Electrical Wiring Instructions. Sundance Spas 680™ Series

Add to My manuals
138 Pages

advertisement

Electrical Wiring Instructions. Sundance Spas 680™ Series | Manualzz

680 SERIES

Export Edison/Hartford/Hawthorne/Peyton 2-Pump Models (50 Hz)

Voltage:

# of Wires:

Frequency:

Current Draw:

Circuit Breaker:

230V/20A*

230 VAC

3

50 Hz

15A

20A

230V/30A**

230 VAC

3

50 Hz

23A

30A

230V/40A***

230 VAC

3

50 Hz

29A

40A

*

In the 20A configuration, the heater

will not operate

while either jets pump is running in high speed.

This is the factory setting.

**

In the 30A configuration, the heater

will not operate

while both jets pumps are running in high speed.

***

In the 40A configuration, the heater

will operate

while both jets pumps are running in high speed.

6.0 Electrical Wiring Instructions

IMPORTANT NOTICE:

The electrical wiring of this spa must meet the requirements of the National Electrical Code/

USA (NEC) and any applicable state or local codes. The electrical circuit must be installed by a qualified electrician and approved by a local building/electrical inspection authority.

1.

Convertible 120/240V Denali/Tacoma Models Only:

!

DANGER:

TO DECREASE THE RISK OF SHOCK,

PRODUCT DAMAGE OR ELECTRICAL FIRE.

120V “Plug-in” Operation: This spa must operate on the supplied 10 feet (3m) 120V GFCI cord at its original length or must be hard-wired for longer runs.

NEVER USE AN EXTENSION CORD FOR ANY

REASON!

• Convertible 120/240V Heater Operation: The included 120V GFCI cord must be discarded for 240V heater operation. This spa must be hard-wired. Supplying power to either configuration above which is not in accordance with these instructions will void both the independent testing agency listing and the manufacturer’s warranty.

Page 14

680 SERIES

2.

Dedicated 240V Edison®, Hartford, Hawthorne Peyton Models:

This spa must be permanently connected (hard-wired) to the power supply. No plug-in connections or extension cords are to be used in conjunction with the operation of this spa. Supplying power to the spa which is not in accordance with these instructions will void both the independent testing agency listing and the manufacturer’s warranty.

3. The power supplied to this spa must be a dedicated circuit with no other appliances or lights sharing the power provided by the circuit.

4. To determine the current, voltage and wire size required, refer to

Section 5.0 “Power Requirements” (pages 12-14).

• Wire size must be appropriate per NEC and/or local codes.

• We recommend type THHN wire.

• All wiring must be copper to ensure proper connections.

Do not use aluminum wire.

• When using wire larger than #6 (10 mm²), add a junction box near the spa and reduce to short lengths of #6 (10 mm²) wire to connect to the spa.

5. The electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422-20 of the National Electrical Code/USA,

ANSI/NFPA 70. The disconnecting means must be readily accessible to the spa’s occupant but installed at least 5 feet (1.5m) from spa water.

6. The electrical circuit supplied for the spa must include a suitable ground fault circuit interrupter (GFCI) as required by NEC Article

680-42.

7. To gain access to the spa’s power terminal block, remove the screws securing the cabinet panel on the side of the spa under the control panel. Then remove the four control box door screws and door

(Figures A-B, page 16).

8. Select the power supply inlet you want to use (Figure A). Feed power cable to control box, then install it through the large opening provided in the bottom side of the box.

9. Connect wires, color to color, on terminal blocks TB1 and TB3

(Figures C-F, page 17). TIGHTEN SECURELY! All wires must be hooked up securely or damage could result.

Page 15

680 SERIES

10. Install control box door and screws and reinstall the cabinet side panels.

Figure A

Equipment Area

7

4

1

WARNING!

DONOT LOOK AT LIT BULB

SEVERE EYE DAMAGE

OR BLINDNESS CAN OCCUR

8

6

9

3

2

2

5

Note:

Equipment location (such as pumps,

CLEAR

RAY

® system, drain, heater etc.) varies by model.

1. Control Box

2. Power Supply Inlet(s)

3. 2-Speed Pump

4. Heater

5. Pump Drain Plugs

6. 1-Speed Pump

7. Control Panel

8. CLEAR

Purification System

5

9. Electronic Ballast (For the CLEAR

System)

RAY

(Ultraviolet) Water

RAY

Figure B

Control Box

2

TB1

1

3

1. Terminal Block

2. Bonding Lug

3. Grounding Terminal

Page 16

680 SERIES

Figure C Figure D

WHT

1

BLK

2

3

TB1

WHT

RED

BLK

BLK to Circuit

Board

GRN

North American Denali/Tacoma Convertible

Models: 120 VAC, 3-Wire Connection (60 Hz)

WHT

1

TB1 to Circuit

Board

WHT

RED

BLK

2

RED

3

BLK

BLK

RED

Move Red

Wire Here

GRN

North American Denali/Tacoma Convertible

Models: 240 VAC, 4-Wire Connection (60 Hz)

CAUTION (For 4-wire 240 VAC Heater Operation):

Move the red wire on the main terminal strip (TB1) from position #1 to position #3. Make certain wires are connected exactly as shown in Figure D before applying power. Failure to do so will result in damage to the circuit board and/or related components and void the manufacturer’s warranty.

Figure E

Figure F

TB2

1

RED

1

BLK

2

Green

TB1

RED

RED

BLK

BLK to Circuit

Board

TB3

North American Models :

240 VAC, 3-Wire Connection (60 Hz)

2

TB1

1

2

Green

TB3

All Export Models:

230 VAC, 3-Wire (50 Hz)

BLUE

BLUE

BROWN

BROWN to Circuit

Board

Page 17

advertisement

Related manuals

Download PDF

advertisement

Table of contents