I/O Wiring. Allen-Bradley PowerFlex 755 IP00

Add to My manuals
78 Pages

advertisement

I/O Wiring. Allen-Bradley PowerFlex 755 IP00 | Manualzz

PowerFlex 755 IP00, NEMA/UL Open Type Drive

I/O Wiring

Important points to remember about I/O wiring:

• Always use copper wire.

• Wire with an insulation rating of 600V or greater is recommended.

• Control and signal wires should be separated from power wires by at least

0.3 meters (1 foot).

• For CE compliance, 115 volt digital input wiring must be shielded or must not exceed 30 meters (98 feet) in length.

• In order to maintain electrical safety for all user-accessible low voltage circuits (ELV/PELV circuits), I/O terminals designated for 24V or lower voltage must not be connected to a circuit of higher voltage or a circuit which is not adequately insulated from dangerous voltages with double or reinforced insulation within other connected equipment or wiring.

• In order to provide electrical safety for user-accessible low voltage I/O circuits which are referenced to earth (PELV circuits) and which may be touched simultaneously, care should be taken to provide a common earth reference for all equipment connected to the drive.

IMPORTANT I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise.

ATTENTION: Hazard of personal injury or equipment damage exists when using bipolar input sources. Noise and drift in sensitive input circuits can cause unpredictable changes in motor speed and direction. Use speed command parameters to help reduce input source sensitivity.

I/O Wire Recommendations

Type

Signal

(1) (2) (3)

Standard Analog I/O

Remote Pot

Wire Type(s)

Combined

Description

0.750 mm

2

(18 AWG), twisted pair, 100% shield with drain.

0.750 mm

2

(18 AWG), 3 conductor, shielded.

0.196 mm

2

(24 AWG) individually shielded pairs.

Min. Insulation

Rating

300V,

75…90 °C

(167…194 °F)

Encoder/Pulse I/O

<30 m (100 ft)

Encoder/Pulse I/O

30 to 152 m

(100 to 500 ft)

Encoder/Pulse I/O

152…259 m

(500…850 ft)

Signal

Power

Combined

Signal

Power

0.196 mm

2

(24 AWG) individually shielded pairs.

0.750 mm

2

(18 AWG) individually shielded pairs

0.330 mm

2

(22 AWG), power is 0.500 mm

2

(20AWG) individually shielded pairs.

0.196 mm

2

(24AWG) individually shielded pairs.

0.750 mm

2

(18 AWG) individually shielded pairs.

0.750 mm

2

(18 AWG) individually shielded pairs.

Combined

Digital I/O

Safety Inputs

Homing Inputs

(1)(2)(3)(4)

Unshielded

Shielded

– Per US NEC or applicable national or local code.

Multi-conductor shielded cable 0.750 mm

2

(18 AWG), 3 conductor, shielded.

300V,

60 °C (140 °F)

(1) Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot).

(2) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.

(3) I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise.

(4) Safety option modules 20-750-S and 20-750-S1 require shielded cable.

Rockwell Automation Publication 750-IN020D-EN-P - May 2017 59

PowerFlex 755 IP00, NEMA/UL Open Type Drive

I/O Terminal Blocks

The various I/O terminal blocks are located in the Control Pod.

Main Control Board

1

2

7

8

5

6

4

3

Main Control Board Details

No.

Name

1 HIM Connector

Description

DPI Port 1 (HIM Cradle) connection.

2

3

Fan Connector

Battery Receptacle

Power supply for internal cooling fan.

User installed CR1220 lithium coin cell battery provides power to the

Real Time Clock (Optional, not supplied). Preserves the Real Time Clock setting in the event power to the drive is lost or cycled.

Cable connection for handheld and remote HIM options.

4 DPI Port 2

5 ENABLE Jumper Hardware enable jumper. Removed when a hardware enable configuration is utilized.

6 Embedded EtherNet/IP

Selectors

(1)

Address Rotary switches for setting lowest octet of EtherNet/IP address (forces address to 192.168.1.xxx). See the PowerFlex 750-Series AC Drives

Programming Manual, publication 750-PM001 for instructions on setting the IP address.

7 Embedded EtherNet/IP

(1)

Connector

Network cable connection.

8 TB1 I/O terminal block.

(1) See the PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual, publication 750COM-UM001 .

60 Rockwell Automation Publication 750-IN020D-EN-P - May 2017

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Terminal Block Specifications

Name

Main Control Board - TB1

Wire Size Range Torque

Maximum Minimum Maximum

2.5 mm

2

(14 AWG)

0.3 mm

2

(28 AWG)

0.25 N•m

(2.2 lb•in)

Recommended

0.2 N•m

(1.8 lb•in)

Strip

Length

6 mm

(0.24 in.)

