Low Voltage—Wye-Delta. Trane Drives, CVHG, Starters, CVHF, Electrical Components, CVHE, CDHG, CDHF 82 Pages
Low Voltage—Wye-Delta. Trane Drives, CVHG, Starters, CVHF, Electrical Components, CVHE, CDHG, CDHF
Add to My manuals82 Pages
advertisement
CTV-PRB004.book Page 18 Sunday, December 18, 2011 6:39 PM
Low-Voltage Starter Types
Figure 6.
Comparison of low-voltage starting current
120
100
80
60
40
20
0
0
X-Line
Solid-State
Wye-Delta
AFD
1 2 3 4 5
Time (seconds)
6 7 8 9 10
Low Voltage—Wye-Delta
Wye-Delta Starters
One of the most common starters in the industry is the wye/star-delta. It is an electromechanical starter initially set up in a “wye” or “star” configuration, then it transitions to a “delta” configuration during the starting sequence.To illustrate a typical starting sequence using a generic
(non-Trane) schematic, refer to Figure 7, p. 19 and its “Starting sequence,” p. 19 .
18 CTV-PRB004-EN
CTV-PRB004.book Page 19 Sunday, December 18, 2011 6:39 PM
Low-Voltage Starter Types
Figure 7.
Simplified wye-delta wiring schematic
LINE
VOLTAGE
WYE-DELTA
STARTER WIRING
CTV-PRB004-EN
F
OL
OL
OL
1M
2M
1M
2M
1M
2M
R 1A
S
R 1A
S
R 1A
S
MOTOR
CPT
F
START-
STOP
PR 1A 2M
S
1M S
TRANSITION
PR
S
1M
2M
1A
Starting sequence
1. The “start” signal from the CenTraVac controller energizes the pilot relay (PR).
2. The PR contacts close to energize the star contactor (S).
3. The S contacts close to connect the motor in the star configuration.
4. An S interlock closes to energize the start contactor (1M).
5. The 1M contacts close to connect the motor to the line.
6. A time delay relay or current monitoring device initiates transition by energizing the resistor contactor (1A).
7.
1A contacts close to connect the resistors to the line in the star configuration and in parallel with the compressor motor.
8. A 1A interlock now opens to de-energize the S contactor.
9. The S contacts open to connect the resistors and motor windings in series in the delta configuration.
10. An S interlock closes to energize the run contactor (2M).
11. The 2M contacts close to bypass the resistors and connect the compressor motor directly to the line in the delta configuration.
Dimensions
The typical unit-mounted wye-delta starter size is shown in Figure 9, p. 20 . Typical remotemounted one-, two- and three-door starter sizes are shown in Figure 10, p. 20 , Figure 11, p. 20 , and
Figure 12, p. 21 . Always consult the submittal drawings for as-built dimensions.
19
CTV-PRB004.book Page 20 Sunday, December 18, 2011 6:39 PM
Low-Voltage Starter Types
The one-door remote-mounted starter size is generally used for 155- to 606-amp starters with no disconnect.The two-door size is used for 640- to 1,700-amp starters with no disconnect.The threedoor size is used for 1,385- to 1,700-amps when disconnects are included.
Figure 8.
Unit-mounted WD Figure 9.
Remote 1-door WD
Squirrel-cage
Stator
60”
Rotor shaft
13.5”
38.5”
84”
Stator
19.3”
32”
Figure 11. Remote 3-door WD Figure 10. Remote 2-door WD
Stator
Squirrel-cage
84”
Rotor shaft
84”
Stator
19.3” 19.3”
56”
84”
20 CTV-PRB004-EN
CTV-PRB004.book Page 21 Sunday, December 18, 2011 6:39 PM
Low-Voltage Starter Types
Figure 12. Unit-mounted, wye-delta starter
2
1
2
1. Top-entry power only
2. 4 kVA control-power transformer
3. Circuit breaker (optional)
4. Transition resistors
3
CTV-PRB004-EN
4
Standard features
• Unit or floor mounted
• Control-power transformer
• Padlock tab for additional locking of the starter door
• Line-side connection terminal block/main lug only
• UL and CUL certified
• Environmental specification
• Designed, developed, and tested in accordance with UL 508
• NEMA 1 enclosure as standard
• Operation from sea level to 6,000 ft (1,829 m)
• Operating ambient temperature range 32°F to 104°F (0°C to 40°C)
• Relative humidity, non-condensing 5 percent to 95 percent
• Non-operating ambient temperature range -40°F to 158°F (-40°C to 70°C)
• Voltage utilization range ±10 percent
21
advertisement
Related manuals
advertisement
Table of contents
- 7 What a Starter Does
- 8 Voltage Classes
- 8 Motors
- 10 Standard Components of Trane Starters
- 10 Chiller Selection Report
- 18 Low Voltage—Wye-Delta
- 18 Wye-Delta Starters
- 22 Low Voltage—Solid-State
- 22 Solid-State Starters
- 25 Low Voltage—Unit-Mounted Adaptive Frequency Drive
- 28 Low Voltage—Remote-Mounted Adaptive Frequency Drive
- 32 Medium Voltage—Across-the-Line (2.3–6.6 kV)
- 32 Across-the-Line Starter (2,300–6,600 volts)
- 35 Medium Voltage—Primary Reactor (2.3–6.6 kV)
- 35 Primary Reactor Starter (2,300–6,600 volts)
- 38 Medium Voltage—Autotransformer (2.3–6.6 kV)
- 38 Autotransformer Starter (2,300–6,600 volts)
- 40 Unit-Mounted Starter Top Hat—NEC 2005 Code Requirement
- 42 Medium Voltage—Remote-Mounted Adaptive Frequency Drive
- 43 Chiller Unit Control Features for the AFD
- 45 Medium Voltage—Across-the-Line (10–13.8 kV)
- 45 Across-the-Line Starter (10,000–13,800 volts)
- 47 Medium Voltage—Primary Reactor (10–13.8 kV)
- 47 Primary Reactor Starter (10,000–13,800 volts)
- 48 Medium Voltage—Autotransformer (10–13.8 kV)
- 48 Autotransformer Starter (10,000–13,800 volts)
- 52 Disconnect Means
- 53 Short-Circuit Interruption
- 54 Power Circuit Requirements
- 61 Multiple Starter Lineups (2,300–6,600 volts)
- 63 Industrial-Grade Starters