Power Circuit Requirements. Trane Drives, CVHG, Starters, CVHF, Electrical Components, CVHE, CDHG, CDHF 82 Pages
Power Circuit Requirements. Trane Drives, CVHG, Starters, CVHF, Electrical Components, CVHE, CDHG, CDHF
Add to My manuals82 Pages
advertisement
CTV-PRB004.book Page 54 Sunday, December 18, 2011 6:39 PM
Electrical System—Design Guidelines by a short circuit (fault current), it may be opened safely at any time. A low-voltage starter door may be opened only if the circuit breaker is in the “off” or open position.
Circuit breakers of various interrupt ratings are offered as options. The interrupting capacity of a circuit breaker must also be considered. An analysis of an installation is usually done by the electrical engineer to calculate the maximum available fault current (AFC) that could be delivered if a short circuit occurred.
When a low-voltage starter is ordered with a circuit breaker, the starter manufacturer furnishes a standard circuit breaker sized at approximately 125 percent of compressor RLA or larger.The trip current of a circuit breaker is adjustable so that it will not trip during starting and acceleration, but will trip instantaneously (typically within one cycle) if a short circuit occurs.
Short-Circuit Current Rating (SCCR)
The disconnect means and the short-circuit protection discussed above are either supplied and installed by the customer upstream of the starter or they can be supplied as options with theTrane ® starter. However, the starter’s SCCR must be communicated to the electrical engineer early in the project to ensure that the starter short-circuit current rating will meet the requirements. If the SCCR is not high enough, the electrical engineer will have to look for solutions upstream of the starter.
Each low-voltageTrane ® starter or frequency drive has a short-circuit current rating, based on the size of the starter as well as the type of disconnect or circuit breaker included. See the appropriate submittal drawings for the starter short-circuit current rating.
Note: Don’t confuse short-circuit current rating (SCCR) with silicone controlled rectifier (SCR)— utilized in solid-state starters and AFDs.
Medium-voltage short circuit interruption
All medium-voltage starters contain current-limiting fuses for short circuit protection.The currentlimiting fuses and isolation switch, which is furnished as standard, fulfill the request for a fused disconnect. If you need more detail on the fuses for a particular starter contact CenTraVac Field
Sales Support.
It turns out that the starter short-circuit current rating is not an issue with medium-voltage starters.
Because Trane ® medium-voltage starters meet UL 347, current-limiting power fuses are required and provided as standard, and the starter short-circuit current rating no longer applies. Mediumvoltage starters fromTrane have an interrupt rating based on the standard current-limiting fuses.
At 4,160 volts, the NEMA E2 fused-interrupt rating is 50,000 amperes or 400 MVA.
Medium voltage fuse coordination suggestions
Proper sizing of fuses and circuit breakers upstream of the starter is the responsibility of the customer or the electrical engineer.
Power Circuit Requirements
Starter Applications
When applying a starter to a chiller motor on a specified power circuit, the power circuit has to meet minimum criteria to allow for a successful chiller start without an immediate shutdown or safety trip.This applies to utility power, local or smaller-scale facility power, and backup or peak-shaving generator power.
The following are some considerations for motor starter power quality requirements:
• Size of the power circuit
• Source and/or total system impedance
• System regulation
• Inrush characteristics of the starter type
• Acceleration time
• Maximum voltage sag
• Maximum voltage swell
54 CTV-PRB004-EN
CTV-PRB004.book Page 55 Sunday, December 18, 2011 6:39 PM
CTV-PRB004-EN
Electrical System—Design Guidelines
• Additional (non-chiller) loads on the power circuit
When evaluating a power system for a chiller-compressor motor with a specified starter type, calculations must be done in order to size or “correct” the power circuit properly in order to successfully start the motor and keep the motor-starter combination online during operation.
Table 9 and Table 10, p. 55 show specific starter characteristics and minimum power requirements.
Table 9.
