Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network. Allen-Bradley 1794-IE8H, 1794-OE8H, FLEX I/O HART Analog Modules
Advertisement
Advertisement
1
Appendix
F
Configure the 1794-OE8H Module in
RSLogix5000 Software Over the ControlNet
Network
What This Appendix
Contains
This appendix provides the information needed to configure the 1794-OE8H analog output module in RSLogix 5000 software over the ControlNet network using version 13 or earlier and the generic profile.
Background Information
Make sure that your Comm-Format is set to Data - INT. In the FLEX generic profile, you need these sizes:
• Input - 0
• Output - 9
• Config - 11
• Status - 4
IMPORTANT
HART commands will only work when the Data Format control is configured for a 4 to 20 mA range. The default configuration when using the generic profile is 0, which configures the module for a 0 to 20 mA range.
Adapter Name is what you named the ControlNet adapter when it was originally created.
Slot is the position of the FLEX module in the rack, starting with zero.
Publication 1794-UM063A-EN-P - March 2006
F-2 Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network
Configuration
Refer to the following tables for configuration information.
Data Format Control
Channel
0 and 1
2 and 3
4 and 5
6 and 7
Bits
[Adapter Name]:[Slot]:C.Data[0].0
[Adapter Name]:[Slot]:C.Data[0].1
[Adapter Name]:[Slot]:C.Data[0].2
[Adapter Name]:[Slot]:C.Data[0].3
[Adapter Name]:[Slot]:C.Data[0].4
[Adapter Name]:[Slot]:C.Data[0].5
[Adapter Name]:[Slot]:C.Data[0].6
[Adapter Name]:[Slot]:C.Data[0].7
[Adapter Name]:[Slot]:C.Data[1].0
[Adapter Name]:[Slot]:C.Data[1].1
[Adapter Name]:[Slot]:C.Data[1].2
[Adapter Name]:[Slot]:C.Data[1].3
[Adapter Name]:[Slot]:C.Data[1].4
[Adapter Name]:[Slot]:C.Data[1].5
[Adapter Name]:[Slot]:C.Data[1].6
[Adapter Name]:[Slot]:C.Data[1].7
Publication 1794-UM063A-EN-P - March 2006
Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network F-3
Data Format Bits
3 2 1 0 Range Resolution Full Range Interpretation
7 6 5 4
0 0 0 0 0…20 mA 0.1% of 0…20 mA 0…22 mA 0…22 mA
0 0 0 1 0…20 mA 0.2% of 0…20 mA 0…22 mA 0…110%
0 0 1 0 Not Valid
0 0 1 1 0…20 mA 0.3% of 0…20 mA 0…20 mA Unsigned Integer
0 1 0 0 4…20 mA 0.1% of 4…20 mA 2…22 mA 2…22 mA
0 1 0 1 Not Valid
0 1 1 0 Not Valid
Not Valid
Not Valid
Not Valid
Not Valid
Not Valid
Not Valid
0 1 1 1 4…20 mA 0.3% of 4…20 mA 4…20 mA Unsigned Integer
Data Value Table
0…22000
0…11000
0…65535
2000…22000
Not Valid
Not Valid
0…65535
1 0 0 0 Not Valid
1 0 0 1 Not Valid
1 0 1 0 Not Valid
1 0 1 1 0…20 mA 0.28% of 0…20 mA 0…22 mA D/A Count
1 1 0 0 Not Valid
0…8000
1 1 0 1 4…20 mA 0.16% of 4…20 mA 3…21 mA -6.25…+106.25% -625…+10625
1 1 1 0 4…20 mA
1 1 1 1 Not Valid
0.16% of 4…20 mA 2…22 mA -12.5…+112.5% -1250…+11250
Count per mA
1000
500
3276
1000
Not Valid
Not Valid
4095
363
625
625
Publication 1794-UM063A-EN-P - March 2006
F-4 Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network
.
Analog Fault State
Analog Fault State for
Channel
2
3
4
5
6
7
0
1
Min Value of Data Range
Max Value of Data Range
Hold Last State
Analog Fault State Value
Bits
[Adapter Name]:[Slot]:C.Data[3]
[Adapter Name]:[Slot]:C.Data[4]
[Adapter Name]:[Slot]:C.Data[5]
[Adapter Name]:[Slot]:C.Data[6]
[Adapter Name]:[Slot]:C.Data[7]
[Adapter Name]:[Slot]:C.Data[8]
[Adapter Name]:[Slot]:C.Data[9]
[Adapter Name]:[Slot]:C.Data[10]
0
1
1
Bits 9 or 11
0
1
0
1
Bits 8 or 10
0
Fault Mode
Channel
0 and 1
2 and 3
4 and 5
6 and 7
Disabled
Enabled
0
1
Bits
[Adapter Name]:[Slot]:C.Data[0].12
[Adapter Name]:[Slot]:C.Data[0].13
[Adapter Name]:[Slot]:C.Data[1].12
[Adapter Name]:[Slot]:C.Data[1].13
Local Fault Mode
The Local Fault Mode uses bit [Adapter Name]:[Slot]:C.Data[0].15.
