VENTILATION SETTINGS

C

OOLING OPERATION

The ST 5121 controls one stage of variable-speed fans (Stage 1), one stage of constant-speed fans (Stages 2) and two optional stages of constantspeed fans (Stages 3 & 4).

Ventilation

Level

1.5 o

F

STAGE 4

STAGE 3

STAGE 2

STAGE 1

1.5 o

F

1.5 o F

Minimum

Ventilation

Cycle

Bandwidth

Stage 1

Temperature

Set Point

Start Temp

Stage 2

Start Temp

Stage 3

Start Temp

Stage 4

Room

Temp.

If room temperature rises:

When room temperature < Set Point, the stage 1 fans run at minimum speed according to the minimum ventilation cycle.

At Set Point: the stage 1 fans stop operating according to the minimum ventilation cycle and increase in speed as the room temperature rises.

At Set Point + Bandwidth 1: the stage 1 fans reach full speed.

At Stage 2 Starting Temp: the stage 2 fans start running.

At Stage 3 Starting Temp: the stage 3 fans start running.

At Stage 4 Starting Temp: the stage 4 fans start running.

QM 1333.rev.00

23

ST 5121

If the room temperature falls:

At Stage 4 Starting Temp - 1.5

o

F: the stage 4 fans return to a stop.

At Stage 3 Starting Temp - 1.5

o

F: the stage 3 fans return to a stop.

At Stage 2 Starting Temp - 1.5

o

F: the stage 2 fans return to a stop.

At Set Point + Bandwidth 1: Stage 1 fans start decreasing in speed as the temperature decreases.

At Set Point: the Stage 1 fans reach minimum speed.

Below the Set Point: the stage 1 fans stop operating continuously and operate according to the minimum ventilation cycle at minimum speed.

24

QM 1333.rev.00

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Precise temperature control within 0.1° increments
  • Up to 4 temperature probe inputs for accurate readings
  • 5 motor curves for compatibility with various motor types
  • Full-speed fan start-up for overcoming inertia and de-icing
  • Temperature and ventilation curves for automated adjustments
  • High/low temperature alarm output for proactive alerts
  • Computer connectivity for centralized management
  • Air inlet movement coordination with SB 2000 controller
  • Overload and overvoltage protection for circuit safety
  • Optional mist cooling stage for humidity control

Related manuals

Frequently Answers and Questions

Can I connect multiple temperature probes to the ST5121?
Yes, you can connect up to 4 temperature probes to obtain a more accurate reading of the average room temperature and faster reaction time
Does the ST5121 have an alarm system?
Yes, it has a high/low temperature alarm output that activates when a predefined temperature range is exceeded
Can I use the ST5121 to control both ventilation and heating equipment?
Yes, you can connect one stage of variable speed cooling fans, one stage of constant-speed fans, and two stages of either constant-speed fans or heating units
Does the ST5121 allow for remote monitoring and control?
Yes, you can connect the ST5121 to a computer for centralized management and control
Can I customize the temperature and ventilation settings over time?
Yes, you can specify a temperature curve and a minimum ventilation speed curve with up to six different points each, allowing for automated adjustments based on your requirements
Does the ST5121 have overload protection?
Yes, it has fuses installed at the input and outputs to protect its circuitry in case of an overload or overvoltage