Additional T1 Outputs

(990-72050-02 System Only)

Connect up to eight optional T1 outputs at the OPTIONS I/O wirewrap pins. See Figure 26 for the connector location, and Figure 30 for the connections.

Note: The shield pin is capacitively coupled to ground, therefore, the shield must be connected at the source end. The shield may also be connected at the TimeSource 3500 end for additional longitudinal noise protection.

1

Figure 30. OPTIONS I/O Wire-Wrap Pin Connections

1 2 3 4

5 6 7 8

S

R

T

S

R

T

3

4

Mixed E1/T1 Outputs

Connect up to eight optional mixed E1/T1 outputs at the

OPTIONS I/O wire-wrap pins. Refer to Figure 26 for the connector location and Figure 30 for the connections.

5

TimeSource 3500

Installation

097-72050-01 Issue 7: August 2003

115

3

S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

Mixed T1/CCK Outputs

(990-72050-07 System Only)

Connect up to eight optional mixed T1/CCK outputs at the

OPTIONS I/O wire-wrap pins. Refer to Figure 26 for the connector location and Figure 30 for the connections.

Composite Clock Outputs

(990-72050-03 System Only)

Connect up to eight optional composite clock outputs at the

OPTIONS I/O wire-wrap pins. Refer to Figure 26 for the connector location and Figure 30 for the connections.

IRIG-B TOD Outputs

(990-72050-05 System Only)

Connect one or two optional IRIG-B TOD outputs at the OPTIONS

I/O wire-wrap pins. See Figure 26 for the connector locations, and

Figure 31 for the connections.

Follow Procedure F to install the IRIG-B BNC adapter, and make the IRIG-B TOD connections.

116

TimeSource 3500

Installation

097-72050-01 Issue 7: August 2003

S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

Figure 31. IRIG-B TOD BNC Output Connections

Screws (4 places)

1

Output 1 Output 2

3

Procedure F. IRIG-B TOD Output Installation

Step Procedure

1 Position the IRIG-B adapter onto the rear of the shelf so that the OPTIONS I/O wire-wrap pins project through holes in the adapter card.

2 Secure the adapter onto the shelf, using the four screws integral to the adapter

(see Figure 31).

3 To prevent small radius turns in the IRIG-B TOD output cables, secure the provided right-angle BNC connectors to the adapter BNC connectors, to direct the cables from the shelf as desired.

4 Connect the IRIG-B TOD outputs from the BNC connectors on the IRIG-B adapter to network elements requiring IRIG-B TOD timing.

End of Procedure