
(2)
(3)
(4)
(5)
No.
(1)
(2)
Name
Power Terminals
PE Grounding Studs
DC Bus and Brake Terminals
PE-A and PE-B
DC+ and DC-
Description
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3
Terminating point to chassis ground for incoming AC line and motor shield.
+DC, -DC, BR1, BR2 (Optional)
MOV and CMC Jumpers
Bus Voltage Test Points
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
25
Reference Section
Floor Mount Frame 8
(4) PE
(1)
R / L1
S / L2
T / L3
(2)
DC+
DC–
(3)
U / T1
V / T2
W / T3
26
(5)
(4)
PE
(3)
(4)
(5)
No.
Name
(1) Power Bus
(2) DC Bus
Power Bus
PE Grounding Bar
DC+ and DC-
Description
R/L1, S/L2, T/L3 (Drive only.)
DC+, DC- (The DC Bus is included with frame 9 and 10 drives. Frame 8 drives require the field installed kit 20-750-BUS1A-F8.)
U/T1, V/T2, W/T3 (Drive only or Cabinet Options Bay without power output options.)
Terminating point to chassis ground for incoming AC line and motor shield.
Bus Voltage Test Points
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
IMPORTANT
PowerFlex 750-Series drives, frames 1…7, leave the factory with jumpers PE-A and PE-B in one of two possible configurations.
PowerFlex 750-Series drives, frames 8…10, leave the factory with jumpers PE-A1, PE-A2, and PE-B in one of two possible configurations. Reconfigure these jumpers based on the power source type available.
Frames 1…7
Jumper PE-A
(MOV / Input Filter Caps)
Connected
Jumper PE-B
(DC Bus Common Mode Caps)
Connected
AC Fed Solidly Grounded
Delta/Wye with Grounded Wye Neutral
Frames 8…10
Jumper PE-A1
(MOV)
Connected
TN-S Five-wire System
L1
L2
PEN or N
PE
L3
Jumper PE-A2
(Input Filter Caps)
Connected
Jumper PE-B
(DC Bus Common Mode Caps)
Connected
DC fed from passive rectifier that has a Solidly Grounded AC Source
+
DC
-
Delta/Wye with Grounded Wye Neutral
Frames 1…7
Jumper PE-A
(MOV / Input Filter Caps)
Disconnected
Jumper PE-B
(DC Bus Common Mode Caps)
Disconnected
AC Fed Ungrounded
Frames 8…10
Jumper PE-A1
(MOV)
Disconnected
Jumper PE-A2
(Input Filter Caps)
Disconnected or
Ungrounded Secondary
Non-solid Impedance Ground Non-solid B-Phase Ground
High-resistance Ground
Any Active Converter/Active Front End
+
Active
Converter
DC
AFE
-
Delta/Delta with Grounded Leg
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Jumper PE-B
(DC Bus Common Mode Caps)
Disconnected
27
Reference Section
Wall/flange mount frames 1, 6, and 7 and floor mount frames 8…10 use jumper wires to complete an electrical connection when installed.
Wall/flange mount frames 2…5 use jumper screws to complete an electrical connection when installed.
Table 1 - Power Jumper Locations for Frames 1…10
Frame 1
Spade Connectors
Drive Jumper Locations
Connected
Disconnected
PE-B
Disconnected
Frames 2…5
Screw Connectors
• Torque: 1.36 N•m (12.0 lb•in)
• Tool: 6.4 mm (0.25 in.) flat or T15 Hexalobular
)
Connected
PE-A
Connected Disconnected
28
Frame 4 Shown
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Table 1 - Power Jumper Locations for Frames 1…10
(Continued)
Drive
Frame 6
Wire Connectors
• Torque: 1.36 N•m (12.0 lb•in)
• Tools: 7 mm hex socket and T20 Hexalobular
Jumper Locations
Connected
Common Mode
Disconnected
PE-B
E4
PE-B
E4
MOV
Reference Section
Frame 7
Wire Connectors
• Torque: 1.36 N•m (12.0 lb•in)
• Tools: 7 mm hex socket and T20 Hexalobular
Connected
Common Mode
Disconnected
MOV
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
29
Reference Section
Table 1 - Power Jumper Locations for Frames 1…10
(Continued)
Drive
Frames 8…10
PE-A1 Wire Connector
• Torque: 1.8 N•m (16.0 lb•in)
• Tool: T20 Hexalobular
PE-A2 Plug-type Connector
Jumper Locations
Connected Disconnected
30
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Table 1 - Power Jumper Locations for Frames 1…10
(Continued)
Drive
Frames 8…10
PE-B Plug-type Connector
• Tray Torque: 1.86 N•m (16.0 lb•in)
• Tool: T20 Hexalobular
AC Input Drive Shown
Jumper Locations
Reference Section
J3
Connected
J4
Disconnected
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
31
Reference Section
20-750-ENC-1 20-750-UFB-1 20-750-S 20-750-S1 20-750-DENC-1
20-750-ATEX
Option Module
Cat. No. 20-750-
2262C-2R, 2263C-1R2T, 2262D-2R
1132C-2R, 1133C-1R2T, 1132D-2R
1132C-2R, 1133C-1R2T, 1132D-2R with 20-750-ATEX installed
ENETR
ENC-1
(1)
UFB-1
No
No
No
Yes
No
Yes
Yes
No
PowerFlex 753 Drives
Frame 1 Ports Frame 2…7 Ports
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Not Supported
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(1) This publication does not cover the use of this option. Refer to the appropriate publication for more information.
No
No
No
Yes
No
No
Yes
Yes
No
Frame 1 Ports
PowerFlex 755 Drives
Frame 2…10 Ports
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
Yes
No
Yes
Yes
Yes
No
No
Yes
No
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
32
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
10, 11
9
5
6
4
13
7
8
Reference Section
Connectors, embedded devices, and installed option modules such as I/O, communication adapters, and DeviceLogix, have unique port number assignments. Connectors and embedded devices have fixed port numbers that cannot be changed. Option modules are assigned a port number when installed.
IMPORTANT
The 750-Series drive uses the term ‘Port’ to designate (in software) the physical location where hardware is located for ease of selecting hardware or functions to program.
0
2
1
3 2
10
11
12
13
Table 2 - Drive Device Ports and Descriptions
Port
0
1
2
3
4…8
9
Device
Host Drive
HIM
DPI Port
Splitter Cable
(optional)
Option Modules
Auxiliary Power Supply
Option Module
Inverter
Converter
Reserved for future use.
EtherNet/IP
Description
Fixed port for the drive.
Fixed port at HIM cradle connector.
Splitter cable connector provides Port 01 when HIM cradle connector is unused.
Handheld or Remote HIM connection.
Splitter cable connection.
Connects to DPI Port 2.
Provides Port 2 and Port 3.
Available ports for option modules. Refer to the PowerFlex 750-Series AC Drives
Installation Instructions, publication 750-IN001 , for more information on each option’s port recommendations.
Important:
Ports 7 and 8 are available on PowerFlex 755 Frame 2 drives and larger only. PowerFlex 755 Frame 1 drives and 753 drives do not support Ports 7 and 8.
Designated port for the Auxiliary Power Supply when connected via cable.
(PowerFlex 755 Frame 1 and 753 drives only.)
Fixed port for Inverter (PowerFlex 755 Frame 8 drives and larger only).
Fixed port for Converter (PowerFlex 755 Frame 8 drives and larger only).
Fixed port for embedded EtherNet/IP (PowerFlex 755 drives only).
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
33
Reference Section
See the PowerFlex 20-HIM-A6 and 20-HIM-C6S HIM (Human Interface Module) User Manual, publication 20HIM-UM001 for more information on the HIM.
The keypad consists of soft keys, navigation and number keys, and single-function keys, which are described in their respective subsections that follow.
The soft keys on the HIM are located at the top of the keypad and highlighted in the figure.
Depending on the screen being displayed or the data entry mode being used, a soft key name and its function changes. When a dynamic soft key (up to a maximum of five keys) is active, its present function and corresponding Soft Key Label is shown at the bottom of the HIM screen.
The five blue multi-function keys (2, 4, 5, 6, and 8) shown in the figure are used to do the following:
• Enter their respective numeric value
• Scroll menus/screens
• Perform corresponding functions displayed in the Data Area.
Table 3 - Navigation and Number Keys
Multi-function Key Name
2/Down Arrow
4/Left Arrow
5/Enter
6/Right Arrow
8/Up Arrow
Function
• Enters the numeric value ‘2’.
• Scrolls down to select an item.
• Enters the numeric value ‘4’.
• Scrolls left to select an item.
• Enters the numeric value ‘5’.
• Displays the next level of a selected menu item.
• Enters new values.
• Performs intended actions.
• Enters the numeric value ‘6’.
• Scrolls right to select an item.
• Enters the numeric value ‘8’.
• Scrolls up to select an item.
The five gray number keys (0, 1, 3, 7, and 9) are used only to enter their respective numeric value.
34
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
There are four single-function keys, which are highlighted below and listed in the following table. Each single-function key always performs only its dedicated function.
Table 4 - Single-function Keys
Single-function Key Name
Start
(1)
Folders
Function
Starts the drive.
(1)
Controls
Accesses folders for parameters, diagnostics, memory functions, preferences, and other tasks.
Accesses jog, direction, auto/manual, and other control functions.
Stop • Stops the drive or clears a fault.
• This key is always active.
• This key is controlled by drive parameter 307 [Start Stop Mode].
(1) During drive startup these keys are temporarily inactive.
The soft key labels identify the present function of a corresponding soft key on the keypad. Different screens can show different soft key labels.
ESC VIEW REF PAR# TEXT
Soft Key Labels
Soft Keys
Table 5 - Soft Key Label Explanation
Soft Key Label Name
.
Decimal Point
Backspace
+ / -
#
Sign
Number
Language
Scroll Up
ACK
ALL
Scroll Down
Scroll Left
Scroll Right
Acknowledge
All
Function
Adds decimal point to the right-most position of a numeric value.
Deletes the character to the left of the cursor.
Changes the sign of a parameter value.
Selects the Direct Numeric Entry Method to change PowerFlex 750-Series drive parameter associations.
Directly accesses the Select Language To Use screen.
• Scrolls up through display lines.
• Increases a value.
• Scrolls down through display lines.
• Decreases a value.
Scrolls left through display lines.
Scrolls right through display lines.
Acknowledges the fault or alarm on the pop-up screen, stops the backlight from flashing, and keeps the pop-up screen active.
• Clears all faults, alarms or events when a pop-up box appears from a queue screen.
• Restores all Host or Port device parameters to factory defaults.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
35
Reference Section
Table 5 - Soft Key Label Explanation
(Continued)
Soft Key Label
CLR
DEL
EDIT
END
ENTER
ESC
EXP
FIX
INFO
INS
LINK
LOWER
MOST
PAR#
PGDN
PGUP
REF
RESET
TEXT
TOP
UPPER
VIEW
ZONES
Name
Clear
Delete
Edit
End
Enter
Escape
Exponent
Fix
Information
Function
• Deletes an entire text string.
