I/O Wiring
Important points to remember about I/O wiring:
• Always use copper wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control and signal wires should be separated from power wires by at least
0.3 meters (1 foot).
• For CE compliance, 115 volt digital input wiring must be shielded or must not exceed 30 meters (98 feet) in length.
• In order to maintain electrical safety for all user-accessible low voltage circuits (ELV/PELV circuits), I/O terminals designated for 24V or lower voltage must not be connected to a circuit of higher voltage or a circuit which is not adequately insulated from dangerous voltages with double or reinforced insulation within other connected equipment or wiring.
• In order to provide electrical safety for user-accessible low voltage I/O circuits which are referenced to earth (PELV circuits) and which may be touched simultaneously, care should be taken to provide a common earth reference for all equipment connected to the drive.
IMPORTANT I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise.
ATTENTION: Hazard of personal injury or equipment damage exists when using bipolar input sources. Noise and drift in sensitive input circuits can cause unpredictable changes in motor speed and direction. Use speed command parameters to help reduce input source sensitivity.
I/O Wire Recommendations
Type
Signal
(1) (2) (3)
Standard Analog I/O
Remote Pot
Wire Type(s)
–
–
Combined
Description
0.750 mm
2
(18 AWG), twisted pair, 100% shield with drain.
0.750 mm
2
(18 AWG), 3 conductor, shielded.
0.196 mm
2
(24 AWG) individually shielded pairs.
Min. Insulation
Rating
300V,
75…90 °C
(167…194 °F)
Encoder/Pulse I/O
<30 m (100 ft)
Encoder/Pulse I/O
30 to 152 m
(100 to 500 ft)
Encoder/Pulse I/O
152…259 m
(500…850 ft)
Signal
Power
Combined
Signal
Power
0.196 mm
2
(24 AWG) individually shielded pairs.
0.750 mm
2
(18 AWG) individually shielded pairs
0.330 mm
2
(22 AWG), power is 0.500 mm
2
(20AWG) individually shielded pairs.
0.196 mm
2
(24AWG) individually shielded pairs.
0.750 mm
2
(18 AWG) individually shielded pairs.
0.750 mm
2
(18 AWG) individually shielded pairs.
Combined
Digital I/O
Safety Inputs
Homing Inputs
Unshielded
Shielded
– Per US NEC or applicable national or local code.
Multi-conductor shielded cable 0.750 mm
2
(18 AWG), 3 conductor, shielded.
300V,
60 °C (140 °F)
(1) Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot).
(2) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.
(3) I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise.
(4) Safety option modules 20-750-S and 20-750-S1 require shielded cable.
Rockwell Automation Publication 750-IN020D-EN-P - May 2017 59
PowerFlex 755 IP00, NEMA/UL Open Type Drive
I/O Terminal Blocks
The various I/O terminal blocks are located in the Control Pod.
Main Control Board
1
2
7
8
5
6
4
3
Main Control Board Details
No.
Name
1 HIM Connector
Description
DPI Port 1 (HIM Cradle) connection.
2
3
Fan Connector
Battery Receptacle
Power supply for internal cooling fan.
User installed CR1220 lithium coin cell battery provides power to the
Real Time Clock (Optional, not supplied). Preserves the Real Time Clock setting in the event power to the drive is lost or cycled.
Cable connection for handheld and remote HIM options.
4 DPI Port 2
5 ENABLE Jumper Hardware enable jumper. Removed when a hardware enable configuration is utilized.
6 Embedded EtherNet/IP
Selectors
(1)
Address Rotary switches for setting lowest octet of EtherNet/IP address (forces address to 192.168.1.xxx). See the PowerFlex 750-Series AC Drives
Programming Manual, publication 750-PM001 for instructions on setting the IP address.
7 Embedded EtherNet/IP
Network cable connection.
8 TB1 I/O terminal block.
(1) See the PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual, publication 750COM-UM001 .
