System Configuration. Bosch FPC-500 -8, FPC-500 -2, FPC-500 -4, FPC-500-8
Below you will find brief information for fire panel FPC-500 FPC-500-2, fire panel FPC-500 FPC-500-4, fire panel FPC-500 FPC-500-8. The Bosch fire panel FPC-500 is a versatile system that can be configured to meet the needs of a variety of applications. The fire panel FPC-500 is a conventional fire panel that has been designed and tested according to EN 54-2 and EN 54-4. You can use the FPC-500 series for smaller and larger projects. The panel offers up to eight supervised zones and incorporates two notification appliances that can be used to activate the audible notification appliances and visual notification appliances.
Advertisement
Advertisement
Conventional Fire Panel System Configuration | en 31
4 System Configuration
To be able to perform the actions in operating level 3, you will need a code you can enter with the zone keys.
Notice!
The following codes are programmed in delivery status:
Operating level 2: 1234
Operating level 3: 3333
The basic settings can be found in Default Settings, page 74.
Calling up operating level 3
Press the "Code input" key.
You will be prompted to enter a code.
C O D E /
Enter the code with zone keys 1 to 8.
!
You are in the programming menu of the system.
Caution!
In operating level 3, the fire panel is not operational. None of the inputs and outputs are monitored.
Automatic exit of level 3
If you are in level 3 and no key has been pressed for 10 minutes, the system will exit level 3 automatically.
One minute before exiting level 3, a pulse tone of the internal buzzer indicates the time. The time up to the automatic exit of level 3 is displayed in the LCD display.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
32 en | System Configuration Conventional Fire Panel
Exiting operating level 3
Notice!
When you exit operating level 3, the fire panel automatically switches to night mode.
If you are in operating level 3, proceed as follows.
RESET
ACK RESET
Press the RESET key.
You exit operating level 3 when you are at the top level of the menu. The configuration is stored and the inputs and outputs are activated.
– Press the ACK key to exit operating level 3.
– If you do not want to exit operating level 3, press the RESET key.
Menu
Operating level 3 of the fire panel offers you the following setting options:
– 1-System Config
– 2-Delay Config
– 3-Zone Config
– 4-Input Config
– 5-Output Config
– 6-View Config
– 7-Output Control
– 8-Config Reset
Notice!
The structure and description of menus of operating levels 1 and 2 can be found in the operating instructions.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 33
Notice!
The menus are described in these instructions as follows:
A hyphen between the number and the menu description "-" shows you that it is a menu item with a submenu.
An equals sign between the number and the menu description
"=" represents a set value.
A space between the number and the menu description " " is a value that can be set.
Preset values are always shown in bold.
Operation
You have different options for navigating in the menu of the fire panel.
Using autoscrolling
ACK
The menus scroll automatically every 2.5 seconds to the next menu item. If you would like to select the menu item currently shown, simply confirm with the
ACK key.
Navigating with the zone keys
1
...
8
In the menu, each menu item has a number from 1 to 8 preceding it. Use the zone keys to select the desired menu item in the menu. The desired menu item does not have to be shown in the display.
Navigating with the arrow keys i
Use the arrow keys to navigate in the menu.
Using the arrow keys stops autoscrolling in the menus.
ACK
Confirm your selection in the menu with the ACK key.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
34 en | System Configuration Conventional Fire Panel
4.1
4.1.1
4.1.2
Exiting submenus
RESET
ESC In the menu and in the submenus, you can jump to a higher level or cancel the setting using the RESET
(ESC) key.
Hold the RESET (ESC) key down for 2 seconds to jump to the uppermost level.
System Configuration
In the System Config menu, you can specify basic settings for your fire panel.
Setting the Date/Time
1
Press zone key 1. This takes you to the System
Config menu.
1
Press zone key 1.
You can now set the date and time.
ACK
To save the currently displayed value, press the ACK key.
Repeat the steps to set the month, year, hour, and minute.
Buzzer Beep
1
Press zone key 1. This takes you to the System
Config menu.
2
1
...
2
Press zone key 2.
This takes you to the Keypad Tone submenu.
Press zone keys 1 or 2:
– 1=On (default setting)
– 2 Off
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 35
4.1.3
4.1.4
EOL Elements
You can use EOL Devices to specify whether you want to use resistors or EOL modules for zone termination.