Communications Fault 0
Any Fault 1
Publication 1794-UM063A-EN-P - March 2006
Latch Retry Mode
Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network F-5
Channel
0…3
4…7
Retry
Latch
Bits
[Adapter Name]:[Slot]:C.Data[1].14
[Adapter Name]:[Slot]:C.Data[1].15
0
1
Analog/Digital Mode
3
4
5
6
7
Channel
0
1
2
Bits
[Adapter Name]:[Slot]:C.Data[2].0
[Adapter Name]:[Slot]:C.Data[2].1
[Adapter Name]:[Slot]:C.Data[2].2
[Adapter Name]:[Slot]:C.Data[2].3
[Adapter Name]:[Slot]:C.Data[2].4
[Adapter Name]:[Slot]:C.Data[2].5
[Adapter Name]:[Slot]:C.Data[2].6
[Adapter Name]:[Slot]:C.Data[2].7
Analog
Digital
0
1
Digital Fault State
4
5
6
7
1
2
3
Channel
0
Reset
Hold Last State
0
1
Bits
[Adapter Name]:[Slot]:C.Data[2].8
[Adapter Name]:[Slot]:C.Data[2].9
[Adapter Name]:[Slot]:C.Data[2].10
[Adapter Name]:[Slot]:C.Data[2].11
[Adapter Name]:[Slot]:C.Data[2].12
[Adapter Name]:[Slot]:C.Data[2].13
[Adapter Name]:[Slot]:C.Data[2].14
[Adapter Name]:[Slot]:C.Data[2].15
Publication 1794-UM063A-EN-P - March 2006
F-6 Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network
Analog Fault State Values
3
4
5
6
7
Channel
0
1
2
Bits
[Adapter Name]:[Slot]:C.Data[3]
[Adapter Name]:[Slot]:C.Data[4]
[Adapter Name]:[Slot]:C.Data[5]
[Adapter Name]:[Slot]:C.Data[6]
[Adapter Name]:[Slot]:C.Data[7]
[Adapter Name]:[Slot]:C.Data[8]
[Adapter Name]:[Slot]:C.Data[9]
[Adapter Name]:[Slot]:C.Data[10]
Output
Refer to the following tables for output information.
Digital Output Data
3
4
5
6
7
Channel
0
1
2
Bits
[Adapter Name]:[Slot]:O.Data[0].0
[Adapter Name]:[Slot]:O.Data[0].1
[Adapter Name]:[Slot]:O.Data[0].2
[Adapter Name]:[Slot]:O.Data[0].3
[Adapter Name]:[Slot]:O.Data[0].4
[Adapter Name]:[Slot]:O.Data[0].5
[Adapter Name]:[Slot]:O.Data[0].6
[Adapter Name]:[Slot]:O.Data[0].7
Global Output Data
The Global reset bit goes in bit [Adapter Name]:[Slot]:O.Data[0].14.
Publication 1794-UM063A-EN-P - March 2006
Input
Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network F-7
Analog Output Data
2
3
4
5
6
7
Channel
0
1
Bits
[Adapter Name]:[Slot]:O.Data[1]
[Adapter Name]:[Slot]:O.Data[2]
[Adapter Name]:[Slot]:O.Data[3]
[Adapter Name]:[Slot] O.Data[4]
[Adapter Name]:[Slot]:O.Data[5]
[Adapter Name]:[Slot]:O.Data[6]
[Adapter Name]:[Slot]:O.Data[7]
[Adapter Name]:[Slot]:O.Data[8]
Refer to the following tables for input information.
Diagnostic Status Data
Diagnostic Description
Normal
Calibration Failure
Configuration Failure
Message Failure
Lead Break Detection
EEPROM Failure
RAM Failure
ROM Failure
Calculation Failure
Data Out of Range
0
0
0
0
0
0
0
1
1
Bit 3
0
0
1
1
0
0
1
1
0
0
Bit 2
0
1
0
0
0
1
1
1
0
1
Bit 1 Bit 0
0 0
0
1
0
1
1
0
1
1
0
HART Rebuild Bit
The HART rebuild bit is [Adapter Name]:[Slot]:I.Data[0].7.
