Chapter
6
Troubleshooting
Faults and Alarms
Drive Status
This chapter provides information to guide you in troubleshooting the
PowerFlex 700L Liquid-Cooled AC drive. Included is a listing and description of faults (with possible solutions, when applicable) and alarms.
Topic
700 Vector Control Fault Descriptions
700S Phase II Control Fault Descriptions
Alarm Descriptions (only 700S Phase II Control)
Replacement of Door Filter of the Input Filter Cabinet (Frames 3A and 3B)
Page
A fault is a condition that stops the drive. There are two fault types.
Type Fault Description
➀
Reserved for future.
➁
Non-Resettable
➂
User Configurable
This type of fault normally requires drive or motor repair. The cause of the fault must be corrected before the fault can be cleared. The fault will be reset on power up after repair.
These faults can be enabled/disabled to annunciate or ignore a fault condition.
An alarm is a condition that, if left untreated, may stop the drive. There are two alarm types.
Type Fault Description
➀
User Configurable
➁
Non-Configurable
These alarms can be enabled/disabled through [Alarm Config 1].
These alarms are always enabled.
The condition or state of your drive is constantly monitored. Any changes will be indicated through the LEDs and/or the HIM (if present).
Frame 2 Drive LED Indicators
Status indicators for Frame 2 drives are located near the top and front of the
). For drive status indications, see Table 6.A
.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
HongKong|UK|China
Aotewell Ltd
6-2
Troubleshooting
www.aotewell.com Industry Automation
Accessing Status Indicators of Powered Frame 3A and 3B Complete
Drives
Status indicators (shown in Table 6.A
) for Frame 3A and 3B complete
drives are inside the power module bay. To access the status indicators, follow the instructions below.
!
ATTENTION:
Risk of injury or death exists. Only qualified electricians should use this procedure. Bypassing the interlock mechanism exposes the user to dangerous high voltage live components. Failure to comply can result in personal injury and/ or death.
To Open:
1.
Unlock the input filter bay door and the power module bay door by using the key provided with the drive.
2.
Turn the circuit breaker handle door locking mechanism release with a
flat head screwdriver ( Figure 6.1
) to unlatch the input filter bay door.
Figure 6.1 Releasing Door Locking Mechanism
Circuit Breaker Handle
Door Locking Mechanism
Release
3.
Swing open the input filter bay several inches until the door interlock mechanism unlatches from the power module bay door.
4.
Swing open the power module bay door to view the status indicators on the power module(s).
To Close:
1.
Close and lock the power module bay door.
2.
Close and lock the input filter bay door.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Troubleshooting
6-3
Table 6.A Status Indications
Item Name Color State
➊
POWER Green Steady
➋
STS
(Status)
Green Flashing
Steady
Yellow Flashing,
Drive Stopped
Flashing,
Drive Running
Red
Steady,
Drive Running
Flashing
Steady
➌
PORT
MOD
NET A
NET B
See the 20-COMM-x
Communication Adapter
User Manual.
Description
Illuminates when power is applied to the drive.
Drive ready, but not running and no faults are present.
Drive running, no faults are present.
A type 2 alarm condition exists, the drive cannot be started. Check parameter 211 [Drive Alarm 2].
An intermittent type 1 alarm condition is occurring.
Check parameter 211 [Drive Alarm 1].
A continuous type 1 alarm condition exists.
Check parameter 211 [Drive Alarm 1].
Fault has occurred. Check [Fault x Code] or Fault Queue.
A non-resettable fault has occurred.
Status of DPI port internal communications (if present).
Status of communications module (when installed).
Status of network (if connected).
Status of secondary network (if connected).
HIM Indication
The LCD HIM also provides visual notification of a fault or alarm condition.
Condition
Drive is indicating a fault.
The LCD HIM immediately reports the fault condition by displaying the following information:
•
“Faulted” appears in the status line
•
Fault number
•
Fault name
•
Time that has passed since fault occurred
Press Esc to regain HIM control.
Drive is indicating an alarm.
The LCD HIM immediately reports the alarm condition by displaying the following information:
•
Alarm name (Type 2 alarms only)
•
Alarm bell graphic
Display
F-> Faulted
0.0
Hz
OverVoltage
Auto
5
F-> Power Loss Auto
0.0
Hz
Main Menu:
Diagnostics
Parameter
Device Select
HongKong|UK|China [email protected]
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Aotewell Ltd
6-4
Troubleshooting
www.aotewell.com Industry Automation
Manually Clearing Faults
To manually clear faults, follow these steps.
1.