1
Press zone key 1. This takes you to the System
Config menu.
3
1
...
3
Press zone key 3.
This takes you to the EOL Devices submenu.
Press zone keys 1 to 3:
– 1=Resistor (default setting, not EN 54‑13 compliant)
– 2 Only 2W Module
– 3 With 4W Module
1 2 3 4 5 6 7 8
CS TH: mA
If you select With 4W Module, you must specify the threshold for the creeping short-circuit.
You can calculate this using the battery calculator included on the CD.
Resetting Zones
In this menu, you can specify the delay times for resetting zones. You can specify how long the zones can be disconnected from the power and how long the stabilization time of the detector should last. This setting is used for the zone test, restarting the fire panel and intermediate alarm storage.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
36 en | System Configuration Conventional Fire Panel
Cut For
1
Press zone key 1. This takes you to the System
Config menu.
4
1
Press zone key 4.
This takes you to the Zone Reset submenu.
Press zone key 1.
This takes you to the Cut For submenu.
1
...
5
Press zone keys 1 to 5.
– 1 1s
– 2=5s (default setting)
– 3 10s
– 4 15s
– 5 20s
Stabilize for
1
Press zone key 1. This takes you to the System
Config menu.
4
2
1
...
5
Press zone key 4.
This takes you to the Zone Reset submenu.
Press zone key 2.
This takes you to the Stabilize For submenu.
Press zone keys 1 to 5.
– 1 1s
– 2=5s (default setting)
– 3 10s
– 4 15s
– 5 20s
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 37
4.1.5
4.1.6
Aux Power
The With Zone setting relates to the last zone of the fire panel.
If the last zone is reset after a pre-alarm or alarm, the AUX power supply is reset simultaneously.
The With Panel setting also resets the power supply each time the fire panel is reset.
If you select Never, the auxiliary power supply is never reset.
1
Press zone key 1. This takes you to the System
Config menu.
5
1
...
3
Press zone key 5.
This takes you to the Aux Power submenu.
Press zone keys 1 to 3.
– 1=With Zone (default setting)
– 2 With Panel
– 3 Never
Faults
The Faults setting specifies whether faults on the fire panel are to be displayed until the fire panel is manually reset.
Notice!
This setting does not apply to system faults.
System faults can only be reset manually.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
38 en | System Configuration Conventional Fire Panel
4.1.7
1
Press zone key 1. This takes you to the System
Config menu.
6
1
...
2
Press zone key 6.
This takes you to the Faults submenu.
Press zone key 1 or 2.
– 1=Latching (default setting)
– 2 Non Latching
Level Code
In the Level Code menu, you can specify new codes for operating levels 2 and 3. The new code must be 4 characters long and is displayed during entry.
Notice!
The following codes are programmed in delivery status:
Operating level 2: 1234
Operating level 3: 3333
1
Press zone key 1. This takes you to the System
Config menu.
7
1
...
2
Press zone key 7.
This takes you to the Code submenu.
– 1- Level 2 Code
– 2- Level 3 Code
1 2 3 4 5 6 7 8
Level 2 Code
Set to: ____
You are prompted to enter the new code.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 39
1 2 3 4 5 6 7 8
Level 2 Code
Confirm: ____
You then have to confirm the new code by entering it again.
The procedure for changing the code for operating level 3 is exactly the same.
Notice!
If you have forgotten your code, contact your Bosch partner.
4.1.8
4.2
Test Log
You can decide whether or not the fire panel creates a Test
History.
1
Press zone key 1. This takes you to the System
Config menu.
8
1
...
2
Press zone key 8.
This takes you to the Test History submenu.
Use zone keys 1 or 2.
– 1=Log Enabled (default setting)
– 2 Log Disabled
Configuring Delays
In the Delay Config menu, you can program different delay times for different zone programs, outputs and fault types.
2
Press zone key 2. This takes you to the Delay Config menu.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
40 en | System Configuration Conventional Fire Panel
4.2.1
Deactivating Day Mode
Specify whether you want day mode (zones with alarm verification start a verification time in the event of an alarm) to be exited manually by the user or automatically at a defined time. You can program the time in this submenu.
Notice!
Day mode must always be started manually; it is not possible to configure an automatic start.
