Evacuation. hussman H-Series Condensing Units
PDF
Document
Advertisement
Advertisement
Condensing Units I M P O R TA N T Keep in store for future reference! HE H-SERIES CONDENSING UNIT PLEASE NOTE: New store installations with refrigerated systems for CA beginning 1/1/2022 must not exceed 50 lbs of charge and use a refrigerant below 2,200 GWP. Systems greater than 50 lbs charge require refrigerants below 150 GWP. Existing store compliance for CA requires weighted average GWP of refrigerants used to less than 1,400 GWP for the the fleet by 2030 or a 55% reduction of overall GHGp (charge not relevant). Installation & Operation Manual P/N 0708232_K September 2021 Spanish P/N 3138514 MANUAL - IO H-SERIES CONDENSING UNITS E EN GARDE MISE EN GARDE RTISSEMENT 2 AVERTISSEMENT BEFORE YOU BEGIN Read the safety information completely and carefully. The precautions and use of the procedures described herein are intended to use the product correctly and safely. Comply with the precautions described below to protect you and others from possible injuries. Relative to their potential danger, the relevant matters are divided into four parts as defined by ANSI Z535.5 ANSI Z535.5 DEFINITIONS ! • DANGER – Indicate[s] a hazardous situation which, if not avoided, will result in death or serious injury. ! • WARNING – Indicate[s] a hazardous situation which, if not avoided, could result in death or ! serious injury. ! ! • CAUTION – Indicate[s] a hazardous situation if not avoided, could result in minor ! which, or moderate injury. ! • NOTICE ! – Not related to personal injury – Indicates[s] situations, which if not avoided, could result in damage to equipment. ! *********************************** Environmental Concerns Hussmann recommends responsible handling of refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those that contain Hydrogen, Chlorine, Fluorine, and Carbon (HCFCs). Only certified technicians may handle these refrigerants. All technicians must be aware and follow the requirements set forth by the Federal Clean Air Act (Section 608) for any service procedure being performed on this equipment that involves refrigerant. Additionally, some states have other requirements that must be adhered to for responsible management of refrigerants. PN 0708232_K PERSONAL PROTECTION EQUIPMENT (PPE) Only qualified personnel should install and service this equipment. Personal Protection Equipment (PPE) is required whenever servicing this equipment. Wear safety glasses, gloves, protective boots or shoes, long pants, and a long-sleeve shirt as required when working with this equipment. Observe all precautions on tags, stickers, labels and literature attached to this equipment. Contractors shall strictly adhere to specifications provided by the Engineer of Record (EOR), as well as US Environmental Protection Agency regulations, OSHA regulations, and all other federal, state and local codes. This work should only be done by qualified, licensed contractors. There are numerous hazards, not limited to, but including: burns due to high temperatures, high pressures, toxic substances, electrical arcs and shocks, very heavy equipment with specific lift points and structural constraints, food and product damage or contamination, public safety, noise, and possible environmental damage. Never leave operating compressors unattended during the manual softstart process. Always power rocker switches off when unattended. Condensing Unit Installation and Operation Manual 2 PN 0708232_K Proper Field Wiring and Grounding Required! Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. August 31, 2018 This warning does not mean that Hussmann products will cause cancer or reproductive harm, or is in violation of any product-safety standards or requirements. As clarified by the California State government, Proposition 65 can be considered more of a ‘right to know’ law than a pure product safety law. When used as designed, Hussmann believes that our products are not harmful. We provide the Proposition 65 warning to stay in compliance with California State law. It is your responsibility to provide accurate Proposition 65 warning labels to your customers when necessary. For more information on Proposition 65, please visit the California State government website. 3 — LOCK OUT / TAG OUT — To avoid serious injury or death from electrical shock, always disconnect the electrical power at the main disconnect when servicing or replacing any electrical component. This includes, but is not limited to, such items as controllers, electrical panels, condensers, lights, fans, and heaters. This manual was written in accordance with originally perscribed equipment that is subject to change. Hussmann reserves the right to change all or part of the equipment for future stores such as, but not limited to, controllers, valves and electrical specifications. It is the installers responsibility to reference the refrigeration drawings supplied for each installation, as directed by the Engineer of Record. This equipment is prohibited from use in California with any refrigerants on the “List of Prohibited Substances” for that specific end-use, per California Code of Regulations, title 17, section 95374. Use in other locations is limited to refrigerants permitted by country, state, or local laws and is the responsibility of the installer/end-user to ensure only permitted refrigerants are used. This disclosure statement has been reviewed and approved by Hussmann and Hussmann attests, under penalty of perjury, that these statements are true and accurate. Condensing Unit Installation and Operation Manual 3 4 TABLE OF CONTENTS MODEL NUMBERING SYSTEM................................................................................................... 6 INSTALLATION INSTRUCTIONS................................................................................................. 7 SHIPPING DAMAGE................................................................................................................. 7 Apparent Loss or Damage...................................................................................................... 7 Concealed Loss or Damage..................................................................................................... 7 RIGGING AND LIFTING.......................................................................................................... 7 MACHINE ROOM REQUIREMENTS..................................................................................... 