CONNECTION TO POWER MAINS

DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS.

THE UNIT MUST BE CONNECTED TO POWER MAINS BY A QUALIFIED ELECTRICIAN.

THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE SHOWN

ON THE RATING PLATE.

• The unit is rated for connection to to 1~230 V/50 (60) Hz or 3~400 V/50 Hz power mains.

• The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.

• The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit in case of overload or short-circuit. The circuit breaker installation place must provide quick access for emergency shutdown of the unit.

The trip current of the automatic circuit breaker QF must exceed the maximum current consumption of the unit (refer to the technical data table). The recommended trip current of the circuit breaker is the next current in the standard trip current row following the maximum current of the connected unit. The automatic circuit breaker is not included in the delivery set.

10

The recommended circuit breaker nominal current and conductor cross section

Model

KSK 150 4E

KSK 150 4D

KSK 160 4E

KSK 160 4D

KSK 200 4E

KSK 200 4D

KSK 250 4E

KSK 250 4D

KSK 315 4E

KSK 315 4D

KSK 315 2E

KSK 315 2D

KSK 355 4E

KSK 355 4D

KSK 355 2E

KSK 355 2D

KSK 400 4E

KSK 400 4D

KSK 400 6Е

KSK 400 6D

KSK 450 4Е

KSK 450 4D

KSK 450 6Е

KSK 450 6D

Rated current of the circuit breaker [A]

2

1

2

1

8

3.15

12.5

4

3

1

16

5

4

2

16

8

8

3,15

2

3,15

10

4

4

2

Recommended cable, n x S, where n is the number of wires, and S is the cross section in mm 2

2х1.5

3х1.5

2х1.5

3х1.5

2х1.5

3х1.5

2х1.5

3х1.5

2x1.5

3x1.5

2x2.5

3x1.5

2x1.5

3x1.5

2x2.5

3x1.5

2x1,5

3x1,5

2x1,5

3x1,5

2x1,5

3x1,5

2x1,5

3x1,5 www.ventilation-system.com

The fan connections shall be made in the terminal box mounted on the fan casing as shown in the wiring diagram.

The wiring diagram sticker is located inside the motor terminal box.

CAUTION!

Make sure that the fan impeller wheel rotates in the direction of the arrow applied to the fan casing.

Air flow direction

Impeller rotation direction

Access to the terminal box

1

3 www.ventilation-system.com

2

4

11