Press the
Esc
(Escape) key to acknowledge the fault.
The fault information is removed so that you can use the HIM.
2.
Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.
3.
After corrective action has been taken, clear the fault by using
one
of these methods:
•
Press the
(
Stop) key.
•
Cycle drive power.
•
Set parameter 239 - [Fault Clear] to “1” (Clear Faults).
•
“Clear Faults” on the HIM Diagnostic menu.
Converter Faults
When a fault is generated in the Converter, that fault is passed to the Inverter so all the faults are recorded in the Inverter fault queue. Faults in the converter are numbered 1 to 99.
When using PowerFlex 700 Vector Control, the fault from the Converter is added to a base number of 300, so all the Converter faults are numbered 301 to 399. The pop-up window on the HIM alerts the user to look at the fault log in the PF700AC to get the specific fault text.
- Fault - F 3 40
F 3 40 S ee PF700AC
Time S ince Fault
00000:00:01
When using PowerFlex 700S Phase II Control, the faults from the Converter are all combined into one fault code (F110) in the Inverter. The pop-up window on the HIM alerts the user to look at the fault log in the PF700AC to get the specific fault text.
- Fault - F 110
700L Cnv Faulted
Time S ince Fault
00000:00:01
For a complete listing of Converter faults, descriptions, and actions, see the
PowerFlex 700L Active Converter User Manual, publication
PFLEX-UM002.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Troubleshooting
6-5
700 Vector Control Fault
Descriptions
Table 6.B 700 Vector Control Fault Types, Descriptions, and Actions
Fault
Port 6 Adapter
Port 6 DPI Loss
700L Dsat U
700L Dsat V
700L Dsat W
700L OvrCurnt
700L OvrVolt
700L Asym Vdc
700L PwrSply
No.
Type
(1)
F76
Description Action
Communication adapter on DPI port 6 reported a fault.
Check communication cable and check adapter fault queue for information about the fault.
F86 DPI Communications to port 6 was lost.
If adapter was not intentionally disconnected, check wiring.
Replace wiring, port expander, or Main Control Board as needed. Check HIM connection.
Phase U Dsat fault on 700L power structure.
Contact Technical Support.
F170
F171
F172
F173
F174
F175
Phase V Dsat fault on 700L power structure.
Phase W Dsat fault on 700L power structure.
Over current on 700L power structure.
Over voltage on 700L power structure.
Contact Technical Support.
Contact Technical Support.
Check programming. Check for cause of excessive current.
Check programming. Check for cause of excessive voltage.
F176
700L HW Disable F177
700L Latch Err
700L Fan Loss
700L Dsat U
700L Dsat V
F178
F179
F180
F181
Asymmetrical voltage on the 700L power structure dc link.
Verify load balance resistors.
Power supply failed on 700L power structure.
Replace power supply if problem persists.
Hardware disable asserted on 700L power structure.
Verify drive enable is present.
Fault reporting failure on 700L power structure. Contact Technical Support.
Fan failure on 700L power structure.
Phase U Dsat fault on secondary 700L power structure.
Verify internal circulating fans are turning.
Contact Technical Support.
Phase V Dsat fault on secondary 700L power structure.
Phase W Dsat fault on secondary 700L power structure.
Contact Technical Support.
Contact Technical Support.
700L Dsat W F182
700L OvrCurnt F183
700L OvrVolt F184
700L Asym Vdc F185
700L PwrSply
700L HW Disable F187
F188
F186
700L Latch Err
700L Fan Loss
Cnvtr Not Login
Cnvtr Not Start
700L NTC Open
F189
F190
F191
F192
Over current on secondary 700L power structure.
Over voltage on secondary 700L power structure.
Asymmetrical voltage on secondary 700L power structure dc link.
Power supply failed on secondary 700L power structure.
Check programming. Check for cause of excessive current.
Check programming. Check for cause of excessive voltage.
Verify load balance resistors.
Replace power supply if problem persists.
Hardware disable asserted on secondary 700L power structure.
Verify drive enable is present.
Fault reporting failure on secondary 700L power structure.
Contact Technical Support.
Fan failure on secondary 700L power structure. Verify internal circulating fans are turning.
Active converter did not begin communication.
Check DPI connection. Check for proper versions.
Active converter did not start when requested.
Check start inhibits. Check parameter 214 - [Start Inhibit].
Thermal sensor failed on 700L power structure. Contact Technical Support.
