AC Input Drives. Allen-Bradley PowerFlex 755 IP00

Add to My manuals
78 Pages

advertisement

AC Input Drives. Allen-Bradley PowerFlex 755 IP00 | Manualzz

8

PowerFlex 755 IP00, NEMA/UL Open Type Drive

AC Input Drives

Drive Ratings

The following tables provide rating and selection information for the PowerFlex

755 IP00 NEMA/UL Open Type AC input drives.

Light Duty

Input

Amps

Output Amps

Cont.

1 min 3 s

534 540 594 NA

578 585 644

604 612 673

739 750 825

784 796 876

819 832 915

1024 1040 1144

1073 1090 1199

1157 1175 1293

1443 1465 1612

1457 1480 1628

1576 1600 1760

1689 1715 1887

2294 2330 2563

380…480V AC, Three-Phase, 50 Hz Input

Three-Phase, 0…400 Hz Output kW

Normal Duty

Input

Amps

Output Amps

Cont.

1 min 3 s kW

Heavy Duty

Input

Amps

Output Amps

Cont.

1 min 3 s kW

Input Voltage

Range

V AC

315 455 460 506 693 250 380 385 578 693 200 360…440

Base Drive

Catalog Number

20G11TC460

315 533 540 594 821 315 450 456 684 821 250 360…440

355 560 567 624 851 315 466 472 708 851 250 360…440

400 640 650 715 975 355 533 540 810 975 315 360…440

450 739 750 825 1125 400 577 585 878 1125 315 360…440

20G11TC540

20G11TC567

20G11TC650

20G11TC750

450 758 770 847 1155 400 634 642 963 1155 355 360…440

560 896 910 1001 1365 500 739 750 1125 1365 400 360…440

630 1024 1040 1144 1584 560 867 880 1320 1584 500 360…440

710 1073 1090 1199 1638 630 896 910 1365 1638 500 360…440

20G11TC770

20G11TC460

20G11TC540

20G11TC567

800 1157 1175 1293 1872 710 1024 1040 1560 1872 560 360…440

850 1443 1465 1612 2198 800 1073 1090 1635 2198 630 360…440

900 1457 1480 1628 2220 850 1157 1175 1763 2220 710 360…440

1000 1566 1590 1749 2385 900 1305 1325 1988 2385 710 360…440

1400 2117 2150 2365 3225 1250 1773 1800 2700 3225 1000 360…440

20G11TC650

20G11TC750

20G11TC770

20G11TC567

20G11TC770

2

3

3

2

2

1

2

2

2

1

1

1

1

Quantity

Required

Equivalent

Frame Size

1 8

8

8

8

8

8

9

9

9

9

10

10

9

9

Light Duty

Input

Amps

Output Amps

Cont.

1 min 3 s

458 485 534 NA

514 545 600

557 590 649

670 710 781

722 765 842

755 800 880

906 960 1056

986 1045 1150

1071 1135 1249

1288 1365 1502

1340 1420 1562

1453 1540 1694

1562 1655 1821

2114 2240 2464

480V AC, Three-Phase, 60 Hz Input

Three-Phase, 0…400 Hz Output

Hp

Normal Duty

Input

Amps

Output Amps

Cont.

1 min 3 s Hp

Heavy Duty

Input

Amps

Output Amps

Cont.

1 min 3 s Hp

Input Voltage

Range

V AC

400 406 430 473 666 350 349 370 555 666 300 432…528

Base Drive

Catalog Number

20G11TD430

450 458 485 534 745 400 391 414 621 745 350 432…528

500 514 545 600 818 450 428 454 681 818 350 432…528

600 582 617 679 926 500 458 485 728 926 400 432…528

20G11TD485

20G11TD545

20G11TD617

650 670 710 781 1065 600 514 545 818 1065 450 432…528

700 698 740 817 1110 650 582 617 926 1110 500 432…528

800 755 800 880 1278 700 670 710 1065 1278 600 432…528

900 906 960 1056 1440 800 750 795 1193 1440 700 432…528

1000 986 1045 1150 1568 900 755 800 1200 1568 750 432…528

1100 1071 1135 1249 1728 1000 906 960 1440 1728 800 432…528

1250 1288 1365 1502 2048 1100 986 1045 1568 2048 900 432…528

1350 1340 1420 1562 2130 1250 1071 1135 1703 2130 1000 432…528

1500 1439 1525 1678 2288 1350 1199 1270 1905 2288 1100 432…528

2000 1953 2070 2277 3105 1750 1633 1730 2595 3105 1650 432…528

20G11TD710

20G11TD740

20G11TD430

20G11TD485

20G11TD545

20G11TD617

20G11TD710

20G11TD740

20G11TD545

20G11TD740

2

2

2

2

3

3

1

1

2

2

1

1

1

1

Quantity

Required

Equivalent

Frame Size

8

8

8

8

8

8

9

9

9

9

9

9

10

10

Rockwell Automation Publication 750-IN020D-EN-P - May 2017

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Light Duty

Input

Amps

Output Amps

Cont.