Sizing requirements
Starter Type Voltage Range
Inrush
Current
% LRA
Chiller Controller
Maximum Acceleration
Time Setpoint (sec) (a)
Percent
Rated
Torque
Wye-Delta
Solid-State
X-Line
Primary Reactor
208–600 V
208–600 V
2.3–13.8 kV
2.3–13.8 kV
33
~45
100
65
27
27
6
16
33
33
100
42
Autotransformer
AFD
2.3–13.8 kV
460–600 V
45
<13
16
12
42
Varies
(a) The Chiller Controller Maximum Acceleration Time Setpoint is the maximum allowable acceleration time; if the chiller has not started within this time, a diagnostic will be set.
Table 10. Motor starter operational voltage range—during a start
Starter Size
155–606 amps
607–1,316 amps
607–1,856 amps
185–1,120 amps
180–960 amps
961–1,600 amps
155–1530 amps
Starter Description
Unit- and Remote-Mounted
Wye-Delta
Unit-Mounted
Wye-Delta
Remote-Mounted
Wye-Delta
Unit- and Remote-Mounted
Solid-State
Remote-Mounted,
High-Fault Solid-State
Remote-Mounted,
High-Fault Wye-Delta
Unit- and Remote-Mounted
Low Voltage AFD
Maximum
Line-to-Line
RMS Voltage Sag
25%
25%
20%
25%
25%
25%
25%
Maximum
Line-to-Line
RMS Voltage Swell
15%
15%
15%
15%
15%
15%
10%
94, 187, 205/288 amps
(205 reduced voltage, 288 full voltage)
Unit-Mounted
Medium Voltage
(2.3–6.6 kV)
94, 187, 360 amps
94 amps
61–250 amps @ 4,160 V
Remote-Mounted
Medium Voltage
(2.3–6.6 kV)
Remote-Mounted
Medium Voltage
(10–13.8 kV)
Remote Medium-Voltage AFD
25%
(20% w/additional protection)
25%
(20% w/additional protection)
25%
(20% w/additional protection)
25%
15%
15%
15%
10%
Note: The maximum allowable under/overvoltage during normal operation is ±10 percent.
55
CTV-PRB004.book Page 56 Sunday, December 18, 2011 6:39 PM
Electrical System–Power Wire Sizing
This section provides guidance for sizing the power conductors forTrane CenTraVac water chillers including wiring from the distribution system to the starter, and wiring from the starter to the compressor motor. The information provided does not constitute a design manual and does not supersede local code requirements or National Electric Code (NEC) recommendations. Final wire size selection must be verified by the Engineer of Record for the installation.
Wire size and count should be coordinated with the starter selection so the starter can be ordered with the proper terminal lugs. The starter is shipped with standard lugs as shown on the as-built submittals. Alternate lugs are often available and can be purchased locally. Standard lugs accept a wide range of wire sizes, but not all possible combinations.
General wiring requirements
• When more than one lead per phase is used (paralleled conductors), the leads must be of the same size and length so that they share the load equally. Paralleled conductors are only permitted for wire sizes of 1/0 and larger.
• When two or more conduits are used, all three phases must be equally represented in each conduit to avoid overheating.
Specific requirements for distribution system to starter wiring
• Wiring to the starter must be copper. A discussion of why aluminum should not be used can be found in the Glossary ( “Aluminum conductors,” p. 73 ).
• Wiring to all starters must be in multiples of three.
Specific requirements for starter to motor wiring
• All wiring to the CenTraVac motor must be copper. The UL listing on the CenTraVac requires copper conductors, and the terminal blocks on the motor studs are only compatible with copper wire.
• Wiring to motors used with variable frequency drive, across-the-line, autotransformer, or primary reactor starters must be in multiples of three. Wire for these starters is sized following the procedure used for sizing supply wire from the distribution system to the starter.
• Wiring to motors used with wye-delta (also referred to as star-delta) or inside-the-delta solidstate starters must be in multiples of six.The solid-state starter wire sizing tables included here are only applicable to the inside-the-delta solid-state starter designs offered for CenTraVac chillers shipped since June 1999. All other solid-state starter designs should follow the acrossthe-line wire sizing tables.
• A minimum of three feet of flexible conduit is required at the connection to the motor junction box to provide vibration isolation.