2
Press zone key 2. This takes you to the Delay Config menu.
1
Press zone key 1.
This takes you to the Day Mode Off submenu.
1
...
2
Use zone keys 1 or 2.
– 1=Manual (default setting)
– 2 Automatic
If you set Day Mode Off to Automatic, you must program the changeover time from day to night mode.
1 2 3 4 5 6 7 8
Off Time: :17:00
Confirm with
Set the time with the arrow keys and confirm using the ACK key.
Alarm Verification 4.2.2
Notice!
This setting only applies to zones that are programmed as alarm verification.
Note that the delay settings are only effective in day mode. In night mode, the alarm is triggered immediately.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 41
In the Alarm Verific menu, you set the times within which the user must confirm a triggered alarm (ACK Within). The Invest
Time submenu specifies the time available to the user to enter the alarm triggering area before the notification appliance is activated. You can also use NAC 1 to specify whether:
– Alert switches NAC 1 on immediately in the event of an alarm. NAC 1 is then switched off during the verification time and switched on again after the verification time.
– With Evacuate, NAC 1 is switched off during the delay time and only activated during the actual alarm.
Time setting for alarm acknowledgement
2
Press zone key 2. This takes you to the Delay Config menu.
2
1
Press zone key 2.
This takes you to the Alarm Verific submenu.
Press zone key 1.
This takes you to the ACK Within submenu.
1
...
4
Use the zone keys to set the respective delay.
– 1 30 s
– 2= 60 s (default setting)
– 3 90 s
– 4 120s
Time setting for verification time
2
Press zone key 2. This takes you to the Delay Config menu.
2
Press zone key 2.
This takes you to the Alarm Verific submenu.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
42 en | System Configuration Conventional Fire Panel
4.2.3
2
1
...
8
Press zone key 2.
This takes you to the Invest Time submenu.
Use the zone keys to set the respective delay.
– 1 1 min (default setting)
– 2 2 min
– 3 3 min
– 4 4 min
– 5 5 min
– 6 6 min
– 7 7 min
– 8 8 min
Notification appliance 1
2
Press zone key 2. This takes you to the Delay Config menu.
2
3
1
...
2
Press zone key 2.
This takes you to the Alarm Verific submenu.
Press zone key 3.
This takes you to the NAC 1 submenu.
Press zone key 1 or 2.
– 1 Alert
– 2=Evacuate (default setting)
Intermediate Alarm Storage
Intermediate alarm storage is an automatic procedure designed to rule out false alarms as far as possible. The entire procedure lasts up to 60 seconds:
– Ten seconds after a fire is detected, the zone is reset
(setting Reset After).
–
The zone is reset for x seconds (setting Cut For, Cut For ,
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 43
!
– There is an x second stabilization phase for the elements in
the zone (setting Stabilize For, Stabilize for, page 36).
Caution!
Detectors of the FCP-320 series must not be used with intermediate alarm storage because the detector calculates a new standby value after the reset. This can generate an increased alarm threshold. If there is a fire, this can thus delay the trigger of an alarm.
Before using automatic fire detectors, find out from the manufacturer whether they can be used for intermediate alarm storage.
In this menu you can change the pre-set time values indicated above.
Reset after
2
Press zone key 2. This takes you to the Delay Config menu.
3
1
1
...
4
Press zone key 3.
This takes you to the Int Alarm Stor submenu.
Press zone key 1.
This takes you to the Reset After submenu.
Use the zone keys to set the respective delay.
– 1 1 s
– 2 5 s
– 3= 10 s (default setting)
– 4 15s
– 5 20 s
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
44 en | System Configuration Conventional Fire Panel
4.2.4
4.3
Display total delay
2
Press zone key 2. This takes you to the Delay Config menu.
3
Press zone key 3.
This takes you to the Int Alarm Stor submenu.
2
Press zone key 2.
This takes you to the Total Delay submenu.
The total delay is displayed.
Delay for Mains Fault
The Power Fault menu option enables you to specify the delay after which an error message indicating a power supply failure
(mains or battery) is to be displayed. If the fault is resolved before the time set here, it is no longer displayed.
2
Press zone key 2. This takes you to the Delay Config menu.
4
1
...
5
Press zone key 4.