8 UNIT PLACEMENT................................................................................................................... 8 SHIPPING BLOCK REMOVAL....................................................................................................... 9 Minimum Allowable Clearances / Piping Considerations......................................................... 9 TWO-TIER APPLICATION......................................................................................................10 RECEIVER CAPACITY.............................................................................................................10 PRESSURE RELIEF.................................................................................................................10 WATER COOLED CONDENSER............................................................................................10 REFRIGERATION PROCESS........................................................................................................11 OVERVIEW................................................................................................................................11 REFRIGERATION CYCLE.......................................................................................................12 HEAT RECLAIM VALVE..........................................................................................................13 DEMAND COOLING................................................................................................................14 The System Parts.........................................................................................................................14 Component Testing................................................................................................................15 Alarm Circuit...............................................................................................................................15 Alarm Relay.................................................................................................................................15 Operational Notes.................................................................................................................16 COMPONENT PIPING...................................................................................................................17 OVERVIEW......................................................................................................................................17 REFRIGERATION LINE RUNS...............................................................................................17 Through Walls or Floors........................................................................................................17 From Machine to Solid Object...............................................................................................18 P-Trap Construction..............................................................................................................18 Reduced Riser........................................................................................................................18 Factory Supplied Stubs..........................................................................................................18 Protecting Valves and Clamps................................................................................................18 Connecting Remote Condenser...............................................................................................18 Purge Valve Location.............................................................................................................18 MERCHANDISER PIPING......................................................................................................20 Suction Line.................................................................................................................................20 Liquid Line – Off Time and Electric Defrost..........................................................................20 Field Connections of Heat Reclaim........................................................................................20 SPECIAL PIPING FOR OPEN ROOMS........................................................................................20 RUN LENGTHS AND EQUIVALENT FEET...........................................................................20 INSULATION............................................................................................................................20 REFRIGERANT LINE SIZING................................................................................................21 General Information..............................................................................................................21 Refrigeration Line Stubs Out.................................................................................................21 Condenser Line Sizing...........................................................................................................21 PN 0708232_K Condensing Unit Installation and Operation Manual 4 PN 0708232_K 5 ELECTRICAL................................................................................................................................. 22 OVERVIEW............................................................................................................................... 22 GUIDELINES FOR FIELD WIRING...................................................................................... 22 Unit Cooler Fan Wiring............................................................................................................... 22 Evaporator Mounted Liquid Line Solenoid............................................................................ 22 Cooler Door Switch Wiring.................................................................................................. 22 Sizing Wire and Overcurrent Protectors................................................................................ 22 Defrost Controls................................................................................................................... 22 Other Controls..................................................................................................................... 22 ABOUT THESE ELECTRICAL DIAGRAMS......................................................................... 22 Electrical Diagrams.............................................................................................................. 23 START-UP ..................................................................................................................................... 