1 min 3 s

335 355 391 NA

373 395 435

411 435 479

434 460 506

481 510 561

514 545 600

651 690 759

717 760 836

788 835 919

849 900 990

925 980 1078

986 1045 1150

1151 1220 1342

1444 1530 1683

600V AC, Three-Phase, 60 Hz Input

Three-Phase, 0…400 Hz Output

Hp

Normal Duty

Input

Amps

Output Amps

Cont.

1 min 3 s Hp

Heavy Duty

Input

Amps

Output Amps

Cont.

1 min 3 s Hp

Input Voltage

Range

V AC

350 278 295 325 490 300 257 272 408 490 250 540…660

Base Drive

Catalog Number

20G11TE295

400 335 355 391 533 350 278 295 443 533 300 540…660

450 373 395 435 593 400 310 329 494 593 350 540…660

500 411 435 479 639 450 335 355 533 639 350 540…660

500 434 460 506 711 500 373 395 593 711 400 540…660

20G11TE355

20G11TE395

20G11TE435

20G11TE460

550 481 510 561 765 500 401 425 638 765 450 540…660

700 562 595 655 918 600 481 510 765 918 500 540…660

800 595 630 693 1071 700 562 595 893 1071 600 540…660

900 717 760 836 1140 800 595 630 945 1140 700 540…660

20G11TE510

20G11TE295

20G11TE355

20G11TE395

950 779 825 908 1260 900 661 700 1050 1260 750 540…660

1000 849 900 990 1368 950 717 760 1140 1368 800 540…660

1100 925 980 1078 1470 1000 769 815 1223 1470 900 540…660

1200 1048 1110 1221 1665 1100 868 920 1380 1665 1000 540…660

1500 1350 1430 1573 2145 1400 1123 1190 1785 2145 1250 540…660

20G11TE435

20G11TE460

20G11TE510

20G11TE395

20G11TE510

2

3

3

2

2

1

2

2

2

1

1

1

1

Quantity

Required

Equivalent

Frame Size

1 8

8

8

8

8

8

9

9

9

9

10

10

9

9

Light Duty

Input

Amps

Output Amps

Cont.

1 min 3 s

311 330 363 NA

349 370 407

386 410 451

433 460 506

471 500 550

499 530 583

612 650 715

669 710 781

744 790 869

810 860 946

904 960 1056

961 1020 1122

1083 1150 1265

1399 1485 1634

690V AC, Three-Phase, 50 Hz Input

Three-Phase, 0…400 Hz Output kW

Normal Duty

Input

Amps

Output Amps

Cont.

1 min 3 s kW

Heavy Duty

Input

Amps

Output Amps

Cont.

1 min 3 s kW

Input Voltage

Range

V AC

315 250 265 292 375 250 203 215 323 375 200 621…759

Base Drive

Catalog Number

20G11TF265

355 311 330 363 473 315 250 265 398 473 250 621…759

400 349 370 407 555 355 290 308 462 555 300 621…759

450 391 415 457 639 400 349 370 555 639 355 621…759

20G11TF330

20G11TF370

20G11TF415

500 433 460 506 675 450 353 375 563 675 375 621…759

530 471 500 550 750 500 389 413 620 750 400 621…759

630 556 590 649 885 560 433 460 690 885 450 621…759

710 612 650 715 975 630 471 500 750 975 500 621…759

800 669 710 781 1065 710 556 590 885 1065 560 621…759

850 721 765 842 1170 750 612 650 975 1170 630 621…759

900 749 795 875 1350 800 706 750 1125 1350 710 621…759

1000 904 960 1056 1440 900 749 795 1193 1440 800 621…759

1100 980 1040 1144 1560 1000 815 865 1298 1560 900 621…759

1500 1319 1400 1540 2100 1400 1093 1160 1740 2100 1120 621…759

20G11TF460

20G11TF500

20G11TF265

20G11TF330

20G11TF370

20G11TF415

20G11TF460

20G11TF500

20G11TF370

20G11TF500

2

2

2

2

3

3

1

1

2

2

1

1

1

1

Quantity

Required

Equivalent

Frame Size

8

8

8

8

8

8

9

9

9

9

9

9

10

10

Rockwell Automation Publication 750-IN020D-EN-P - May 2017 9

PowerFlex 755 IP00, NEMA/UL Open Type Drive

AC Input Drive Installation Kits

The following kits are available to assist you with installation of drive components in your enclosure. Note that certain kits are required for proper installation and for UL certification.

