Frame 2 Installation. Allen-Bradley PowerFlex 700L
Advertisement
Advertisement
Aotewell Ltd www.aotewell.com Industry Automation
Chapter
2
Frame 2 Installation
Topic
Verifying the Drive’s Watts Loss Rating
Removing the Active Converter Control Cassette
Removing the Inverter Control Cassette
Determining Wire Routing for Control, Ground, Drive Input, and Motor Output
Ungrounded or Resistive Grounded Installations
DPI Connections for Frame 2 Drives
Because most start-up difficulties are the result of incorrect wiring, take every precaution to verify that the wiring is completed as instructed. Read and understand all items before starting actual installation.
Page
!
ATTENTION:
The following information is merely a guide for proper installation. Rockwell Automation does not assume responsibility or liability for the compliance or noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
Mounting Considerations Total Area Required for Drive Installation
Overall drive dimensions are shown in Figure 2.1
as an aid in calculating the total area required for installing Frame 2 drives.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
HongKong|UK|China [email protected]
www.aotewell.com Industry Automation Aotewell Ltd
2-2
Frame 2 Installation
Figure 2.1 Frame 2 Drive Installation Dimensions
389.6
(15.34)
351.0
(13.82)
Dimensions are in millimeters and (inches).
See
DETAIL
A
566.1
(22.29)
Ground Terminal with 2 Clearance
Holes for M8 Stud
66.6
(2.62)
423.8
(16.68)
730.2
(28.75)
591.2
(23.28)
153.8
(6.06)
BACK VIEW
See
DETAIL
B
4x Ø
8.5 (0.33)
4x Ø
15.0 (0.59)
DETAIL A
16.0 (0.63)
4x
Approximate Weight
186 kg (410 lb)
Motor
Output
Terminals
W/T3
V/T2
U/T1
955.7
(37.63)
3x Clearance
Hole for
M8 Stud
46.9
(1.85)
Coolant Inlet
37 Deg Flare -12
Coolant Outlet
37 Deg Flare -12
3x Clearance
Hole for
M8 Stud
SIDE VIEW
R/L1 S/L2 T/L3
AC Input Terminals
Stirring
Fan
Housing
FRONT VIEW
8.6 (0.34)
4x
DETAIL B
14.9 (0.59)
4x
Recommended Mounting Clearances
Specified vertical clearance requirements (
from drive to drive. Other objects can occupy this space; however, reduced air flow may cause protection circuits to fault the drive. In addition, inlet air temperature must not exceed the product specification.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com
Figure 2.2 Frame 2 Drive Minimum Mounting Clearances
Industry Automation
Frame 2 Installation
2-3
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
Equipment Lifting
Verifying Drive Input Ratings Match Supplied Power
It is important to verify that plant power meets the input power requirements
of the PowerFlex 700L Frame 2 drive circuitry. See Appendix A
for input power rating specifications. Be sure input power to the drive corresponds to the drive nameplate voltage and frequency.
This section explains how to lift the drive.
!
ATTENTION:
To guard against possible personal injury and/or equipment damage, observe the following:
• Do not allow any part of the drive or lifting mechanism to make contact with electrically charged conductors or components.
• At no time should a person or their limbs be directly underneath the items being lifted.
•
Do not subject the load to high rates of acceleration or deceleration.
• Inspect all lifting hardware for proper attachment before lifting any drive unit.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
HongKong|UK|China
Aotewell Ltd
2-4
Frame 2 Installation
www.aotewell.com Industry Automation
Attaching the Lifting Feet to the Drive
1.
Remove the four shipping bolts that hold the drive to the skid.
2.
Attach the two lifting feet provided with the drive to the bottom drive
mounting holes as shown in Figure 2.3
.
Figure 2.3 Attaching Lifting Feet to the Drive
Attaching the Lifting Hardware to the Drive
Apply lifting hooks (see Figure 2.4
). Take precautions to verify that there
are lifting hooks secured in all four locations ( Figure 2.5
) on the drive.
Figure 2.4 Attaching Lifting Hardware to the Frame 2 Drive
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Frame 2 Installation
2-5
Connecting Lifting Hooks to Proper Locations
Locate all four lifting features on the drive (see
locations must be used to maintain the drive center of gravity when lifting.