This takes you to the Power Fault submenu.
Use the zone keys to set the respective delay.
– 1=No Delay (default setting)
– 2 1 min
– 3 5 min
– 4 10 min
– 5 15 min
Zone Configuration
In the Zone Config menu, you can program the individual zones of the fire panel. Depending on the panel, you can set 2, 4 or 8 zones. The following zone types are available:
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 45
No delay (No Delay)
A zone programmed as No Delay triggers an alarm immediately.
If you are using manual call points, they must be set as No
Delay.
Notice!
Only use manual call points in zones which are programmed as
No Delay.
Int Alarm StorIntermediate alarm storage
A zone triggers an alarm. This is evaluated by the fire panel as a pre-alarm and is not displayed. The zone is reset automatically.
If it triggers an alarm again, the panel switches immediately to alarm. If a second alarm is not triggered, the fire panel reverts to its normal state after 10 minutes.
Alarm verification (Alarm Verific)
Notice!
Note that the delay is only effective in day mode. In night mode, the alarm is triggered immediately.
Notice!
If the fire panel automatically switches to night mode during an ongoing verification time, an alarm is triggered immediately.
Notice!
If during the verification time in one zone an alarm is triggered in another zone, which is programmed as alarm verification, an alarm is triggered immediately.
If a zone programmed as alarm verification detects an alarm, it triggers an alarm, which is delayed.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
46 en | System Configuration Conventional Fire Panel
!
The LCD display prompts you to verify the alarm. You must confirm the alarm within a pre-defined time using the ACK key.
After this pre-defined time the verification time begins. Within this time you must investigate the alarm triggering area and, if necessary, trigger an alarm.
During the verification time, the panel can be reset without triggering an alarm. After the verification time has expired, the panel goes into the alarm state.
Dual-detector dependency (2-Det Depend)
Caution!
Detectors with connected remote displays must not be used with the dual-detector dependency.
Dual-detector dependency only works with detectors that use an alarm resistance of 820 ohm +/- 5% or 910 ohm +/- 5%.
Otherwise, in the event of a fire, proper functioning of the fire panel cannot be guaranteed.
Notice!
The fire panel does not support dual-detector dependency with
4-wire detectors.
The zone must contain more than one detector. If one of the detectors in the zone triggers, this is evaluated as a pre-alarm. If an additional detector in the same zone is activated, an alarm is triggered. The panel automatically attempts to reset the prealarm every 10 minutes. However, this is not possible if a detector remains active. This procedure is repeated until no more detectors are active and the panel returns to its normal state, or until a second detector becomes active, thus elevating the pre-alarm to an alarm.
Dual-zone dependency (2-Zone Depend)
Applies to adjacent zones, for example zones 1 and 2.
If a zone detects an alarm, this is evaluated as a pre-alarm. An alarm is only triggered when the second zone detects an alarm.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
4.4
System Configuration | en 47
Possible zone dependencies:
– FPC‑500-2: 1&2
– FPC‑500‑4: 1&2, 3&4
– FPC‑500‑8: 1&2, 3&4, 5&6, 7&8
If you set a zone to dual-zone dependency, the other associated zone is also changed automatically.
Zones 1 to 8
3
Press zone key 3. This takes you to the Zone Config menu.
1
Press zone key 1.
This takes you to the zone 1 submenu.
1
...
6
Use the zone keys to program the zone.
– 1=No Delay (default setting)
– 2 Int Alarm Stor
– 3 Alarm Verific
– 4 2-Det Depend
– 5 2-Zone Depend
Zones 2 to 8 are pre-programmed in the same way as zone 1.
You can change the settings as with zone 1.
Notice!
Zones 3 and 4 are only available on the FPC‑500‑4 and
FPC‑500‑8 panels. Zones 5–8 are only available on the
FPC‑500‑8.
Configuring Inputs
In the Input Config menu, you can program the behavior of the inputs.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
48 en | System Configuration Conventional Fire Panel
Notice!
Only use buttons (no locking element) if you have programmed inputs as Drill/Evacuate, Silence, or Reset Panel.
Access levels as per EN 54‑2 must be observed.
Notice!
Depending on the panel, there is one input on the FPC‑500‑2 and FPC‑500‑4, and two inputs on the FPC‑500‑8.
