Appendix C.

CVHE, CVHF, and CVHG CenTraVac™

Chiller Start-up Tasks to be Performed by Trane

de atth

•• F

•• P

•• R an d u n S ub yo u M

an d M

niin gss,, cca uttiio nss,, a

Inspect chiller for damage (shipping or rigging).

Verify and record unit nitrogen holding charge pressure.

Inspect water piping for proper installation.

Inspect strainers, flow sensing devices, isolation valves, pressure gauges, thermometer wells, flow balancing valves, vent cocks, and drains.

Inspect cooling tower piping.

Verify proper clearances.

Power wiring meets size requirement.

Verify proper voltage and amperage rating.

Verify proper foundation installation.

Verify unit isolator pads/springs have been installed.

Verify low voltage circuits are isolated from high voltage circuits.

Check equipment room for ventilation, refrigerant monitor, rupture disk piping, and

Personal Protective Equipment (PPE).

established requirements for unit installation

MUST be corrected prior to start-up. Any nonconforming condition which is not corrected prior to start-up must be noted in the

Non-

Compliance Form

(PROD-ADF001*-EN) by the start-up technician; this information must also be signed by responsible site personnel before start-up and the completed

Non-Compliance

Form

will become part of the start-up record, submitted with a

Start-up Check Sheet

and a

Chiller Service Report

.

Op erra

Verify nitrogen holding charge.

Calibrate the high pressure cutout control

(HPC).

Meg compressor motor.

Confirm proper oil pump operation.

Evacuate unit.

Check condenser installation.

Check evaporator installation.

urriin g e an d cco e--d a he n tth n u niittss w

Check electrical and controls.

Inspect motor starter and control panel.

Confirm all wiring connections are tight, free of abrasion and have no sharp bends in panel and on compressors.

Inspect contactors and relays.

Verify unit wiring (low and high voltage) is correctly isolated, phased, and properly grounded.

Connect external 120 Vac power to power up the control panel.

Run the oil pump to verify pump can provide

C–1 CVHE-SVX02M-EN

C–2

18 to 22 psid (124.1 to 151.7 kPaD) net pressure.

Verify and record control parameters.

Verify all control interlocks are installed and properly functioning.

Dry run starter (non-Adaptive Frequency™

Drive [AFD]).

Measure condenser pressures and flow.

Adjust condenser flow sensing device.

Measure evaporator pressures and flow.

Adjust evaporator flow sensing device.

Inspect motor starter panel and perform starter panel checkout procedures.

Confirm proper phase check incoming power.

Inspect control panel.

Apply separate source 120 Vac power to control to perform control panel checkout procedure.

Review and record unit configuration parameters.

Confirm oil pump pressure—regulating valve setting.

Verify vane operator is working properly and moves without binding.

Dry run test starter (non-AFD).

Remove separate source power and reconnect wiring.

ep attiio

Relieve nitrogen holding charge.

Evacuate and charge the system.

Apply power to the starter panel.

Verify current to the oil sump heater.

Set Purge mode to “On.”

Bump-start the compressor and verify compressor motor rotation.

Start chiller.

Verify no unusual noises or vibrations and observe operating conditions.

If necessary, adjust oil pressure regulator between 18 to 22 psid (124.1 to 151.7 kPaD) net.

Measure and verify refrigerant pump pressure.

When chiller is stable, take system log three times at 15-minute intervals.

Set Purge mode to “Adaptive.”

Reset the “Starter Energy Consumption” resettable.

Record a

Chiller Service Report

.

Review “AdaptiView Display Customer Training

Checklist.”

Equipment Description

Stopping/Starting Chiller Operation

Alarms

Reports

Data Graphs

Equipment Settings

Display Settings

Security Settings

Basic Troubleshooting

CVHE-SVX02M-EN