38 Leak Testing ....................................................................................................................... 38 Test Charge.......................................................................................................................... 38 Oil Levels................................................................................................................................... 38 Evacuation........................................................................................................................................ 39 Setup.................................................................................................................................... 39 Procedure.................................................................................................................................... 39 Pre-Charge Check List......................................................................................................... 39 Charging.............................................................................................................................. 39 Winter Charge............................................................................................................................ 39 Compressor Motor Rotation (Scroll)........................................................................................... 39 Final Checks......................................................................................................................... 39 MAINTENANCE............................................................................................................................. 42 COMPRESSOR REPLACEMENT.......................................................................................... 42 REPLACING DRIER AND FILTER CORES.......................................................................... 42 APPENDIX A – DIMENSION DRAWINGS.................................................................................. 43 TROUBLESHOOTING INFORMATION..................................................................................... 91 TROUBLESHOOTING GUIDE..................................................................................................... 92 Condensing Unit Installation and Operation Manual 5 6 NOTE: These refrigeration systems are not intended for use in Walk-in Coolers of Freezers where US Department of Energy (DOE) or Natural Resources Canada (NRCan) efficiency requirements apply. PN 0708232_K Condensing Unit Installation and Operation Manual 6 PN 0708232_K 7 INSTALLATION INSTRUCTIONS SHIPPING DAMAGE All equipment should be thoroughly examined for shipping damage before and while unloading. This equipment has been carefully inspected at our factory and the carrier has assumed responsibility for safe arrival. If damaged, either apparent or concealed, claim must be made to the carrier. Apparent Loss or Damage If there is an obvious loss or damage, it must be noted on the freight bill or express receipt and signed by the carrier’s agent, otherwise, carrier may refuse claim. The carrier will supply the necessary claim forms. Concealed Loss or Damage When loss or damage is not apparent until after equipment is uncrated, a claim for concealed damage is made. Upon discovering damage, make request in writing to carrier for inspection within 15 days and retain all packing. The carrier will supply inspection report and required claim forms. RIGGING AND LIFTING Under no circumstances should the manifolds, piping return blends or control panel be used for lifting or moving the unit. Use lifting eyes provided on two tier units. On singles tier units, secure lifting hooks to the under side of the base, or use the holes provided in the base. The installer is responsible to see that equipment used to move the unit is operated within its limits. 1 ½ times overall unit height minimum Spreader bar = unit width + 1 in. Secure lifting hooks on underside of base where sheet metal ends. Figure 1-1 Rigging and Lifting Condensing Unit Installation and Operation Manual 7 8 MACHINE ROOM REQUIREMENTS The equipment room floor must solidly support the compressor unit as a live load. Ground level installation seldom presents problems, but a mezzanine installation must be carefully engineered. Equipment must be located in the machine room to provide enough working space for service personnel, and to meet electrical codes. When a Remote Condenser Unit, Satellite Unit or a Water Cooled Condensing Unit is installed, the ventilation should be 100 cfm per compressor unit horsepower. The air inlet should be sized for a maximum of 600 fpm velocity (0.5 ft² of air intake per compressor unit horsepower). The Indoor Condensing Unit ventilation should be 750 to 1,000 cfm with 2 to 2.5 ft² of air intake per compressor unit horsepower. The ventilation fans should cycle by thermostatic control. All machine room ventilation equipment must be field supplied. Check local codes for variances. Proper ventilation provides airflow across the compressors. Duct work may be necessary. Provide a floor drain for disposal of condensate that may form on the compressor unit or header defrost assembly. Consult NEC National Fire Handbook, particularly “Installation of Switch Boards” and “Working Space Requirements.” Refer to local codes for each installation. Reference individual drawings shown in the Appendix. SHIPPING BLOCK REMOVAL Hard mounting is standard on all units. All piping was carefully design to absorb the vibration that is generated by the compressor and fan motors. When the spring mounting kit (optional) is installed, the unit is shipped with blocks under each compressor foot to prevent transit damage. Loosen the mounting spring nuts at least one full turn and remove the blocks. Adjust the torque on the mounting spring nuts so that the compressor feet are 1 inch above the unit’s base. UNIT PLACEMENT When setting the units, plan in relation to the rest of the equipment to be installed and existing structures. Some minimum and maximum distances are listed. Note: Piping equivalent is not the same as linear distance. PN 0708232_K Condensing Unit Installation and Operation Manual 8 PN 0708232_K 9 MINIMUM ALLOWABLE CLEARANCES Between an Outdoor Condensing Unit and any vertical structure (except open chain link fence) the minimum allowable distance is 4 feet. Between one Outdoor Condensing Unit exhaust and another Outdoor Condensing Unit intake the minimum allowable distance is 15 feet. Between