Operator’s Guide. McQuay MicroTech II
McQuay MicroTech II is an advanced rooftop unit controller designed to provide precise and efficient control of heating, ventilation, and air conditioning (HVAC) systems. With its user-friendly interface, flexible scheduling options, and comprehensive alarm monitoring capabilities, the MicroTech II empowers users to optimize comfort and energy efficiency in their buildings.
Advertisement
Advertisement
Operator’s Guide
The following “Operator’s Guide” sections provide information regarding the day-to-day operation of the MicroTech II
Applied Rooftop Unit Controller. Topics covered are such common tasks as scheduling, displaying and clearing alarms, and setting the controller for manual operation. Programmable parameters that affect the operation being described are listed at the beginning of each applicable sub-section. The factory default values for these parameters are shown in italic letters.
For detailed information regarding the control processes and
their programmable parameters, refer to “Description of
Determining Unit Status
The System menu includes several parameters that can be used to determine the overall status of the unit. There are five key items in this menu that summarize the current operating condition of the unit. These are: UnitStatus= , Clg
Capacity= , Htg Capacity= , Clg Status=, and Htg Status= and are described in the following sections.
UnitStatus
The UnitStatus= parameter in the System menu is very useful because the item summarizes the overall operating condition of the unit. Each of the possible conditions is referred to as an “operating state”. The following are the possible operating states displayed by the UnitStatus= parameter.
l l l l l l l l l l l l l l
Off
Calib
Startup
Recirc
Fan Only
Econo
Cooling
MWU
Heating
Min DAT
UnocEcon
UnocClg
UnocHtg
Man Ctrl
The unit makes transitions between these operating states as conditions change. For detailed information regarding these
states, refer to “Operating States and Sequences” on page 61.
Clg Capacity
Clg Capacity= is a status item which indicates the percentage of the unit maximum cooling capacity currently operating. When the unit is equipped with chilled water cooling, 0-
100% is displayed as the cooling valve actuator strokes from the closed to open position. When the unit is equipped with compressorized cooling, the percentage value changes incrementally based on the number operating cooling stages.
Htg Capacity
Htg Capacity= is a status item which indicates the percentage of the unit maximum heating capacity currently operating. When the unit is equipped with modulating heat, 0-
100% is displayed as the heating valve actuator strokes from the closed to open position. When the unit is equipped with staged heat, the percentage value changes incrementally based on the number operating heating stages
Clg Status
Clg Status= is a status item which indicates whether or not cooling (economizer and/or mechanical) is currently allowed. If cooling is disabled, the reason is indicated. The following are descriptions of the various “Clg Status” states.
All Clg
The Clg Status= parameter indicates “All Clg” when both of the following conditions are true:
1. The unit is equipped with an economizer and the outdoor air is suitable for free cooling ( OA Ambient= parameter in the OA Damper menu indicates “Low”).
2. The unit is equipped with chilled-water cooling or the unit is equipped with compressorized cooling and the outdoor air is warm enough to allow compressor operation ( OA Temp= parameter in the Temperatures menu has risen above the OATComp Lock= parameter by more that the OATLock Diff= setting in the Zone Cooling menu).
In this state the unit uses the economizer, mechanical cooling or both as required to maintain the cooling set points.
Econo
The Clg Status= parameter indicates “Econo” when both of the following conditions are true:
1. The unit is equipped with an economizer and the outdoor air is suitable for free cooling ( OA Ambient= parameter in the OA Damper menu indicates “Low”).
2. The unit is equipped with compressorized cooling and the outdoor air is too cool to allow compressor operation
( OA Temp= parameter in the Temperatures menu has dropped below the OATComp Lock= setting in the Zone
Cooling menu).
In this state the unit only uses the economizer to maintain the cooling set points. Compressor operation is disabled.
Mech Clg
The Clg Status= parameter indicates “Mech Clg” when both of the following conditions are true:
OM 138 43
1. The unit is not equipped with an economizer or the outdoor air is not suitable for free cooling ( OA Ambient= parameter in the OA Damper menu indicates “High”).
2. The unit is equipped with chilled-water cooling or the unit is equipped with compressorized cooling and the outdoor air is warm enough to allow compressor operation ( OA Temp= parameter in the Temperatures menu has risen above the OATComp Lock= parameter by more that the OATLock Diff= setting in the Zone Cooling menu).
In this state the unit uses mechanical cooling to maintain the cooling set points. Economizer operation is disabled, and the outdoor air damper is maintained at the Eff Min OA Pos= value.
Off Amb
The Clg Status= parameter indicates “Off Amb” when both of the following conditions are true:
1. The unit is not equipped with an economizer or outdoor air is not suitable for free cooling ( OA Ambient= parameter in the OA Damper menu indicates “High”).
2. The unit is equipped with compressorized cooling and the outdoor air is too cool to allow compressor operation
( OA Temp= in the Temperatures menu has dropped below the OATComp Lock= setting in the Zone Cooling menu).
In this state both economizer and mechanical cooling operation is disabled.
For applications that use an economizer, the “Off Amb” state should not occur if the economizer changeover and mechanical cooling lockout set points are adjusted properly. If it does occur, it may indicate a problem with the enthalpy control device.
Off Alm
The Clg Status= parameter indicates “Off Alm” when cooling related alarms cause all cooling circuits to be completely disabled and economizer operation is not available. For detailed information regarding cooling alarms and their
Off Sw
The Clg Status= parameter indicates “Off Sw” when the field cooling enable terminals 101 to 105 on terminal block
TB2 in the main control panel are not made (binary input
MCB-BI3 is off). Refer to the “Manual Cooling and Heating
Enable/Disable” section of IM 696, MicroTech Applied Rooftop Unit Controller . All cooling is disabled during the “Off
Sw” state.
Off Man
The Clg Status= parameter indicates “Off Man” when cooling is disabled via the Ctrl Mode= parameter in the System menu. This occurs when the Ctrl Mode= parameter is set to either “Heat Only” or “Fan Only.” All cooling is disabled during the “Off Man” state.
Off Net
The Clg Status= parameter indicates “Off Net” when cooling is disabled by a network signal affecting the Appl Mode= parameter in the System menu. This is the case when the
Appl Mode= parameter is set to either “Heat Only” or “Fan
Only.” All cooling is disabled during the “Off Net” state.
Off None
The Clg Status= parameter indicates “Off None” when the unit is equipped with no cooling of any kind.
Htg Status
Htg Status= is a status item which indicates whether or not heating is currently allowed. If heating is disabled, the reason is indicated. The following are descriptions of the various “Htg Status” states.
Htg Ena
The Htg Status= parameter indicates “Htg Ena” when the unit is equipped with some kind of heating and the outdoor air is cool enough to allow heating operation and heat is not disabled for some other reason. ( OA Temp= parameter in the
Temperatures menu has dropped below the OATHtg Lock= parameter by more that the OATLock Diff= setting in the
Zone Heating menu). In this state the unit uses the heat as required to maintain the heating set points.
Off Amb
The Htg Status= parameter indicates “Off Amb” when the unit is equipped with heat and the outdoor air is too warm to allow heating operation ( OA Temp= parameter in the Temperatures menu has risen above the OATHtg Lock= setting in the Zone Heating menu). In this state heating operation is disabled.
Off Alm
The Htg Status= parameter indicates “Off Alm” when heating related alarms cause all heating to be completely disabled. For detailed information regarding heating alarms and
Off Sw
The Htg Status= parameter indicates “Off Sw” when the field heating enable terminals 101 to 106 on terminal block
TB2 in the main control panel are not made (binary input
MCB-BI4 off). Refer to the “Manual Cooling and Heating
Enable/Disable” section of IM 696, MicroTech Applied Rooftop Unit Controller . Heating is disabled during the “Off Sw” state.
Off Man
The Htg Status= parameter indicates “Off Man” when heating is disabled via the Ctrl Mode= parameter in the System menu. This occurs when the Ctrl Mode= parameter is set to either “Cool Only” or “Fan Only.” Heating is disabled during the “Off Man” state.
44 OM 138
WARNING
Electric shock and moving machinery hazard. Can cause personal injury or death.
When the unit is in any Off operating state, power is not removed from the unit controller or components.
Remove power by turning off the disconnect-switch before servicing line voltage equipment or entering the unit.
Off Net
The Htg Status= parameter indicates “Off Net” when heating is disabled by a network signal affecting the Appl Mode= parameter in the System menu. This occurs when the Appl
Mode= parameter is set to either “Cool Only” or “Fan Only.”