• Displays the Select Action pop-up box used to clear the selected fault, alarm or event, or the entire fault, alarm or event queue.
Deletes a highlighted character.
• Accesses a displayed parameter to edit.
• Accesses the Edit Process Display screen.
• Displays the end (least recent) fault, alarm or event in a queue
• Scrolls to the end line of data on the Device Version information screen.
• Displays the next level of a selected menu item.
• Enters new values.
• Performs the intended action.
• Cancels port verification conflict pop-up box during procedure to resolve a conflict.
• Cancels the existing screen and returns to the previous screen.
• Cancels an entry.
• Cancels pop-up Fault Display screen.
• Displays the time zone groups list screen (only when the Date/Time Set Edit Mode screen is shown).
Allows data entry using scientific notation for 32-bit REAL (floating point) values.
Fixes ‘Changed’ or ‘Requires Configuration’ port verification conflicts upon powerup.
• Shows additional information about a selected port verification conflict upon powerup.
• Shows additional information about Set Default actions.
Insert
Link
Lower
Most
Inserts a space to the left of a highlighted character.
Displays a Link Edit pop-up box to link parameters (only PowerFlex 7-Class drives).
Displays the lower 16 bits (bits 0…15) of a 32-bit Bit-type parameter.
Restores most Host or Port device parameters to factory defaults.
Parameter Number Navigates directly to a parameter.
Page Down Scrolls down to the next page of data lines on the Device Version information screen.
Page Up
Reference
Scrolls up to the previous page of data lines on the Device Version information screen.
Enters the speed reference for the Host Drive.
Reset
Text
Top
Upper
View
Zones
Resets the Process screen’s displayed monitoring items to the factory default monitoring items.
Edits user-definable text for the device selected.
• Displays the top (most recent) fault, alarm or event in a queue.
• Scrolls to the top line of data on the Device Version information screen.
Displays the upper 16 bits (bits 16…31) of a 32-bit Bit-type parameter.
• Toggles between select screens and views.
• Displays the time stamp screen from a fault, alarm or event queue screen.
Displays the Select Time Zone screen.
36
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
1. Access the Status screen.
00
ESC
Stopped
0.000 Hz
Host Drive
240V 4.2A
20G...D014
REF PAR#
AUTO
F
TEXT
Status Screen
2. Use the or key to scroll to the port of the device whose parameters you want to set to factory defaults
(for example, Port 00 for the host drive or the respective port number for one of the drive’s connected peripherals).
3. Press the key to display its last-viewed folder.
4. Use the
5. Use the
6. Press the
or
or
key to scroll to the Memory folder.
key to select
Set Defaults
.
(Enter) key to display the Set Defaults pop-up box (see examples below).
Stopped
0.000 Hz
Port 00 Set Defaults
Host and Ports (Preferred)
This Port Only
AUTO
F
ESC INFO
Stopped
0.000 Hz
Port xx Set Defaults
This Port Only
AUTO
F
ESC INFO
For Host Drive For Connected Peripheral
7. Use the or key to select the appropriate action.
• Host and Ports (Preferred): Selects the host device and all ports for a factory default action.
• This Port Only: Selects only this port for a factory default action.
TIP
For a description of a selected menu item, press the Info soft key.
8. Press the (Enter) key to display the warning pop-up box to reset defaults.
‘Host and Ports (Preferred)’ Pop-Up Box
Stopped
0.000 Hz
AUTO
F
WARNING
Sets most parameters in the
Host device and all ports to factory defaults.
Continue?
ESC ENTER
‘This Port Only’ Pop-Up Box
Stopped
0.000 Hz
AUTO
F
WARNING
Use MOST to reset typical
▲ settings on this port
(preferred). Use ALL to reset all settings.
▼
ESC ALL MOST
Press the
ENTER
soft key to affirm and set most parameters for the host drive and port devices to factory defaults. Press the
ESC soft key to cancel.
Press the
MOST
soft key to set
most
settings for the selected port device to factory defaults. Press the
ESC
soft key to cancel.
IMPORTANT
Setting the drive to factory default results in Fault 48 “System Defaulted”. This is normal and expected.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
37
Reference Section
The Control screen (shown below) is used to directly control the drive. It displays vertical bar graphs of the drive’s Speed
Reference and Feedback values, and a Key Function Map that corresponds to the navigation/number keys for drive control.
Press the (Controls) key to display the Control screen.
IMPORTANT
To navigate from the Control screen to another HIM menu screen, you must always press the ESC
soft key
to deactivate the Control screen and display the previous screen.
IMPORTANT
The HIM can be located in Port 1, Port 2, or Port 3 (default is Port 1). Port 2 and Port 3 can be used for door-mounted or remote-mounted HIMs. See the following table for parameter 545 [SXX] setup for speed reference. (add from Roman's chart in the
Word document P871, P872, P873)
Table 6 - Speed Reference Parameter Settings
No.
Drive
Parameter
Name
545 Spd Ref A Sel
User
Setting
877
Default Value/Options
871 P871 = Port 1 HIM reference
P877 = Port 13 reference
Notes
Selects the source parameter number for the speed reference while in “Auto” (typical) mode. Reference value from port devices. For a speed reference from a communication network, set this parameter to Port 0 and select P871…877 [Port_
n
_Reference] as appropriate.
Important Example
: 20-COMM-E, EtherNet/IP Communication Adapter = Dint for speed reference multiplied by 1,000 (60 Hz = 60,000 and 1750 RPM = 1,750,000).
Control Screen Key Function Map corresponds to Navigation/Number Keys
Stopped
0.000 Hz
REMOVE
HIM
REV
REF FBK
ESC
JOG
REF
EDIT
REF
REF
AUTO
F
MANUAL
FWD
HELP
See table below for key functions.
Table 7 - Control Screen Soft Key
Label
ESC
Name
Escape
Function
Deactivates the Control Screen and reverts back to the previous screen.
38
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 8 - Control Screen Navigation/Number Keys
Key Label
JOG
REF
HELP
REV
EDIT REF
FWD
REMOVE HIM
REF
Function
Jogs the host drive.
Decreases the speed reference for the host drive.
Displays Rockwell Automation Drives Technical Support direct phone number, website address, and email address.
Sets the direction to reverse for the host drive.
Enables direct data entry of the speed reference for the host drive.
Sets the direction to forward for the host drive.
Allows HIM removal without causing a fault if the HIM is not the last controlling device. (The REMOVE HIM label is not available when the HIM has manual control of the host drive. In this case, a fault occurs if the HIM is removed.)
Increases the speed reference for the host drive.
MANUAL
Switches between Auto and Manual modes.
Table 9 - Start and Stop Keys
Single-function Key Name
Start
Stop
Function
Starts the drive.
• Stops the drive or clears a fault.
• This key is always active.
• This key is controlled by drive parameter 307 [Start Stop Mode].
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
39
Reference Section
Terminal block TB1 and the input mode jumpers are mounted directly on the main control board.
SK-R1-MCB1-PF753
1
2
4
3
Table 10 - 753 Main Control Board Details
No. Name
1 Jumper J4 Input Mode
2 TB1
3 TB3
4 TB2
Description
Analog input mode jumper. Selects voltage mode or current mode.
I/O terminal block.
Digital input terminal block.
Relay terminal block.
Table 11 - J4 Input Mode Jumper
Jumper Position Voltage Mode Current Mode
3 1
J4
4 2
J4
3 1
4 2
40
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Table 12 - TB1 Terminal Designations
Ptc-
Ptc+
To0
24VC
+24V
Di C
Di 1
Di 2
Ao0-
Ao0+
10VC
+10V
Ai0-
Ai0+
Terminal
Ao0–
Ao0+
10VC
+10V
Ai0–
Ai0+
Ptc–
Ptc+
T0
24VC
+24V
Di C
Di 1
Di 2
Name
Analog Out 0 (–)
Analog Out 0 (+)
10 Volt Common
+10 Volt Reference
Analog Input 0 (–)
Analog Input 0 (+)
Motor PTC (–)
Motor PTC (+)
Transistor Output 0
24 Volt Common
+24 Volt DC
Digital Input Common
Digital Input 1
Digital Input 2
Description Related
Param
Bipolar, ±10V
(1)
, 11 bit & sign, 2 k ohm minimum load.
4-20 mA
(1)
, 11 bit & sign, 400 ohm maximum load.
270
For (+) 10 Volt references.
2k ohm minimum.
Isolated
(2)
, bipolar, differential, 11 bit & sign.
Voltage Mode:
(3)
±10V @ 88k ohm input impedance.
Current Mode:
(3)
0-20 mA @ 93 ohm input impedance
255
Motor protection device
(Positive Temperature Coefficient).
250
Open drain output, 48V DC, 250 mA maximum load.
Drive supplied logic input power.
150 mA maximum
24V DC (30V DC Max.) - Opto isolated
High State: 20…24V DC
Low State: 0…5V DC
220
(1) Mode is selected by parameter only.
(2) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(3) Mode is selected by jumper J4.
Table 13 - 0…20 mA Analog Input - Unipolar Speed Reference
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Common
+
Ai0–
Ai0+
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port 0: P260 [Anlg In0 Value]
753 Main Control Board TB1
Adjust Scaling
Port 0: P261 [Anlg In0 Hi] = 20 mA
Port 0: P262 [Anlg In0 Lo] = 0 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
J4
3 1
4 2
View Results
Port 0: P260 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Jumper set to current mode.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
41
Reference Section
Table 14 - 0…+10V Analog Input - Unipolar Speed Reference
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Common
+
Ai0–
Ai0+
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port 0: P260 [Anlg In0 Value]
753 Main Control Board TB1
Adjust Scaling
Port 0: P261 [Anlg In0 Hi] = 10 Volt
Port 0: P262 [Anlg In0 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
J4
3 1
4 2
View Results
Port 0: P260 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Jumper set to voltage mode.
Table 15 - 10k Ohm Potentiometer - Unipolar Speed Reference
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
10VC
+10V
Ai0–
Ai0+
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port 0: P260 [Anlg In0 Value]
J4
3 1
4 2
753 Main Control Board TB1
Adjust Scaling
Port 0: P261 [Anlg In0 Hi] = 10 Volt
Port 0: P262 [Anlg In0 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
View Results
Port 0: P260 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Jumper set to voltage mode.