the sides of two Outdoor Condensing Units the minimum allowable distance is 5 feet. On Indoor Condensing Unit, Satellite Unit, Remote Condenser Unit and Water Cooled Condensing Unit, the minimum distance between the Control Panel and the wall is 42 inches. On Indoor Condensing Unit, Satellite Unit, Remote Condenser Unit and Water Cooled Condensing Unit, the minimum distance between the Control Panel and another live panel is 4 feet. On Indoor Condensing Units the minimum distance between the Condenser Air Intake and a louvered wall is 30 inches. Shipping Block Figure 1-4 Shipping Block Removal PIPING CONSIDERATIONS When piping a suction riser the maximum vertical distance between P-traps is 20 feet. When piping from Remote Condenser Unit to a Condenser, the maximum allowable piping equivalent is 100 feet. Condensing Unit Installation and Operation Manual 9 10 TWO-TIER APPLICATION The two-tier unit is only an option when it is installed on the heavy duty base (option) and it is designed for indoor, water-cooled, remote condenser or satellite application. WARNING: Two Tier Remote Condenser Units Are Front Heavy. PRESSURE RELIEF It is standard that a fusible plug is installed on all the receivers. The connection size for piping from the fusible plug to outside is 3/8” NPT. It is also available as an option a relief valve, which replaces the fusible plug, and has the same connection size for piping (3/8” NPT). WATER COOLED CONDENSER Flush the water lines before connecting them to the water-cooled condenser. Consult Water Cooled Condensing Unit Catalog for pressure drop, recommended inlet water temperature and water flow through the condenser. Take appropriate precautions during shipment and moving of unit. Fasten to floor upon final placement. Figure 1-5 Two Tier Remote Condenser Units RECEIVER CAPACITY The receiver capacity is listed on the table below. Capacity - 90% H-series Receivers 6x12 6x18 6x23 6x30 8-5/8x30 10-3/4x30 10-3/4x38 12-3/4x30 5x12 6x15 6x12 6x36 PN 0708232_K R404A/R507A R448A/R449A 11.1 16.7 21.4 27.9 53.9 82.3 106.2 100.1 7.9 14.6 11.4 36.1 11.7 17.6 22.5 29.3 56.6 86.5 111.6 105.2 8.3 15.3 12.0 37.9 R407A R407F 12.2 18.4 23.6 30.7 59.4 90.7 117.0 110.3 8.7 16.1 12.6 39.8 11.9 18.0 23.0 30.0 57.9 88.5 114.2 107.6 8.5 15.7 12.3 38.8 Condensing Unit Installation and Operation Manual 10 PN 0708232_K 11 REFRIGERATION PROCESS OVERVIEW This section details the refrigeration process by tracking the refrigerant flow through the system components. Heat Reclaim, Demand Cooling, Oil separation and return is explained. See Piping for piping guidelines. Typically, refrigeration falls into low or medium temperature ranges. An average low temperature condensing unit maintains a suction temperature of -20°F with a low-temp Satellite operating at -33°F. A common medium temperature condensing unit operates at +25°F with a lowtemperature Satellite operating at +7°F. In these instructions the following constants are maintained to assist the reader. In the diagrams refrigerant flow direction is generally clockwise and indicated by directional arrows. Electric solenoid valves carry the same initial abbreviations as in the electric schematics. Refrigeration lines not actually in the cycle being discussed are shown closed or removed. Pressure in oil lines will also retain a fixed pattern. Heat Reclaim Coil Heat Reclaim Valve Evaporator Check Valve Oil Return Line Check Valve Oil Separator Sensor Demand Cooling Module Accumulator Suction Filter Sight Glass Differential Check Valve Injection Valve Oil Line Solenoid Compressor Liquid Line Solenoid Condenser Receiver Liquid Dryer High Pressure Hot Vapor High Pressure Warm Liquid High Pressure Warm Vapor Low Pressure Cool Vapor Condenser Adjustable Flooding Valve Fixed Flooding Valve Receiver Figure 2-1 Refrigeration Cycle Condensing Unit Installation and Operation Manual 11 12 REFRIGERATION CYCLE The Condenser rejects the heat that must be Beginning with the Compressor, refrigerant vapor removed from refrigerant to cause it to condense. is compressed and flows to the Oil Separator, which separates the oil from the discharge gas For Low Ambient Conditions, Fan Cycling or by centrifugal force and screen baffles. The oil Flooding Valves are required. These valves may is stored in the bottom of the Oil Separator and be fixed or adjustable. The adjustable flooding returned to the compressors through the oil return valve works in parallel with a 20 pound differential line. check valve. The Flooding Valve maintains head pressure in low ambient conditions by restricting liquid refrigerant flow from the Condenser. This causes liquid refrigerant to be backed up in the condenser thus reducing available heat transfer surface and causing the discharge pressure to rise. Figure 2-2 Oil Separator Outdoor High-Efficiency units are equipped with adjustable ORI flooding valves for winter When an Oil Separator is installed the following control and ORD differential valves for receiver pressure regulation. (standard) Outdoor multicomponents are required: • Check Valve on the discharge line after the fan High-Efficiency units are also equipped with Oil Separator, to prevent refrigerant migration a temperature control to cycle off half the fans in during low ambient temperatures from the low-ambient conditions (standard). condenser to the Oil Separator, and from that to the Compressor. • Oil Line Solenoid on the oil return line, to prevent the oil to return from the compressor when the compressor is not running. The excessive oil in the carter when the compressor starts, could cause damage to the compressor such as broken valve plate or piston, etc. A 3-Way Heat Reclaim Valve directs the superheated discharge gas to either the condenser or a Heat Reclaim device when energized. When the reclaim solenoid is deenergized, the valve directs the refrigerant to the condenser. Adjustable Fixed Flooding Flooding Valve Valve and Differential Check Valve Figure 2-4 Flooding Valves Figure 2-3 Heat Reclaim Valve PN 0708232_K Condensing Unit Installation and Operation Manual 12 PN 0708232_K The Receiver is a holding vessel for liquid refrigerant that compensates for fluctuations in liquid requirements due to changing load, defrost, and weather. 