Figure 2.5 Lifting Locations on the Frame 2 Drive
HongKong|UK|China
Applying Strap Angles
TIP:
To ensure that this angle is greater than 60°, make the length of chain or cable between the center and the corners (B) longer than the distance between the opposite corners (A).
B > A
Min. 60°
A
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Aotewell Ltd
2-6
Frame 2 Installation
www.aotewell.com Industry Automation
Rotating the Drive About the Board
shows the drive, with the lifting feet attached, on a skid. To avoid
damage to the drive input terminals when lifting the drive to a vertical position, do the following.
1.
After the straps are in place (see
Applying Strap Angles on page 2-5 ),
carefully lift the drive to rotate it 90° to a vertical position.
2.
Remove the lifting feet before installing the drive into the enclosure.
Figure 2.6 Frame 2 Drive on Skid
Input Terminals
Lifting Feet
Mounting Requirements
Skid
The PowerFlex700L Frame 2 drive is a single integrated assembly consisting of a filter section and a power section. The filter section provides the mounting feet and represents greater than 50% of the approximate 186 kg (410 lb) total weight. Follow these mounting requirement guidelines.
1.
Mount the Frame 2 drive into an enclosure that is designed according to
Electrical Equipment Pollution Degree 2 requirements.
2.
Size and fasten any enclosure mounting panel appropriately to accommodate for the weight of the drive.
3.
The Frame 2 drive is designed to use eight M8 x 1.25 fasteners in mounting slots shown in Detail A and Detail B of
.
4.
The M8 x 1.25 fasteners must be class 5.8 or greater.
5.
Use a lock washer or similar mechanism to prevent the fasteners from loosening after mounting.
6.
All M8 x 1.25 fastener threads must engage a steel panel with 6 to 7 full threads or a permanent backing nut such as a weld nut or a self-clinching PEM
® (1)
nut with 4 full threads.
7.
Tighten the M8 x 1.25 fasteners to 11.3 ± 2.8 N
• m (100 ± 25 lb
• in) unless the lock washer mechanism requires a different torque. If this is
(1) the case, the holding force must be equivalent.
PEM is a registered trademark of PennEngineering.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Frame 2 Installation
2-7
Verifying the Drive’s Watts
Loss Rating
When mounting the drive inside of an enclosure, determine the watts loss rating of the drive from
Table A.E on page A-6 . This table lists the typical
full load power loss watts value at 4 kHz (rated carrier frequency). Make sure that the enclosure is adequately ventilated with 0…50 °C (32…122 °F) ambient air based on the drive’s watts loss rating.
Removing the Drive Cover
(5 Captive Screws)
Removing the Active
Converter Control Cassette
The Frame 2 regenerative-type drive is equipped with an Active Converter control cassette.
shows the location and removal of this cassette
to access its terminal blocks for control wiring. See the PowerFlex 700
Active Converter Power Module User Manual, publication PFLEX-UM002, for control wiring details.
Figure 2.7 Removing the Frame 2 Active Converter Control Cassette
Detail
Synchronization Cable
(For use with 700S Phase II Control only)
40-Pin
Ribbon Cable
Pin 1
Internal DPI Cable
P1
Synchronization Cable
(For use with 700 Vector Control only)
P2
Communications
Adapter Option
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
HongKong|UK|China
Aotewell Ltd
2-8
Frame 2 Installation
Removing the Inverter
Control Cassette
www.aotewell.com Industry Automation
For Frame 2 drives, the Inverter is equipped with either the standard
PowerFlex 700 Vector Control cassette or an optional PowerFlex 700S
Phase II Control cassette. In either case, the cassette is removed in the same way.
PowerFlex 700 Vector Control Cassette (standard)
shows the location and removal of the drive’s standard
PowerFlex 700 Vector Control cassette to access its terminal blocks for control wiring. See the PowerFlex 700 Adjustable Frequency AC Drive
User Manual - Series B, publication 20B-UM002, for control wiring details.