Table 16 - 2-Wire Control on PF753 Main Control Board
Non-Reversing - Internal Supply
Set Direction Mode
Port 0: P308 [Direction Mode] = 2 “Rev Disable”
Stop-Run
24VC
+24V
Di C
Di 1
Set Selection
Port 0: P163 [DI Run] = Port 0: P220 [Digital In Sts], bit 1 = Digital In 1
753 Main Control Board TB1
Reversing - External Supply
+24V
Common
View Results
Port 0: P220 [Digital In Sts]
Port 0: P935 [Drive Status 1]
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Run Fwd
Set Selection
Port 0: P164 [DI Run Forward] = Port 0: P220 [Digital In Sts], bit 1 = Digital In 1
Port 0: P165 [DI Run Reverse] = Port 0: P220 [Digital In Sts], bit 2 = Digital In 2
Run Rev
Di C
Di 1
Di 2
753 Main Control Board TB1
View Results
Port 0: P220 [Digital In Sts]
Port 0: P935 [Drive Status 1]
42
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Table 17 - 3-Wire Control on PF753 Main Control Board
Internal Supply
Set Selection
Port 0: P158 [DI Stop] = Port 0: P220 [Digital In Sts], bit 1 = Digital In 1
Port 0: P161 [DI Start] = Port 0: P220 [Digital In Sts], bit 2 = Digital In 2
Stop
Start
24VC
+24V
Di C
Di 1
Di 2
View Results
Port 0: P220 [Digital In Sts]
Port 0: P935 [Drive Status 1]
+24V
753 Main Control Board TB1
External Supply
Common
Stop
Start
Di C
Di 1
Di 2
Set Selection
Port 0: P158 [DI Stop] = Port 0: P220 [Digital In Sts], bit 1 = Digital In 1
Port 0: P161 [DI Start] = Port 0: P220 [Digital In Sts], bit 2 = Digital In 2
View Results
Port 0: P220 [Digital In Sts]
Port 0: P935 [Drive Status 1]
753 Main Control Board TB1
Reference Section
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
43
Reference Section
Terminal block TB1 and the input mode jumpers are mounted on the option module installed in the drive.
Table 18 - Analog Input Mode Jumpers
Voltage Mode Current Mode
P4
1
2 2
1
P5
P4
1
2 2
1
P5
Table 19 - TB1 Terminal Designations
Di2
Di2P
Ip
Ic
EnC
EnNO
Ai0+
Sh
Di0
Di0P
Di1
Di1P
–10V
10VC
+10V
Sh
Ao0–
Ao0+
Sh
Ai0–
Ip
Ic
Di2
Di2P
Di0
Di0P
Di1
Di1P
EnC
EnNO
Terminal
–10V
10VC
+10V
Sh
Ao0–
Ao0+
Sh
Ai0–
Ai0+
Name Description Related
Param
(4)
–10 Volt Reference Negative 10V DC for analog inputs. 2k ohm minimum.
10 Volt Common For (–) and (+) 10 Volt references.
+10 Volt Reference Positive 10V DC for analog inputs. 2k ohm minimum.
Shield Terminating point for wire shields when an EMC plate or conduit box is not installed.
Analog Out 0 (–) Bipolar, ±10V, 11 bit & sign, 2 k ohm minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum load.
Analog Out 0 (+)
Shield
Analog Input 0 (–)
Analog Input 0 (+)
75 on Port X
Terminating point for wire shields when an EMC plate or conduit box is not installed.
Differential
(2)
, bipolar, 11 bit & sign.
Voltage Mode: ±10V @ 88k ohm input impedance.
Current Mode: 0-20 mA @ 93 ohm input impedance.
50, 70 on Port X
Sh Shield
Input Power
Input Common
Terminating point for wire shields when an EMC plate or conduit box is not installed.
Digital Input 0
Digital Input 0 Power
(1)
Digital Input 1
Digital Input 1Power
(1)
24V DC (30V DC Max.) - Opto isolated
High State: 20…24V DC 11.2 mA DC
Low State: 0…5V DC
120V AC (132V AC Max.) 50/60 Hz
(3)
- Opto isolated
Digital Input 2
Digital Input 2 Power
(1)
High State: 100…132V AC
Low State: 0…30V AC
External 24V DC or 115V AC power supply input connections. Does not power the main control board.
1 on Port X
Enable Output ATEX fault enable output. Used only when an ATEX option module is installed.
(1) Digital Inputs are either 24 Volts DC (1132C) or 115 Volts AC (1132D) based on module catalog number. Ensure applied voltage is correct for I/O module.
(2) Differential - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(3) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).
(4) I/O Module parameters also have a Port designation.
44
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 20 - 0…20 mA Analog Input - Unipolar Speed Reference
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Common
+
Ai0–
Ai0+
Sh
Set Selection
: P50 [Anlg In0 Value]
11-Series I/O Module TB1
P4
1
2 2
1
P5
Adjust Scaling
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P51 [Anlg In0 Hi] = 20 mA
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P52 [Anlg In0 Lo] = 0 mA or 4 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Jumper set to current mode.
Table 21 - 0…+10V Analog Input - Unipolar Speed Reference
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Common
+
Ai0–
Ai0+
Sh
Set Selection
: P50 [Anlg In0 Value]
11-Series I/O Module TB1
P4
1
2 2
1
P5
Adjust Scaling
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P51 [Anlg In1 Hi] = 10 Volt
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P52 [Anlg In1 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Jumper set to voltage mode.
Table 22 - 10k Ohm Potentiometer - Unipolar Speed Reference
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
10VC
+10V
Set Selection
: P50 [Anlg In0 Value]
P4
1
2 2
1
P5
11-Series I/O Module TB1
Ai0–
Ai0+
Sh
Adjust Scaling
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P51 [Anlg In0 Hi] = 10 Volt
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P52 [Anlg In0 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Jumper set to voltage mode.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
45
Reference Section
Table 23 - 2-Wire Control on 11-Series I/O Module
Non-Reversing - Internal Supply
Stop-Run
Di0
Di0P
Set Direction Mode
Port 0: P308 [Direction Mode] = 2 “Rev Disable”
Set Selection
Port 0: P163 [DI Run] = Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P1 [Dig In Sts], bit 0 = Input 0
11-Series I/O Module TB1
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See
Port 0: P935 [Drive Status 1]
P3
3
1
3
P8
1
Jumpers set to internal supply source.
Reversing - External Supply
Run Fwd
Run Rev
Di0
Di0P
Di1
Di1P
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Set Selection
Port 0: P164 [DI Run Forward] = Port 4 (or port where your 11-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 0 = Input 0
: P1 [Dig In Sts], bit 1 = Input 1
+24V
Common
Ip
Ic
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See
Port 0: P935 [Drive Status 1]
11-Series I/O Module TB1
P3
3
1
3
P8
1
Jumpers set to external supply source.
46
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 24 - 3-Wire Control on 11-Series I/O Module
Start
Internal Supply
Stop
Di0
Di0P
Di1
Di1P
Set Selection
Port 0: P158 [DI Stop] = Port 4 (or port where your 11-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 0 = Input 0
Port 0: P161 [DI Start] = Port 4 (or port where your 11-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 1 = Input 1
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
11-Series I/O Module TB1
P3
3
1
3
P8
1
Jumpers set to internal supply source.
External Supply
+24V or +120V
Common
11-Series I/O Module TB1
Ip
Ic
Di0
Di0P
Di1
Di1P
Set Selection
Port 0: P158 [DI Stop] = Port 4 (or port where your 11-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 0 = Input 0
Port 0: P161 [DI Start] = Port 4 (or port where your 11-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 1 = Input 1
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See page 10
: P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
IMPORTANT:
Connect 24V supply only to 20-750-1132C-2R or 20-750-1133C-1R2T.
Connect 120V supply only to 20-750-1132D-2R.
P3
3
1
3
P8
1
Jumpers set to external supply source.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
47
Reference Section
Terminal block TB1 and the input mode jumpers are mounted on the option module installed in the drive.
Table 25 - Input Mode Jumpers
Jumper
Position
Voltage Mode Current Mode
Ai1
Ai0
Ai1
Ai0
Table 26 - TB1 Terminal Designations
Terminal Name Description
Terminating point for wire shields when an EMC plate or conduit box is not installed.
Related
Param
(4)
Di0
Di1
Di2
Di3
Di4
Di5
Ai0+
Ai1–
Ai1+
24VC
+24V
DiC
Ao1–
Ao1+
–10V
10VC
+10V
Ai0–
Sh
Sh
PTC–
PTC+
Ao0–
Ao0+
Ao1+
–10V
10VC
+10V
Ai0–
Ai0+
Ai1–
Ai1+
24VC
+24V
Sh
Sh
Ptc–
Ptc+
Ao0–
Ao0+
Ao1–
Shield
Di C
Di 0
Di 1
Di 2
Di 3
Di 4
Di 5
Motor PTC (–)
Motor PTC (+)
Analog Out 0 (–)
Motor protection device (Positive Temperature
Coefficient).
Analog Out 0 (+)
Analog Out 1 (–)
Bipolar, ±10V, 11 bit & sign, 2 k ohm minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum load.
Analog Out 1 (+)
–10 Volt Reference 2k ohm minimum.
10 Volt Common For (–) and (+) 10 Volt references.
+10 Volt Reference 2k ohm minimum.
Analog Input 0 (–)
Analog Input 0 (+)
Isolated
(2)
, bipolar, differential, 11 bit & sign.
Voltage Mode: ±10V @ 88k ohm input impedance.
Current Mode: 0-20 mA @ 93 ohm input impedance.
Analog Input 1 (–)
Analog Input 1 (+)
24 Volt Common
+24 Volt DC
Drive supplied logic input power.
200 mA max. per I/O module
600 mA max per drive
Digital Input Common Common for Digital Inputs 0…5
Digital Input 0
(1)
Digital Input 1
(1)
24V DC (30V DC Max.) - Opto isolated
High State: 20…24V DC 11.2 mA DC
Digital Input 2
(1)
Low State: 0…5V DC
120V AC (132V AC Max.) 50/60 Hz
(3)
- Opto isolated
Digital Input 3
(1)
Digital Input 4
(1)
High State: 100…132V AC
Low State: 0…30V AC
Digital Input 5
(1)
40 on Port X
75 on Port X
85 on Port X
50, 70 on Port X
60, 70 on Port X
1 on Port X
(1) Digital Inputs are either 24 Volts DC (2262C) or 115 Volts AC (2262D) based on module catalog number. Ensure applied voltage is correct for I/O module.
(2) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(3) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).
(4) I/O Module parameters also have a Port designation.
48
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 27 - 0…20 mA Analog Input - Unipolar Speed Reference at Terminals Ai0±
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Common
+
Ai0–
Ai0+
Set Selection
: P50 [Anlg In0 Value]
22-Series I/O Module TB1
Ai1
Ai0
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See
: P51 [Anlg In0 Hi] = 20 mA
Port 4 (or port where your 22-Series I/O Module is installed), See
: P52 [Anlg In0 Lo] = 0 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
Jumpers set to current mode.
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
: P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Table 28 - 0…+10V Analog Input - Unipolar Speed Reference at Terminals Ai0±
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Common
+
Ai0–
Ai0+
Set Selection
22-Series I/O Module TB1
Ai1
Ai0
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See
: P51 [Anlg In0 Hi] = 10 Volt
Port 4 (or port where your 22-Series I/O Module is installed), See
: P52 [Anlg In0 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
Jumpers set to voltage mode.