13 At critical locations along the refrigerant path, service valves or ball valves allow isolation of components. HEAT RECLAIM VALVE A Liquid Line Drier removes moisture and contaminants from the refrigerant. The Sight Glass allows service personnel to view refrigerant flow inside the liquid line. The Liquid Line Solenoid Valve closes off refrigerant supply to the evaporator. A 3-Way Heat Reclaim Valve directs the refrigerant to either the Condenser or a Heat Reclaim Coil. When the solenoid is deenergized the valve directs the refrigerant to the condenser. When the solenoid is de-energized the highpressure inlet is stopped and the passage between suction and valve chamber is open. When the solenoid is energized the suction outlet is stopped and the passage between high pressure and the valve chamber is open. “B” version of the valve has a bleed port through the drive piston to the suction manifold. The bleed port provides a vent for fluids trapped in the Heat Reclaim circuits during normal operation. Figure 2-5 Liquid Line Solenoid Valve The Thermostatic Expansion Valve (TEV), located in the merchandiser, meters liquid refrigerant through its orifice to the low pressure side of the system where it absorbs heat from the coil causing the liquid to evaporate. De-energized To Suction Manifold Bleed Port To Heat Reclaim From Discharge Manifold Figure 2-6 Thermostatic Expansion Valve The Accumulator catches liquid refrigerant in the suction line and provides a means for it to boil off before it reaches the compressor. To Condenser Valve in Normal Operation Figure 2-7 Heat Reclaim Valve Normal Operation A Suction Filter is placed upstream of the compressor to remove system contaminants from the refrigerant vapor. Condensing Unit Installation and Operation Manual 13 14 Energized To Suction Manifold To Heat Reclaim From Discharge Manifold To Condenser Valve in Heat Reclaim Mode Figure 2-8 Heat Reclaim Valve Heat Reclaim Mode DEMAND COOLING Temperature °F 77 282 292 310 Approximate Ohm Reading 90,000 2,400 2,100 1,700 The Control Module responds to the Temperature Sensor input by energizing the Injection Valve Solenoid when 292°F is exceeded. Too high or too low a resistance from the thermistor circuit will cause the Module to shutdown the compressor after one minute. The Injection Valve meters saturated refrigerant into the suction cavity of the compressor. The valve orifice is carefully sized to meet the requirements of a specific compressor. Valve sizes correspond to the four compressor bodies- 2D, 3D, 4D. The Demand Cooling System is designed to inject Probe test readings between 100,000 Ohms and saturated refrigerant into the suction cavity when 1,600 Ohms usually indicate an operating probe. the compressor internal head temperature exceeds Temperature 292°F. Injection continues until the temperature Sensor Module is reduced to 282°F. If the temperature remains Injection above 310°F for one minute the control shuts Valve down the compressor. After correcting the cause of shutdown, manual reset is required. The System Parts Temperature Sensor Control Module Injection Valve The Temperature Sensor uses a Negative Temperature Coefficient (NTC) Thermistor to provide signals to the Control Module. The NTC resistance drops on temperature rise. Temperature Sensor Module Injection Valve Solenoid Figure 2-9 Demand Cooling Components PN 0708232_K Condensing Unit Installation and Operation Manual 14 PN 0708232_K 15 Component Testing Remove power to the system. Unplug the Temperature Sensor from the Module. The Sensor should ohm out between 1,600 Ohms and 100,000 Ohms. Leave the Sensor unplugged and restart the system. There should be no voltage between terminals “S” and “L2” on the Module. The inlet and outlet sides of the Injection Valve should feel the same temperature. After one minute the alarm relay should trip. Remove power to the system. Press the manual reset on the Module. Figure 2-10 Demand Cooling Alarm Connections Using a small piece of wire, jump the Sensor circuit at the female plug in the Module. Restart the system. There should be voltage between terminals “S” and “L2” on the Module. The outlet side of the Injection Valve should feel colder than the inlet side. After one minute the alarm relay should trip. Remove power to the system. Press the manual reset on the Module. Temperature Sensor Remove the jumper wire and plug in the Temperature Sensor. Restart the System. Injection Valve Alarm Circuit The Alarm Circuit has three terminals in the Control Module. Compressor Terminal Box Not all wires shown “L” – Common “M” – Normally Closed “A” – Normally Open To Control Panel “L” and “M” are wired into the compressor Figure 2-11 Demand Cooling Wiring control circuit so an alarm condition removes the compressor from the line and power to the Module. A manual reset is required to call Alarm Relay The Alarm Relay is activated after a one minute attention the alarm condition. delay under the following three conditions: • Compressor discharge temperature exceeds 310°F. Condensing Unit Installation and Operation Manual 15 16 • A shorted circuit or very low Thermistor Resistance. • An open circuit or very high Thermistor Resistance. Operational Notes Demand Cooling does NOT replace head cooling fans, which may be required on low temperature applications. On indoor and outdoor condensing units, the condenser fans replace the head cooling fan. When fan cycling is applied, at least one condenser fan MUST always be ON with the compressor, so head cooling fan will be not necessary. Temperature Sensor cables must not touch any hot surfaces or the cable will be damaged. PN 0708232_K Condensing Unit Installation and Operation Manual 16 PN 0708232_K 17 COMPONENT PIPING OVERVIEW This section deals with the information necessary for installing the refrigeration lines for a condensing unit. The components are piped as completely as practical at the factory. Use only clean, dehydrated, sealed refrigeration grade copper tubing. Use dry nitrogen in the tubing during brazing to prevent the formation of copper oxide. All joints should be made with silver alloy brazing material, and use 45% silver solder for dissimilar metals. Floor Run WARNING Always use a Pressure Regulator on the nitrogen tanks. REFRIGERATION LINE RUNS Liquid Lines and suction lines must be free to expand and contract independently of each other. Do not clamp or solder them together. Ceiling Run Run supports must allow tubing to expand and contract freely. Do not exceed 100 feet without a Figure 3-1 Supporting Refrigeration Lines change of direction and / or offset. Plan proper pitching, expansion allowance and P-traps at the base of all suction risers. Use long radius elbows Through Walls or Floors Refrigeration lines run through walls or floors to reduce line resistance and breakage. must be properly insulated. Avoid running