Introduction
The D9210B Access Control Interface
Relay
D9210B
Terminal
Blocks
7
SDIB
8
T +
9
ZNCOM
10
ZN +
11
RTE
12
COM
1
PWR +
2
LCKN/C
3
LCKCOM
4
LCKN/O
5
COM
6
SDIA
13
REX
14
+5.20V
15
DATA 0
16
DATA 1
17
BUZZER
18
LED
ON
4
5
6
1
2
3
DIP Switch
EPROM
Diagnostic and
Status LEDs
OPER
MON
D0
READER
D1
READER
Figure 1. D9210B Access Control Interface Module
Terminal Blocks. The D9210B comes with three banks of terminal blocks for connecting the D9210B to its power source, the panel and associated readers and relays.
Relay. A removable (model D136) relay provides a dry contact single pull, double throw output.
Dipswitch. The D9210B dipswitch has six on-off switch settings. Setting these switches allows each unique D9210B to be programmed for a specific address.
EPROM. The D9210B is controlled by a programmable read-only memory microprocessor.
Diagnostic and Status LEDs. The D9210B has a series of light emitting diodes
(LEDs) for identifying operational and diagnostic states. These are listed below.
LED
Operational Monitor (Green)
D0 Reader (Green)
D1 Reader (Yellow)
Action
LED blinks on and off
LED is on or off (solid)
LED rapidly blinking
LED is off
LED rapidly blinking
LED is off
Table 1. D9210B Diagnostic and Status LEDs
State
System is operational
System is off or not operational
Card data executing
No card data is being received
Card data executing
No card data is being sent
32206C 3/97 D9210B Operation & Installation Manual
Page 5
© 1997 Radionics
Materials Included
Radionics ships the D9210B Access Control Interface module pre-assembled from the factory with a power supply, in its own can, or as a unit less can. You will receive the following parts with your package depending upon what model is ordered, (see Ordered separately).
• D136 removable relay mounted on the board.
• Battery Leads (for the D9210BLC).
• 1K
Ω
1/2 watt end of line resistor.
• Literature Pack containing: D9210B Operation and Installation Manual,
D9210 Program Entry Guide, ACCESS Program Record Sheet, and Power
Supply Installation Instructions.
• Hardware pack containing: three #6x3/8 self-tapping sheet metal screws to secure the module on the mounting skirt or the enclosure. Two strain relief cable ties.
Ordered Separately
The D9210B Door Controller can be used with the Radionics D7412 (supports 2 doors) or D9412 (supports 8 doors) Control/Communicator security panels and associated control keypads and access control readers. Following are the available options.
• D9210BLC: The D9210BLC (up to 4) can be installed in the same enclosure as the control panel using the mounting screws and fasteners. Two additional modules can be mounted using the D136 brackets. Radionics recommends that you use a separate power supply for the D9210Bs to isolate them from other SDI devices.
• D9210BC: The D9210BC is a complete unit mounted on a mounting skirt,
(D9201M) with a switchable 12/24 VDC (500-1500 mA) power supply, 24
VAC/40 VA fused transformer, and (1) D9210B. It can be installed with another D9210BLC in a single D8103, D8109 or D8108A enclosure.
• D9210B: The D9210B is mounted in a 5
(W) x8
(L) x3
(H)
enclosure and can be mounted as a standalone unit in the field.
• Compatible Readers: Readers are not shipped with the unit (see Table 3).
Listings and Approval Information
Underwriters Laboratories (UL). The D9210B, when used with the D7412 or
D9412 panels, is listed by UL for use as part of an Access Control System;
Local, Police-Connect, Central Station, or Proprietary Burglar Alarm System; and a Commercial Fire Alarm System. In addition to the manual, refer to the
D7412/D9412 installation documentation regarding Burglar Alarm Grades and
Fire Alarm services supported. The D9210B is a Signaling Device Subassembly also suitable as a Burglar Alarm Unit Accessory Subassembly and Access
Control Unit Subassembly.
Other Listings and Approvals. FCC 15B, CSFM (highrise)