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
: P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Table 29 - 10k Ohm Potentiometer - Unipolar Speed Reference at Terminals Ai0±
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
10VC
+10V
Ai0–
Ai0+
Set Selection
: P50 [Anlg In0 Value]
22-Series I/O Module TB1
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P51 [Anlg In0 Hi] = 10 Volt
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P52 [Anlg In0 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
Ai1
Ai0
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Jumpers set to voltage mode.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
49
Reference Section
Table 30 - 0…20 mA Analog Input - Unipolar Speed Reference at Terminals Ai1±
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Common
+
Ai1–
Ai1+
Set Selection
: P60 [Anlg In1 Value]
22-Series I/O Module TB1
Ai1
Ai0
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P61 [Anlg In1 Hi] = 20 mA
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P62 [Anlg In1 Lo] = 0 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
Jumpers set to current mode.
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P60 [Anlg In1 Value]
Port 0: P592 [Selected Spd Ref]
Table 31 - 0…+10V Analog Input - Unipolar Speed Reference at Terminals Ai1±
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Common
+
Ai1–
Ai1+
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port 4, (or port where your 22-Series I/O Module is installed)See
page 10 : P60 [Anlg In1 Value]
22-Series I/O Module TB1
Ai1
Ai0
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P61 [Anlg In1 Hi] = 10 Volt
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P62 [Anlg In1 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
Jumpers set to voltage mode.
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P60 [Anlg In1 Value]
Port 0: P592 [Selected Spd Ref]
Table 32 - 10k Ohm Potentiometer - Unipolar Speed Reference at Terminals Ai1±
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
10VC
+10V
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P60 [Anlg In1 Value]
Ai1–
Ai1+
22-Series I/O Module TB1
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P61 [Anlg In1 Hi] = 10 Volt
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P62 [Anlg In1 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
Ai1
Ai0
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P60 [Anlg In1 Value]
Port 0: P592 [Selected Spd Ref]
Jumpers set to voltage mode.
50
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 33 - 2-Wire Control on 22-Series I/O Module
Non-Reversing - Internal Supply
Set Direction Mode
Port 0: P308 [Direction Mode] = 2 “Rev Disable”
Stop-Run
24VC
+24V
Di C
Di 0
Set Selection
22-Series I/O Module TB1
+24V
Reversing - External Supply
Common
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
: P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Stop Fwd
Stop Rev
Di C
Di 0
Di 1
Set Selection
Port 0: P164 [DI Run Forward] = Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 0 = Input 0
Port 0: P165 [DI Run Reverse] = Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 1 = Input 1
22-Series I/O Module TB1
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
: P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
IMPORTANT:
Connect 24V supply only to 20-750-2262C-2R or 20-750-2263C-1R2T.
Table 34 - 3-Wire Control on 22-Series I/O Module
Internal Supply
Set Selection
Port 0: P158 [DI Stop] = Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 0 = Input 0
Port 0: P161 [DI Start] = Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 1 = Input 1
Stop
Start
24VC
+24V
Di C
Di 0
Di 1
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
: P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
+24V
22-Series I/O Module TB1
External Supply
Common
Stop
Start
Di C
Di 0
Di 1
22-Series I/O Module TB1
Set Selection
Port 0: P158 [DI Stop] = Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 0 = Input 0
Port 0: P161 [DI Start] = Port 4 (or port where your 22-Series I/O Module is installed), See
page 10 : P1 [Dig In Sts], bit 1 = Input 1
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See
: P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
IMPORTANT:
Connect 24V supply only to 20-750-2262C-2R or 20-750-2263C-1R2T.
Connect 120V supply only to 20-750-2262D-2R.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
51
Reference Section
IMPORTANT
This section assumes that an EtherNet/IP network has been set up to connect to the drive.
1. Remove power from the drive.
2. Remove the drive cover and lift up the drive HIM bezel to its open position to access the drive control pod.
3. Use static control precautions.
4. Connect one end of an Ethernet cable to the network. See the following figure for an example of wiring to an
EtherNet/IP network.
Controller
(ControlLogix shown with
1756-ENBT Bridge)
PowerFlex 755 Drives
(each with embedded EtherNet/IP adapter)
Ethernet
Switch
ATTENTION:
Risk of injury or death exists. The drive may contain high voltages that can cause injury or death. Remove power from the drive. Verify power has been discharged before connecting the embedded EtherNet/IP adapter to the network.
5. Route the other end of the Ethernet cable through the bottom of the PowerFlex 755 drive, and insert the cable plug into the embedded EtherNet/IP adapter mating socket.
Embedded
EtherNet/IP
Port
52
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
There are three ways to set the IP address on a PowerFlex 755 embedded EtherNet adapter.
• BOOTP server
• Manually via the rotary switches
• Manually via adapter parameters
TIP
If the PowerFlex 755 drive is connected to a Stratix 6000 or Stratix 8000 managed Ethernet switch and the drive is set for BOOTP mode, the ‘dynamic IP address assignment by port’ (Stratix 6000) or ‘DHCP persistence’ (Stratix 8000) feature will automatically set the IP address for the drive. For more details, see the Stratix 6000 Ethernet Managed Switch User Manual, publication 1783-UM001 or the Stratix 8000 and Stratix 8300 Ethernet Managed Switches User Manual, publication 1783-UM003 .
By default, the drive is set up to receive its IP address via the BOOTP server.
1. Verify the rotary switches are set to the value of 999 or any value other than 001…254 and 888.
Hundreds
Position
Tens
Position
Ones
Position
2
3
4
1
5
0
9
6
7
8
2
3
4
1
5
0
9
6
7
8
2
3
4
1
5
0
9
6
7
8
2. Verify parameter 36 [BOOTP] on Port 13 is set to ‘1’ (Enabled).
3. Verify communication has been established (ENET status indicator is steady green).
If the status indicator is not steady green, refer to the PowerFlex 755 Drive Embedded EtherNet/IP Adapter User
Manual, publication 750COM-UM001 and/or your network administrator to validate connectivity.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
53
Reference Section
You can use the rotary switches to set the IP address if the following are met.
• The IP address follows the format 192.168.1.xxx
• The subnet mask is 255.255.255.0
• There is no gateway address
IMPORTANT
When using the adapter rotary switches, set the IP address before power is applied because the adapter uses the IP address it detects when it first receives power.
1. Verify that the drive is not powered.
2. Set the IP address to a valid address (001…254) by turning the rotary switches using a small screwdriver.
For example, if the IP address needs to be 192.168.1.123, turn the top switch so the arrow is pointing at 1, turn the middle switch so the arrow is pointing at 2, and turn the bottom switch so the arrow is pointing at 3.
See
for more information on the address settings.
2
3
4
1
5
0
9
6
7
8
2
3
4
1
5
0
9
6
7
8
2
3
4
1
5
0
9
6
7
8
Table 35 - IP Address Settings and Descriptions
Settings
001…254
888
Description
The adapter will use the rotary switch settings for the IP address (192.168.1.xxx, where xxx = rotary switch settings).
The value stored in
parameter 36 - [BOOTP]
is automatically ignored.
Resets the adapter IP address function to factory defaults. Thereafter, the drive must be powered down, the switches set to a correct value (001…254), and then the drive must be powered up again to accept the new address.
Disables the rotary switches and requires using
parameter 36 - [BOOTP]
to select the BOOTP server as the source for the IP address or, if disabled, selects the adapter parameters as the source.
Any other setting
3. Apply power to the drive.
4. Verify communication has been established.
If communication is not established, refer to the PowerFlex 755 Drive Embedded EtherNet/IP Adapter User
Manual, publication 750COM-UM001 and/or your network administrator to validate connectivity.
54
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
1. Verify that the IP address rotary switches are set to any value other than 001…254 or 888. The default setting is 999.
See
for more information on the address settings.
ATTENTION:
Risk of equipment damage, injury, or death exists. Unpredictable operation may occur if you fail to verify that parameter settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive.
2. Apply power to the drive.
3. Set the value of parameter 36 [BOOTP] to ‘0’ (Disabled).
Stopped
0.000 Hz
Edit BOOTP
Disabled
ESC
▲
0 << 1
▼
AUTO
F
0
ENTER
Value Setting
0 Disabled
1 Enabled (Default)
4. Set the value of parameters 38 [IP Addr Cfg 1] through 41 [IP Addr Cfg 4] to a unique IP address.
Default = 0.0.0.0
255.255.255.255
Stopped
0.000 Hz
Edit IP Addr Cfg 1
0
0 << 255
ESC
AUTO
F
ENTER
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
5. Set the value of parameters 42 [Subnet Cfg 1] through 45 [Subnet Cfg 4] to the desired value for the subnet mask.
Default = 0.0.0.0
255.255.255.255
Stopped
0.000 Hz
Edit Subnet Cfg 1
0
0 << 255
ESC
AUTO
F
ENTER
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
6. If required, set the value of parameters 46 [Gateway Cfg 1] through 49 [Gateway Cfg 4] to the desired value for the gateway device.
Default = 0.0.0.0
255.255.255.255
Stopped
0.000 Hz
Edit Gateway Cfg 1
0
0 << 255
ESC
AUTO
F
ENTER
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
7. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s
DIAGNOSTIC folder.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
55
Reference Section
Table 36 - PowerFlex 755 Embedded EtherNet/IP Port 13 Parameter Settings
No.
Drive
Parameter
Name
33
36
Port Number
BOOTP
User
Setting
13
0
Default
0
1
Value/Options
0 = Disabled
1 = Enabled
Notes
A reset of the adapter is required. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
38 IP Addr Cfg 1
39 IP Addr Cfg 2
40 IP Addr Cfg 3
41 IP Addr Cfg 4
192
168
1 xxx
0
Example IP Address.
Set to desired value.
42 Subnet Cfg 1
43 Subnet Cfg 2
44 Subnet Cfg 3
42 Subnet Cfg 4
255
255
255
0
Leave the remainder of the Embedded EtherNet/IP (Port 13) parameters at their default settings.
By default, the Start and Stop commands are enabled over the EtherNet/IP adapter. To set the speed reference via the
EtherNet/IP adapter, set parameter 545 [Spd Ref A Sel]. See
.
Table 37 - Speed Reference Parameter Setting
No.
Drive
Parameter
Name
545 Spd Ref A Sel
User
Setting
877
Default Value/Options
871 P871 = Port 1 HIM reference
Notes
P877 = Port 13 reference
Selects the source parameter number for the speed reference while in “Auto” (typical) mode. Reference value from port devices. For a speed reference from a communication network, set this parameter to Port 0 and select P871…877 [Port_
n
_Reference] as appropriate.
Important Example
: 20-COMM-E, EtherNet/IP Communication Adapter = Dint for speed reference multiplied by 1,000 (60 Hz = 60,000 and 1750 RPM = 1,750,000).