Wire size guidelines
The following information is based on the 2011 National Electric Code (NEC). Most local codes are based on the NEC; however, local codes may vary from the NEC on specific details. Final wire size selection must be verified by the Engineer of Record for the installation.
Various factors are involved in selecting the proper wire including amperage draw of the load, type of load, voltage, temperature rating of the wire, number of conductors within a conduit, and ambient temperature. In addition, the wires connecting the starter to the motor may need to be sized differently than the wires that connect the distribution system to the starter.
Good circuit design also involves checking the voltage drop of the distribution circuit.The NEC does not require this step, but does suggest that 3 percent voltage drop on a branch circuit feeder and
5 percent overall will provide “reasonable efficiency of operation”.
The NEC requires HVAC manufacturers to calculate and include “minimum supply circuit conductor ampacity” (also referred to as Minimum Circuit Ampacity [MCA]) on the unit name plate
(section 440.4 [B]). MCA is equal to 1.25 times the RLA of the largest motor plus 100 percent of all
56 CTV-PRB004-EN
CTV-PRB004.book Page 57 Sunday, December 18, 2011 6:39 PM
Electrical System–Power Wire Sizing other electrical loads. Branch circuit wires supplying the unit must have an ampacity greater than the MCA.
Table 11, p. 58 through Table 16, p. 60 are based on the 2011 NEC conductor ampacities tables for copper wire, run in conduit, in air, for several common wire types and configurations. Where required by the NEC the values in the tables have been adjusted for more than three wires in a conduit.
Table 11, p. 58 through Table 14, p. 59 are for 0–2000 V applications where the ambient temperature around the conduit is between 78°F–86°F (26°C–30°C); Table 15, p. 60 and Table 16, p. 60 are for 2,001 V–35 kV applications where the ambient temperature around the conduits is
104°F (40°C) or less. Installations with ambient temperatures outside these ranges require an additional ampacity adjustment for proper wire selection.
The tables provide an easy way to estimate wire size. Enter the appropriate table, knowing the nameplate MCA of the chiller; a table value greater than the MCA indicates a valid wire/conduit selection (for the conditions described earlier in this section).
Example
The example chiller has a remote-mounted wye-delta starter and the nameplate indicates an RLA of 300 and an MCA of 384 at 460 volts.
If 75°C conductors are used, the supply leads from the distribution system to the starter are sized using Table 11, p. 58 . Comparing the MCA to the table values indicates the conductors could be any of the following combinations:
• one conduit containing three 600 MCM conductors
• one conduit containing six 250 MCM conductors
• two conduits containing three 3/0 conductors each, and so on
Because this is a wye-delta starter the leads from the starter to the motor are sized differently than the supply leads to the starter. If 75°C conductors are used the leads from the starter to the motor are sized using Table 12, p. 58 . Comparing the MCA to the table indicates the following combinations are allowed:
• one conduit containing six 300 MCM conductors
• two conduits containing three 4/0 conductors each
• two conduits containing six 1/0 conductors each
Conductor ampacity tables
The wire selection tables ( Table 11, p. 58 through Table 16, p. 60 ) may be used for estimating conductor and conduit combinations that will support the amperage draw of CenTraVac chillers.
Wire sizes are given in units of AWG (American wire gauge) or kcmil (thousands of circular mils), also referred to as MCM or KCM.
Find the appropriate table based on voltage, wire temperature rating, and where the wire will be used. A table value greater than the nameplate MCA indicates a valid wire/conduit selection (for the conditions described earlier in this section). Then check that the selected combination will fit in the starter lugs by reviewing the starter submittal data. Final wire size selection must be confirmed by the Engineer of Record for the installation.
CTV-PRB004-EN 57
CTV-PRB004.book Page 58 Sunday, December 18, 2011 6:39 PM
Electrical System–Power Wire Sizing
Table 11. MCA look-up table for 75°C copper conductors rated for 0–2,000 Volts (a)
Note: Use this table to select supply leads for all starters, and motor leads for remote-mounted across-theline, primary reactor, autotransformer, and Adaptive Frequency Drives. Value in table must be larger than the MCA to use the wire combination.
