CONNECTION TO POWER MAINS
DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS.
THE UNIT MUST BE CONNECTED TO POWER MAINS BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE SHOWN
ON THE RATING PLATE.
• The unit is rated for connection to to 1~230 V/50 (60) Hz or 3~400 V/50 Hz power mains.
• The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.
• The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit in case of overload or short-circuit. The circuit breaker installation place must provide quick access for emergency shutdown of the unit.
The trip current of the automatic circuit breaker QF must exceed the maximum current consumption of the unit (refer to the technical data table). The recommended trip current of the circuit breaker is the next current in the standard trip current row following the maximum current of the connected unit. The automatic circuit breaker is not included in the delivery set.
10
The recommended circuit breaker nominal current and conductor cross section
Model
KSK 150 4E
KSK 150 4D
KSK 160 4E
KSK 160 4D
KSK 200 4E
KSK 200 4D
KSK 250 4E
KSK 250 4D
KSK 315 4E
KSK 315 4D
KSK 315 2E
KSK 315 2D
KSK 355 4E
KSK 355 4D
KSK 355 2E
KSK 355 2D
KSK 400 4E
KSK 400 4D
KSK 400 6Е
KSK 400 6D
KSK 450 4Е
KSK 450 4D
KSK 450 6Е
KSK 450 6D
Rated current of the circuit breaker [A]
2
1
2
1
8
3.15
12.5
4
3
1
16
5
4
2
16
8
8
3,15
2
3,15
10
4
4
2
Recommended cable, n x S, where n is the number of wires, and S is the cross section in mm 2
2х1.5
3х1.5
2х1.5
3х1.5
2х1.5
3х1.5
2х1.5
3х1.5
2x1.5
3x1.5
2x2.5
3x1.5
2x1.5
3x1.5
2x2.5
3x1.5
2x1,5
3x1,5
2x1,5
3x1,5
2x1,5
3x1,5
2x1,5
3x1,5 www.ventilation-system.com
The fan connections shall be made in the terminal box mounted on the fan casing as shown in the wiring diagram.
The wiring diagram sticker is located inside the motor terminal box.
CAUTION!
Make sure that the fan impeller wheel rotates in the direction of the arrow applied to the fan casing.
Air flow direction
Impeller rotation direction
Access to the terminal box
1
3 www.ventilation-system.com
2
4
11
advertisement
Related manuals
advertisement
Table of contents
- 2 SAFETY REQUIREMENTS
- 4 PURPOSE
- 4 DELIVERY SET
- 4 DESIGNATION KEY
- 5 TECHNICAL DATA
- 7 DESIGN AND OPERATING PRINCIPLE
- 8 INSTALLATION AND SET-UP
- 10 CONNECTION TO POWER MAINS
- 12 TECHNICAL MAINTENANCE
- 13 Troubleshooting
- 13 Storage and transportation regulations
- 14 MANUFACTURER’S WARRANTY
- 15 CERTIFICATE OF ACCEPTANCE
- 15 SELLER INFORMATION
- 15 INSTALLATION CERTIFICATE
- 15 WARRANTY CARD