56
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
to complete the EtherNet/IP setup.
IMPORTANT
This section addresses the setup on the PowerFlex 20-750-ENETR Dual-port EtherNet/IP Option module that is installed in Port 6 of the drive.
ATTENTION:
Risk of injury or death exists. The drive may contain high voltages that can cause injury or death. Remove power from the drive. Verify power has been discharged before connecting the embedded EtherNet/IP adapter to the network.
1. Remove power from the drive.
2. Remove the drive cover and lift up the drive HIM bezel to its open position to access the drive control pod.
3. Use static control precautions.
4. Connect one end of an Ethernet cable to the network. See the following figure for an example of wiring to an
EtherNet/IP network.
Controller
(ControlLogix shown with
1756-ENBT Bridge)
PowerFlex 750-Series Drives
(each with EtherNet/IP adapter)
Ethernet
Switch
5. Route the other end of the Ethernet cable through the bottom of the PowerFlex 750-Series drive, and insert the cable plug into the EtherNet/IP adapter mating socket.
EtherNet/IP
Port
4
5
6
0
4 5 6
0
4 5 6
0
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
57
Reference Section
There are three ways to set the IP address on a PowerFlex 20-750-ENETR Dual-port EtherNet/IP option module.
• DHCP or BOOTP server
• Manually via the rotary switches
• Manually via adapter parameters
TIP
If the PowerFlex 750-Series drive is connected to a Stratix 6000 or Stratix 8000 managed Ethernet switch and the drive is set for
BOOTP mode, the ‘dynamic IP address assignment by port’ (Stratix 6000) or ‘DHCP persistence’ (Stratix 8000) feature will set the IP address for the drive. For more details, see the Stratix 6000 Ethernet Managed Switch User Manual, publication 1783-UM001 or the Stratix 8000 and Stratix 8300 Ethernet Managed Switches User Manual, publication 1783-UM003 .
IMPORTANT
When the DHCP lease expires, the option module stops communicating on the network, which requires a power cycle or option module reset.
By default, the drive is set up to receive its IP address via the BOOTP server.
1. Verify the rotary switches are set to the value of 999 or any value other than 001…254 and 888.
3
4
5
6
7
0
3
4
5
6
7
3
4
0
5
6
7
0
Hundreds
Position
Tens
Position
Ones
Position
3
4
5
6
7
1
9
0
3
4
5
6
7
1
9
0
3
4
5
6
7
1
9
0
2. Verify parameter 5 [Net Addr Sel] on Port 6 is set to either ‘2’ (BOOTP) or ‘3’ (DHCP).
Stopped
0.000 Hz
Edit Net Addr Sel
Parameters
ESC
▲
1 << 3
▼
AUTO
F
0
ENTER
2
3
Value Setting
1 Parameters
BOOTP
DHCP (Default)
3. Verify communication has been established (ENET status indicator is steady green).
If the status indicator is not steady green, refer to the PowerFlex 20-750-ENETR Dual-port EtherNet/IP Option
Module User Manual, publication 750COM-UM008 and/or your network administrator to validate connectivity.
58
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
You can use the rotary switches to set the IP address if the following are met.
• The IP address follows the format 192.168.1.xxx
• The subnet mask is 255.255.255.0
• There is no gateway address
IMPORTANT
When using the adapter rotary switches, set the IP address before power is applied because the adapter uses the IP address it detects when it first receives power.
1. Verify that the drive is not powered.
2. Set the IP address to a valid address (001…254) by turning the rotary switches using a small screwdriver.
For example, if the IP address needs to be 192.168.1.123, turn the top switch so the arrow is pointing at 1, turn the middle switch so the arrow is pointing at 2, and turn the bottom switch so the arrow is pointing at 3.
See Table 38 for more information on the address settings.
3
4
5 6
7
0
3
4
5 6
7
0
3
4
5 6
7
0
3
4
5
6
7
1
9
0
3
4
5
6
7
1
9
0
3
4
5
6
7
1
9
0
Table 38 - IP Address Settings and Descriptions
Settings
001…254
888
Description
The adapter will use the rotary switch settings for the IP address (192.168.1.xxx, where xxx = rotary switch settings).
The value stored in
parameter 36 - [BOOTP]
is automatically ignored.
Resets the adapter IP address function to factory defaults. Thereafter, the drive must be powered down, the switches set to a correct value (001…254), and then the drive must be powered up again to accept the new address.
Disables the rotary switches and requires using
parameter 36 - [BOOTP]
to select the BOOTP server as the source for the IP address or, if disabled, selects the adapter parameters as the source.
Any other setting
3. Apply power to the drive.
4. Verify communication has been established.
If communication is not established, refer to the PowerFlex 20-750-ENETR Dual-port EtherNet/IP Option
Module User Manual, publication 750COM-UM008 and/or your network administrator to validate connectivity.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
59
Reference Section
1. Verify that the IP address rotary switches are set to any value other than 001…254 or 888. The default setting is 999.
See
for more information on the address settings.
ATTENTION:
Risk of equipment damage, injury, or death exists. Unpredictable operation may occur if you fail to verify that parameter settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive.
2. Apply power to the drive.
3. Set the value of parameter 36 [BOOTP] to ‘0’ (Disabled).
Stopped
0.000 Hz
Edit BOOTP
Disabled
ESC
▲
0 << 1
▼
AUTO
F
0
ENTER
Value Setting
0 Disabled
1 Enabled (Default)
4. Set the value of parameter 5 [Net Addr Sel] to ‘1’ (Parameters).
Stopped
0.00 Hz
Edit Net Addr Sel
DHCP
ESC
▲
1 << 3
▼
AUTO
F
3
ENTER
Value Setting
1
2
3
Parameters
BOOTP
DHCP (default)
5. Set the value of parameters 7 [IP Addr Cfg 1] through 10 [IP Addr Cfg 4] to a unique IP address.
Default = 0.0.0.0
255.255.255.255
Stopped
0.000 Hz
Edit IP Addr Cfg 1
0
0 << 255
ESC
AUTO
F
ENTER
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
6. If required, set the value of parameters 11 [Subnet Cfg 1] through 14 [Subnet Cfg 4] to the desired value for the subnet mask.
Default = 0.0.0.0
255.255.255.255
Stopped
0.000 Hz
Edit Subnet Cfg 1
0
0 << 255
ESC
AUTO
F
ENTER
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
60
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
7. If required, set the value of parameters 15 [Gateway Cfg 1] through 18 [Gateway Cfg 4] to the desired value for the gateway device.
Default = 0.0.0.0
255.255.255.255
Stopped
0.000 Hz
Edit Gateway Cfg 1
0
0 << 255
ESC
AUTO
F
ENTER
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
8. Reset the option module. See
Reset the Option Module on page 62
.
Table 39 - PowerFlex 750-Series 20-750-ENETR Option Module Parameter Settings
2
5
No.
Drive
Parameter
Name
Port Number
Net Addr Sel
User
Setting
5
13
Default
0
3
Value/Options
4, 5, or 6
1 = Parameters
2 = BOOTP
3 = DHCP
Notes
Port Number
7
8
IP Addr Cfg 1
IP Addr Cfg 2
9 IP Addr Cfg 3
10 IP Addr Cfg 4
192
168
1 xxx
0
Example IP Address.
Set to desired value.
11 Subnet Cfg 1
12 Subnet Cfg 2
13 Subnet Cfg 3
14 Subnet Cfg 4
255
255
255
0
Leave the remainder of the Embedded EtherNet/IP (Port 13) parameters at their default settings.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
61
Reference Section
Changes to switch and jumper settings and some option module parameters require you to reset the option module before the new settings take effect. You can reset the option module by power cycling the drive or by using parameter 25 [Reset
Module].
ATTENTION:
Risk of injury or equipment damage exists. If the option module is transmitting control I/O to the drive, the drive can fault when you reset the option module. Determine how your drive responds before resetting the option module.
1. Set Device parameter 25 [Reset Module] (located on the communication card) to “1” (Reset Module).
Stopped
0.000 Hz
Edit Reset Module
Ready
ESC
▲
0 << 2
▼
AUTO
F
0
ENTER
1
2
Value Description
0 Ready (Default)
Reset Module
Set Defaults
When you enter “1” (Reset Module), the option module immediately resets. An alternate method to reset the module is by power cycling the drive.
By default, the Start and Stop commands are enabled over the PowerFlex 20-750-ENETR Dual-Port EtherNet/IP option module. To set the speed reference via the EtherNet/IP option module, set parameter 545 [Spd Ref A Sel]. See Table 40 .
Table 40 - Speed Reference Parameter Setting
No.
Drive
Parameter
Name
545 Spd Ref A Sel
User
Setting
876
Default Value/Options
871 P871 = Port 1 HIM reference
Notes
P876 = Port 6 reference
Selects the source parameter number for the speed reference while in “Auto” (typical) mode. Reference value from port devices. For a speed reference from a communication network, set this parameter to Port 0 and select P871…876 [Port_
n
_Reference] as appropriate.
Important Example
: 20-COMM-E, EtherNet/IP Communication Adapter = Dint for speed reference multiplied by 1,000 (60 Hz = 60,000 and 1750 RPM = 1,750,000).
62
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
The two types of ladder control circuits commonly used are the 2-wire control circuit and the 3-wire control circuit.
The 2-wire control circuit uses “maintained” contact devices to control the drive/motor. A typical 2-wire control circuit is shown in the following figure.
Stop/Start or Run
OL
M
M
VFD
Stop/Start
Motor
DI0 Run
24V Common
Dig In Common
+24V DC
Motor
A 2-wire control circuit consists of a normally open “maintained” contact device that, when closed, energizes the coil of a magnetic motor starter. This in turn energizes the connected motor load, or in the case of VFD, initiates a Run command to energize the motor load. The 2-wire control circuit provides what is known as “low-voltage release.” In the event of a power failure, the magnetic motor starter or VFD shuts down. When power is restored, the magnetic motor starter or VFD automatically reenergizes, provided that none of the maintained contact devices have changed state.
This can be quite advantageous in applications such as refrigeration, air conditioning, or remote pump stations where you do not need someone to restart the equipment after a power failure. It can, however, be extremely dangerous in applications where equipment automatically starts, placing the operator in danger.
The 3-wire control circuit uses “momentary” contact devices to control the driver/motor starter. A typical 3-wire control circuit is shown in the following figure.
Stop Stop Stop
Start
M
OL
Start
Start
M
Motor
M
Stop Stop Stop
Start
Start
Start
VFD
DI0 Run
DI1 Run
24V Common
Dig In Common
+24V DC
Motor
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
63
Reference Section
A 3-wire control circuit consists of a normally closed stop button (STOP), a normally open start button (START), and sealing contact (M), and the coil of a magnetic motor starter. When the normally open start button is pressed, the coil of the magnetic motor starter is energized. An auxiliary contact seals around the start button to provide a latched circuit. In the case of a VFD, the internal logic control of the VFD functions identical in principle to the sealing contact.