Figure 2.8 Removing the Standard PowerFlex 700 Vector Control Cassette
Pin 1
Detail
Communications
Adapter Option
PowerFlex 700S Phase II Control Cassette (optional)
Figure 2.9
shows the location and removal of the drive’s optional PowerFlex
700S Phase II Control cassette to access its terminal blocks for control wiring. See the PowerFlex 700S High Performance AC Drive - Phase II
Control User Manual, publication 20D-UM006, for control wiring details.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Frame 2 Installation
2-9
Figure 2.9 Removing the Optional PowerFlex 700S Phase II Control Cassette
Detail
TB2 Terminals
TB1 Terminals
Communications
Adapter Option
Determining Wire Routing for Control, Ground, Drive
Input, and Motor Output
All wiring should be installed in conformance with the applicable local, national, and international codes (for example, NEC/CEC). Signal wiring, control wiring, and power wiring must be routed in separate conduits to prevent interference with drive operation. When hubs are not provided, use grommets to guard against wire chafing.
!
ATTENTION:
Do not route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe this precaution can result in damage to, or destruction of, the equipment.
Do not route more than three sets of motor leads through a single conduit.
This minimizes cross-talk that can reduce the effectiveness of noise reduction methods. If more than three drive/motor connections per conduit are required, shielded cable must be used. If possible, each conduit should contain only one set of motor leads.
!
ATTENTION:
Unused wires in conduit must be grounded at both ends to avoid a possible shock hazard caused by induced voltages. Also, if a drive sharing a conduit is being serviced or installed, disable all drives using this conduit to eliminate the possible shock hazard from cross-coupled motor leads. Failure to observe these precautions can result in bodily injury.
shows locations for Frame 2 control wire routing, ground, drive input, motor output, DPI communication ports/cable routing, and coolant connections.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
HongKong|UK|China
Aotewell Ltd
2-10
Frame 2 Installation
www.aotewell.com Industry Automation
Figure 2.10 Frame 2 Drive Locations for Control Wire Routing, DPI Communication
Port, and Coolant Connections
28.0
(1.10)
Dimensions are in millimeters and (inches).
DPI Communications
Port
Control Wire
Conduit Plug
62.7 (2.47) Dia.
Coolant Inlet
223.2
(8.79)
280.5
(11.04)
222.0
(8.74)
152.0
(5.98)
112.0
(4.41)
72.0
(2.83)
Coolant Outlet
Bottom View of Drive
R/L1
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
257.1
(10.12)
S/L2
199.9
(7.87)
T/L3
12.6
(0.50)
Control Wire
Conduit Plug
22.2 (0.87) Dia.
Bottom Drive Cover
245.8
(9.68)
290.4
(11.43)
481.8
(18.97)
+86-755-8660-6182
Aotewell Ltd
Grounding the Drive
www.aotewell.com Industry Automation
Frame 2 Installation
2-11
!
ATTENTION:
The user is responsible for conforming with all applicable local, national, and international codes. Failure to observe this precaution can result in damage to, or destruction of, the equipment.
The customer must supply a grounding conductor between the ground lug of the drive and the ground lug in the cabinet. For PE ground terminal location, see Figure 2.15
. Tighten the ground connection to the recommended torque shown in
Ungrounded or Resistive
Grounded Installations
PowerFlex 700L Frame 2 drives are equipped with a common mode input filter capacitor and MOV that are referenced to ground. If the drive is installed on a resistive ground or ungrounded distribution system, disconnect this capacitor and MOV to prevent drive damage.
Disconnecting the Common Mode Capacitor
To disconnect the 1 µF common mode capacitor from the circuit, see
and perform the following steps.
1.
Disconnect the Faston wire from the 1 µF common mode capacitor.
2.
Insulate the wire end by applying a wire nut or electrical tape.
3.
Tie wrap the disconnected wire to keep it away from any electrical connections.
Disconnecting the MOV from Ground
To disconnect the MOV from ground, see
and perform the following steps.
1.
Unbolt the ground wire lug from the MOV’s ground connection point.
2.
Screw the bolt back into the panel.
3.
Cut the lug off the disconnected ground wire and apply a wire nut to its end.
4.
Tie wrap the disconnected ground wire to keep it away from any electrical connections.