Heating is disabled during the “Off Net” state.
Off None
The Htg Status= parameter indicates “Off None” when the unit is equipped with no heating.
Auto/Manual Operation
The System menus includes two parameters that determine whether cooling, heating, both cooling and heating or neither are enabled during unit operation. These are the Ctrl Mode= and Appl Mode= parameters. The Occupancy menu includes five parameters that relate to the occupied/unoccupied condition (start/stop) of the unit. These are the Occupancy= , Occ
Mode= , Occ Src= , Bypass Time= , and Emerg Override= parameters. These are described in the following sections.
Ctrl Mode
Table 10: Programmable Parameters
Keypad/Display ID
Menu Name
System
Item Name
Ctrl Mode= Auto
Parameter Name
Control Mode
Cool Only
When the Control Mode is set to “Cool Only”, cooling operation is allowed to operate to maintain the cooling set points.
Heating operation is disabled ( Htg Status= is “Off Man”).
Heat Only
When the Control Mode is set to “Heat Only”, heating operation is allowed to operate to maintain the heating set points.
Cooling operation is disabled ( Clg Status= is “Off Man”).
Fan Only
When the Control Mode is set to “Fan Only”, the fans are allowed to operate but cooling and heating operation is disabled ( Clg Status= and Htg Status= are “Off Man”).
Auto
When the Control Mode is set to “Auto”, the heat/cool, cool only, heat only, and fan only decision is determined by the
Appl Mode= parameter, which is set via a network signal as described below. The Appl Mode= parameter has no effect on unit operation unless the Control Mode is set to “Auto.”
Appl Mode
Table 11: Programmable Parameters
Keypad/Display ID
Menu Name
System
Item Name
Appl Mode= Heat/Cool
Parameter Name
Application Mode
The unit cooling and heating can be set up for automatic heat/cool, cool only, heat only, fan only, or network cool/heat operation by setting the Control Mode. The unit can also be manually disabled via the Control Mode. The following are descriptions of the six available Control Mode selections.
Off
When the Control Mode is set to “Off”, the UnitStatus= is
“Off Man” and the unit is completely disabled.
Heat Cool
When the Control Mode is set to “Heat/Cool”, both cooling and heating operation are allowed to operate as required to maintain the cooling and heating set points.
The unit heating and cooling can be set up for automatic heat/cool, heat only, cool only or fan only operation based on a network signal by setting the Ctrl Mode= parameter to
“Auto.” With the Ctrl Mode= parameter set to “Auto”, the heat/cool, cool only, heat only, and fan only decision is determined by the Application Mode. The Application Mode is set by a network signal. The following sections describe the five available Application Mode selections.
Note: The Application Mode has no effect on the unit operation unless the Ctrl Mode= parameter is set to
“Auto.”
Off
When the Application Mode is set to “Off”, the UnitStatus= is “Off Net” and the unit is completely disabled, including unoccupied heating (night set back) and unoccupied cooling
(night set up) operation.
OM 138 45
Heat/Cool
When the Application Mode is set to “Heat/Cool”, both cooling and heating operation are allowed to operate as required to maintain the cooling and heating set points.
Cool Only
When the Application Mode is set to “Cool Only”, cooling operation is allowed to operate as required to maintain the cooling set points. Heating operation is disabled ( Htg Status= is “Off Net”).
Heat Only
When the Application Mode is set to “Heat Only”, heating operation is allowed to operate as required to maintain the heating set points. Cooling operation is disabled ( Clg Status= is “Off Net”).
Fan Only
When the Application Mode is set to “Fan Only”, the fans are allowed to operate but cooling and heating operation is disabled ( Clg Status= and Htg Status= are “Off Net”).
Occupancy
Occupancy= is a status item which indicates whether the unit is in an occupied or unoccupied mode of operation. The following are descriptions of the various “Occupancy” states.
Occ
The Occupancy= parameter indicates “Occ” when the unit is in the occupied mode. In this mode, the unit generally starts and runs continuously, cooling and heating as required to maintain the occupied temperature set points.
1 The unit is in the occupied mode if any of the following conditions are true:
1. A field supplied external time clock or a tenant override switch signal in the form of a set of dry contacts is closed across terminals 101 and 102 on the unit field terminal block TB2 (binary input MCB-BI1 on). For detailed information refer to “External Time Clock or
Tenant Override (Non-Timed)” in IM 696, MicroTech
Applied Rooftop Unit Controller .
2. The Occ Mode= parameter is set to “Occ.”
3. The Occ Mode= parameter is set to “Auto” and the unit internal time clock schedule, optimal start function, one time event schedule, or an optional network schedule indicates an occupied period.
Unocc
The Occupancy= parameter indicates “Unocc” when the unit is in the unoccupied mode. In the unoccupied mode, the unit is off and remains off unless unoccupied cooling (night set up or purge) or unoccupied heating (night set back) opera-
1. The unit will not start regardless of the occupancy mode when the UnitStatus= parameter indicates “Off Sw”, “Man
Ctrl”, “Off Alm”, “Off Net”, or “Off Man”. For a description of
these operating states, refer to “Operating State Descriptions” on page 61.
tion is activated. Refer to “Unoccupied Control” on page 89.
The unit is in the unoccupied mode if all of the following conditions are true:
1. The Occ Mode= parameter is set to either “Unocc” or
“Auto” and any field supplied external time clock or a tenant override switch contacts are open across terminals 101 and 102 on the unit field terminal block (TB2).
For detailed information refer to “External Time Clock or Tenant Override (Non-Timed)” in IM 696, MicroTech
Applied Rooftop Unit Controller .
2. The Occ Mode= parameter is set to either “Unocc” or
“Auto” and the Bypass Time= parameter indicates 0 time.
3. The Occ Mode= parameter is not set to “Occ.”
4. The Occ Mode= parameter is set to “Auto” and the unit internal time clock schedule, optimal start function, one time event schedule, and optional network schedule all indicate an unoccupied period.
Note: The unit reverts to unoccupied mode if the calibrate function is active. For more information on cali-
brate mode, refer to “Calibrate Mode” on page 56
Bypass
The Occupancy= parameter indicates “Bypass” when the unit is in the bypass mode. In the bypass mode the unit starts
up and function as it does in occupied mode.
the bypass mode if the Bypass Time= parameter is set to a non-zero value. For details regarding how the Bypass Time=
is set, refer to “Bypass Time (Tenant Override)” on page 48
Occ Mode
Table 12: Programmable Parameters
Keypad/Display ID
Menu Name
Occupancy
Item Name
Occ Mode= Auto
Parameter Name
Occupancy Mode
The unit can be set up for automatic or manual occupied/unoccupied operation by setting the Occupancy Mode.
The following are descriptions of the four available Occupancy Mode selections.
Auto
When the Occupancy Mode is set to “Auto”, the unit operates automatically. This means that the Occupancy= parameter changes automatically between “Occ” and Unocc”. The
Occupancy= parameter indicates “Occ” and the unit starts if either the unit internal time clock schedule, optimal start function, one time event schedule, or an optional network schedule indicate an occupied period
Occupancy= parameter indicates “Unocc” and the unit stops if the unit internal time clock schedule, optimal start function, one time event schedule, and an optional network schedule all indicate an unoccupied period.
Exceptions:
46 OM 138
1. The Occupancy= parameter is “Occ” and the unit starts if a field supplied external time clock or a tenant override switch signal in the form of a set of dry contacts is closed across terminals 101 and 102 on the unit field terminal block TB2 (binary input MCB-BI1 on)
. For detailed information refer to “External Time Clock or
Tenant Override (Non-Timed)” in IM 696, MicroTech
Applied Rooftop Unit Controller .
2. The Occupancy= parameter indicates “Bypass” and the unit starts if the Bypass Time= parameter is set to a nonzero value
3. The Occupancy= parameter indicates “Unocc” and the unit stops if the Calibrate function is activated. Refer to
4. While the Occupancy= parameter indicates “Unocc”, the unit can start and operate in the unoccupied heating
(night set back) or the unoccupied cooling (night set up
. Refer to “Unoccupied Control” on page 89.
Occ
When the Occupancy Mode is set to “Occ”, the Occupancy= parameter indicates “Occ” and the unit starts and runs con-
tinuously in the occupied mode 1 . Any scheduling commands
are prevented from shutting down the unit.