(1)
for a description of fault types.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
HongKong|UK|China
www.aotewell.com Aotewell Ltd
6-6
Troubleshooting
700S Phase II Control Fault
Descriptions
Table 6.C 700S Phase II Control Fault Types, Descriptions, and Actions
Fault No.
700L Dsat Phs U1 F097
Type
(1)
Description
Phase U Dsat fault on 700L power structure.
Action
Contact Technical Support.
700L Dsat Phs V1 F098
700L Dsat Phs W1 F099
Phase V Dsat fault on 700L power structure.
Phase W Dsat fault on 700L power structure.
Contact Technical Support.
Contact Technical Support.
700L Ovr Current1 F100
700L Ovr Volt1 F101
700L AsymDcLink1 F102
700L Pwr Suply1 F103
700L HW Disable1 F104
Over current on 700L power structure.
Over voltage on 700L power structure.
Check programming. Check for cause of excessive current.
Check programming. Check for cause of excessive voltage.
Asymmetrical voltage on the 700L power structure dc link.
Verify load balance resistors.
Power supply failed on 700L power structure.
Replace power supply if problem persists.
700L Latch Err1 F105
Hardware disable asserted on 700L power structure.
Verify drive enable is present.
Fault reporting failure on 700L power structure. Contact Technical Support.
700L Fan Fail1 F106
700L Cnv Faulted F110
Cnv NotLogin
Cnv NotStart F112
700L Dsat Phs U2 F113
700L Dsat Phs V2 F114
700L Dsat Phs W2 F115
F111
700L Ovr Current2
700L Ovr Volt2
700L AsymDcLink2
F116
F117
F118
700L Pwr Suply2 F119
700L HW Disable2 F120
700L Latch Err2
700L Fan Fail2
F121
F122
Fan failure on 700L power structure.
Active converter has faulted.
Verify internal circulating fans are turning.
Check active converter fault log.
Active converter did not begin communication.
Check DPI connection. Check for proper versions.
Active converter did not start when requested.
Check start inhibits. Check parameter 214 - [Start Inhibits].
Contact Technical Support.
Phase U Dsat fault on secondary 700L power structure.
Phase V Dsat fault on secondary 700L power structure.
Contact Technical Support.
Phase W Dsat fault on secondary 700L power structure.
Over current on secondary 700L power structure.
Contact Technical Support.
Check programming. Check for cause of excessive current.
Over voltage on secondary 700L power structure.
Asymmetrical voltage on secondary 700L power structure dc link.
Check programming. Check for cause of excessive voltage.
Verify load balance resistors.
Power supply failed on secondary 700L power structure.
Replace power supply if problem persists.
Hardware disable asserted on secondary 700L power structure.
Verify drive enable is present.
Fault reporting failure on secondary 700L power structure.
Contact Technical Support.
Fan failure on secondary 700L power structure. Verify internal circulating fans are turning.
(1)
for a description of fault types.
Industry Automation
Clearing Alarms
Alarms are automatically cleared when the condition that caused the alarm is no longer present.
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
+86-755-8660-6182
Aotewell Ltd www.aotewell.com Industry Automation
Troubleshooting
6-7
Alarm Descriptions (only
700S Phase II Control)
The following alarm can occur when the PowerFlex 700L Liquid-Cooled
AC drive is equipped with the optional 700S Phase II Control cassette.
Table 6.D 700S Phase II Control Alarm Descriptions
Alarm No.
Type
(1)
700L Cnv Alarm A109
➁
Description
Indicates an alarm in the Active Converter control has occurred. See the Active Converter User Manual for alarm descriptions.
(1)
See
page 6-1 for a description of alarm types.
Replacement of Door Filter of the Input Filter Cabinet
(Frames 3A and 3B)
!
!
ATTENTION:
Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, start-up, and subsequent maintenance of the system. Failure to comply can result in personal injury and/ or equipment damage.
ATTENTION:
To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged completely before servicing. After removing power to the drive, wait 5 minutes for the bus capacitors to discharge. Measure the DC bus voltage at the
DC+ and DC- TESTPOINT sockets on the front of the power
). The voltage must be zero.
When the door filter of the Input Filter Cabinet requires replacement, remove the dirty filter and replace it with an equivalent clean filter.
Important:
If the CE Shield Barrier has been removed for servicing, it must be reinstalled to restore the casual touch protection this barrier provides.
Figure 6.2 Input Filter Cabinet Door Filter Replacement
CE Shield Barrier
Filter
Filter
Input Filter Cabinet
(Door Closed)
Input Filter Cabinet
(Door Open) [email protected]
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
HongKong|UK|China
Aotewell Ltd
6-8
Troubleshooting