For more information on ungrounded distribution systems, see Wiring and
Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001.
Note:
Removing the Common Mode capacitor and input MOVs makes the drive more vulnerable to high voltage line spikes.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
HongKong|UK|China
Aotewell Ltd
2-12
Frame 2 Installation
www.aotewell.com
Figure 2.11 Removing Common Mode Capacitor and MOV
Common Mode
Capacitor Removal
Industry Automation
MOV Removal
Side View of Drive
Power Wiring
This section describes incoming line components and how to install them, and provides instructions on wiring input power, output contactors, motor overload protection, and output wiring to the motor.
Installing Transformers and Reactors (Not Recommended)
Frame 2 drives may be used on distribution systems with 200,000 amps or less symmetrical fault current capacity. The drive input components consist of a 3% line reactor and a harmonic line filter. Additional input inductance is not recommended.
Selecting and Verifying Control Transformer Voltage
A control transformer is used to match the input line voltage of the drive to the 115V control voltage. If your line voltage is different than the voltage class specified on the drive nameplate, it may be necessary to change transformer taps as described in the following steps.
1.
Unfasten seven screws and remove the bottom drive cover
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
(
+86-755-8660-6182
Aotewell Ltd www.aotewell.com
Figure 2.12 Removing the Bottom Drive Cover
Industry Automation
Frame 2 Installation
2-13
2.
Remove the power section stirring fan.
a.
Unfasten two bracket screws.
b.
Disconnect the fan power leads (two fastons).
c.
Lift the fan from the drive (
Figure 2.13 Removing the Power Section Stirring Fan
HongKong|UK|China
3.
Depending on the supplied AC line voltage used to power the drive, see
Table 2.A
to determine which transformer tap to use.
Table 2.A Control Transformer Tap Usage
AC Line Voltage Transformer Tap To Use
380V AC
400V AC
440V AC
400V
460V AC
480V AC
480V
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Aotewell Ltd
2-14
Frame 2 Installation
www.aotewell.com Industry Automation
4.
Pull the faston from the present tap and push it onto the appropriate tap.
Verify that the faston is fully seated on the tap.
TIP:
Do not bend the faston. A straight blade screwdriver helps to remove the faston by carefully prying on the bottom edge of the faston.
Figure 2.14 Control Transformer Voltage Taps
690V 600V
480V 400V
5.
Reinstall the power section stirring fan.
6.
Before fastening the two bracket screws, connect power to the fan power leads.
7.
Reinstall the bottom drive cover by fastening the six screws.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Frame 2 Installation
2-15
Installing Input Power Wiring to the Drive
Use the following steps to connect AC input power to the drive.
!
ATTENTION:
Do not route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe this precaution can result in damage to, or destruction of, the equipment.
1.
Connect the three-phase AC input power leads (three-wire 380-480V
AC) to the R/L1, S/L2, and T/L3 input power terminals on the Frame 2 drive.
For terminal locations, see Figure 2.15
.
2.
Tighten the AC input power terminal connections to the recommended
Table 2.B Frame 2 Drive Power Terminal Specifications
Item Name
➊
Input Power Bus Bar
R/L1, S/L2, T/L3
(2)
Description
Input power
Recommended
Tightening
Torque (+10%)
40 N
• m
(354 lb
• in)
Terminal
Bolt Size
(1)
M8
➋
Output Power Bus Bar
U/T1, V/T2, W/T3
(2)
Motor connections 40 N
• m
(354 lb
• in)
➌
PE, Motor Ground Bus Bar
(2)
Terminating point for wiring shields and grounds
40 N
• m
(354 lb
• in)
M8
M8
➍
DC Bus Test Point Socket
(2 Terminals; DC+, DC-)
(3)
4 mm socket for DC bus voltage measurement only
— —
(1)
(2)
These connections are bus bar type terminations and require the use of lug connectors.
(3)
Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt to avoid damage to the terminal.
Use only to verify that DC bus capacitors are discharged before servicing the Power Module. No other external use is permitted.
