GROUND FAULT TESTING PROCEDURE. SymCom P2 777-LR-P2, P2 777-575-LR-P2

Below you will find brief information for overload relay P2 777-LR-P2, overload relay P2 777-575-LR-P2. The 777-LR-P2 is an electronic overload relay that is fully programmable for customized protection. It’s designed to protect 3-phase systems with operating voltages of 200-480VAC (500-600VAC for the Model 777-575-LR-P2). The 777-LR-P2 can be safely programmed prior to installation by supplying power with a 9V battery.

PDF Download
Document
SymCom overload relay P2 777-LR-P2 Installation Instructions | Manualzz

Advertisement

Advertisement

Advertisement

Key features

  • Fully programmable
  • 3-phase system protection
  • 9V battery programming
  • Fail-safe operation
  • Current unbalance protection
  • Ground fault protection
  • Undercurrent protection
  • Overcurrent protection
  • Restart delay timer

Frequently asked questions

Connect the 9V battery cable to the pins on the left side of the unit (when looking at the display), and then attach a standard 9V battery to the cable. Rotate MODE SELECT to the parameter to be programmed. Press and hold the RESET/PROGRAM button and rotate the DISPLAY/PROGRAM knob until the proper setting is displayed. Release the RESET/PROGRAM button.

RD1 provides protection against short cycling and allows adequate cool-down time between motor starts. RD2 is used to restart the motor after a trip due to current unbalance, current single-phasing, or an overcurrent condition. RD3 initiates after an undercurrent trip and is used to allow the well to recharge in pumping applications.

Disconnect power, hook up the three line voltages to L1, L2, and L3, program the desired parameters, construct a test circuit that simulates a ground fault condition. Place the unit in RUN mode, apply 3-phase power, and energize the test circuit until the unit trips. The display should show “GrF” and the NO contacts should be open.