4.4.1
4
Press zone key 4.
This takes you to the Input Config menu.
Input 1
4
Press zone key 4.
This takes you to the Input Config menu.
1
1
...
7
Press zone key 1.
This takes you to the Input 1 submenu.
Use the zone keys to set the programming for input
1.
– 1= Not Used (default setting)
– 2 Drill/Evacuate
– 3 Silence
– 4 Level 2
– 5 Reset Panel
– 6 Ext PS Fault
– 7 Ext Batt Fault
Notice!
You do not have to confirm the input functions on the panel.
Thus use a key switch if possible to activate inputs.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 49
4.4.2
4.5
4.5.1
!
Input 2 (FPC-500‑8 only)
4
Press zone key 4.
This takes you to the Input Config menu.
2
Press zone key 2.
This takes you to the Input 2 submenu.
Additional settings correspond to those for Input 1.
Configuring Outputs
In the Output Config menu, you can program the behavior of the individual fire panel outputs.
Notification Appliances
In the NAC submenu, you specify the behavior of the notification appliances. You can use NAC Zones to assign the notification appliances to particular zones. Reactive NAC specifies whether silenced notification appliances are reactivated by a new alarm in another zone. You can use NAC in test to specify whether the notification appliances are activated for 15 seconds when a zone test is performed.
Caution!
When assigning the zones to notification appliances, make sure that each zone of the fire panel is assigned to at least one notification appliance.
Zones not assigned do not trigger any alarm signaling via the notification appliance if there is a fire.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
50 en | System Configuration Conventional Fire Panel
Notification appliance 1 zone assignment
5
Press zone key 5.
This takes you to the Output Config menu.
1
1
1
...
8
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 1.
This takes you to the NAC Zones submenu.
Use the zone keys to select the corresponding zones whose alarm you want to activate notification appliance 1.
You can select multiple zones. If you press the zone key again, the selection is cancelled.
Confirm your selection.
ACK
Notification appliance 2 zone assignment
See "Notification appliance 1 zone assignment", Notification
appliance 1 zone assignment, page 50.
Reactivating notification appliances
5
Press zone key 5.
This takes you to the Output Config menu.
1
3
1
...
2
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 3.
This takes you to the Reactive NAC submenu.
Press zone keys 1 or 2.
1=By Other Zone (default setting)
2 No Reactivate
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 51
4.5.2
Notification appliance behavior in zone test
5
Press zone key 5.
This takes you to the Output Config menu.
1
4
1
...
2
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 4.
This takes you to the NAC in test submenu.
Press zone keys 1 or 2.
1 Activation
2=No Activation (default setting)
Alarm Relay
In the Alarm Relay submenu, you can specify the properties of the alarm relay. These include the Silencable and Drillable settings. You can use Silencable to specify whether the relay can be silenced manually. Drillable specifies whether the alarm relay is also activated during a manual alarm (Drill/Evac).
Alarm relay can be muted
5
Press zone key 5.
This takes you to the Output Config menu.
2
1
1
...
2
Press zone key 2.
This takes you to the Alarm Relay submenu.
Press zone key 1.
This takes you to the Silencable submenu.
Press zone keys 1 or 2.
1 Silencable
2=Not Silencable (default setting)
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
52 en | System Configuration Conventional Fire Panel
4.5.3
Alarm relay follows manual alarm
5
Press zone key 5.
This takes you to the Output Config menu.
2
2
1
...
2
Press zone key 2.
This takes you to the Alarm Relay submenu.
Press zone key 2.
This takes you to the Drillable submenu.
Press zone keys 1 or 2.
1 Drillable
2= Not Drillable (default setting)
OC/Relay Extensions
In the OC/Relay Ext menu, you can individually set the properties of all OC/Relay outputs. The possible settings for the
OC/Relay outputs 2 to 8 correspond to those for the first OC/
Relay . The following settings are possible:
– Zone = Alarm: The output is activated if the zone triggers an alarm. Here zone 1 is assigned to output 1, etc.
– Zone Normal: If the zone is not in a normal state, the output is activated. Assignment: zone 1 to output 1 etc.
– Sum Alarm: When the fire panel is in an alarm state, this output is activated regardless of the zone.
– Sum PreAlarm: When the fire panel is in a pre-alarm state, this output is activated regardless of the zone.