lines Avoid completely the use of 45 degree elbows. through the refrigeration cases. When this is done Install service valves at several locations for ease the lines must be adequately insulated. of maintenance and reduction of service costs. These valves must be UL approved for 410 psig minimum working pressure. Riser Insulation Insulation 2nd Layer Support Detail Condensing Unit Installation and Operation Manual Figure 3-2 Insulating a Riser 17 18 From Machine to Solid Object When mounting lines from machinery to a solid object allow line freedom for vibration to prevent metal fatigue. Reduced Riser Clamp Here Factory Clamp 10 X Pipe Diameter Figure 3-3 Vibration Allowance P-Trap Construction A P-Trap must be installed at the bottom of all suction risers to return oil to the compressors. Using Elbows Riser Keep this distance as short as possible Using P-Trap Riser Figure 3-5 Reduced Riser Factory Supplied Stubs Stub sizes provided do not automatically correspond to the line sizes necessary. It is the installer’s responsibility to supply reduction couplings. Protecting Valves and Clamps When brazing near factory installed clamps or valves be sure to protect them with a wet rag to avoid overheating. Connecting Remote Condenser • Discharge Line will be routed directly to the condenser inlet stub with a purge valve at the highest point. • Liquid Return line will be pitched downstream and provide trap less drainage to the Receiver. Purge Valve Location The purge valve will be installed at the highest point of an inverted P-Trap, with at least a 6” rise. (Use with approved recovery vessel.) WARNING Vent the Receiver Safety Relief Device properly. Figure 3-4 P-Trap Construction Reduced Riser When a reduced riser is necessary, place the reduction coupling downstream of the P-Trap. PN 0708232_K Condensing Unit Installation and Operation Manual 18 PN 0708232_K 19 Fixed Flooding Valve Piping Heat Reclaim Valve Header End of Condenser 3” Min Rise All Piping and Valves in this box are field supplied and Installed. Bleed Line to Suction Fixed Flooding Valve Liquid Return Line Receiver Heating Coil From Heat Reclaim To Heat Reclaim Bleed Line to Suction 12” Min Heat Reclaim Valve Pitch ¼” per Foot Adjustable Flooding Valve Liquid Return Line Differential Check Valve Receiver Discharge Lines Ball Valve Liquid Return Lines Check Valve Purge Valve Service Valve Figure 3-6 Remote Condensing Unit Piping Note: The Heat Reclaim Valve could be factory or field installed and depends on the customer request. Condensing Unit Installation and Operation Manual 19 20 MERCHANDISER PIPING SPECIAL PIPING FOR OPEN ROOMS Suction Line • Pitch in direction of flow. • May be reduced by one size at one third of run load and again after the second third. Do not reduce below evaporator connection size. • Suction returns from evaporators enter at the top of the branch line. An open preparation room allows heat infiltration from the rest of the store at a rate which may jeopardize total refrigeration performance. To protect the rest of the refrigeration system, open preparation evaporators must be piped with a Crankcase Pressure Regulating Valve (CPR). The CPR is field installed in the suction line(s) from the evaporator(s). And the installer is responsible for proper adjustment of the Valve. (See: Control Valve Section for adjustment procedures.) Suction Line Return 3” Loop Liquid Line Take Off RUN LENGTHS AND EQUIVALENT FEET When figuring run lengths, angle valves and 90 degrees elbows are figured as additional straight pipe. The chart below gives equivalent lengths for these components. Figure 3-7 Line Piping Inside Merchandisers Tubing Size Angle Valve Liquid Line – Off Time and Electric Defrost • May be reduced by one size after one half of the case load run. Do not reduce below evaporator connection size. • Take-offs to evaporators exit the bottom of the liquid line. Provide an expansion loop for each evaporator take-off (Minimum 3 inch diameter). /2 /8 7 /8 1 1/8 1 3/8 1 5/8 2 1/8 2 5/8 3 1/8 3 5/8 4 1/8 6 7 9 12 15 18 24 29 35 41 47 Field Connections of Heat Reclaim Each circuit of the heat reclaim coil is tagged to correspond with a specific condensing unit and must be connected only to that unit. The supply and return lines are to be installed as shown in Figure 3-6. Notice that heat reclaim could be factory or field installed, and depends on customer order. PN 0708232_K 1 5 Long Radius Elbow 90° 0.9 1.0 1.4 1.7 2.3 2.6 3.3 4.1 5.0 5.9 6.7 Table 3-1 Equivalent Feet for Angle Valve and Elbow 90º (ASHARE 1994 Refrigeration Handbook) INSULATION Additional insulation for the balance of the liquid and suction lines is recommended wherever condensation drippage is objectionable or the lines are exposed to ambient conditions. Condensing Unit Installation and Operation Manual 20 PN 0708232_K 21 REFRIGERANT LINE SIZING General Information This document supersedes all previously published line sizing data – including planning data, installation instructions, or other standalone documents. require two single point connections, one for the compressor (460V or 575V) and one for the control and defrost circuits (208-230V). When a single point connection is specified for 460V and 575V condensing units, the factory will install a transformer to supply 208-230V for just the Refer to ASHARE standards for line sizing. The control circuit. installer is responsible for sizing the piping for each application. Refer to the serial plate located on the control panel to determine wire size (MCA) and overRefrigeration Line Stubs Out current protection (MOPD). Stub sizes do not match line sizes. Reduction fittings are field supplied and installed. These are GUIDELINES FOR FIELD WIRING general guidelines. The installer is responsible to account for any factors which may affect the Condensing Unit components are wired as system. completely as possible at the factory with all work completed in accordance with UL file. All Condenser Line Sizing deviations required by governing electrical codes A Condenser Line Sizing chart is established for will be the responsibility of the installer. an equivalent pipe run of 100 feet. For longer runs use the following formula: The main lugs in the compressor control panel are sized for copper wire only, with 75° C insulation. All wiring must be in compliance with governing Table Capacity * √100/Longer Length = Longer electrical codes. Line • For 208-230/1/60 Condensing Units: Capacity To each condensing unit provide; one 208-230/1/60 branch circuit, Note: This formula applies only to