Exception :
1. The Occupancy= parameter indicates “Unocc” and the unit stops if the Calibrate function is activated. Refer to
Unocc
When the Occupancy Mode is set to “Unocc”, the Occupancy= parameter indicates “Unocc” and the unit is off and remains off unless unoccupied cooling (night set up or purge) or unoccupied heating (night set back) operation is
activated. Refer to “Unoccupied Control” on page 89 1
.
Exceptions:
1. The Occupancy= parameter changes to “Occ” and the unit starts if a field supplied external time clock or a tenant override switch signal in the form of a set of dry contacts is closed across terminals 101 and 102 on the unit field terminal block TB2 (binary input MCB-BI1 on)
1 . For detailed information refer to “External Time
Clock or Tenant Override (Non-Timed)” in IM 696,
MicroTech Applied Rooftop Unit Controller .
2. The Occupancy= parameter changes to “Bypass” and the unit starts if the Bypass Time= parameter is set to a non-zero value
1. The unit will not start regardless of the occupancy mode when the UnitStatus= parameter indicates “Off Sw”, “Man
Ctrl”, “Off Alm”, “Off Net”, or “Off Man”. For a description of
these operating states, refer to “Operating State Descriptions” on page 61.
Bypass
When the Occupancy Mode is set to “Bypass”, the Bypass
Time= parameter is set to the Bypass Time Increment= value.
The Occupancy= parameter indicates “Bypass” and the unit starts and operates as in the occupied mode until the Bypass
Time= parameter times out. Any scheduling commands are prevented from shutting down the unit while the bypass operation is active.
Note: Once the Occupancy Mode is set to “Bypass” and the Bypass Time= parameter is set to the Bypass
Time Increment= value, the Occupancy Mode automatically reverts to the “Auto” setting.
Exception:
1. The Occupancy= parameter indicates “Unocc” and the unit stops if the Calibrate function is activated. Refer to
Occ Src
Occ Src= is a status item which indicates the input source or function that is responsible for setting the Occupancy= parameter to “Occ.” There are a number of things that can change the Occupancy= parameter to “Occ” and the Occ
Src= parameter is very helpful in determining which function has started the unit.
None
The Occ Src= parameter indicates “None” when the Occupancy= parameter indicates “Unocc” or “Bypass.”
Int Sched
The Occ Src= parameter indicates “Int Sched” when the
Occupancy= parameter indicates “Occ” due to the unit internal schedule or one event schedule indicating an occupied period. Refer to “Scheduling” on page 48.
Net Sched
The Occ Src= parameter indicates “Net Sched” when the
Occupancy= parameter indicates “Occ” due to a network schedule indicating an occupied period.
Occ Mode
The Occ Src= parameter indicates “Occ Mode” when the
Occupancy= parameter indicates “Occ” due to the Occupancy Mode being manually set to “Occ.”
Remote Sw
The Occ Src= parameter indicates “Remote Sw” when the
Occupancy= parameter indicates “Occ” due to a field supplied external time clock or a tenant override switch signal in the form of a set of dry contacts is closed across terminals
101 and 102 on the unit field terminal block TB2 (binary input MCB-BI1 on). For detailed information refer to
“External Time Clock or Tenant Override (Non-Timed)” in
IM 696, MicroTech Applied Rooftop Unit Controller .
OM 138 47
Bypass Time (Tenant Override)
Table 13: Programmable Parameters
Keypad/Display ID
Menu Name
Occupancy
Timer Settings
Item Name
Occ Mode= Auto
Bypass Time= 0 min
Bypass= 120 min
Parameter Name
Occupancy Mode
Bypass Timer
Bypass Time Increment
There are two types of tenant override functions: timed and non-timed. Timed override uses the Bypass Timer and
Bypass Time Increment to place the unit into bypass mode.
Non-timed override uses a simple field supplied SPST switch to override unoccupied operation.
Timed Tenant Override
The tenant-override button provided with the optional zone temperature sensor packages is used to override unoccupied operation for a preprogrammed time period. This time period is set with the Bypass Time Increment. This value can be adjusted from 0 to 300 minutes (default is 120 minutes).
When an occupant presses and releases the tenant-override button on the zone temperature sensor (ZNT1), the Bypass
Timer is set equal to the Bypass Time Increment. (The button must be held for at least 1 second but not more than 30 seconds.) The unit then starts and runs in the bypass mode which is the same as occupied mode except that it is temporary.
1 The Bypass Timer begins timing out and the unit runs until the timer expires. If the tenant override button is pressed again while the unit is operating in bypass mode, the
Bypass Timer is reset to the Bypass Time Increment and the unit continues to operate. For example, assume that the
Bypass Time Increment is 120 minutes. One press of the override button provides at 120 minutes of unit operation. If the button is pressed again 60 minutes later, the Bypass
Timer is reset to 120 minutes, and a total of 180 minutes of uninterrupted operation results.
Note: The same operation occurs if, instead of pressing the override button on a zone temperature sensor, the Occupancy Mode is set to “Bypass.” Once set to
“Bypass”, the Occupancy Mode automatically reverts to the “Auto” setting once the Bypass Timer is set to the Bypass Time Increment.
Non-Timed Tenant Override
If an field supplied external time clock or a tenant override switch signal in the form of a set of dry contacts is closed across terminals 101 and 102 on the unit field terminal block
TB2 (binary input MCB-BI1 on), the unit is placed into occupied mode
. When this switch is open, the unit is con-
1. The unit will not start regardless of the occupancy mode when the UnitStatus= parameter indicates “Off Sw”, “Man
Ctrl”, “Off Alm”, “Off Net”, or “Off Man”. For a description of
these operating states, refer to “Operating State Descriptions” on page 61.
trolled by any active scheduling function (internal time clock schedule, optimal start function, one time event schedule, or an optional network schedule). If there is no active scheduling function, the unit remains in the unoccupied mode. For detailed information refer to “External Time Clock or Tenant
Override (Non-Timed)” in IM 696, MicroTech Applied Rooftop Unit Controller .
Operator Override
The Bypass Timer can be manually set. When the Bypass
Timer is set to a non-zero value, the unit starts and runs in
the bypass mode regardless of any scheduling features.
unit stops when the timer expires. The Bypass Timer can be set from 0-300 minutes.
Note: If the Bypass Timer remaining time is larger than the Bypass Time Increment, pressing the tenant override button on the space sensor has no effect. If the Bypass Timer remaining time is less than the
Bypass Time Increment, pressing the tenant override button resets the Bypass Timer to the Bypass
Time Increment value.
Emergency Override
Table 14: Programmable Parameters
Keypad/Display ID
Menu Name Item Name
Parameter Name
Occupancy Emerg Override= Norm
Emergency Override Mode
Flag
The unit can be shutdown by setting the Emergency Override Mode Flag. When the Emergency Override Mode Flag is set to “Off”, the UnitStatus= parameter indicates “Off
Net” and the unit remains off regardless of any time schedule or other occupied or unoccupied start commands. The only way a unit can be restarted is to set Emergency Override
Mode Flag back to “Norm.” The Emergency Override Mode
Flag can either be set manually at the unit keypad or via a network signal.
Scheduling
The rooftop unit can be scheduled for operation by using the following three methods:
1) Unit internal time scheduling functions
2) External time clock function
3) Network time scheduling function
Provided the unit is not locally or remotely disabled, the unit operates when any of these scheduling functions is calling for occupied operation. Conversely, the unit enters the unoccupied mode when all of these scheduling functions are calling for unoccupied operation. Therefore, any unused scheduling functions should be set for continuous unoccu-
pied operation. Refer also to“Auto/Manual Operation” on page 45.
48 OM 138
The next four sections: “Setting Controller Date and Time”,
“Internal Daily Scheduling”, “Holiday Scheduling”, and One
Event Scheduling” describe functions related to the internal unit scheduling functions. These are followed by a section describing the optimal start function which can be use with internal scheduling and network scheduling. This is followed by two sections that describe the external time scheduling and network time scheduling functions.
Setting Controller Date and Time
Table 15: Programmable Parameters
Keypad/Display ID
Menu Name
Time/Date
Item Name
Time= hh:mm:ss
Day= ddd
Date= dd-mm-yyyy
Parameter Name
Current Time
Current Day
Current Date
The MicroTech II controller uses the date and time to execute its internal scheduling functions. Once set, the battery backed internal time clock keeps the current time regardless of whether or not power is being supplied to the unit.
The time of day can be set by entering the hour (00-23), minute (00-59), and second (00-59) into three fields of the
Current Time. Note that MicroTech II uses “military” time.
The day of the week is not adjustable. The Current Day is set automatically by the controller based on the Current Date.