Pressing the normally closed stop button disrupts the circuit. The 3-wire control circuit provides what is known as “lowvoltage protection.” In the event of a power failure, the magnetic motor starter drops out. In this case, however, when power is restored the magnetic motor starter does not automatically reenergize. The operator must press the start button to initiate the sequence of operations.
The 3-wire control circuit figure illustrates a control circuit with multiple start and stop push buttons. In this circuit, multiple normally closed stop buttons are placed in series and multiple open start buttons are placed in parallel to operate a magnetic motor starter in VFD. This is a common application of a 3-wire control circuit in which you need to start and stop the same VFD/motor from multiple locations within a facility. The 3-wire control circuit can be used in a variety of ways to meet specific circuit application.
64
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 41 - PowerFlex 753 Status Indicator Descriptions
Name
STS
(Status)
Color
Green
Yellow
Red
Red /
Yellow
State
Flashing
Steady
Flashing
Steady
Flashing
Steady
Flashing
Alternately
Yellow /
Green
Green /
Red
Flashing
Alternately
Flashing
Alternately
Description
Drive ready but not running, and no faults are present.
Drive running, no faults are present.
Drive is not running, a start inhibit condition exists and the drive cannot be started.
See parameter 933 [Start Inhibits].
A type 1 (user configurable) alarm exists. If the drive is stopped, it is prevented from starting until the alarm condition is cleared. If the drive is running, it continues to run but cannot restart until the alarm condition is cleared.
See parameters 959 [Alarm Status A] and 960 [Alarm Status B].
A major fault has occurred. Drive stops. Drive cannot be started until fault condition is cleared. See parameter 951 [Last Fault Code].
A non-resettable fault has occurred.
A minor fault has occurred. When running, the drive continues to run. System is brought to a stop under system control. Fault must be cleared to continue. Use parameter 950 [Minor Flt Cfg] to enable. If not enabled, acts like a major fault.
When running, a type 1 alarm exists.
See parameters 959 [Alarm Status A] and 960 [Alarm Status B].
Drive is flash updating.
Table 42 - PowerFlex 755 Status Indicator Descriptions
Name
STS
(Status)
Color
Green
Yellow
ENET
LINK
Red
Red /
Yellow
State
Flashing
Steady
Flashing
Steady
Flashing
Steady
Flashing
Alternately
Description
Drive ready but not running, and no faults are present.
Drive running, no faults are present.
Drive is not running, a type 2 (non-configurable) alarm condition exists and the drive cannot be started. See parameter 961 [Type 2 Alarms].
A type 1 (user configurable) alarm exists. If the drive is stopped, it is prevented from starting until the alarm condition is cleared. If the drive is running, it continues to run but cannot restart until the alarm condition is cleared.
See parameters 959 [Alarm Status A] and 960 [Alarm Status B].
A major fault has occurred. Drive stops. Drive cannot be started until fault condition is cleared. See parameter 951 [Last Fault Code].
A non-resettable fault has occurred.
A minor fault has occurred. When running, the drive continues to run. System is brought to a stop under system control. Fault must be cleared to continue. Use parameter 950 [Minor Flt Cfg] to enable. If not enabled, acts like a major fault.
When running, a type 1 alarm exists.
See parameters 959 [Alarm Status A] and 960 [Alarm Status B].
Drive is flash updating.
Yellow /
Green
Green /
Red
Unlit
Flashing
Alternately
Flashing
Alternately
Off
Red
Red /
Green
Green
Unlit
Green
Flashing
Steady
Flashing
Alternately
Flashing
Steady
Off
Flashing
Steady
Embedded EtherNet/IP is not properly connected to the network or needs an IP address.
An EtherNet/IP connection has timed out.
Adapter failed the duplicate IP address detection test.
Adapter is performing a self-test.
Adapter is properly connected but is not communicating with any devices on the network.
Adapter is properly connected and communicating on the network.
Adapter is not powered or is not transmitting on the network.
Adapter is properly connected and transmitting data packets on the network.
Adapter is properly connected but is not transmitting on the network.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
65
Reference Section
Determine whether your drive and motor utilize a dynamic brake resistor.
Dynamic brake resistors generate heat so they are usually outside of the panel in a protective cage.
Record if a dynamic brake resistor is connected for each of your drive/motor combinations.
Drive/Motor 1
❑
Yes
❑
No
Drive/Motor 2
❑
Yes
❑
No
Drive/Motor 3
❑
Yes
❑
No
Drive/Motor 4
❑
Yes
❑
No
Typical resistor cage
Drive/Motor 5
❑
Yes
❑
No
Many fan, pump, and conveyor-like applications are allowed to coast to stop. If a controlled ramp to stop is required, the regenerative energy needs to be converted or dissipated and dynamic braking may be necessary. Adding a dynamic brake can help prevent over voltage to the drive VFD bus, fault conditions, or damage to the drive.
For purposes of this publication, a solution that allows the drive to feed the regenerated electrical power to a resistor, which then transforms it into thermal energy, is provided to prevent bus over voltage or potential damage. This process is referred to as dynamic braking (DB).
Internal dynamic braking chopper circuitry, including DB resistor power terminals BR1 and BR2, are standard on
PowerFlex 750-series drives frames 1…5 and are optional on frames 6 and 7. DB resistor connections BR1 and BR2 are not available on frames 8…10, however dynamic braking can be achieved via an independent chopper module that is connected to the DC+ and DC- terminals by using an appropriate-sized DB resistor connected to it. In the latter case, the properlysized external chopper module senses and regulates the DC bus voltage level independent of the drive control.
For more information on how to size a dynamic brake chopper and/or resistor, see PowerFlex Dynamic Braking Resistor
Calculator Application Technique, publication PFLEX-AT001 .
66
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
to configure these parameters so the dynamic brake properly functions.
Table 43 - Dynamic Brake Resistor Parameter Settings
No.
Parameter Name External Resistor
User Setting
370 Stop Mode A 1
372
382
383
384
385
Bus Reg Mode A
DB Resistor Type
DB Ext Ohms
DB Ext Watts
DB ExtPulse Watts
2
1
Resistor NP
Resistor NP
Resistor NP
(1)
Internal Resistor
User Setting
1
2
0
N/A
N/A
N/A
Values
Default:
Options:
Default:
Options:
Default:
Options:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Notes
1 = “Ramp”
0 = “Coast”
1 = “Ramp”
1 = “Adjust Freq”
1 = “Adjust Freq”
2 = “Dyn Brake”
3 = “Both DB 1st”
0 = “Internal”
0 = “Internal”
1 = “External”
Fans, pumps, and compressors are typically allowed to coast to stop - dynamic braking is not required.
Ramp to stop mode may cause regenerative energy - dynamic braking can be required.
The shorter the decel time, P537 [Decel Time], the greater potential need for dynamic braking.
Ohms
Based on Drive Rating
Minimum Resistor Rating
Observe minimum resistance rating by drive size.
Watt
100
1.00 to 500000.00
Watt Sec
2000
1.00 to 100000000.00
Not considered when P370 [Stop Mode A] = 0 “Coast”.
If dynamic brake resistor is installed, this parameter must be set to either 2 “Dyn Brake” or 3 “Both DB 1st”.
Not considered when P370 [Stop Mode A] = 0 “Coast”.
Sets the continuous rated power reference for the eternal dynamic brake resistor.
Refer to the PowerFlex Dynamic Braking Resistor Calculator
Application Technique, publication PFLEX-AT001 , for external resistor pulse watts settings. Or consult the resistor manufacturer for this specification.
(1) If this information is not available for the dynamic brake resistor, increase the value until nuisance DynBrake OvrTemp Alarm 10 ceases.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
67
Reference Section
Longer acceleration times can be an application consideration due to high inertia of the load and motor rotating mass. A typical application example that requires this consideration is a centrifugal fan load. Issues that can occur include overload conditions of the motor and/or drive or over current conditions of the drive. Results of these issues can be the drive exhibiting a fault condition in either motor or drive overload fault (F7 and F64 respectively) or can cause a hardware over current fault (F12). If these faults are present and in order to prevent these faults as part of startup, acceleration time must be set to the capabilities of the drive based on the load and application requirements. The normal solution will be to set parameter 535 [Accel Time 1] to longer time period so that an overload or over current condition of the drive does not occur.
An approach to perform this configuration is to set acceleration times to incremental 30 second acceleration times above the last setting and restart the drive until the load is able to start without a fault condition. The maximum acceleration time for most applications is up to 5 minutes, however very high inertia loads could require higher acceleration times (for example, 30 minutes may be common for a centrifuge). If faster acceleration time is required for the load, contact your
Allen-Bradley distributor or Allen-Bradley technical support for further application review or potential drive sizing considerations.
If the load has a large inertia value and acceleration time is not an application concern, set the current limit of the drive in amps to the continuous current rating of the drive in amps. The overload current setting is configured in parameter 422
[Current Limit 1]. This lets the drive apply its rated current to the motor on a continuous basis until the application reaches full speed. Default values for this parameter that are time limited equal 110% of the Normal Duty (ND) or 150% of the Heavy Duty (HD) rating of the drive that may have induced a hardware over current fault. To obtain the continuous current rating of the drive, see parameter 21 [Rated Amps].
If the drive faults on either an overload or an over voltage condition during deceleration, it is likely due to the deceleration time being too short for the system, which results in the fault condition. Either the drive can be set to coast to rest
(parameter 370 [Stop Mode A] is set to “0”) or parameter 537 [Decel Time 1] can be extended to a longer period of time to eliminate the fault condition. Set parameter 537 [Decel Time 1] to the longest necessary decel time allowed by the system.
If drive faults or over load conditions continue to exist, dynamic braking can be required. Refer to PowerFlex Dynamic
Braking Resistor Calculator, publication PFLEX-AT001 , in order to apply a dynamic brake to the application.
68
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Table 44 - Acceleration and Deceleration Parameter Settings
No.
Parameter Name User Setting
535 Accel Time 1
537 Decel Time 1
422 Current Limit 1
Values
Units:
Default:
Min/Max:
Secs
10
0.00 / 3600.00
Units:
Default:
Min/Max:
Secs
10
0.00 / 3600.00
Units:
Default:
Min/Max:
Amps
Based on drive rating and ND/HD selection
Based on drive rating
Notes
Sets the acceleration rate for all speed changes and is dependent on inertia and acceleration torque. Also, set parameter 422 [Current Limit 1] to drive rating.
For more information, see Acceleration Time on page 68
.
Sets the deceleration rate for all speed changes and is dependent on inertia and deceleration torque.
Decel rate can affect the extent of the dynamic braking needed.
Increase the decel rate to reduce regenerative energy demand or increase the dynamic brake capacity.
For more information, see Deceleration Time on page 68
or the
PowerFlex Dynamic Braking Resistor Calculator Application
Technique, publication PFLEX-AT001 .