No. Kit

1 Converter (AC Input) Field

Termination

2 Inverter (AC Output) Field

Termination

3 Inverter (DC Bus) Field

Termination - 400/480V

Inverter (DC Bus) Field

Termination - 600/690V

4 Mounting, Back Panel

Frame 8 Equivalent

Catalog Number

20-750-BUS2-F8

20-750-BUS3-F8

20-750-BUS4-F8

(1)

Qty. Catalog Number

1

1

1

1

Frame 9 Equivalent

20-750-BUS2-F9

20-750-BUS3-F9

20-750-BUS4-F9

20-750-BUS6-F9

(3)

(3)

Qty. Catalog Number

1

1

1

1

Frame 10 Equivalent

20-750-BUS2-F10

20-750-BUS3-F10

20-750-BUS4-F10

20-750-BUS6-F10

(3)

(3)

Qty.

1

1

1

1

Description

Provides power wiring connection.

Notes

(4) (5)

5

6

7

8

Mounting, Floor/Rail

Ducting, Outlet Top

Ducting, Bottom Inlet

Control Pod

20-750-MNT2-F8

20-750-MNT3-F8

20-750-DUCT2-F8

20-750-DUCT4-F8

20-750-POD1-F8

Control Pod Remote Harness 20-750-RPD1-F8

1

1

1

1

1

1

20-750-MNT2-F9

20-750-MNT3-F9

20-750-DUCT2-F8

20-750-DUCT4-F8

20-750-POD1-F8

20-750-RPD1-F8

(9)

2

1

1

2

2

1

20-750-MNT2-F10

20-750-MNT3-F10

20-750-DUCT2-F8

20-750-DUCT4-F8

20-750-POD1-F8

20-750-RPD1-F8

(9)

1 Drive mounting kit includes four brackets per drive unit to mount the drive to the back of the enclosure.

1 Includes bottom rails and hardware to utilize the roll-out feature of the drive.

3 A duct adaptor is provided to direct exhaust air from the top of the drive. Can be used for horizontal or vertical installations.

3 Provides a duct to direct air flow into the bottom of the cabinet. Requires the Floor/Rail kit to secure the duct.

1 Control Pod including Main Control Board and

Fiber Interface Board. Mount in the left most bay of the drive or remotely (see below).

3 Hardware, fiber-optic, and power supply cables to remotely mount the control pod up to 23 m (75 ft) from the drive.

1 For control pod connection in the drive.

Important: Not required if the Remote

Mount kit is ordered.

(5)

(5)

(5)

(4) (6)

(5)

(7)

(7)

(8)

3

9 24V Harness

10 Fiber-optic Cable, 0.6 m

(22 in.)

Fiber-optic Cable, 2.8 m

(110 in.)

11 Roll-out Cart

20-750-PH1-F8

(2)

20-750-FCBL1-F8

0

1

20-750-PH2-F9

20-750-FCBL1-F10

1

2

20-750-PH3-F10

20-750-FCBL1-F10

12 EMC Core

20-750-CART1-F8 1 20-750-CART1-F8 1 20-750-CART1-F8 1 A wheeled roll-out cart that facilitates drive installation and removal.

20-750-EMCBUS1-F8 1 20-750-EMCBUS1-F8 2 20-750-EMCBUS1-F8 3 Common mode core kit for converter section input on AC input drives. To be used with 20-

750-BUS2-F8. EN 61800-3 compliant installations only.

20-750-EMCCM1-F8 1 20-750-EMCCM1-F8 2 20-750-EMCCM1-F8 3 Common mode core kit for inverter section output. For AC Input or Common DC Input drives. EN 61800-3 compliant installations only.

(1) Optional for Frame 8 equivalent applications; only use if application requires connection to the DC bus (such as a brake or chopper).

(2) Frame 8 equivalent 24V DC harness ships with each drive unit.

(3) Fuses are included.

(4) This kit is required for UL installations.

(5) This is a recommended kit.

(6) This kit is required.

(7) Required when mounting control pod in the drive.

(8) 20-750-PH1-F8 and 20-750-FCBL1-F8 are used for a drive mounted control pod. If the control pod is to be remote mounted up to 23m (75ft), order 20-750-RPD1-F8 kit instead.

(9) For frame 9 and 10 installations, remove the two-position connector from the harnesses and combine the leads into one connector that plugs into P14 on the Fiber Interface Board (see page

43

).

(5)

10 Rockwell Automation Publication 750-IN020D-EN-P - May 2017

7

9

10

8

Power

755

11

12

Frame 8

4

1

PowerFlex 755 IP00, NEMA/UL Open Type Drive

6

PE

PE

Frame 9

4

1

6

4

2

3

PE

PE

Frame 10

4

1

6

2

4

3

?

5

3

2

4

5

Rockwell Automation Publication 750-IN020D-EN-P - May 2017

5

11

advertisement

Related manuals