HongKong|UK|China [email protected]
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Aotewell Ltd
2-16
Frame 2 Installation
www.aotewell.com
Figure 2.15 Frame 2 Drive Power Terminal Locations
➌
DC+
Testpoint
➍
DC-
Testpoint
W/T3
➋
V/T2
U/T1
A A
Section A-A
Industry Automation
R/L1 S/L2
➊
T/L3
Installing Mechanical Motor Overload Protection (Optional)
To provide the motor with overload protection, local, national, and international codes (for example, NEC/CEC) may require one of the following items:
•
A motor thermostat be installed internal to the motor.
•
A mechanical thermal motor overload relay, sized to protect the motor, be installed between the motor and the drive’s output terminals.
In multiple motor applications (only V/Hz regulation), each motor must have its own user-supplied overload and branch circuit protection.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Frame 2 Installation
2-17
Installing Output Wiring from the Drive Output Terminals to the Motor
Important:
See the PowerFlex 700L Technical Data, publication
20L-TD001, for motor lead length restrictions.
Follow these steps to connect the AC output power wiring from the drive to the motor.
1.
Route the three-phase AC output power motor leads to the drive power module.
Do not route more than three sets of motor leads through a single conduit. This minimizes cross-talk that can reduce the effectiveness of noise reduction methods. If more than three drive/motor connections per conduit are required, shielded cable must be used. If possible, each conduit should contain only one set of motor leads.
!
!
ATTENTION:
Do not route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe these precautions can result in damage to, or destruction of, the equipment
ATTENTION:
Unused wires in conduit must be grounded at both ends to avoid a possible shock hazard caused by induced voltages. Also, if a drive sharing a conduit is being serviced or installed, disable all drives using this conduit to eliminate the possible shock hazard from cross-coupled motor leads. Failure to observe these precautions can result in bodily injury.
2.
Connect the three-phase AC power motor leads to the U/T1, V/T2, and
W/T3 output power terminals.
For terminal locations, see Figure 2.15
.
3.
Tighten the AC output power terminal connections to the proper torque
HongKong|UK|China [email protected]
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
www.aotewell.com Industry Automation Aotewell Ltd
2-18
Frame 2 Installation
This section provides details on control wiring to the drive.
Control Wiring
!
!
ATTENTION:
Risk of equipment damage exists. Do not use drive terminal blocks TB5-1 and TB5-3 to connect any type of power wiring for auxiliary equipment. These terminals are only for low amperage control wiring.
ATTENTION:
Do not route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe this precaution can result in damage to, or destruction of, the equipment.
Connect wiring to terminals in accordance with Table 2.C
, Figure 2.16
, and
the Frame 2 drive schematic on page B-2
.
Item Name
➊
Active Converter Cassette
Terminal Blocks—P1 and P2
➋
SHLD Terminal
➌
Terminal Block—TB1
1b 5: +12/+24V Cooling Loop
1b 6: Cooling Loop Return
1b 7: +24V (digin)
1b 8: Gate Enable
Table 2.C Frame 2 Drive Control Wiring Terminal Specifications
Wire Size Range
(1)
Description
Maximum Minimum
Active Converter AC power and control wiring 3.3 mm
2
(#12 AWG)
0.3 mm
2
(#22 AWG)
Recommended
Tightening
Torque (+10%)
0.8 N
• m
(7 lb
• in)
Wire Strip
Length
8 mm
(0.31 in.)
Terminating point for control wiring shields on the drive
2.1 mm
2
(#14 AWG)
0.3 mm
2
(#22 AWG)
Drive control wiring:
Output dry contact (12V DC/24V DC, 2
Amps max.) indicating the drive is powered and has completed precharge.
Drive-supplied +24V DC
Enables the firing of the IGBTs.
Factory-installed jumper from terminal 1b
7 to terminal 1b 8 allows firing of the
IGBTs.
4.0 mm
2
(#10 AWG)
0.2 mm
2
(#24 AWG)
1.4 N
• m
(12 lb
• in)
0.9 N
• m
(8 lb
• in)
10 mm
(0.39 in.)
8 mm
(0.31 in.)
4.0 mm
2
(#12 AWG)
0.5 mm
2
(#22 AWG)
0.6 N
• m
(5.3 lb
• in)
➍
PS- Terminal
PS+ Terminal
300V DC Auxiliary Control voltage
(1)
Maximum/minimum sizes that the terminals will accept - these are not recommendations.