Wire Size
8
1 Conduit
3 Wires
50
1 Conduit
6 Wires
1
0
00
000
3
2
6
4
65
85
100
115
130
150
175
200
0000
250
300
350
230
255
285
310
400
500
335
380
536
608
600 420 672
(a) Based on 2011 NEC Table 310.15(B)(16)
240
280
320
368
408
456
496
2 Conduits
3 Wires ea.
300
350
400
460
510
570
620
670
760
840
3 Conduits
3 Wires ea.
450
525
600
690
765
855
930
1005
1140
1260
2 Conduits
6 Wires ea.
480
560
640
736
816
912
992
1072
1216
1344
4 Conduits
3 Wires ea.
600
700
800
920
1020
1140
1240
1340
1520
1680
5 Conduits
3 Wires ea.
750
875
1000
1150
1275
1425
1550
1675
1900
2100
6 Conduits
3 Wires ea.
900
1050
1200
1380
1530
1710
1860
2010
2280
2520
Table 12. MCA look-up table for 75°C copper conductors rated for 0–2,000 Volts (a)
Note: Use this table to select motor leads for remote-mounted wye-delta and solidstate starters (inside-the-delta designs only).Value in table must be larger than the MCA to use the wire combination.
Wire Size
8
1 Conduit
6 Wires
69
2 Conduits
3 Wires ea.
86
1
0
00
000
3
2
6
4
179
206
241
275
89
117
137
158
0000
250
300
350
317
351
393
427
396
439
491
534
400
500
462
524
577
655
600 579 724
(a) Based on 2011 NEC Table 310.15(B)(16)
224
258
301
344
112
146
172
198
2 Conduits
6 Wires ea.
413
482
551
634
703
786
855
924
1048
1158
4 Conduits
3 Wires ea.
517
603
689
793
879
982
1069
1155
1310
1448
3 Conduits
6 Wires ea.
620
724
827
951
1055
1179
1282
1386
1572
1737
6 Conduits
3 Wires ea.
775
905
1034
1189
1319
1474
1603
1732
1965
2172
58 CTV-PRB004-EN
CTV-PRB004.book Page 59 Sunday, December 18, 2011 6:39 PM
Electrical System–Power Wire Sizing
Table 13. MCA look-up table for 90°C copper conductors rated for 0–2,000 Volts (a)
Wire Size
1 Conduit
3 Wires
1 Conduit
6 Wires
2 Conduits
3 Wires ea.
3 Conduits
3 Wires ea.
2 Conduits
6 Wires ea.
4 Conduits
3 Wires ea.
5 Conduits
3 Wires ea.
6 Conduits
3 Wires ea.
4
3
8
6
55
75
95
115
2
1
0
00
000
0000
250
300
350
400
500
600
130
145
170
195
225
260
290
320
350
380
430
475
272
312
360
416
464
512
560
608
688
760
340
390
450
520
580
640
700
760
860
950
510
585
675
780
870
960
1050
1140
1290
1425
544
624
720
832
928
1024
1120
1216
1376
1520
680
780
900
1040
1160
1280
1400
1520
1720
1900
850
975
1125
1300
1450
1600
1750
1900
2150
2375
1020
1170
1350
1560
1740
1920
2100
2280
2580
2850
Note:
Use this table to select supply leads for all starters and motor leads for remote-mounted across-the-line, primary reactor, autotransformer, and
Adaptive Frequency Drives. Value in table must be larger than the MCA to use the wire combination.