The current date can be set by entering the date (00-31), month (01-12) and year (1999-2155) into the three fields of the Current Date.
Internal Daily Scheduling
Table 16: Programmable Parameters
Keypad/Display ID
Menu Name
Daily Schedule
Item Name
Mon= 00:00 - 00:00
Tue= 00:00 - 00:00
Wed= 00:00 - 00:00
Thu= 00:00 - 00:00
Fri= 00:00 - 00:00
Sat= 00:00 - 00:00
Sun= 00:00 - 00:00
Hol= 00:00 - 00:00
Parameter Name
Monday Schedule
Tuesday Schedule
Wednesday Schedule
Thursday Schedule
Friday Schedule
Saturday Schedule
Sunday Schedule
Holiday Schedule
When the Occ Mode=
parameter, described in “Auto/Manual Operation” on page 45, is set to “Auto”, and the unit is
not disabled for other reasons, it starts and stops according to the controller internal schedule. One start and one stop time can be set for each day of the week and for designated holidays. An example of how to use the keypad to enter or mod-
ify a schedule is given in “Getting Started” on page 6.
As shown in Figure 5, each daily schedule has four adjust-
able fields: Start Hour, Start Minute, Stop Hour, and Stop
Minute. The schedule shown would cause the unit to start up at 6:30 a.m. and shut down at 6:00 p.m. every Monday, Tuesday and Wednesday.
Figure 5: Daily Schedule Fields
Menu Line
Item Line Being Edited
**Edit Mode
Mon= 06:30 - 18:00
Tue= 06:30 - 18:00
Wed= 06:30 - 18:00
Stop Minute
Stop Hour
Start Minute
Start Hour
For continuous unit operation, the schedule fields can be set to “00:00-23:59.” For no unit operation for the entire day, the schedule fields can be set to “00:00-00:00” (this is the default setting).
Holiday Scheduling
Table 17: Programmable Parameters
Keypad/Display ID
Menu Name Item Name
Daily Schedule Holiday= 00:00 - 00:00
Holiday Schedule Hol *= mmm dt - mmm dt
Parameter Name
Holiday Schedule
Holiday Period
Special operating hours can be scheduled for up to 16 holiday periods during the year by using the holiday scheduling feature. (The wildcard character “*” in the above table could be any number between 1 and 16.) Whenever a holiday period occurs, the controller uses the Holiday Schedule start and stop time for the period. For example, assume that
Christmas Eve occurs on a Thursday. The building is shut down on both Christmas Eve and Christmas Day, but operates normally on the weekend. This holiday period would be scheduled by setting the Holiday Schedule to “00:00-00:00” and setting the Holiday Period to “Dec 24 - Dec 25.”
If any of the 16 holiday periods are not required, the Holiday
Period is set to “N/A - N/A.”
One Event Scheduling
Table 18: Programmable Parameters
Keypad/Display ID
Menu Name Item Name
Parameter Name
One Event
Beg= mmm dd @ hh:mm
End= mmm dd @ hh:mm
One Event Beginning
Date/Time
One Event Ending
Date/Time
The unit can be scheduled to operate during a specified period by using the one event scheduling feature. During the specified period defined by the One Event Beginning
OM 138 49
Date/Time and One Event Ending Date/Time parameters the unit starts up and runs continuously regardless of any other time scheduling functions. For example, assume that a space served by the unit is occupied for a special event on March
12 from 5:00 p.m. to 10:00 p.m. when the normal time scheduling has the unit shut off after 4:00 p.m. on that date.
This event can be accounted for by setting the One Event
Beginning Date/Time to “Mar 12 @ 17:00” and the One
Event Ending Date/Time to “Mar 12 @ 22:00.” If a oneevent schedule is not required, the One Event Beginning
Date/Time and One Event Ending Date/Time parameters are both set to “N/A.”
Optimal Start
The optimal start function can only be used with the unit internal time schedule or a network supplied time schedule that indicates “time-to-occupancy”. When the Optimal Start
Flag is set to “Yes”, the controller calculates an early start time before each normally scheduled start. The controller uses the start history, outdoor air temperature, and space temperature to determine when the unit should start. The unit may be started by the optimal start function up to four hours before the scheduled start time.
If the Ctrl Temp= parameter, which is the temperature input selected by the CtrlTemp Src= parameter, is below the Effective Heating Enable Set Point by more than half the Heating
Enable Deadband setting, optimal start operation is based on the optimal start heating parameters. If the Ctrl Temp= value is above the Effective Cooling Enable Set Point by more than half Cooling Enable Deadband setting, optimal start operation is based on the optimal start cooling parameters.
Unit startup occurs at the scheduled start time if the Ctrl
Temp= value is in between these limits.
Table 19: Programmable Parameter
Menu Name
Zone Cooling
Zone Heating
Optimal Start
Keypad/Display ID
Item Name
Eff Clg Spt= 75.0 ºF
Clg Deadband= 1.0 ºF
Eff Htg Spt= 75.0 ºF
Htg Deadband= 1.0 ºF
Optimal Start= No
Auto Update= Yes
Htg Rate= 0.4 ºF/min
Htg OAT= 35.0 ºF
Htg Zero OAT = 0 ºF
Clg Rate= 0.4 ºF/min
Clg OAT= 85.0 ºF
Clg Zero OAT= 100 º F
Parameter Name
Effective Cooling Enable Set Point
Cooling Enable Deadband
Effective Heating Enable Set Point
Heating Enable Deadband
Optimal Start Flag
Automatic Update Flag
Heating Rate
Heating Outdoor Air Temperature
Heating Outdoor Air Temperature Zero
Cooling Rate
Cooling Outdoor Air Temperature
Cooling Outdoor Air Temperature Zero
When heating is required, a “heating rate” that varies with the outdoor air temperature is calculated using the formula:
Calculated Heating Rate = Heating Rate ×
The minutes before occupancy are calculated based on the following formula:
Minutes Before Occupancy =
Calculated Heating Rate
When cooling is required, a “cooling rate” that varies with the outdoor air temperature is calculated using the formula:
Calculated Cooling Rate = Cooling Rate ×
The minutes before occupancy are on the following formula:
Minutes Before Occupancy =
If the Automatic Update Flag is set to “Yes”, the controller revises the optimal start parameters after each start in which
Calculated Cooling Rate they are used and the temperature change is significant.
50 OM 138
External Time Scheduling
An external time clock can be used to schedule unit operation. This is accomplished by a field supplied external time clock signal in the form of a set of dry contacts wired across terminals 101 and 102 on the unit field terminal block TB2
(binary input MCB-BI1). In this case, all internal daily schedules should be set to “00:00-00:00” (default setting).
For details on how to connect an external time clock, refer to
“Field Wiring” in IM 696, MicroTech Applied Rooftop Unit
Controller .
Network Time Scheduling
A network time schedule can be used to operate the unit. In this case, all internal daily schedules should be set to “00:00-
00:00” (default setting). Scheduling a unit via a network signal is supported through optional communication modules
(Ethernet-BACnet, MSTP-BACnet and LonWorks).
Alarm Monitoring
About Alarms
The MicroTech II Applied Rooftop Unit Controller is programmed to monitor the unit for alarm conditions. Alarm conditions are categorized in three types: “faults”, “problems”, and “warnings.” In general, “faults” are more serious than “problems” and “problems” more serious that “warnings.” Therefore, “faults” are assigned a higher priority than
“problems” and “problems” a higher priority than “warnings.” Within the three types, the alarms are prioritized.
Some alarms require manual clearing and some are cleared
automatically. Table 20 summarizes all alarms, listing them
by type and priority, and listing the required clearing method.
