Conventional Fire Panel Technical Data | en 59
6
6.1
Technical Data
Zones
Max. number of detectors in accordance with EN 54‑2
Max. number of detectors per zone in accordance with
EN 54‑2
Max. number of extensions
Prog. inputs
AUX output
Alarm device output
Relay
Electrical Data
Power supply voltage
Current consumption
AC power consumption
Operating voltage
I min
I max, a
I max, b
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
2
64
4
128
8
256
0
1
32
1
1
2
2
2
2
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
230 VAC +10%/-15%, 50–
60 Hz
275 mA 312 mA 375 mA
80 W
21.4 VDC to 29 VDC
70 mA
0.7 A
2.3 A
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
60 en | Technical Data Conventional Fire Panel
Zones
–
–
–
AUX
–
–
Voltage
Max. output current
Max. line resistance
– Voltage
– Max. output current
Max. line resistance
Fuse
Notification appliance outputs
– Voltage
– Max. output current
– Max. line resistance
– Fuse
Relay outputs
– Breaking capacity
– Max. line resistance
Transistor outputs
– Breaking capacity
– Max. line resistance
Recommended cable type
Batteries
– Max. inner resistance
– Max. current consumption
– Fuse
End-point voltage
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
20 VDC ±1VDC
100 mA ±5 mA
22.5 Ohm
21 VDC to 29 VDC
500 mA ±10%
22.5 Ohm
0.75 A @ 60 V
21 VDC to 29 VDC
500 mA ±10% per output
22.5 Ohm
0.75 A @ 60 V
1 A @ 30 VDC
22.5 Ohm
No inductive loads
20 mA @ 24 VDC
22.5 Ohm
Unshielded cable, 0.8-mm cable diameter, cable cross section up to 1.5 mm 2
800 mOhm
2.3 A
5 A @ 60 V
21.4 V
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Technical Data | en 61
6.1.1
Communication parameters
Notification appliances
Standby
– A-
– B+
Alarm state
– A-
– B+
Inputs
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
10 V to 15 V
0 V to 0.5 V
0 V to 1 V
21 V to 29 V
– Alarm resistor 820 ohm ±5%
– EOL Resistor 3900 ohm ±1%
Zones (with resistance combination)
– Alarm resistor
– EOL Resistor
Zones (with EOL modules)
820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
3900 ohm ±1%
– Alarm resistor 820 ohm ±5%
910 ohm ±5%
No 2-Det Depend: 680 ohm
±5%
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
62 en | Technical Data Conventional Fire Panel
6.2
6.3
Mechanical
Dimensions (H x W x D)
Weight
Housing material
– Front
– Back
Housing color
– Front
– Back
FPC-500
‑2
FPC-500
‑4
FPC-500
-8
351 x 351 x 90 mm
2200 g, without batteries
ABS+PC
ABS-FR
RAL 9003 (Signal White)
PANTONE 10 C (Cool Grey)
Environmental Conditions
FPC-500
‑2
IP 30
FPC-500
‑4
FPC-500
-8
Protection category according to EN 60529
Protection class as per
EN 60950
EMC interference immunity, emissions
EMC interference immunity
Vibrations
Permitted operating temperature
II
EN 61000-6-3
EN 50130-4
EN 60068-2-6
0 °C to +40 °C
Permitted storage temperature -10 °C to +55 °C (14 °F to 131
°F)
Relative humidity Max. 95% non-condensing
2014.06 | 7.0 | F.01U.172.980
Bosch Sicherheitssysteme GmbH
Conventional Fire Panel Technical Data | en 63
6.4
Information as per EN 54‑4, chapter 7.1
a) This is a power supply unit that is installed in the FPC‑500
Fire Panel. It provides power to the device and the connected peripherals and is used to charge the two connectable batteries.
b) Technical data
61 W 1) Recommended power output
2) Power supply
Operating voltage
3) Communication parameters
4) Fuse values
5) Batteries
230 VAC +10%/-15%, 50–60 Hz
26 VDC to 29 VDC
None
3.15 A/250 V
2 x 7.0–7.2 Ah (max.) lead gel battery
2.3 A 6) Max. current consumption
7) Max. battery inner resistance
8) I min
I max, a
I max, b
9) Cable parameters
Battery
Board power supply
230-V power supply
800 mOhm
70 mA
0.7 A
2.3 A
Cable enclosed
Wired ex works
1.5-mm 2 standard cable
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
64 en | Technical Data
6.5
Conventional Fire Panel c) The power supply unit is a component of the FPC‑500 Fire
Panel and is supplied preinstalled. No additional installation instructions are necessary.
1) Please refer to the information on environmental conditions in this document.
2) The power supply unit is supplied preinstalled – assembly instructions are not required.
3) For connection instructions, please refer to the FPC‑500 installation instructions.
d) The power supply unit is a component of the FPC‑500 Fire
Panel – there are no additional operating instructions.e) The power supply unit is a component of the FPC‑500 Fire Panel – no operation is required.f) Have maintenance and installation work carried out regularly by trained, qualified personnel. Bosch
Sicherheitssysteme GmbH recommends carrying out a functional and visual check at least once a year. Replace the batteries on a regular basis. Please observe the appropriate requirements stipulated by the local authorities etc.
Options with requirements as per EN
54‑2:1997/A1:2006
The FPC‑500 provides the following options with requirements under EN 54‑2:1997/A1:2006
– Alarm counter
– Test status
– Output for activation of fire alarm devices
– Transmission delay
– Dependency of fire detection status on more than one alarm signal
– Type A dependency
– Type B dependency
2014.06 | 7.0 | F.01U.172.980