(a) , Based on 2011 NEC Table 310.15(B)(16)
Table 14. MCA look-up table for 90°C copper conductors rated for 0–2,000 Volts (a)
Wire Size
8
1 Conduit
6 Wires
75
2 Conduits
3 Wires ea.
94
2 Conduits
6 Wires ea.
4 Conduits
3 Wires ea.
3 Conduits
6 Wires ea.
6 Conduits
3 Wires ea.
1
0
00
000
3
2
6
4
0000
250
300
350
103
131
158
179
200
234
269
310
358
400
441
482
129
163
198
224
250
293
336
387
448
500
551
603
469
537
620
717
800
882
965
586
672
775
896
1000
1103
1206
703
806
931
1075
1200
1324
1448
879
1008
1163
1344
1500
1655
1810
400
500
524
593
655
741
600 655 819 1310 1637 1965 2456
Note:
Use this table to size motor leads from remote-mounted wye-delta and solid-state starters (inside-the-delta designs only). Value in table must be larger than the MCA to use the wire combination.
(a) Based on 2011 NEC Table 310.15(B)(16)
1048
1186
1310
1482
1572
1779
1965
2224
CTV-PRB004-EN 59
CTV-PRB004.book Page 60 Sunday, December 18, 2011 6:39 PM
Electrical System–Power Wire Sizing
Table 15. MCA look-up table for 90°C copper conductors rated for 2,001–5,000 Volts (a)
Wire Size
1 Conduit
3 Wires
2 Conduits
3 Wires ea.
3 Conduits
3 Wires ea.
1
0
00
000
4
2
8
6
155
180
205
240
55
75
97
130
360
410
480
540
615
720
0000
250
350
500
750
280
315
385
475
600
560
630
770
950
1200
840
945
1155
1425
1800
Note: Use this table to select line-side wiring to the starter and load-side wiring between the starter and the motor. Value in table must be larger than the MCA to use the wire combination.
(a) Based on 2011 NEC Table 310.60(C)(73)
Table 16. MCA look-up table for 90°C copper conductors rated for 5,001–35,000 Volts (a)
Wire size
1 Conduit
3 Wires
2 Conduits
3 Wires ea.
3 Conduits
3 Wires ea.
0
00
000
0000
2
1
6
4
195
225
260
295
83
110
150
170
390
450
520
590
585
675
780
885
250
350
500
750
330
395
480
585
660
790
960
1170
990
1185
1440
1755
Note:
Use this table to select line-side wiring to the starter and load-side wiring between the starter and the motor. Value in table must be larger than the MCA to use the wire combination.
(a) Based on 2011 NEC Table 310.60(C)(73)
60 CTV-PRB004-EN
advertisement
Related manuals
advertisement
Table of contents
- 7 What a Starter Does
- 8 Voltage Classes
- 8 Motors
- 10 Standard Components of Trane Starters
- 10 Chiller Selection Report
- 18 Low Voltage—Wye-Delta
- 18 Wye-Delta Starters
- 22 Low Voltage—Solid-State
- 22 Solid-State Starters
- 25 Low Voltage—Unit-Mounted Adaptive Frequency Drive
- 28 Low Voltage—Remote-Mounted Adaptive Frequency Drive
- 32 Medium Voltage—Across-the-Line (2.3–6.6 kV)
- 32 Across-the-Line Starter (2,300–6,600 volts)
- 35 Medium Voltage—Primary Reactor (2.3–6.6 kV)
- 35 Primary Reactor Starter (2,300–6,600 volts)
- 38 Medium Voltage—Autotransformer (2.3–6.6 kV)
- 38 Autotransformer Starter (2,300–6,600 volts)
- 40 Unit-Mounted Starter Top Hat—NEC 2005 Code Requirement
- 42 Medium Voltage—Remote-Mounted Adaptive Frequency Drive
- 43 Chiller Unit Control Features for the AFD
- 45 Medium Voltage—Across-the-Line (10–13.8 kV)
- 45 Across-the-Line Starter (10,000–13,800 volts)
- 47 Medium Voltage—Primary Reactor (10–13.8 kV)
- 47 Primary Reactor Starter (10,000–13,800 volts)
- 48 Medium Voltage—Autotransformer (10–13.8 kV)
- 48 Autotransformer Starter (10,000–13,800 volts)
- 52 Disconnect Means
- 53 Short-Circuit Interruption
- 54 Power Circuit Requirements
- 61 Multiple Starter Lineups (2,300–6,600 volts)
- 63 Industrial-Grade Starters