Current setting above continuous current rating of the drive is time limited. Refer to the Recommendation in
Reference Section
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
69
Reference Section
Table 45 - 753 Main Control Board TB1 2-Wire Control with Reversing Wiring
2-Wire Control Reversing
Internal 24V Supply
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Run Fwd
Run Rev
Set Selection
Port 0: P164 [DI Run Forward] = Port 0: P220 [Digital In Sts], bit 1 = Digital In 1
Port 0: P165 [DI Run Reverse] = Port 0: P220 [Digital In Sts], bit 2 = Digital In 2
2-Wire Control Reversing
External 24V Supply
+24V
753 Main Control Board TB1
Common
Run Fwd
Run Rev
Di C
Di 1
Di 2
753 Main Control Board TB1
View Results
Port 0: P220 [Digital In Sts]
Port 0: P935 [Drive Status 1]
Table 46 - 750-Series I/O Module TB1 2-Wire Control with Reversing Wiring
2-Wire Control Reversing
External 24V Supply
20-750-2262C-2R
20-750-2263C-1R2T
+24V
Common
Run Fwd
Run Rev
Di C
Di 0
Di 1
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Configuration
Port 0: P150 [Digital In Cfg], = 1 “Run Level”
750-Series I/O Module TB1
Set Selection
Port 0: P164 [DI Run Forward] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts], bit 0 = Input 0
Port 0: P165 [DI Run Reverse] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts], bit 1 = Input 1
View Results
Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
70
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Table 47 - 753 Main Control Board TB1 & TB3 3-Wire Control with Reversing Wiring
3-Wire Control Reversing
Internal Supply
Set Selection
Port 0: P158 [DI Stop] = Port 0: P220 [Digital In Sts], bit 1 = Digital In 0
Port 0: P161 [DI Start] = Port 0: P220 [Digital In Sts], bit 2 = Digital In 1
Port 0: P162 [DI Fwd Reverse] = Port 0: P220 [Digital In Sts], bit 3 = Digital In 2
Stop
Start
View Results
Port 0: P220 [Digital In Sts]
Port 0: P935 [Drive Status 1]
Rev Fwd
TB1
3-Wire Control Reversing
External 24V Supply
TB3
753 Main Control Board TB1 & TB3
Common
Stop
Start
TB1
Rev Fwd
TB3
753 Main Control Board TB1 & TB3
Reference Section
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
71
Reference Section
Table 48 - 750-11 Series I/O Module TB1 3-Wire Control with Reversing Wiring
3-Wire Control Reversing
Internal Supply
Fwd Rev
Start
Stop
Set Selection
Port 0: P158 [DI Stop] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts], bit 0 = Input 0
Port 0: P161 [DI Start] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts], bit 1 = Input 1
Port 0: P162 [DI Fwd Reverse] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts], bit 2 = Input 2
View Results
Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
3-Wire Control Reversing
External 24V Supply
20-750-1132C-2R
20-720-1133C-1R2T
750-11 Series I/O Module TB1
Fwd Rev
Start
Stop
+24V
Common
3-Wire Control Reversing
External 120V Supply
20-750-1132D-2R
750-11 Series I/O Module TB1
Fwd Rev
Start
Stop
+24V
Common
72
750-11 Series I/O Module TB1
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 49 - 750-22 Series I/O Module TB1 3-Wire Control with Reversing Wiring
3-Wire Control Reversing
Internal Supply
Stop
Start
Set Selection
Port 0: P158 [DI Stop] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts], bit 0 = Input 0
Port 0: P161 [DI Start] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts], bit 1 = Input 1
Port 0: P162 [DI Fwd Reverse] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts], bit 2 = Input 2
Rev Fwd
View Results
Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
3-Wire Control Reversing
External 24V Supply
20-750-2262C-2R
20-720-2263C-1R2T
750-22 Series I/O Module TB1
+24V Common
Stop
Start
Rev Fwd
3-Wire Control Reversing
External 120V Supply
20-750-2262D-2R
750-22 Series I/O Module TB1
+120V Common
Stop
Start
Rev Fwd
750-22 Series I/O Module TB1
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
73
Reference Section
Table 50 - 753 Main Control Board TB1 Analog Output Wiring
Analog Voltage Output
±10V, 0…20 mA Bipolar
+10V Unipolar
+ –
Ao0–
Ao0+
753 Main Control Board TB1
Configuration
Port 0: P270 [Anlg Out Type], bit 0 = 0
Set Selection
Port 0: P275 [Anlg Out0 Sel] = Port 0: P3 [Mtr Vel Fdbk]
Adjusting Scale
Port 0: P278 [Anlg Out0 DataHi] = 60 Hz
Port 0: P279 [Anlg Out0 DataLo] = 0 Hz
Port 0: P280 [Anlg Out0 Hi] = 10V/20 mA
Port 0: P281 [Anlg Out0 Lo] = 0V/0 mA
View Results
Port 0: P277 [Anlg Out0 Data]
Port 0: P282 [Anlg Out0 Val]
Table 51 - 750-Series I/O Module TB1 Analog Output Wiring
Analog Voltage Output
±10V, 0…20 mA Bipolar
+10V Unipolar
+ –
Ao0–
Ao0+
750-Series I/O Module TB1
Configuration
Port 4 (or port where your I/O module is installed): P70 [Anlg Out Type], bit 0 = 0
Set Selection
Port 4 (or port where your I/O module is installed): P75 [Anlg Out0 Sel] = Port 0: P3 [Mtr Vel Fdbk]
Adjusting Scale
Port 4 (or port where your I/O module is installed): P78 [Anlg Out0 DataHi] = 60 Hz
Port 4 (or port where your I/O module is installed): P79 [Anlg Out0 DataLo] = 0 Hz
Port 4 (or port where your I/O module is installed): P80 [Anlg Out0 Hi] = 10V/20 mA
Port 4 (or port where your I/O module is installed): P81 [Anlg Out0 Lo] = 0V/0 mA
View Results
Port 4 (or port where your I/O module is installed): P77 [Anlg Out0 Data]
Port 4 (or port where your I/O module is installed): P82 [Anlg Out0 Val]
74
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 52 - 753 Main Control Board Digital Output Wiring
Digital Output
Internal Supply
T0
+24V
753 Main Control Board TB1
Digital Output
External Supply
OR
+24V
PLC
1756-1B16
Common
IN-0
GND-0
OR
PLC
1756-1V16
5 kΩ
2 W
+24VDC
Common
T0
24VC
T0
24VC
DC-0+
IN-0
+24VDC
Common
753 Main Control Board TB1
T0
24VC
Set Selection
Port 0: P240 [TO0 Sel] = Port 0: P935 [Drive Status 1], bit 7= Faulted
View Results
Port 0: P225 [Dig Out Sts]
When TO is On, IN-O is Off.
Table 53 - 750-Series I/O Module TB1 Digital Output Wiring
Digital Output
Internal Supply
20-750-2263C-1R2T
24VC
+24V
Set Selection
Port 4 (or port where your I/O module is installed): P20 [TO0 Sel] = Port 0: P935 [Drive Status 1], bit 7= Faulted
View Results
Port 4 (or port where your I/O module is installed): P5 [Dig Out Sts]
T0
TC
T1
750-Series I/O Module TB1
750-Series I/O Module TB2
Digital Output
External Supply
20-750-2263C-1R2T
OR
PLC
1756-1B16
+24V
Common
IN-0
GND-0
OR
PLC
1756-1V16
+24VDC
Common
DC-0+
IN-0
+24VDC
Common
750-Series I/O Module TB2
T0
TC
T1
T0
TC
T1
T0
TC
T1
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
75
Reference Section
Table 54 - 750-Series Control Board and I/O Module TB1 Relay Output Wiring
Relay Output
External Supply
Set Selection
Port 0: P230 [RO0 Sel] = Port 0: P935 [Drive Status 1], bit 7 = Faulted
Power
Source
753 Main Control Board
R0NC
R0C
R0NO
View Results
Port 0: P225 [Dig Out Sts]
Set Selection
Port 4 (or port where your I/O module is installed): P10 [RO0 Sel] = Port 0: P935 [Drive Status 1], bit 7= Faulted
R1NO
R1C
R1NC
or
Power
Source
750-Series I/O Module
R0NO
R0C
R0NC
View Results
Port 4 (or port where your I/O module is installed): P5 [Dig Out Sts]
76
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
There are times when disabling the HIM is necessary, such as when the user requires only to use other discrete input or communications that are controlled by Start/Run, Jog, and Direction commands.
Parameter 324 [Logic Mask] is used to disable or “mask” out the HIM performing any Start, Jog, and Direction Logic function by setting bit 01 on Port 1 equal to “0”.
IMPORTANT
Setting parameter 324 [Logic Mask] to “0” to disable the Start, Jog, and Direction commands DOES NOT mask the Stop commands.
The Stop function cannot be disabled.
1. Starting from either screen, press the
PAR#
soft key.
00
ESC
Stopped
0.000 Hz
PowerFlex 753
480V 4.2A
20F...B4P2
REF PAR#
AUTO
F
TEXT
OR
00
ESC
Stopped
0.000 Hz
0.00 Amps
0.000 Bus VDC
0.00 Out
VIEW REF PAR#
AUTO
F
EDIT
Status Screen
2. Press the EDIT soft key.
3. Use the soft key or the
Stopped
0.000 Hz
Port 00 Dev Param
Logic Mask x1xx xx1x x111 1111
Bit 00 - Digital In
ESC
324
AUTO
F
PAR# EDIT
Status Screen
on the keypad to highlight bit 01.
P
Stopped
0.000 Hz
Edit Logic Mask x1xx xx1x x111 1111
Bit 00 - Digital In
1
ESC
AUTO
F
ENTER
P
Stopped
0.000 Hz
Edit Logic Mask x1xx xx1x x111 1111
Bit 01 - Port 1
1
ESC
AUTO
F
ENTER
Logic Mask Screen
Edit Logic Mask Screen
4. Press the or
5. Press the ENTER soft key.
6. Press the ESC soft key.
on the keypad to change bit 01 to “0”.
P
Stopped
0.000 Hz
Edit Logic Mask x1xx xx1x x111 1111
Bit 01 - Port 1
0
ESC
AUTO
F
ENTER
Stopped
0.000 Hz
Port 00 Dev Param
Logic Mask x1xx xx1x x111 1101
Bit 01 - Digital In
324
AUTO
F
ESC PAR# EDIT
Edit Logic Mask Screen
00
ESC
Stopped
0.000 Hz
PowerFlex 753
480V 4.2A
20F...B4P2
REF PAR#
AUTO
F
TEXT
Edit Logic Mask Screen
Logic Mask Screen Status Screen
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
77
Reference Section
PowerFlex 750-Series drives and PowerFlex 7-Class drives provide a CopyCat function that enables you to upload individual parameter sets for the host drive or any of its connected peripherals into the HIM. Furthermore, an Upload All
Ports function enables you to conveniently upload multiple parameter sets for the host drive and all of its connected peripherals in one single file. In either case, this information can then be used as backup or can be transferred to another drive or peripheral device by downloading the file from the HIM’s memory.