60 Rockwell Automation Publication 750-IN020D-EN-P - May 2017
PowerFlex 755 IP00, NEMA/UL Open Type Drive
Terminal Block Specifications
Name
Main Control Board - TB1
Wire Size Range Torque
Maximum Minimum Maximum
2.5 mm
2
(14 AWG)
0.3 mm
2
(28 AWG)
0.25 N•m
(2.2 lb•in)
Recommended
0.2 N•m
(1.8 lb•in)
Strip
Length
6 mm
(0.24 in.)
TB1 Terminal Designations
Fixed I/O
Di 0ac
Di C
Di 0dc
+24V
24VC
Terminal Name
Di 0ac Digital Input 0 (120V AC)
Di C
Di 0dc
Digital Input Common
Digital Input 0 (24V DC)
+24V
24VC
+24 Volt Power
24 Volt Common
Description
Connections for AC power supply.
Digital input common
Connections for DC power supply.
Connections for drive supplied 24V power. 150 mA maximum
Hardware Enable Circuitry
Digital Input 0 can be used as a general purpose programmable input, or by removal of a jumper, configured as a dedicated hardware enable, which is unaffected by parameter settings.
To configure Digital Input 0 as a dedicated hardware enable, complete the following steps.
1.
Access the Control Pod.
2.
Locate and remove the ENABLE Jumper on the Main Control Board (see
Fiber Interface Board
1
2
3
4
P1 P2 P3
Rockwell Automation Publication 750-IN020D-EN-P - May 2017 61
PowerFlex 755 IP00, NEMA/UL Open Type Drive
Fiber Interface Board Details
No.
Name
1 Main Control Board Connector
Description
98 pin main control board interface connection.
2 P13
3
4
P14
Inverter Connections
Connections for user-supplied 24 volt power.
Powers control circuits when main power is removed.
Connections for internal drive-supplied 24 volt power. Connection is factory wired and must not be modified by the user. Powers control circuits when main power is connected.
Fiber optic ports: P1 = INV1, P2 = INV2, P3 = INV3
Terminal Block Specifications
Name
Fiber Interface Connector P13
Fiber Interface Connector P14
Wire Size Range Torque
Maximum Minimum Maximum
4.0 mm
2
(12 AWG)
0.25 mm
(24 AWG)
2
0.5 N•m
(4.4 lb•in)
2.5 mm
2
(14 AWG)
0.3 mm
2
(28 AWG)
0.25 N•m
(2.2 lb•in)
Recommended
0.4 N•m
(3.5 lb•in)
0.2 N•m
(1.8 lb•in)
Strip
Length
7 mm
(0.28 in.)
6 mm
(0.24 in.)
P13 Terminal Designations
Power Block Terminal Name
AP+ +24 Volt Auxiliary Power
AP– Auxiliary Power Common
AP+
AP–
Sh
Sh Shield
Description
Connections for customer supplied power supply:
24V DC ±10%, 5 A, PELV (Protective Extra Low
Voltage) or SELV (Safety Extra Low Voltage)
Terminating point for wire shields.
P14 Terminal Designations
Power Block Terminal Name
1 +24 Volt Power
1
2
2 Power Common
Description
Connections for drive supplied power.
Option Modules
For a complete listing and description of all available Option Modules, see the
PowerFlex 750-Series AC Drives Installation Instructions, publication
750-IN001 .
Compatible port locations may be restricted for each option module.
An icon with position number(s) is provided to indicate which module ports are compatible. For example, the icon to the right indicates that the option module is only compatible with port 4.
62 Rockwell Automation Publication 750-IN020D-EN-P - May 2017
PowerFlex 755 IP00, NEMA/UL Open Type Drive
ATTENTION: Hazard of equipment damage exists if an option module is installed or removed while the drive is powered. To avoid damaging the drive, verify that the voltage on the bus capacitors has discharged completely and all control power is removed before performing any work on the drive. Measure the
DC bus voltage at the DC+ and DC- TESTPOINT sockets on the front of the power
). The voltage must be zero
To install an option module:
1.