TB1 Terminal Designations

Fixed I/O

Di 0ac

Di C

Di 0dc

+24V

24VC

Terminal Name

Di 0ac Digital Input 0 (120V AC)

Di C

Di 0dc

Digital Input Common

Digital Input 0 (24V DC)

+24V

24VC

+24 Volt Power

24 Volt Common

Description

Connections for AC power supply.

Digital input common

Connections for DC power supply.

Connections for drive supplied 24V power. 150 mA maximum

Hardware Enable Circuitry

Digital Input 0 can be used as a general purpose programmable input, or by removal of a jumper, configured as a dedicated hardware enable, which is unaffected by parameter settings.

To configure Digital Input 0 as a dedicated hardware enable, complete the following steps.

1.

Access the Control Pod.

2.

Locate and remove the ENABLE Jumper on the Main Control Board (see

page 60 ).

Fiber Interface Board

1

2

3

4

P1 P2 P3

Rockwell Automation Publication 750-IN020D-EN-P - May 2017 61

PowerFlex 755 IP00, NEMA/UL Open Type Drive

Fiber Interface Board Details

No.

Name

1 Main Control Board Connector

Description

98 pin main control board interface connection.

2 P13

3

4

P14

Inverter Connections

Connections for user-supplied 24 volt power.

Powers control circuits when main power is removed.

Connections for internal drive-supplied 24 volt power. Connection is factory wired and must not be modified by the user. Powers control circuits when main power is connected.

Fiber optic ports: P1 = INV1, P2 = INV2, P3 = INV3

Terminal Block Specifications

Name

Fiber Interface Connector P13

Fiber Interface Connector P14

Wire Size Range Torque

Maximum Minimum Maximum

4.0 mm

2

(12 AWG)

0.25 mm

(24 AWG)

2

0.5 N•m

(4.4 lb•in)

2.5 mm

2

(14 AWG)

0.3 mm

2

(28 AWG)

0.25 N•m

(2.2 lb•in)

Recommended

0.4 N•m

(3.5 lb•in)

0.2 N•m

(1.8 lb•in)

Strip

Length

7 mm

(0.28 in.)

6 mm

(0.24 in.)

P13 Terminal Designations

Power Block Terminal Name

AP+ +24 Volt Auxiliary Power

AP– Auxiliary Power Common

AP+

AP–

Sh

Sh Shield

Description

Connections for customer supplied power supply:

24V DC ±10%, 5 A, PELV (Protective Extra Low

Voltage) or SELV (Safety Extra Low Voltage)

Terminating point for wire shields.

P14 Terminal Designations

Power Block Terminal Name

1 +24 Volt Power

1

2

2 Power Common

Description

Connections for drive supplied power.

Option Modules

For a complete listing and description of all available Option Modules, see the

PowerFlex 750-Series AC Drives Installation Instructions, publication

750-IN001 .

Compatible port locations may be restricted for each option module.

An icon with position number(s) is provided to indicate which module ports are compatible. For example, the icon to the right indicates that the option module is only compatible with port 4.

62 Rockwell Automation Publication 750-IN020D-EN-P - May 2017

PowerFlex 755 IP00, NEMA/UL Open Type Drive

ATTENTION: Hazard of equipment damage exists if an option module is installed or removed while the drive is powered. To avoid damaging the drive, verify that the voltage on the bus capacitors has discharged completely and all control power is removed before performing any work on the drive. Measure the

DC bus voltage at the DC+ and DC- TESTPOINT sockets on the front of the power

module (see page 47

). The voltage must be zero

To install an option module:

1.

Firmly press the module edge connector into the desired port.

2.

Tighten the top and bottom retaining screws.

IMPORTANT Do not over-tighten retaining screws.

T15 or F - 6.4 mm (0.25 in.)

0.45 N•m (4.0 lb•in)

Rockwell Automation Publication 750-IN020D-EN-P - May 2017 63

PowerFlex 755 IP00, NEMA/UL Open Type Drive

20-750-2262C-2R (24 Volts DC)

20-750-2263C-1R2T (24 Volts DC)

20-750-2262D-2R (120 Volts AC)

I/O Module

ATTENTION: Risk of equipment damage exists. Ensure that the correct voltage is applied to the I/O Module digital inputs. See the I/O Module catalog number to determine the voltage rating.

• 20-750-2262 C -2R is rated 24 Volts DC

• 20-750-2262 C -1R2T is rated 24 Volts DC

• 20-750-2262 D -2R is rated 120 Volts AC

Input Mode Jumpers

Jumper

Position Voltage Mode

Ai1

Ai0

Current Mode

Ai1

Ai0

I/O Option Module Terminal Block Specifications

Name

I/O Module TB1

I/O Module TB2

Wire Size Range Torque

Maximum Minimum Maximum

2.5 mm

2

(14 AWG)

0.3 mm

2

(28 AWG)

0.25 N•m

(2.2 lb•in)

4.0 mm

2

(12 AWG)

0.25 mm

2

(24 AWG)

0.5 N•m

(4.4 lb•in)

Recommended

0.2 N•m

(1.8 lb•in)

0.4 N•m

(3.5 lb•in)

Strip

Length

6 mm

(0.24 in.)

