Insulation . Trane CVHE-SVX02M-EN, CVHG, CVHF, CVHE

Insulation . Trane CVHE-SVX02M-EN, CVHG, CVHF, CVHE
Add to My manuals

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Insulation . Trane CVHE-SVX02M-EN, CVHG, CVHF, CVHE | Manualzz

Insulation

Unit Insulation Requirements

Factory-installed insulation is available as an option for all units. Factory installation does NOT include insulation of the chiller feet; if required, insulation for chiller feet is provided by others. In applications where the chiller is not factory-insulated, install insulation over the areas outlined and highlighted with dashed lines as shown in

Figure 28, p. 45 .

Insulate all 1/4-in. (6.35-mm) eductor lines, one from the suction cover and one from the evaporator, to prevent sweating.

The quantities of insulation required based on unit size and insulation thickness are listed in the following table. Insulation thickness is determined at normal design conditions which are:

• Standard comfort-cooling leaving chilled water temperature

• 85°F (29.4°C) dry bulb ambient temperature

• 75 percent relative humidity

Operation outside of normal design conditions as defined in this section may require additional insulation; contact Trane for further review.

insulation around the evaporator bulbwells and ensure that the bulbwells and connections for the waterbox drains and vents are still accessible after insulation is applied. The sensor modules

(Low Level Intelligent Devices [LLIDs]) and interconnecting four-wire cable inter-processor communication (IPC) bus must be raised up above the field-installed insulation. Secure the

IPC bus to the insulation top/outer surface after insulation is completed.

wiring, or sensor modules.

ov e tth e sse orr..

Table 13.

Evaporator insulation requirements

EVSZ (a)

Standard Unit

3/4 in. (19.05 mm) (a)

Insulation(Square

Feet)

3/8 in. (9.525 mm)

Insulation (b)

Feet)

(Square

337 52

Free Cooling

3/4-in. (19.05 mm)

Insulation (a)

(Square Feet)

3/8 in. (9.525 mm)

Insulation (b)

Feet)

(Square

347 74 032 Short

032 Long

050 Short

050 Long

080 Short

080 Long

365

385

420

505

553

52

63

63

84

84

377

398

436

515

566

74

72

72

97

97

142 Medium

142 Long

142 Extended

210 Long

555

578

603

700

98

98

104

98

555

578

629

710

133

133

133

133

250 Extended 770 97 780 133

otte

Chillers equipped with refrigerant pumps are NOT insulated on the motor or refrigerant drain lines.

(a)

(b)

3/4-in. (19.05-mm) sheet insulation is installed on the evaporator, evaporator waterboxes, suction elbow, and suction cover.

3/8-in. (9.525-mm) sheet insulation is installed on all economizers. All liquid lines and other pipes require the use of 1/2-in. (12.7-mm) pipe insulation or

3/8-in. (9.525-mm) sheet insulation. Copper oil eductor tube lines require pipe insulation.

Insulation Thickness

Requirements

Factory Applied Insulation

All low-temperature surfaces are covered with 3/4 in.

(19.05 mm) Armaflex® II or equal (thermal conductivity

= 0.28 Btu/h-ft

2

[1.59 W/m

2

-K]), including the evaporator, waterboxes, and suction elbow. The economizer and motor cooling lines are insulated with

3/8 in. (9.525 mm) and 1/2 in. (12.7 mm) insulation, respectively.

The insulation is Armaflex® or equivalent closed cell elastomeric insulation to prevent the formation of condensation up to a dew point rating of 74°F (23.3°C),

K = 0.25. Chillers in high humidity areas or ice storage,

44 CVHE-SVX02M-EN

low leaving water temperature (less than 36°F [2.2°C] chilled water temperature/glycol) units, may require double thickness to prevent formation of condensation.

•• D

•• D o n ag e..

ag e tto xp ossu

Figure 28.

Recommended area for unit insulation

• Bulbwells, drain, and vent connections must be accessible after insulating.

• All units with evaporator marine waterboxes wrap waterbox shell insulation with strapping and secure strapping with seal.

• Evaporators with ASME nameplates must have insulation cut out around the nameplate. Do NOT glue insulation to the nameplate.

• Apply 2-in. (50.8-mm) wide black tape on overlap joints. Where possible apply 3-in. (76.2-mm) wide strip of

0.38-in. (9.7-mm) thick insulation over butt joint seams.

• Insulate all economizer supports.

CVHE-SVX02M-EN 45

advertisement

Related manuals

Download PDF

advertisement

Table of contents