If an alarm condition occurs, the controller displays a message and executes the appropriate action to make the unit fail-safe. The controller displays a local message on the unit keypad/display and a remote indication on a Remote Alarm
Output (binary output MCB-BO4) wired to terminals for
field connection. For the meaning of each alarm, see “Alarm
Table 20: Unit Alarms
Alarm Type
Fault
Alarm Message
Freeze
Smoke
Space Sensor
Return Sensor
Disch Sensor
Hi Return Tmp
Hi Disch Tmp
Lo Disch Tmp
Fan Fail
OA Dmpr Stuck
Indication
Freezestat condition while SAF on
Smoke detected by SAF and/or RAF smoke detector
Space temp sensor failure when CtrlTemp Src= parameter is set to “Space”
RAT sensor failure
DAT sensor failure
RAT exceeded the Hi Return Tmp setting
DAT exceeded the Hi Disch Tmp setting
DAT fell below the Lo Disch Tmp setting
Airflow not sensed by PC7 after SAF was started
OA Dampers < 50% open after Startup (100% OA units only)
Alarm Reset
Manual
Manual a
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
OM 138 51
Table 20: Unit Alarms (Continued)
Alarm Type
Problem
Warning
Alarm Message
Freeze
OAT Sensor
Space Sensor
Return Sensor
Ent Fan Sensor
Lo Airflow
Heat Fail
Hi Pres-Ckt1
Hi Pres-Ckt2
Lo Pres-Ckt1
Lo Pres-Ckt2
Frost-Ckt1 d
Comp #1 Alm
Comp #2 Alm
Comp #3 Alm
Comp #4 Alm
PumpDown-Ckt1 LP1 still closed 180 seconds into ckt #1 pumpdown operation
PumpDown-Ckt2 LP2 still closed 180 seconds into ckt #2 pumpdown operation
Ckt1 Clg Ena
Ckt2 Clg Ena
Clg enable input to CCB1 off when cooling was on
Clg enable input to CCB2 off when cooling was on
GenC Clg Ena
HtgB Htg Ena
Clg enable input to CCB1 off when cooling was on
Htg enable input to EHB1 off when heating was on
Ckt1 Comm Fail Comm failure occurred between MCB and CCB1
Ckt2 Comm Fail Comm failure occurred between MCB and CCB2
GenC Comm Fail Comm failure occurred between MCB and CCB1
HtgB Comm Fail Comm failure occurred between MCB and EHB1
ERecB Comm Fail Comm failure occurred between MCB and ERB1
OA Dmpr Stuck
OA dampers not at 0% when unit off or not at 100% during mechanical cooling while
OA Ambient= parameter indicates “Low”
Airflow Switch
Dirty Filter
Dirty FnlFltr
Ckt1 H/W
Ckt2 H/W
GenC H/W
HtgB H/W
Freezestat tripped while SAF was off
OAT sensor failure when CtrlTemp Src= parameter not set to “OAT”
Space temp sensor failure on unit with RAT sensor
RAT sensor failure CtrlTemp Src= parameter not set to “Return”
EFT sensor failure
Excessive temperature rise sensed across heat section on single stage heat unit
Gas furnace safety lockout condition occurred
HP1 or HP3 open indicating ckt # 1 high refrigerant pressure
HP2 or HP4 open indicating ckt # 2 high refrigerant pressure
LP1 remained opened after ckt #1 solenoid valve open
LP2 remained opened after ckt #2 solenoid valve open
Evaporator coil frost condition occurred on ckt #1
Evaporator coil frost condition occurred on ckt #2
Comp #1 off on low oil pressure (OP1) or motor protector (MP1)
Comp #2 off on low oil pressure (OP2) or motor protector (MP2)
Comp #3 off on low oil pressure (OP3) or motor protector (MP3)
Comp #4 off on low oil pressure (OP4) or motor protector (MP4)
PC7 sensed airflow when unit was off
Indication
Pressure drop across first filter section exceeded the setting of PC5
Pressure drop across final filter section exceeded the setting of PC6
Clg enable input to CCB1 on when cooling off
Clg enable input to CCB2 on when cooling off
Clg enable input to CCB1 on when cooling off
Htg enable input to EHB1 on when heating off
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual a.
The SAF and RAF smoke detectors must be manually reset after tripping. This can be accomplish be cycling control system power (S1 Switch).
b.
A manual reset of the flame safeguard control FSG is required before the Heat Fail problem clears.
c.
Manual clearing is required if this alarm occurs three times within a 24-hour period (2:00 a.m. of one day until 2:00 a.m. of the next). The oil pressure safety devices require a manual reset on the device.
d.
Not applicable on units equipped with hot gas bypass.
Alarm Reset
Automatic
Automatic
Automatic
Automatic
Automatic
Manual
Automatic b
Manual
Manual
Automatic c
Manual
Manual
Manual
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Remote Alarm Indication
The MicroTech II control system includes a Remote Alarm
Output (MCB-B04) to provide remote indication of alarm conditions. Under normal (no active alarm) conditions, the
Remote Alarm Output (MCB-B04) is closed. The LED associated with the alarm output indicates the state of the output:
On indicates MCB-B04 is closed, and off indicates MCB-
B04 is open. The Remote Alarm Output can be connected to some type of field-supplied annunciator. If an alarm occurs, the Remote Alarm Output condition changes to either an
“off” or “blinking” state. Each possible alarm condition can be set up to cause the output to either blink rapidly, blink slowly, turn off or remain on (no remote indication of the
alarm). Refer to “Configuring Remote Alarm Output” on page 54.
Note: If there are multiple active alarms, only the highest priority alarm affects this output. This is always the alarm indicated by the Active Alarm 1 menu. Refer to “Remote Alarm Output” in the “Field Wiring” section of IM 696, MicroTech Applied Rooftop Unit
Controller .
52 OM 138
Figure 6: Active and Previous Alarm Menu Display
Menu Line
Alarm Name Item Line
Alarm Type Item Line
Alarm Date/Time Item Line
Active Alarm 1
Dirty Filter
Warning-Active
12-Mar-00 04:50:49
Previous Alarm 1
Dirty Filter
Warning-Clear
12-Mar-00 05:15:34
Local Alarm Indication (Keypad/Display)
Alarm information is provided via the unit keypad/display by four “active” and eight “previous” alarm menus.
Up to four active alarms are displayed in the Active Alarm 1,
Active Alarm 2, Active Alarm 3, and Active Alarm 4 menus.
The highest priority active alarm is displayed in the Active
Alarm 1 menu, the second highest priority active alarm in the Active Alarm 2, the third highest priority active alarm in the Active Alarm 3 and the forth highest priority active alarm in the Active Alarm 4 menu. If it happens that there are more than four active alarms, the additional alarms do not appear until one of these four active alarms are cleared.
When an active alarm is cleared the remaining active alarms are resorted such that the highest priority active alarm remaining is displayed in Active Alarm 1, the second highest priority active alarm remaining is displayed in Active Alarm
2 and so forth. Figure 6 shows the typical display of an
active alarm menu. The first line of the display is the menu line, the second line indicates the alarm name, the third line indicates the alarm “type” (fault, problem, or warning) and the forth line indicates the date and time the alarm occurred.
Whenever there is an active alarm, a red alarm LED on the unit keypad turns on. If there are no active alarms, this LED remains off.
When an active alarm is cleared, it is stored in the Previous
Alarm 1 menu. Any alarm that might be in the Previous
Alarm 1 menu is moved to the Previous Alarm 2 menu, any alarm that might be in the Previous Alarm 2 menu is moved to the Previous Alarm 3 menu and so forth. Any alarm that might be in the Previous Alarm 8 menu is permanently
remove from the keypad. Figure 6 shows a typical display of
a previous alarm menu. The first line of the display is the menu line, the second line indicates the alarm name, the third line indicates the alarm “type” (fault, problem, or warning) and the forth line indicates the date and time the alarm occurred.
Displaying Alarms
Active Alarms. When an active alarm exists the red LED on the keypad is on. The active alarm or alarms can be viewed as follows:
1. Pressing the Alarm key while the red LED on the keypad is on changes the display to the Active Alarm 1 menu.
2. Pressing the Right Arrow key changes the display to the
Active Alarm 2 menu. Pressing the Right Arrow key again changes the display to the Active Alarm 3 menu.
Pressing the Right Arrow key again changes the display to the Active Alarm 4 menu.
3. Pressing the Left Arrow key changes the display back to the Active Alarm 3 menu. Repeating this key two more times changes the display back to the Active Alarm 1 menu.
Previous Alarm. When active alarms are cleared, they are stored in the previous alarm menus. The previous alarm menus can be viewed as follows:
1. Pressing the Back/Cancel key changes the display to back to the main menu if not already there.
2. Assuming the blinking cursor is positioned on the System Summary menu, pressing the Down Arrow (-) key six times changes the cursor position to the Previous
Alarms menu.
3. Pressing the Enter/Save key changes the display to the
Previous Alarm 1 menu.
4. Pressing the Right Arrow key changes the display to the
Previous Alarm 2 menu. Pressing the Right Arrow key again changes the display to the Previous Alarm 3
OM 138 53
menu. Pressing the Right Arrow key five more times changes the display to the Previous Alarm 8 menu.
5. Pressing the Left Arrow key changes the display back to the Active Alarm 7 menu. Repeating this six more times changes the display back to the Previous Alarm 1 menu.