TIP
TIP
The Upload All Ports and Download All Ports functions are only available for the host drive (Port 00) due to their unique functionality.
Before beginning the Download All Ports function, verify that your option cards are located in the same ports as the drive you are copying the parameters from. Also, verify the port you are working on before beginning the CopyCat from Device to HIM function.
The CopyCat function also enables you to rename or delete individual or multiple parameter sets stored in the HIM.
The HIM can store up to 50 individual parameter sets or up to 5 multiple parameter sets. Due to the memory capacity of the HIM, these maximums will vary when storing combinations of individual and multiple parameter sets.
Generally, the upload or download transfer process manages all conflicts. However, the download will stop and a text message will appear if any of the following conditions exist:
• A device mismatch, such as firmware revision, device type, or device series is detected.
• The drive is password protected.
• The drive is running.
You then have the option to completely stop the download or continue after noting the discrepancy for the parameters that could not be downloaded. These parameters can then be manually adjusted.
IMPORTANT
When using the HIM with a PowerFlex 753 drive with firmware revision 1.05 or earlier, or a PowerFlex 755 drive with firmware revision 1.10 or earlier, the CopyCat function cannot upload/download DeviceLogix values for DLX Out xx and DLX In xx parameters and DeviceLogix program routines. Drives with a later firmware revision support this function, but the HIM does not support screen formatting for the DeviceLogix program.
1. Access the Status screen.
00
ESC
Stopped
0.000 Hz
Host Drive
240V 4.2A
20G...D014
REF PAR#
AUTO
F
TEXT
78
2. Use the or key to scroll to the Port of the device whose parameter set you want to copy (for example,
Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
4. Use the
5. Use the
6. Press the
or
or
key to scroll to the MEMORY folder.
key to select HIM CopyCat.
(Enter) key to display the CopyCat Files selection screen.
Stopped
0.000 Hz
Port 00
CopyCat from Device to HIM
CopyCat from HIM to Device
Delete CopyCat File
Rename CopyCat File
ESC
AUTO
F
CopyCat Files
TIP
Before any CopyCat files are created, only the ‘CopyCat From Device to HIM’ menu item is shown. When Port 00 for the Host Drive is selected in Step 2, the ‘Upload All Ports’ menu item also appears.
7. Use the or key to select the appropriate action and press the (Enter) key to initiate that action.
8. With New File selected on the Select Upload File screen, press the (Enter) key to create the file. A pop-up box will appear to confirm that the CopyCat file was successfully created. Press the ENTER soft key to complete the procedure.
TIP
When a CopyCat file is created, its default file name corresponds to the device whose file is being copied. For example, a newly created CopyCat file for a PowerFlex 755 drive has a default file name of ‘PowerFlex 755’.
When selecting an item row that is an existing CopyCat file—not a ‘New File’ row—to create a new CopyCat file, an
Overwrite pop-up box will appear. Press the
ENTER
soft key to affirm and overwrite the existing CopyCat file—or press the ESC soft key to cancel.
IMPORTANT
Text editing is not supported when using Asian language characters. Only characters in the ISO 8859-1 Latin 1 Character Set, which is supported by U.S. and European personal computers, are available. If a software tool is used for text editing Asian characters, the
HIM will replace all unsupported characters with a [] (narrow rectangle) mark.
1. Access the Status screen.
00
ESC
Stopped
0.000 Hz
Host Drive
240V 4.2A
20G...D014
REF PAR#
AUTO
F
TEXT
2. Use the or key to scroll to the Port of the device whose CopyCat file you want to rename (for example,
Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
79
Reference Section
4. Use the
5. Use the
6. Press the
or
or
key to scroll to the MEMORY folder.
key to select HIM CopyCat.
(Enter) key to display the CopyCat Files selection screen.
Stopped
0.000 Hz
Port 00
AUTO
F
CopyCat Files
CopyCat from Device to HIM
CopyCat from HIM to Device
Delete CopyCat File
Rename CopyCat File
ESC
7. Use the
8. Press the
9. Use the
10. Press the
or
or
key to select Rename CopyCat File.
(Enter) key to display the Select File To Rename pop-up box.
key to select the file to be renamed.
(Enter) key to display the Edit CopyCat File Text pop-up box.
Stopped
0.00 Hz
AUTO
F
Edit CopyCat File Text
P owerFlex 755
, =Move Cursor =Char Set
ESC INS DEL CLR ENTER
11. Use the or key to move the cursor to the desired character position in the displayed name.
12. Press the key to access the last-viewed character set.
13. Press the appropriate numeric key to access the desired character set.
Numeric Key Function
Selects the numeric character set.
Selects the symbols character set.
Selects the upper case letter character set.
Selects the lower case letter character set.
Also, use the appropriate soft keys to help create the new name.
Soft Key
DEL
INS
CLR
Function
Deletes a highlighted character.
Inserts a space to the left of a highlighted character.
Deletes an entire text string.
14. With the desired character selected in that character position, press the
15. Repeat steps 11 through 14 for each character position.
key to select and enter the character.
80
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
16. When the desired name is displayed on the edit pop-up box, press the ENTER soft key to enter and save the new name.
1. Access the Status screen.
00
ESC
Stopped
0.000 Hz
Host Drive
240V 4.2A
20G...D014
REF PAR#
AUTO
F
TEXT
2. Use the or key to scroll to the Port of the device whose parameter set you want to delete (for example,
Port 00 for the host drive).
3. Press the
4. Use the
key to display its last-viewed folder.
or key to scroll to the MEMORY folder.
5. Use the
6. Press the
or key to select HIM CopyCat.
(Enter) key to display the CopyCat Files selection screen.
Stopped
0.000 Hz
Port 00
CopyCat from Device to HIM
CopyCat from HIM to Device
Delete CopyCat File
Rename CopyCat File
ESC
AUTO
F
CopyCat Files
7. Use the
8. Press the
or key to select Delete CopyCat File.
(Enter) key to display the Select File To Delete pop-up box.
Stopped
0.000 Hz
Select File To Delete
PowerFlex 755 Cfg
Delete All Files
AUTO
F
ESC
9. Use the or key to select the file (or all files) to delete.
10. Press the (Enter) key to display the confirmation pop-up box.
11. Press the ENTER soft key to affirm and delete the selected CopyCat file, or press the ESC soft key to cancel.
Another pop-up box will appear to confirm that the CopyCat file was successfully deleted.
12. Press the
ENTER
soft key to affirm and complete the procedure.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
81
Reference Section
It can be necessary to adjust parameter 414 [Mtr OL Hertz]. Adjusting this parameter to a default of 20 Hz is a conservative setting to protect a typical induction motor that is not designed to adequately cool itself at full load when its rotor/internal fan is turning less than 20 Hz. Understand the speed range specifications of your motor in order to set parameter 414
[Mtr OL Hertz] to the approximate minimum operating speed under full load.
Motor and drive applications operate on a wide variety of operating speed ranges. Typical speed ratios for constant and variable torque motors in applications are expressed in terms of Motor Base Speed to Motor Minimum Speed.
Table 55 - Typical Speed Ratios for Constant and Variable Torque Motors
438
175
88
17.5
1.8
Example Motor Base Speed = 1750 RPM / 60 Hz
Minimum Speed
RPM
875
Hz
30
% Motor Base Speed Speed Range Ratio
50 2:1
15
6
3
0.6
0.06
25
10
5
1
0.1
4:1
10:1
20:1
100:1
1000:1
82
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
If your drive application is for a fan or a pump and you are having difficulty tuning the motor to the drive, review the recommendation Knowledgebase article “486982 - PowerFlex 753 or 755 Drive: Centrifugal Fan/Pump Setup Guide”.
Prior to contacting technical support resource, collect the following information and be ready to provide it to the support representative.
Drive Catalog Number
Nameplate 1 : Specifications and Custom Catalog Number representing options installed at factory.
See Nameplate 2 (Located behind HIM) for equivalent base catalog number and separate options
Series: A Cat No. 20G11 N G 011 AA0NNNNN
UL Open Type/IP20 - without Debris Hood and Conduit Plate
UL Type 1 - only with Debris Hood and Conduit Plate
400V Class 480V Class
If Nameplate 1 is not visible, record the values of the following parameters.
P20 [Rated Volts] P21 [Rated Amps]
1…3
20F
(753)
20G
(755)
4 5 6
P22 [Rated kW]
7 8…10 11 12 13
Access the Device Version screen on the HIM and record the necessary information.
1. Access the Status screen.
00
ESC
Stopped
0.000 Hz
PowerFlex 753
480V 4.2A
20F...B4P2
REF PAR#
AUTO
F
TEXT
2. Use the or key to scroll to the Port of the device whose firmware version you want to view (for example,
Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
83
Reference Section
5. Use the or
00
ESC
Stopped
0.000 Hz
DIAGNOSTIC
Alarms
Diagnostic Items
Reset Device
Device Version
AUTO
F
key to select Device Version.
6. Press the (Enter) key to display device version information.
Stopped
0.000 Hz
AUTO
F
PowerFlex 753
Product Rev 9.001
Product Ser Num 00000000
–Main Control Board
FW Revision 9.001
ESC TOP END PGUP PGDN
7. Record the information.
Product Series Product Revision Product Serial Number Main Control Board Firmware Revision
Power Jumper Configuration
Jumper PE-A - MOV / Input Filter Caps
❑
Connected
❑
Disconnected
Jumper PE-B - DC Bus Common Mode Caps
❑
Connected
❑
Disconnected
84
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Advertisement
High performance
Rugged construction
Easy to use
Versatile
Energy efficiency
Network connectivity
Safety features
The PowerFlex 755 is used in a variety of applications, including industrial automation, robotics, and material handling.
The key features of the PowerFlex 755 include high performance, rugged construction, ease of use, versatility, energy efficiency, network connectivity, and safety features.
Yes, the PowerFlex 755 is easy to use with its intuitive programming and built-in diagnostic tools.
Yes, the PowerFlex 755 is energy efficient with its built-in energy-saving features.
Yes, the PowerFlex 755 can be connected to a variety of networks with its built-in Ethernet port.
Yes, the PowerFlex 755 offers a variety of safety features, such as safe torque off (STO) and safe stop 1 (SS1).
What are the parameters for static tuning?
The parameter for static tuning on the device is "Static Tune 2."
How do I access the parameter for static tuning?
To access this parameter, press the "F" key, select "Static Tune 2," and then press the "Start" key to initiate the tuning process.
What is the parameter for static tuning and how is the tuning process initiated?
The parameter for static tuning on the device is "Static Tune 2." To access this parameter, you need to press the "F" key, select "Static Tune 2," and then press the "Start" key to initiate the tuning process.
Login to continue