remote condenser lines, and only to longer runs of these • For 208-230/3/60 Condensing Units: lines. A 25 ft run does not necessarily have double To each condensing unit provide; one the capacity of a 100 ft. run. 208-230/3/60 branch circuit, • For 460/3/60 Condensing Units: OVERVIEW To each condensing unit provide; The scope of this section is limited to main field one 460/3/60 branch circuit, wiring connections, and to the control panel. one 208/3/60 circuit – see Note 1 The standard Condensing Unit is available • For 575/3/60 Condensing Units: wired for 208-230/1/60, 208-230/3/60, 460/3/60, To each condensing unit provide; 575/3/60 or 380/3/50 compressors (note that some one 575/3/60 branch circuit, compressors may be available in all voltages). In one 208/3/60 circuit – see Note 1 either case, the control circuit is 208-230V. The standard 460V and 575V Condensing Unit Condensing Unit Installation and Operation Manual 21 22 ELECTRICAL ABOUT THESE ELECTRICAL DIAGRAMS • For 380/3/50 Condensing Units: To each condensing unit provide; one 380/3/50 branch circuit, one Neutral All diagrams show the electrical system DEenergized and in refrigeration mode. Diagrams emphasize individual circuit continuity and Note 1 – Omit when single point connection kit is logic. They aid troubleshooting and testing by identifying point-to-point connections. Color used. coding wires allows easy transfer to the control panel. The diagrams normally move from Unit Cooler Fan Wiring Off Time Defrost: the unit cooler fan should left to right so the user can read the series of be wired from the condensing unit panel or an components and their terminals which make up a circuit. outside panel. Electric Defrost: the unit cooler fan should be Generally, in a control circuit the loads are limited to coils, lights, and bells. By identifying wired from the condensing unit panel. one control circuit load and “reading” the schematic to the load, the sequence of operation Evaporator Mounted Liquid Line Solenoid Power for a liquid line solenoid can be picked up becomes obvious. Troubleshooting that circuit then breaks into test point terminals. Take only from the fan circuit. one circuit at the time. Cooler Door Switch Wiring The switch must be mounted to the cooler door Important Note: frame, and must be wired to control the field The electrical diagrams in this section show installed liquid line solenoid and evaporator fans. circuit logic. They are not intended for troubleshooting or design work. For unit cooler Door switches are wired in series. fan power, electric defrost sub circuit balance, and other location specific circuits refer to the Sizing Wire and Overcurrent Protectors Check the serial plate for Minimum Circuit schematics on control panel. Ampacity (MCA) and Maximum Overcurrent Protective Devices (MOPD), follow NEC guidelines. Defrost Controls The basic defrost circuits are shown on the wiring diagrams in this section. Other Controls When other controls are used, refer to the manual included with that control. PN 0708232_K Condensing Unit Installation and Operation Manual 22 23 PN 0708232_K 14AWG L1 L1 L1 � FAN CYCLING SEE DWG 1H81161001 CONTROL CIRCUIT PROTECTOR � IR R : B y R COMPRESSOR PROTECTOR COMPRESSOR CONTACTOR ii R �B � DEFROST PROTECTOR UNIT COOLER FAN CONTACTOR UNIT COOLER FAN PROTECTOR if DEFROST CONTACTOR BIB DEFR. SUB BRKR DIAG. HIGH OIL SEPARATOR HEATER PRESSURE CONTROL BL� BL --e-- Y R y fil fil PRESSURE CONTROL LOW B ( J.. M Ao O I 240 0- 120 I OR d ,------ � 8 B \l L1 <>--+---- R---------------�1- O I �: B ------<@-s OR-----©---8 P ---OR�B � I �--oR------t--B HEAD COOLING FAN 1 UNLOADER SOLENOID WITH LOW PRESSURE CONTROL Y� BL B T 8 CRAIG APPR BY �gg�tf WAYNE CHKD BY DEMAND RAM REV BY B 0 8------48 y t WITHOl!T OIL FAILURE CONTROL IS CN' OFF BROWN WIRE AND SPLICE BLUE TO ORANGE INJECTION SOLENOID DATE lIMP SNSR 11MAY16 rl B L2 L2 L2 L2 L2 B B I ANGLE PROTION 1uc30, c ooo1 I H // /..J. ..J (SEE DRAWING N0#3010445 FOR WIRING OPTION BLOCKS) NOTE: NOT ALL COMPONENTS ARE USED ON A SPECIFIC APPLICATION. DELETION OR ADDITION OF COMPONENTS MUST MAINTAIN CIRCUIT INTEGRllY AND PHASE BALANCE. PROTECTORS MAY BE EITHER CIRCUIT BREAKER OR FUSES. DIAGRAM-COMPR/DEFROST/UNIT COOLER:208-230V/1 PH - THERMOSTAT: WITHOUT LIQUID LINE SOLEN VALVE R------E>-j �B-B OIL AUXILIAR os t CONTACTOR SOLENOID OR � I ,-----------------8---------------� ECCAP-000 2691-A ECN B R-B-R----o---"'c PUMPDOWN i; us SWITCH LIQUID LINE SOLENOID VALVE (FIELD INSTALLED SV ) � REFRiG T'STAT REMOVE JUMPER WHEN USED FAN DELAY T'STAT UNIT COOLER _J �---BL� �e--{D-, - - - - WITHOl!T OIL FAIWRE CON'TROL OR CN' OFF BROWN WIRE AND SPICE BLUE TO ORANGE CONNECTION LOCATED IN COMPRESSOR STATOR BOX --,1-------------------------+-+--. OIL FAILURE CONTROL COPELAND 2D, 3D, 4D, 6D p T::1-- I e.-c FAN CONTACTOR #1 FAN #2 FAN --------------------------------------8-----------------------------------� APPLY 18AWG CONDUCTORS ON CONTROL CIRCUIT WIRING BELOW BL� B ______J R �BL 2 � s CH CH HEATER ll;al : b w POWER SUPPLY 208-230 VOLT 1 PHASE 60 HERTZ R R l C PHASE j_ MONITOR yNo CONT. ,--1IMER c,--FX""'! I R r I L!N--, I UNIT COOLERS I TERM BLOCKS L _J� L _J DEFR TERMINATION T'STAT H REV / SS OTHERWISE SP TOLERANCES ARE ALS .xx ±.03, .xxx ° DECIM.01ANGL � 2 23 Condensing Unit Installation and Operation Manual � � 24 R PHASE MONITOR = L1 - L1 - L1 r-1IMER B B 8 R B B. #1 FAN CONTROL CIRCUIT PROTECTOR FAN CONTACTOR #3 FAN PHASE MONITOR ell #4 FAN #5 FAN FAN CYCLING SEE DWG 1H81162001 #2 FAN R � �BB -t OIL MC-AUX os SOLENOID CONTACT � �--- BL � I DEFROST PROTECTOR DEFROST CONTACTOR R �B � OIL SEPARATOR HEATER y UNIT COOLER FAN PROTECTOR 6:TACTOR UNIT COOLER 16 6 6 COMPRESSOR PROTECTOR COMPRESSOR CONTACTOR B B B NOTE: B OR----©----8 B L2 L2 L2 L2 L2 1uc30, c4QQ1 // /..J. ..J· I � H � (SEE DWG# 3010445 FOR WIRING OPTION BLOCKS.) NOT ALL COMPONENTS ARE USED ON A SPECIFIC APPLICATION. DELETION OR ADDITION OF COMPONENTS MUST MAINTAIN CIRCUIT INTEGRl1Y AND PHASE BALANCE. PROTECTORS MAY BE EITHER CIRCUIT BREAKER OR FUSES. BL � B _____J R � BL � 6 CH 2 CH HEATER ,----- 240 0- 120 OIL FAIWRE CONTROL CORESENSE 2D, 3D, 4D, 6D � r,, IS INJECTION SOLENOID I B B � WITHOUT OIL FAIWRE CONTROL CAP OFF BROWN WIRE AND SPLICE BLUE TO ORANGE RAM REV BY OR B � OR �B HEAD COOLING FAN OR �B @ 1 ---a-f-s CRAIG APPR BY BL UNLOADER SOLENOID WITH LOW PRESSURE CONTROL B Y� WAYNE CHKD BY B L2 .xxx B �p r,{\ rl 21 � � DIAGRAM -TIMER 208-230V/3/60 SUPPLY � � � 0 Hu 5 5 m n n n ® � P ----©--s _______J o----+----- R IDIP SNSR � o--,f---------8 L1 �a--(D-, - - - - FAN