Clearing Alarms. Before any active alarm is cleared, the alarm conditions that caused it must have returned to normal.
When the alarm conditions are no longer present, an active alarm may be cleared either automatically or manually.
Note: Some of the safety devices that detect alarm condition require a manual reset at the device before the
alarm can be cleared. Refer to Table 20 on page 51
for listing of possible alarms and to determine whether an alarm is manual or automatic reset.
An automatic reset active alarm immediately clears when the alarm conditions that caused it disappear. A manual reset active alarm is cleared using the keypad/display as follows.
1. The active alarm to be cleared is first displayed. Refer to
“Displaying Alarms” on page 53.
controller. This clears the active alarm and returns the unit to normal operation if no other alarms are active.
Remote Alarm Clearing
Although it is always recommended that active alarms be cleared at the unit via the keypad/display, there are other methods that effectively clear active alarms. Three such methods are described in the following sections.
Unit System Switch (S1)
Cycling the main controller system switch (S1) located in the unit main control panel has the effect of clearing the active alarm menus. The disadvantage of clearing alarms in this manor is that the active alarm data is not placed into the previous alarm buffer and alarm information is lost.
Note: Turning off the unit power disconnect switch has the same effect.
Manual Unit Enable/Disable Input
Disabling the unit via the manual unit enable/disable input
(this occurs when a field supplied and installed switch across terminals 101 and 104 on the unit field terminal block (TB2) is changed from the on (closed) to off (open) position. Refer to the “Manual Unit Enable/Disable” section of IM 696,
MicroTech Applied Rooftop Unit Controller .
Network Signal
The active alarms can be cleared via a network signal through optional communication modules (including Ethernet-BACnet, MSTP-BACnet and LonWorks).
Configuring Remote Alarm Output
2. Pressing the Clear Alarm key while the active alarm to be cleared is in the display sends a clear command to the
Table 21: Programmable Parameters
Keypad/Display ID
Menu Name
Alarm Out Faults
Item Name
Freeze= Fast
Smoke= Fast
Space Sensor= Fast
Return Sensor= Fast
Disch Sensor= Fast
Hi Return Tmp= Fast
Hi Disch Tmp= Fast
Lo Disch Tmp= Fast
Fan Fail= Fast
OA Dmpr Stuck= Fast
Parameter Name
Freeze Fault Remote Output Setup
Smoke Fault Remote Output Setup
Space Sensor Fault Remote Output Setup
Return Sensor Fault Remote Output Setup
Disch Sensor Fault Remote Output Setup
Hi Return Tmp Fault Remote Output Setup
Hi Disch Tmp Fault Remote Output Setup
Lo Disch Tmp Fault Remote Output Setup
Fan Fail Fault Remote Output Setup
OA Dmpr Stuck Fault Remote Output Setup
54 OM 138
Table 21: Programmable Parameters (Continued)
Keypad/Display ID
Menu Name
Alarm Out Problems
Alarm Out Warnings
Parameter Name
Item Name
Freeze= Slow
OAT Sensor= Slow
Space Sensor= Slow
Return Sensor= Slow
Ent Fan Sensor= Slow
Lo Airflow= Slow
Heat Fail= Slow
Hi Pres-Ckt1= Slow
Hi Pres-Ckt2= Slow
Lo Pres-Ckt1= Slow
Lo Pres-Ckt2= Slow
Frost-Ckt1= Slow
Frost-Ckt2= Slow
Comp #1 Alm= Slow
Comp #2 Alm= Slow
Comp #3 Alm= Slow
Freeze Problem Remote Output Setup
OAT Sensor Problem Remote Output Setup
Space Sensor Problem Remote Output Setup
Return Sensor Problem Remote Output Setup
Ent Fan Sensor Problem Remote Output Setup
Lo Airflow Problem Remote Output Setup
Heat Fail Problem Remote Output Setup
Hi Pres-Ckt1 Problem Remote Output Setup
Hi Pres-Ckt2 Problem Remote Output Setup
Lo Pres-Ckt1 Problem Remote Output Setup
Lo Pres-Ckt2 Problem Remote Output Setup
Frost-Ckt1 Problem Remote Output Setup
Frost-Ckt2 Problem Remote Output Setup
Comp #1 Alm Problem Remote Output Setup
Comp #2 Alm Problem Remote Output Setup
Comp #3 Alm Problem Remote Output Setup
Comp #4 Alm= Slow
PumpDown-Ckt1= Slow
PumpDown-Ckt2= Slow
Ckt1 Clg Ena= Slow
Ckt2 Clg Ena= Slow
GenC Clg Ena= Slow
HtgB Htg Ena= Slow
Ckt1 Comm Fail= Slow
Comp #4 Alm Problem Remote Output Setup
PumpDown-Ckt1 Problem Remote Output Setup
PumpDown-Ckt2 Problem Remote Output Setup
Ckt1 Clg Ena Problem Remote Output Setup
Ckt2 Clg Ena Problem Remote Output Setup
GenC Clg Ena Problem Remote Output Setup
HtgB Htg Ena Problem Remote Output Setup
Ckt1 Comm Fail Problem Remote Output Setup
Ckt2 Comm Fail= Slow Ckt2 Comm Fail Problem Remote Output Setup
GenC Comm Fail= Slow GenC Comm Fail Problem Remote Output Setup
HtgB Comm Fail= Slow HtgB Comm Fail Problem Remote Output Setup
ERecB Comm Fail= Slow ERecB Comm Fail Problem Remote Output Setup
OA Dmpr Stuck= Off
Airflow Switch= Off
Dirty Filter= Off
Dirty FnlFltr= Off
OA Dmpr Stuck Warning Remote Output Setup
Airflow Switch Warning Remote Output Setup
Dirty Filter Warning Remote Output Setup
Dirty FnlFltr Warning Remote Output Setup
Ckt1 H/W= Off
Ckt2 H/W= Off
GenC H/W= Off
HtgB H/W= Off
Ckt1 H/W Warning Remote Output Setup
Ckt2 H/W Warning Remote Output Setup
GenC H/W Warning Remote Output Setup
HtgB H/W Warning Remote Output Setup
Each possible alarm condition can be configured to cause the
Remote Alarm Output (MCB-B04) to blink rapidly, blink slowly, turn off, or remain on (no remote indication of the alarm). This allows the action of the Remote Alarm Output to be “tailored” according to the specific requirements of the application. When there are no active alarms within the controller the Remote Alarm Output is “on” continuously. If an alarm output setup parameter is set to “Slow”, the Remote
Alarm Output cycles on and off at a slow rate when the alarm occurs. If an alarm output setup parameter is set to
“Fast”, the Remote Alarm Output cycles on and off at a rapid rate when the alarm occurs. If an alarm output setup parameter is set to “Off”, the Remote Alarm Output turns off when the alarm occurs. If an alarm output setup parameter is set to
“On”, the Remote Alarm Output remains on when the alarm occurs.
For example, it may be necessary that only alarms that shut a unit off completely (faults) be indicated remotely. In this case all of the “fault” alarms are set to “Slow”, “Fast” or
“Off.” All others are set to “On.”
Refer to “Remote Alarm Output” in the “Field Wiring” section of IM 696, MicroTech Applied Rooftop Unit Controller .
OM 138 55
Setting Alarm Limits
Table 22: Programmable Parameters
Keypad/Display ID
Menu Name Item Name
Alarm Limits
Parameter Name
Hi Disch Alm= 170 ºF
Lo Disch Alm= 40 ºF
Hi Return Alm= 120 ºF
High Discharge Air Temperature Alarm Limit
Lo Discharge Air Temperature Alarm Limit
High Return Air Temperature Alarm Limit
Three of the alarm faults have adjustable limits that are used to trigger the alarm. These are the Hi Disch Tmp, Lo Disch
Tmp and Hi Return Tmp faults. Although the default settings should be suitable for most applications, the alarm limits can be set as necessary via the unit keypad/display. The default settings are shown in the table above.
Unit Configuration/Service
Parameters
Calibrate Mode
Table 23: Programmable Parameters
Keypad/Display ID
Parameter Name
Menu Name Item Name
Unit Configuration Calibrate Mode= No Calibrate Mode Flag
Calibrate Mode is a special service mode used to calibrate control actuator feedback signals and to zero static pressure sensor inputs. When the Calibrate Mode Flag is set to “Yes”, the position feedback potentiometers on the outdoor air damper, return or exhaust fan inlet vane, modulating cooling valve and modulating heating valve actuators are automatically calibrated. Any unit static pressure transducers are also calibrated (or zeroed). The following is a description of the
Calibrate Mode procedure.