Firmly press the module edge connector into the desired port.
2.
Tighten the top and bottom retaining screws.
IMPORTANT Do not over-tighten retaining screws.
T15 or F - 6.4 mm (0.25 in.)
0.45 N•m (4.0 lb•in)
Rockwell Automation Publication 750-IN020D-EN-P - May 2017 63
PowerFlex 755 IP00, NEMA/UL Open Type Drive
20-750-2262C-2R (24 Volts DC)
20-750-2263C-1R2T (24 Volts DC)
20-750-2262D-2R (120 Volts AC)
I/O Module
ATTENTION: Risk of equipment damage exists. Ensure that the correct voltage is applied to the I/O Module digital inputs. See the I/O Module catalog number to determine the voltage rating.
• 20-750-2262 C -2R is rated 24 Volts DC
• 20-750-2262 C -1R2T is rated 24 Volts DC
• 20-750-2262 D -2R is rated 120 Volts AC
Input Mode Jumpers
Jumper
Position Voltage Mode
Ai1
Ai0
Current Mode
Ai1
Ai0
I/O Option Module Terminal Block Specifications
Name
I/O Module TB1
I/O Module TB2
Wire Size Range Torque
Maximum Minimum Maximum
2.5 mm
2
(14 AWG)
0.3 mm
2
(28 AWG)
0.25 N•m
(2.2 lb•in)
4.0 mm
2
(12 AWG)
0.25 mm
2
(24 AWG)
0.5 N•m
(4.4 lb•in)
Recommended
0.2 N•m
(1.8 lb•in)
0.4 N•m
(3.5 lb•in)
Strip
Length
6 mm
(0.24 in.)
7 mm
(0.28 in.)
64 Rockwell Automation Publication 750-IN020D-EN-P - May 2017
PowerFlex 755 IP00, NEMA/UL Open Type Drive
TB1 Terminal Designations
Di3
Di4
Di5
Di0
Di1
Di2
24VC
+24V
DiC
10VC
+10V
Ai0–
Ai0+
Ai1–
Ai1+
Sh
Sh
PTC–
PTC+
Ao0–
Ao0+
Ao1–
Ao1+
–10V
Terminal Name
Sh Shield
Sh
Ptc–
Ptc+
Ao0–
Ao0+
Ao1–
Ao1+
–10V
10VC
+10V
Ai0–
Ai0+
Ai1–
Ai1+
24VC
+24V
Motor PTC (–)
Motor PTC (+)
Analog Out 0 (–)
Analog Out 0 (+)
Analog Out 1 (–)
Analog Out 1 (+)
–10 Volt Reference
10 Volt Common
+10 Volt Reference
Analog Input 0 (–)
Analog Input 0 (+)
Analog Input 1 (–)
Analog Input 1 (+)
24 Volt Common
(1)
+24 Volt DC
Description
Terminating point for wire shields when an
EMC plate or conduit box is not installed.
Motor protection device (Positive
Temperature Coefficient).
Bipolar, ±10V, 11 bit & sign, 2 k ohm minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum load.
2k ohm minimum.
For (–) and (+) 10 Volt references.
2k ohm minimum.
Isolated
(3)
, bipolar, differential, 11 bit & sign.
Voltage Mode: ±10V @ 88k ohm input impedance.
Current Mode: 0-20 mA @ 93 ohm input impedance.
Drive supplied logic input power.
200 mA max. per I/O module
600 mA max per drive
Related
Param
40 on Port X
75
(5) on Port X
85 on Port X
50, 70 on Port X
60, 70 on Port X
Di C Digital Input Common Common for Digital Inputs 0…5
Di 0
Di 1
Di 2
Di 3
Di 4
Digital Input 0
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
(2)
24V DC - Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC 11.2 mA DC
115V (132V Max) AC, 50/60 Hz
(4)
- Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC
1 on Port X
Di 5 Digital Input 5
(1) Not present on 120V versions.