7 mm

(0.28 in.)

64 Rockwell Automation Publication 750-IN020D-EN-P - May 2017

PowerFlex 755 IP00, NEMA/UL Open Type Drive

TB1 Terminal Designations

Di3

Di4

Di5

Di0

Di1

Di2

24VC

+24V

DiC

10VC

+10V

Ai0–

Ai0+

Ai1–

Ai1+

Sh

Sh

PTC–

PTC+

Ao0–

Ao0+

Ao1–

Ao1+

–10V

Terminal Name

Sh Shield

Sh

Ptc–

Ptc+

Ao0–

Ao0+

Ao1–

Ao1+

–10V

10VC

+10V

Ai0–

Ai0+

Ai1–

Ai1+

24VC

+24V

Motor PTC (–)

Motor PTC (+)

Analog Out 0 (–)

Analog Out 0 (+)

Analog Out 1 (–)

Analog Out 1 (+)

–10 Volt Reference

10 Volt Common

+10 Volt Reference

Analog Input 0 (–)

Analog Input 0 (+)

Analog Input 1 (–)

Analog Input 1 (+)

24 Volt Common

(1)

+24 Volt DC

(1)

Description

Terminating point for wire shields when an

EMC plate or conduit box is not installed.

Motor protection device (Positive

Temperature Coefficient).

Bipolar, ±10V, 11 bit & sign, 2 k ohm minimum load.

4-20 mA, 11 bit & sign, 400 ohm maximum load.

2k ohm minimum.

For (–) and (+) 10 Volt references.

2k ohm minimum.

Isolated

(3)

, bipolar, differential, 11 bit & sign.

Voltage Mode: ±10V @ 88k ohm input impedance.

Current Mode: 0-20 mA @ 93 ohm input impedance.

Drive supplied logic input power.

200 mA max. per I/O module

600 mA max per drive

Related

Param

40 on Port X

75

(5) on Port X

85 on Port X

50, 70 on Port X

60, 70 on Port X

Di C Digital Input Common Common for Digital Inputs 0…5

Di 0

Di 1

Di 2

Di 3

Di 4

Digital Input 0

Digital Input 1

Digital Input 2

Digital Input 3

Digital Input 4

(2)

(2)

(2)

(2)

(2)

24V DC - Opto isolated

Low State: less than 5V DC

High State: greater than 20V DC 11.2 mA DC

115V (132V Max) AC, 50/60 Hz

(4)

- Opto isolated

Low State: less than 30V AC

High State: greater than 100V AC

1 on Port X

Di 5 Digital Input 5

(2)

(1) Not present on 120V versions.

(2) Digital Inputs are either 24 Volts DC (2262C) or 115 Volts AC (2262D) based on module catalog number. Ensure applied voltage is correct for I/O module.

(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.

(4) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).

(5) I/O Module parameters will also have a Port designation.

TB2 Terminal Designations (2 Relay Outputs: 2R)

R1NO

R1C

R1NC

R0NO

R0C

R0NC

Relay Out Terminal Name

R0NO Relay 0 N.O.

R0C

R0NC

Relay 0 Common

Relay 0 N.C.

R1NO

R1C

R1NC

Relay 1 N.O.

Relay 1 Common

Relay 1 N.C.

Description

Relay Normally Open contact output:

240V AC, 24V DC, 2 A max.

General Purpose (Inductive) / Resistive

Relay Normally Closed contact output:

240V AC, 24V DC, 2 A max.

Resistive Only

Related

Param

10, 100,

101, 105,

106 on Port X

20, 110,

111, 115,

116 on Port X

Rockwell Automation Publication 750-IN020D-EN-P - May 2017 65

PowerFlex 755 IP00, NEMA/UL Open Type Drive

TB2 Terminal Designations (1 Relay and 2 Transistor Outputs: IR2T)

Relay Out

TC

T1

R0NO

R0C

R0NC

T0

Terminal Name

R0NO Relay 0 N.O.

R0C

R0NC

Relay 0 Common

Relay 0 N.C.

T0

TC

T1

Transistor Output 0

Transistor Output

Common

Transistor Output 1

Description

Relay Normally Open contact output:

240V AC, 24V DC, 2 A max.

General Purpose (Inductive) / Resistive

Relay Normally Closed contact output:

240V AC, 24V DC, 2 A max.

Resistive Only

Related

Param

10, 100,

101, 105,

106 on Port X

Transistor output

Rating: 24V DC = 1 A max.

24V DC = 0.4 A Max for U.L. applications

Resistive

20 on Port X

30 on Port X

66 Rockwell Automation Publication 750-IN020D-EN-P - May 2017