When the Calibrate Mode Flag is set to “Yes”, the Occupancy= parameter is overridden and is set to “Unocc” and accordingly the unit shuts off. When the unit is off the outdoor air dampers, return or exhaust vanes, modulating cooling valve, and modulating heating valve actuators are driven to the 100% open position for three minutes. After three minutes, the controller records the analog input feedback values from the actuators as equivalent to their fully open positions. The controller then drives the actuators to the opposite or fully “closed” position for three minutes. After three minutes, the controller records the analog input feedback values from the actuators as equivalent to their fully closed positions. The controller also records the analog input voltage signals from all connected pressure transducers as equivalent to 0 “W.C.
Note: It is best to calibrate the unit with all the sensing tubing to the static pressure sensors disconnected.
This assures that the sensors are truly seeing 0 “WC when calibrated.
After the Calibrate Mode procedure is complete, the Ctrl
Mode= parameter is set to “Off” which means the unit remains off until the Ctrl Mode= parameter is set to some-
thing other than “Off” as described in “Auto/Manual Operation” on page 45
Note: If the Calibrate Mode Flag is set to “Yes” while the
Manual Control= parameter in the Manual Control menu is set to “Yes”, the Manual Control= parameter reverts to “No.”
Zone (Space) Temperature Sensor
Table 24: Programmable Parameters
Keypad/Display ID
Menu Name Item Name
Parameter Name
Unit Configuration Space Sensor= Yes
Space Sensor
Present Flag
An optional zone (space) temperature sensor can be installed in the field and wired to the unit. When the optional sensor is installed, the Space Sensor Present Flag should be set to
“Yes.” When the optional sensor is not installed, the Space
Sensor Present Flag must be set to “No” to deactivate alarm functions associated with an open circuit at the space temperature analog input to the controller. The factory setting for the Space Sensor Present Flag is “Yes.”
The optional space temperature sensor is required to take advantage of the MicroTech II unoccupied heating (night setback) and cooling (night setup and purge) functions.
These functions are disabled when the Space Sensor Present
Flag is set to “No.” Also, optimal start and the option of setting the CtrlTemp Src= parameter to “Space” are not available when the Space Sensor Present Flag is set to “No.”
Refer to “Zone Temperature Sensor Packages” in the “Field
Wiring” section of IM 696, MicroTech Applied Rooftop Unit
Controller .
56 OM 138
Miscellaneous Service Parameters
Table 25: Programmable Parameters
Keypad/Display ID
Menu Name Item Name
Parameter Name
Unit Configuration
EFT Sensor=
2nd P Sensor= None
RF/EF Ctrl= Tracking
Rem RF/EF Cap=
25%
Eng Units=
No
English
Entering Fan Sensor
Present Flag
Second Pressure
Sensor Present Flag
Return/Exhaust Fan
Capacity Control
Flag
Remote
Return/Exhaust Fan
Capacity Set Point
Engineering Units
Control Flag
The Unit Configuration menu contains several miscellaneous control parameters as listed in the table above. These parameters are generally the type that are set at the factory and might be adjusted when the equipment is started up and generally do not required further adjustment. The following sections describe these parameters.
EFT Sensor
When a unit is equipped with gas or electric heat, it is equipped with an entering fan temperature (EFT) sensor.
This sensor senses the temperature of the air entering the discharge air fan and is compared to the unit discharge air temperature to obtain an indication of the temperature rise across the gas or electric heat section. The controller uses this information to assure the heat rise across the heater does not exceed the safe limit for the heat exchanger. When the entering fan temperature sensor is installed the Entering Fan Sensor Present Flag is set to “Yes.” When the entering fan temperature sensor is not installed the Entering Fan Sensor
Present Flag is set to “No.” Setting this parameter to “No” disables the alarm function associated with an open circuit at the EFT temperature sensor input.
2nd P Sensor
The Second Pressure Sensor Present Flag is used to indicate whether or not an optional building static pressure sensor is installed in the “second sensor” input location.
Note: When the unit is equipped for zone (or space comfort) control, the “second sensor” input location is design only for a building static pressure input.
There is no “first sensor” location.
The Second Pressure Sensor Present Flag should be set to
“None” when the Return/Exhaust Fan Capacity Control Flag is set to “None” or “Position”. When the Return/Exhaust Fan
Capacity Control Flag is set to “Bldg”, the Second Pressure
Sensor Present Flag automatically reverts to “Bldg”. For detailed information regarding return fan capacity control,
refer to “Return Fan Capacity Control” on page 88.
RF/EF Ctrl
The Return/Exhaust Fan Capacity Control Flag is used to select the type of return or exhaust fan capacity control, if any, to be used. When the unit is not equipped with return fan vanes or a VFD, the Return/Exhaust Fan Capacity Control Flag should be set to “None”. When the unit is equipped with return fan vanes or a VFD, the Return/Exhaust Fan
Capacity Control Flag can either be set to “Bldg” or “Position”.When the Return/Exhaust Fan Capacity Control Flag is set to “Bldg”, the return or exhaust fan capacity is controlled to maintain the building static pressure at a building static pressure set point. When the Return/Exhaust Fan Capacity
Control Flag is set to “Position”, then the return or exhaust fan capacity is controlled to the Remote Return/Exhaust Fan
Capacity Set Point. For detailed information regarding return
or exhaust fan capacity control, refer to“Return Fan Capacity
Control” on page 88 or “Energy Recovery” on page 86.
Rem RF/EF Cap
The the return or exhaust fan capacity is controlled to maintain the Remote Return/Exhaust Fan Capacity Set Point when the Return/Exhaust Fan Capacity Control Flag is set to
“Position”. The Remote Return/Exhaust Fan Capacity Set
Point is normally adjusted via a network signal but can also be adjusted via the keypad/display in the absence of a network connection to the parameter. For detailed information regarding return or exhaust fan capacity control, refer
to“Return Fan Capacity Control” on page 88 or “Energy
Eng Units
The Engineering Units Control Flag is used to select the system of engineering units used for displaying data on the keypad. If this parameter is set to “English”, the keypad data is displayed in inch-pound (I-P) units. If this parameter is set to
“SI Canada”, the keypad data is displayed in the International System of Units (SI) used in Canada. If this parameter is set to “SI Europe”, the keypad data is displayed in the
International System of Units (SI) used in Europe.
OM 138 57
Control Timer Settings
Table 26: Programmable Parameters
Keypad/Display ID
Menu Name Item Name
Service= 0 min
Recirculate= 3 min
Timer Settings
Low DAT= 3 min
Max MWU= 90 min
Bypass= 120 min
Start Init= 120 min
Min Exh On= 120 sec
Min Exh Off= 120 sec
Parameter Name
Fast Service Timer
Recirculate State
Timer
Low Discharge Temperature Ignore Timer
Maximum Morning
Warm-up Timer
Bypass Time Increment
Startup Initialization
Timer
Minimum Exhaust
Fan On Timer
Minimum Exhaust
Fan Off Timer
Several MicroTech II internal control timers can be adjusted via the keypad/display Timer Settings menu. The following sections describe these timers.
Service
Many of the internal control timers can be temporarily sped up by using the Fast Service Timer. When set to a time value, the Fast Service Timer begins counting down. While this parameter is counting down the following normal unit timers are set to 20 seconds: l l l l
Startup Initialization Timer
Post Heat Timer
Cooling Interstage Timer
Heating Interstage Timer
These timers return to their normal settings if the Fast Service Timer is manually set to 0 or when it counts down to 0.
Caution: This fast timers feature is meant to be used only by a knowledgeable service technician to facilitate testing the unit.
Recirculate
The Recirculate State Timer defines the duration of the
Recirc operating state applicable on units with return air
(100% OA units have no Recirc operating state). Whenever a unit with return air is started or restarted, it always transitions through a “start sequence” which includes the Startup, followed by the Recirc operating state. During the Recirc operating state, the unit fans run while the outdoor air dampers remain closed. Heating and cooling operation are disabled during the Recirc operating state to allow the “system” air temperature conditions to equalize before temperature control begins. Once in the Recirc operating state, the unit remains there until the Recirculate State Timer expires.