– Sum Fault: This output is activated if there is a fault.
– Sum Disable: If a fire panel element is disabled, this output is activated (zones, notification appliances, relays).
– Sum Test: This output is activated if a zone in the fire panel is in test mode.
– Not Used: The output is not used.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel
4.6
System Configuration | en 53
5
Press zone key 5.
This takes you to the Output Config menu.
3
Press zone key 3.
This takes you to the OC/Relay Ext submenu.
Press zone key 1 to choose Open Collector 1.
1
1
...
8
Use the zone keys to make the corresponding setting.
– 1=Zone = Alarm (default setting)
– 2 Zone Normal
– 3 Sum Alarm
– 4 Sum PreAlarm
– 5 Sum Fault
– 6 Sum Disable
– 7 Sum Test
– 8 Not Used
The procedure for OC/Relay 2 to 8 is the same.
Displaying the Configuration
In the View Config menu, you can display the programming of the fire panel.
6
Press zone key 6.
This takes you to the View Config menu.
i
Use arrow keys to scroll more quickly through the displayed programming.
Hold the arrow key down to scroll through the menu in increments of 10 steps.
To exit the display, press the ESC key.
RESET
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
54 en | System Configuration Conventional Fire Panel
4.7
4.7.1
4.7.2
Controlling Outputs
In the Output Control menu you can activate and deactivate the individual outputs for test purposes. When you exit operating level 3, all activations of the outputs are reset to the normal state again.
Notification appliance 1
7
Press zone key 7.
This takes you to the Output Control menu.
1
ACK RESET
Press zone key 1.
This takes you to the NAC 1 submenu.
– Press the ACK key.
Notification appliance 1 is activated.
– Press the RESET key.
Notification appliance 1 is deactivated.
Notification appliance 2
7
Press zone key 7.
This takes you to the Output Control menu.
2
ACK RESET
Press zone key 2.
This takes you to the NAC 2 submenu.
– Press the ACK key.
Notification appliance 2 is activated.
– Press the RESET key.
Notification appliance 2 is deactivated.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 55
4.7.3
4.7.4
4.7.5
Alarm Relay
7
Press zone key 7.
This takes you to the Output Control menu.
3
ACK RESET
Press zone key 3.
This takes you to the Alarm Relay submenu.
– Press the ACK key.
The alarm relay is activated.
– Press the RESET key.
The alarm relay is deactivated.
Fault Relay
7
Press zone key 7.
This takes you to the Output Control menu.
4
ACK RESET
Press zone key 4.
This takes you to the Fault Relay submenu.
– Press the ACK key.
The fault relay is activated.
– Press the RESET key.
The fault relay is deactivated.
OC/Relay Extension
7
Press zone key 7.
This takes you to the Output Control menu.
5
Press zone key 5.
This takes you to the OC/Relay Ext submenu.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
56 en | System Configuration Conventional Fire Panel
4.7.6
4.8
1
Press zone key 1.
This takes you to the OC/Relay 1 submenu.
ACK
RESET
– Press the ACK key.
The OC/Relay 1 output is activated.
– Press the RESET key.
The OC/Relay 1 output is deactivated.
Continue in the same way for the Open Collector outputs 2 to 8.
Control all outputs
7
Press zone key 7.
This takes you to the Output Control menu.
6
ACK RESET
Press zone key 6.
This takes you to the All submenu.
– Press the ACK key.
All outputs are activated.
– Press the RESET key.
All outputs are deactivated.
Resetting To Delivery State
You can use Config Reset to reset the programming of the fire panel to the default values set when delivered.
Notice!
Resetting the fire panel deletes all of your changes to the programming. The panel is reset to the default programming,
see Default Settings, page 74.
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel System Configuration | en 57
8
Press zone key 8.
This takes you to the Config Reset menu.
ACK RESET
– Press the ACK key.
The fire panel is reset to the delivery state.
– Press the RESET key.
You exit the menu without making changes.
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Advertisement
Key features
- Up to 8 monitored detector zones
- Two monitored notification appliance outputs
- Alarm verification
- Intermediate alarm storage
- EN 54-13 compliant (BOSEC certificate TCC 2 - 977),
- Three operating levels
- Emergency power supply using batteries