(2) Digital Inputs are either 24 Volts DC (2262C) or 115 Volts AC (2262D) based on module catalog number. Ensure applied voltage is correct for I/O module.
(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(4) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).
(5) I/O Module parameters will also have a Port designation.
TB2 Terminal Designations (2 Relay Outputs: 2R)
R1NO
R1C
R1NC
R0NO
R0C
R0NC
Relay Out Terminal Name
R0NO Relay 0 N.O.
R0C
R0NC
Relay 0 Common
Relay 0 N.C.
R1NO
R1C
R1NC
Relay 1 N.O.
Relay 1 Common
Relay 1 N.C.
Description
Relay Normally Open contact output:
240V AC, 24V DC, 2 A max.
General Purpose (Inductive) / Resistive
Relay Normally Closed contact output:
240V AC, 24V DC, 2 A max.
Resistive Only
Related
Param
10, 100,
101, 105,
106 on Port X
20, 110,
111, 115,
116 on Port X
Rockwell Automation Publication 750-IN020D-EN-P - May 2017 65
PowerFlex 755 IP00, NEMA/UL Open Type Drive
TB2 Terminal Designations (1 Relay and 2 Transistor Outputs: IR2T)
Relay Out
TC
T1
R0NO
R0C
R0NC
T0
Terminal Name
R0NO Relay 0 N.O.
R0C
R0NC
Relay 0 Common
Relay 0 N.C.
T0
TC
T1
Transistor Output 0
Transistor Output
Common
Transistor Output 1
Description
Relay Normally Open contact output:
240V AC, 24V DC, 2 A max.
General Purpose (Inductive) / Resistive
Relay Normally Closed contact output:
240V AC, 24V DC, 2 A max.
Resistive Only
Related
Param
10, 100,
101, 105,
106 on Port X
Transistor output
Rating: 24V DC = 1 A max.
24V DC = 0.4 A Max for U.L. applications
Resistive
20 on Port X
30 on Port X
66 Rockwell Automation Publication 750-IN020D-EN-P - May 2017
advertisement
Related manuals
advertisement
Table of contents
- 2 Summary of Changes
- 2 General Precautions
- 3 Certifications
- 4 Overview
- 4 Selecting and Integrating an IP00 System
- 5 Catalog Number Explanation
- 6 Installation Overview
- 8 AC Input Drives
- 8 Drive Ratings
- 10 AC Input Drive Installation Kits
- 12 Common DC Input Drives
- 12 Drive Ratings
- 14 Common DC Input Drive Installation Kits
- 16 Installation Tools
- 16 Enclosure Requirements
- 16 Bus Bars
- 17 Environmental Requirements
- 17 Cooling Airflow and Ventilation - IP20, NEMA Type 1 Enclosures
- 22 Drive Grounding
- 23 CE Conformity
- 26 Horizontal Mounting Guidelines – Single Drive Unit Only
- 28 Dimensions
- 36 Lifting
- 36 Vertical Lifting
- 38 Horizontal Lifting
- 38 Drive Installation
- 38 Preparing the Enclosure
- 41 Selecting/Verifying Control Transformer Voltage
- 42 Installing the Control Pod in the Drive
- 45 Power Wiring
- 45 Grounding Requirements
- 45 Recommended Grounding Scheme
- 45 Shield Termination - SHLD
- 46 Wire Recommendations
- 46 Motor Considerations
- 47 Power Terminals
- 49 Kit Installation Guidelines
- 58 Cable Routing
- 58 Control Pod Cable Routing
- 59 I/O Wiring
- 60 I/O Terminal Blocks
- 67 Fuse and Circuit Breaker Ratings
- 76 Additional Resources