10 mm
(0.39 in.)
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Frame 2 Installation
2-19
Figure 2.16 Frame 2 Drive Control Wiring Terminal Locations
➊
1
P1
P2
15
7
1
S HLD
S HLD
➋
TB4 (NOTE: On drives without TB4, there are additional terminals on TB1.)
➌ ➍
TB1
HongKong|UK|China
TB1
➌
➍
C us tomer Connection S ide
TB1 When TB4 i s Pre s ent
PE2 PE1
PE1 PE2
C us tomer Connection S ide
TB1 When TB4 i s Not Pre s ent [email protected]
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
www.aotewell.com Industry Automation Aotewell Ltd
2-20
Frame 2 Installation
Synchronization
Connections
Coupled Power Modules
Frame 2 combined Converter/Inverter Power Modules are configured only as coupled power modules. Coupling the Converter and Inverter is achieved by using two factory-installed cables: a control synchronization cable and an inverter-to-converter DPI communication cable. The two cables are described in the next two subsections.
TB2 Header on
700 Vector
Control Cassette
Control Synchronization Cable
To enable synchronization between the Inverter control board and the
Converter control board, a factory-installed control synchronization cable connects each board. No user connection is required. However, the connection method is different for PowerFlex 700L drives with 700 Vector
Control than for 700S Phase II Control. The 700 Vector Control
synchronization cable connection is shown in Figure 2.17
. The 700S Phase
II Control synchronization cable connection is shown in Figure 2.18
.
Figure 2.17 Frame 2 700 Vector Control Synchronization Cable Connection
TB2-2
TB2-1
P1 Terminal Block on Active Converter
Control Cassette
1
15
P1-7
P1-8
Control Synchronization
Cable (Factory-Installed)
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Frame 2 Installation
2-21
Figure 2.18 Frame 2 700S Phase II Control Synchronization Cable Connection
P6 Header on
700S Phase II
Control Cassette
J9 Header on
Active Converter
Control Cassette
Control Synchronization
Cable (Factory-Installed)
Inverter-to-Converter DPI Communication Cable
To enable the Inverter and Converter section of the Frame 2 drive to communicate with each other, a factory-installed DPI communication cable is used. No user connection is required.
HongKong|UK|China [email protected]
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
www.aotewell.com Industry Automation Aotewell Ltd
2-22
Frame 2 Installation
DPI Connections for Frame
2 Drives
Drive Connection Points
The PowerFlex 700L Frame 2 drive provides a number of cable connection points as shown in
. If an additional external HIM is required for the application, the HIM can be connected to the DPI port on the bottom of the drive. Only one additional external HIM device may be connected. The use of two external HIM devices is not supported. If multiple external HIM devices are required, then install a user-supplied splitter cable or splitter box.
Figure 2.19 Frame 2 Drive DPI Connection Points
Extern a l
HIM Option
➋
➌
➎
Active
Converter
PCB
Drive
HIM Option
➊
Comm u nic a tion s
Ad a pter Option
➍
Extern a l
DPI C ab le
Bottom View of Drive
R/L1 S /L2 T/L 3
Item Connector
➊
DPI Port 1
Description
HIM connection when installed in the drive.
➋
DPI Port 2 Cable connection for handheld and remote options.
➌
DPI Port 3 or 2 Splitter cable connection to DPI Port 2 provides additional port.
➍
DPI Port 5
➎
DPI Port 6
Cable connection for communications adapter.
Internal DPI connection to Active Converter pcb.
External Door-Mounted HIM Connection (optional)
For a Frame 2 drive installed in a user-supplied enclosure, an optional external door-mounted HIM may be connected as an alternative to the external HIM option. The cable supplied with the door-mount HIM option
kit connects to the DPI port on the bottom of the drive (see Figure 2.19
additional installation information, see the instructions provided with the door-mount HIM option kit.
Coolant Loop Connections
See Chapter 4 , Cooling Loop Installation
for details.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182

Public link updated
The public link to your chat has been updated.
Advertisement