Publication 1794-UM063A-EN-P - March 2006
F-8 Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network
Fault Alarm
2
3
4
5
6
7
Channel
0
1
Bits
[Adapter Name]:[Slot]:I.Data[0].8
[Adapter Name]:[Slot]:I.Data[0].9
[Adapter Name]:[Slot]:I.Data[0].10
[Adapter Name]:[Slot]:I.Data[0].11
[Adapter Name]:[Slot]:I.Data[0].12
[Adapter Name]:[Slot]:I.Data[0].13
[Adapter Name]:[Slot]:I.Data[0].14
[Adapter Name]:[Slot]:I.Data[0].15
HART Failure
4
5
6
7
1
2
3
Channel
0
Bits
[Adapter Name]:[Slot]:I.Data[2].0
[Adapter Name]:[Slot]:I.Data[2].1
[Adapter Name]:[Slot]:I.Data[2].2
[Adapter Name]:[Slot]:I.Data[2].3
[Adapter Name]:[Slot]:I.Data[2].4
[Adapter Name]:[Slot]:I.Data[2].5
[Adapter Name]:[Slot]:I.Data[2].6
[Adapter Name]:[Slot]:I.Data[2].7
HART Readback
5
6
7
2
3
4
Channel
0
1
Bits
[Adapter Name]:[Slot]:I.Data[2].8
[Adapter Name]:[Slot]:I.Data[2].9
[Adapter Name]:[Slot]:I.Data[2].10
[Adapter Name]:[Slot]:I.Data[2].11
[Adapter Name]:[Slot]:I.Data[2].12
[Adapter Name]:[Slot]:I.Data[2].13
[Adapter Name]:[Slot]:I.Data[2].14
[Adapter Name]:[Slot]:I.Data[2].15
Publication 1794-UM063A-EN-P - March 2006
Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network F-9
HART Communication
3
4
5
6
7
Channel
0
1
2
Bits
[Adapter Name]:[Slot]:I.Data[3].0
[Adapter Name]:[Slot]:I.Data[3].1
[Adapter Name]:[Slot]:I.Data[3].2
[Adapter Name]:[Slot]:I.Data[3].3
[Adapter Name]:[Slot]:I.Data[3].4
[Adapter Name]:[Slot]:I.Data[3].5
[Adapter Name]:[Slot]:I.Data[3].6
[Adapter Name]:[Slot]:I.Data[3].7
HART Transmitter
4
5
6
7
1
2
3
Channel
0
Bits
[Adapter Name]:[Slot]:I.Data[3].8
[Adapter Name]:[Slot]:I.Data[3].9
[Adapter Name]:[Slot]:I.Data[3].10
[Adapter Name]:[Slot]:I.Data[3].11
[Adapter Name]:[Slot]:I.Data[3].12
[Adapter Name]:[Slot]:I.Data[3].13
[Adapter Name]:[Slot]:I.Data[3].14
[Adapter Name]:[Slot]:I.Data[3].15
Publication 1794-UM063A-EN-P - March 2006
F-10 Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network
Publication 1794-UM063A-EN-P - March 2006
How Are We Doing?
Your comments on our technical publications will help us serve you better in the future.
Thank you for taking the time to provide us feedback.
You can complete this form and mail (or fax) it back to us or email us at
Pub. Title/Type FLEX I/O HART Analog Modules
Cat. No.
1794-IE8H and
1794-OE8H
Pub. No.
1794-UM063A-EN-P Pub. Date March 2006 Part No.
953002-48
Please complete the sections below. Where applicable, rank the feature (1=needs improvement, 2=satisfactory, and 3=outstanding).
Overall Usefulness 1 2 3 How can we make this publication more useful for you?
Completeness
(all necessary information is provided)
1 2 3 Can we add more information to help you?
procedure/step illustration example explanation guideline definition feature other
Technical Accuracy
(all provided information is correct)
1 2 3 Can we be more accurate?
text illustration
Clarity
(all provided information is easy to understand)
1 2 3 How can we make things clearer?
Other Comments You can add additional comments on the back of this form.
Your Name
Your Title/Function
Location/Phone
Would you like us to contact you regarding your comments?
___No, there is no need to contact me
___Yes, please call me
___Yes, please email me at _______________________
___Yes, please contact me via _____________________
Return this form to: Rockwell Automation Technical Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705
Fax: 440-646-3525 Email: [email protected]
Publication CIG-CO521C-EN-P- May 2003 PN953002-48
Other Comments
PLEASE FASTEN HERE (DO NOT STAPLE)
PLEASE FOLD HERE
BUSINESS REPLY MAIL
FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE PAID BY THE ADDRESSEE
1 ALLEN-BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES

Public link updated
The public link to your chat has been updated.
Advertisement