Low DAT
The Low Discharge Temperature Ignore Timer sets the duration of a time period after unit start up during which the Lo
Disch Tmp fault is ignored. This may be particularly important in colder climates when a unit has been off for a significant time period during which the unit, including the discharge air temperature sensor, has become very cold. This time period allows the unit to run long enough to warm the discharge sensor above the alarm limit, preventing nuisance unit alarm shutdown. For detailed information regarding the
Lo Disch Tmp fault refer to “Alarm Control” on page 91.
Max MWU
The Maximum Morning Warm-up Timer sets a maximum duration for the MWU operating state applicable on units with return air (100% OA units have no MWU operating state). Whenever a unit with return air leaves the Recirc operating state, it enters the MWU operating state if the Ctrl
Temp= parameter value is cold. The unit remains in the
MWU operating state until either the Ctrl Temp= parameter value warms up or until the Maximum Morning Warm-up
Timer expires. For detailed information regarding MWU
operation, refer to “Heating: Multistage” on page 78, or
“Heating: Modulating” on page 80, as applicable.
Bypass
The Bypass Time Increment sets the time period for which the unit operates each time the tenant override button on the optional space temperature sensor is pressed or the Occ
Mode= parameter is set to “Bypass.” The Bypass Time= parameter in the Occupancy menu is set or reset to this value when the tenant override button is pressed or the Occ Mode= parameter is set to “Bypass.” The unit then operates until the
Bypass Timer= parameter counts down to 0. For detailed
information regarding bypass operation, refer to “Bypass
Time (Tenant Override)” on page 48.
Start Init
The Startup Initialization Timer defines the duration of the
Startup operating state. When a unit is started or restarted, it always transitions through a “start sequence” that begins with the Startup operating state. During the Startup operating state, the unit fans remain off and heating and cooling are disabled. On units equipped with return air, the outdoor air damper actuator is driven closed. On units equipped with
100% outdoor air hoods, the outdoor air dampers are driven fully open. Return fan inlet vane actuators (if present) are
driven to a 17% minimum startup position. Refer to “Operating States and Sequences” on page 61.
58 OM 138
Manual Output Control
Table 27: Programmable Parameters
Keypad/Display ID
Menu Name Item Name
Parameter Name
Manual Control
Manual Control = No
Discharge Fan = Off
RF/EF Fan = Off
Fan Operation = Off
Alarm = Normal
OA Damper = Auto
Mod Cooling = Auto
Mod Heating = Auto
RF/EF Vanes = Auto
RF/EF VFD = Auto
Manual Control Mode
Flag
Manual Discharge
Fan Control Flag
Manual
Return/Exhaust Fan
Control Flag
Manual Fan Operation
Output Control Flag
Manual Remote Alarm
Output Control Flag
Manual OA Damper
Control Flag
Manual Modulating
Cooling Valve Control
Flag
Manual Modulating
Heating Valve Control
Flag
Manual
Return/Exhaust Vane
Actuator Control Flag
Manual
Return/Exhaust VFD
Control Flag
The Manual Control menu is a special service menu that can be used to control many of the outputs on the main control board (MCB) in a manual mode. This can be used to test the operation of the various devices controlled by the outputs.
This is very useful in determining whether a problem is the result of a wiring problem or defective device rather than a problem within the main controller.
Manual Control
The Manual Control Mode Flag is used to turn the manual control mode of operation on and off. When this parameter is set to “No” the unit operates normally. When this parameter is set to “Yes” normal operation of the control outputs is overridden and the condition of each output is defined by setting the remaining items within the Manual Control menu.
All alarms are inactive when the Manual Control Mode Flag is set to “Yes”.
Note: If the Calibrate Mode= parameter in the Unit Configuration menu is set to “Yes” while the Manual
Control Mode Flag is set to “Yes”, the Manual Control Mode Flag reverts to “No.”
Discharge Fan
The Manual Discharge Fan Control Flag is used to manually turn the discharge air fan on and off. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to
“On” the discharge air fan is turned on. When the Manual
Control Mode Flag is set to “Yes” and this parameter is set to
“Off” the discharge air fan is turned off.
RF/EF Fan
The Manual Return/Exhaust Fan Control Flag is used to manually turn the return or exhaust fan on and off. When the
Manual Control Mode Flag is set to “Yes” and this parameter is set to “On” the return or exhaust fan is turned on. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to “Off” the return or exhaust fan is turned off.
Fan Operation
The Manual Fan Operation Output Control Flag is used to manually turn the Fan Operation Output (MCB-BO3) on and off. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to “On” the Fan Operation Output is turned on. When the Manual Control Mode Flag is set to
“Yes” and this parameter is set to “Off” the Fan Operation
Output is turned off. For detailed information regarding the
Fan Operation Output, refer to “Fan Operation Output” in the “Field Wiring” section of IM 696, MicroTech Applied
Rooftop Unit Controller .
Alarm
The Manual Remote Alarm Output Control Flag is used to manually turn the Remote Alarm Output (MCB-BO4) on and off. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to “Normal” the Remote Alarm
Output is turned on. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to “Alarm” the Remote
Alarm Output is turned off. For detailed information regarding the Remote Alarm Output, refer to “Remote Alarm Output” in the “Field Wiring” section of IM 696, MicroTech
Applied Rooftop Unit Controller .
OA Damper
The Manual OA Damper Control Flag is used to manually drive the outdoor air dampers open and closed. When the
Manual Control Mode Flag is set to “Yes” and this parameter is set to “Open” the open outdoor damper output (MCB-
BO6) is turned on and the outdoor air dampers stroke open continuously. When the Manual Control Mode Flag is set to
“Yes” and this parameter is set to “Close” the close outdoor damper output (MCB-BO5) is turned on and the outdoor air dampers stroke closed continuously. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to
“Auto” the open and close outdoor damper outputs remain off and the outdoor air dampers remain at their current position.
Mod Cooling
The Manual Modulating Cooling Valve Control Flag is used to manually drive the modulating cooling valve open and closed. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to “Open” the open cooling valve output (MCB-BO8) is turned on and the cooling valve strokes open continuously. When the Manual Control Mode
Flag is set to “Yes” and this parameter is set to “Close” the
OM 138 59
close cooling valve output (MCB-BO7) is turned on and the cooling valve strokes closed continuously. When the Manual
Control Mode Flag is set to “Yes” and this parameter is set to
“Auto” the open and close cooling valve outputs remain off and the cooling valve remains at its current position.
Mod Heating
The Manual Modulating Heating Valve Control Flag is used to manually drive the modulating heating valve open and closed. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to “Open” the open heating valve output (MCB-BO10) is turned on and the heating valve strokes open continuously. When the Manual Control Mode
Flag is set to “Yes” and this parameter is set to “Close” the close heating valve output (MCB-BO9) is turned on and the heating valve strokes closed continuously. When the Manual
Control Mode Flag is set to “Yes” and this parameter is set to
“Auto” the open and close heating valve outputs remain off and the heating valve remains at its current position.
RF/EF Vanes
The Manual Return/Exhaust Vane Actuator Control Flag is used to manually drive the return air or exhaust fan inlet vanes open and closed. When the Manual Control Mode
Flag is set to “Yes” and this parameter is set to “Open” the open return or exhaust inlet vanes output (MCB-BO16) is turned on and the vanes stroke open continuously. When the
Manual Control Mode Flag is set to “Yes” and this parameter is set to “Close” the close return or exhaust inlet vanes output (MCB-BO15) is turned on and the vanes are stroked closed continuously. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to “Auto” the open and close return or exhaust inlet vanes outputs remain off and the vanes remain at their current position.
RF/EF VFD
The Manual Return/Exhaust VFD Control Flag is used to manually increase and decrease the return air or exhaust fan
VFD speed. When the Manual Control Mode Flag is set to
“Yes” and this parameter is set to “Faster” the increase return or exhaust fan VFD speed output (MCB-BO-16) is turned on and the VFD speed increases continuously. When the Manual Control Mode Flag is set to “Yes” and this parameter is set to “Slower” the decrease return or exhaust fan VFD speed output (MCB-BO15) is turned on and the VFD speed decreases continuously. When the Manual Control Mode
Flag is set to “Yes” and this parameter is set to “Auto” the increase and decrease return or exhaust fan VFD speed outputs remain off and the VFD remains at its current position.
60 OM 138
Advertisement
Key features
- Controls heating, cooling, and ventilation systems
- User-friendly interface with keypad and display
- Flexible scheduling options for optimal comfort and energy efficiency
- Comprehensive alarm monitoring for quick troubleshooting
- Remote alarm indication for timely response
- Calibrate mode for accurate temperature readings
- Control timer settings for precise operation
- Manual output control for maintenance and testing