DELAY T'STAT UNIT COOLER R�BL� BL DEMAND COOLING MODULE REVISION HISTORY REVISION DESCRIPTION H-DIAGRAM MAJOR RE-DESIGN. ADDED SHEET DWG #3010445 FOR DETAIL BLOCKS. PRESSURE CONTROL HIGH CONNECTION LOCATED IN COMPRESSOR STATOR BOX DATE 11MAY16 R �----------------8---------------__J REFRIG ,-------------------OR� B R REMOVE T'STAT JUMPER USED [email protected] i; PUMPDOWN u.s SWITCH WHEN B LIQUID LINE SOLENOID VALVE (FIELD INSTALLED SV ) ECN ECN-CAP-000 2691-A OR -------------------------------------8----------------------------------� #6 FAN 3 POWER SUPPLY B L2 20 8-230 VOLT � B L1 ,, 3 PHASE B 60 HERTZ CD MAIN PROTECTOR Cl B B B a... 1c NO 1 R L! r I I UNIT COOLERS I TERM BLOCKS 1 �X ""'! N L _J� L _J DEFR TERMINATION T'STAT H REV .xx 1 MATERIAL- ---I MODEL BY / DWG BY- RAM CHECKED BYWAYNE REF- SUPERSEDES APPROVED BYCRAIG DATE DRAWN - I IMAYl6 SHEET I OF 1 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE THIRD ±.03, ±.010 \ ANGLE DECIMALS 1 � 1 ° ANGLES± 2 '-V -........J PROJECTION 24 Condensing Unit Installation and Operation Manual PN 0708232_K I 25 PN 0708232_K PHASE MONITOR roITT. N L2 L1 J 4 TIMER B B B PHASE I MONITOR MAIN PROTECTOR 5 OR LLS MOTOR PROlECTOR COMPRESSOR MOTOR CONTACTOR CH B I�I B BIBIB HEATER OIL SEPARATOR B B B B I jl B I�I B BI BIB DEFR. SUB BRKR DIAG. HEATER 1 I B jl I� B CONTACTOR ill - R � BL� BL� BL 1 5 �CRANKCASE 6 CH 2 R BL - I I B I B I B L___ B B B f1 FAN f2 FAN f3 FAN #4 FAN FAN CYCLING SEE DWG 1H81163001 MOTOR CONTACTOR N.O. CONTACTS t w R � � PINK ---e--- B B ______,, HEAD COOLING FAN FAN CONTACTOR NEUTRAL TERMINAL BLOCK '/ti B B B B � NOID J_ LP-©- �. �OR-<@>- B 1 e UNLOADER SOLENOID Wml LOW PRESSURE CONTROL Y--o-r BL ----o-f-B B I OR O� � B 1R � CRAIG APPR BY NOTE: NOT ALL COMPONENTS ARE USED ON A SPECIFIC APPLICATION. DELETION OR ADDITION OF COMPONENTS MUST MAINTAIN CIRCUIT INTEGRllY AND PHASE BALANCE. B // U. I � l, � � DIAGRAM -TIMER 4 WIRE 380/3/60 VOLT � � � o Hu 5 5 m n n n ® � 1LJC:J056001 H � (SEE DRAWING N0#3010445 FOR WIRING OPTION BLOCKS) PROTECTORS MAY BE EITHER CIRCUIT BREAKER OR FUSES. B $ E:l B----------------------------� R---o-1 � AUXILIAR CONTACTOR WITHOl/T OIL FAILURE CONTROL CAP OFF BROWN WIRE AND SPLICE BLUE TO ORANGE 2 0 WAYNE CHKD BY INJECTION SOLENOID B --e-f-e---B OIL FAIWRE CONTROL COPELAND 2D, 3D, 4D, SD BL IL M B RAM REV BY _ _ _ _ _ _J i - - - - - - - - - - - - - - - - - - - - J R i - - - - - - - - - - - - R _J CONNECTION LOCATED IN COMPRESSOR STATOR BOX PRESSURE CONTROL HIGH Ao �:l TEMP SNSR REVISION HISTORY REVISION DESCRIPTION y DEMAND COOLING MODULE Y R� BL-e- BL � fil LA M PRESSURE CONTROL LOW R DATE 11MAY16 B R-JsRl- R� -t- � PUMPDOWN SWITCH LIQUID LINE SOLENOID VALVf. (FIELD INSTALLED SV) ECN ECN-CAP-0002691-A - --------R -------------------R---' 3 POWER SUPPLY 380 VOLT 3 PHASE 60 / 50 HERTZ C T NO 1 R r I I I I UNIT COOLERS I TERM BLOCKS L'T-, <>----'x� L _J�FRL _J TERMINATION T'STAT H REV H-DIAGRAM MAJOR RE-DESIGN. ADDED SHEET DWG #3010445 FOR DETAIL BLOCKS. .xxx 1 MATERIAL- ---I MODEL BY / DWG BY- RAM CHECKED BYWAYNE REF- SUPERSEDES APPROVED BYCRAIG DATE DRAWN - I IMAYl6 SHEET I OF 1 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE THIRD DECIMALS .XX ±.03, ±.010 ANGLE ° ANGLES ± 2 PROJECTION 25 Condensing Unit Installation and Operation Manual 26 B B IL2 [lJ Cl c.. B B #2 FAN #3 FAN !!l Iii PHASE MONITOR ct11J #4 FAN #5 FAN FAN CYCLING SEE DWG 1H81162001 �III #1 FAN CONTROL CIRCUIT PROTECTOR FAN CONTACTOR B IL3 MAIN PROTECTOR L1 POWER SUPPLY � 575/460 VOLT � L1 3 PHASE 60 HERTZ FUSES -- PRIMARY � +-,575V/460V/ 380V R C NO 1 L1 L1 L1 I R - - - R B itJfo R - � - P #03 - R #6 FAN DEFROST PROTECTOR UNIT COOLER FAN CONTACTOR UNIT COOLER FAN PROTECTOR III DEFROST CONTACTOR DEFR. SUB BRKR DIAG. R �B � OIL SEPARATOR HEATER DEMAND COOLING MODULE - y - CH 8 ,, l. ill R �BL L1 o---+------R S L2: '. I 8 2 ----i B - - COMPRESSOR PROTECTOR COMPRESSOR CONTACTOR 0- 240 120 INJECTION """""' �B ® OIL FAILURE CONTROL L M B 1 - 1'---------------OR oL � 1 c� PRESSURE #01 11 1� rI OR - RELAY 120V ----§-w� I --§-s �a J #02 REVISION HISTORY REVISION DESCRIPTION H-DIAGRAM MAJOR RE-DESIGN. ADDED SHEET DWG #3010445 FOR DETAIL BLOCKS. RAM REV BY ,:! 888 CRANKCASE HEATER B OR CRAIG B IH l I L2 L2 L2 L2 L2 CONT� CURRENT SENSING RELAY 8 (SEE DWG# 3010445 FOR WIRING OPTION BLOCKS.) 070..J,,c:042 8 HEAD COOLING FAN (WHEN REQ'D) �oR---t--s 7 OID WITH LOW us (::I::'\ rl DIAGRAM -ALTECH 575V/460V-3/60 SUPPLY Hussmnnn® � NOTE: NOT ALL COMPONENTS ARE USED ON A SPECIFIC APPLICATION. DELETION OR ADDITION OF COMPONENTS MUST MAINTAIN CIRCUIT INTEGRITY AND PHASE BALANCE. PROTECTORS MAY BE EITHER CIRCUIT BREAKER OR FUSES. � I P, a I RELAY I 208V B , B j BL�B _______ 6 CH 2 APPR BY y� p � B LOR� �---OR� OR � B WAYNE CHKD BY '------8----------------------' '-- Y--D--Y --EB-BL� SOLID STATE E CTS tw��� R�8t6J #01 To HvAc coNTRoL PANEL 120V - DATE 30SEP2016 DDDCJJ RELAY BOARD #0 � R-----E>-j �B B �OIL AUX OS CONTACTOR SOLENOID L � ��-� #02 - _J (WHEN REQ'D) CABLE ECN .xxx I '-----------------------------------------8-------------------------------------� SECONDARY -- 208-230V -T-RANSFORMER R � PHASE MONITOR CONT. t_ �-----R OR 20BV PRIMARY I �---BL ---n1 I SECONDARY H REV ECN-CAP-000 2691-A .xx MATERIAL- ---I MODEL BY / DWG BY- RAM CHECKED BYWAYNE APPROVED BYCRAIG REF- SUPERSEDES DATE DRAWN -30SEPl6 SHEET I OF 1 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE THIRD ±.03, ±.010 \ �� / l__ I ANGLE DECIMALS ° ANGLES + 2 '--L/ � PROJECTION 26 Condensing Unit Installation and Operation Manual � � � � � � � 8j PN 0708232_K 27 PN 0708232_K le L1 L1 L1 I I B I - a.. I I #3 FAN I jl B B B ell PHASE MONITOR #4 FAN #5 FAN FAN CYCLING SEE DWG 1H81162001 J=: III I II B #1 FAN CONTROL CIRCUIT PROTECTOR #2 FAN =10--0,0-'L--Gt-___J I -� I I MAIN PROTECTOR I� I -� B B IMER R �I FAN DELAY T'STAT UNIT COOLER #6 FAN DEFROST PROTECTOR DEFROST CONTACTOR dl B B B DEFR. SUB BRKR DIAG. R �B � OIL SEPARATOR HEATER PRESSURE CONlROL HIGH UNIT COOLER FAN PROTECTOR UNIT COOLER ���TACTOR I dl [ill] 666 B_ 120 COMPRESSOR PROTECTOR COMPRESSOR CONTACTOR B OR ,----_J OIL FAILURE CONTROL 2 2401 WAYNE CHKD BY I II B B B m OR APPR BY CRAIG 1 @) B L2 L2 L2 L2 L2 B .� CURRENT SENSING RELAY CONTACTS rl IB (SEE DWG# 3010445 FOR WIRING OPTION BLOCKS.) 1 I � � DIAGRAM -TIMER 460!575V-3/60 SUPPLY � 21 � � 0 Hu 5 5 m n n n ® � O /70..J•1 c:46 9 H �� NOTE: NOT ALL COMPONENTS ARE USED ON A SPECIFIC APPLICATION. DELETION OR ADDITION OF COMPONENTS MUST MAINTAIN CIRCUIT INTEGRITY AND PHASE BALANCE. PROTECTORS MAY BE EITHER CIRCUIT BREAKER OR FUSES. B_ Y� BL --e-f-s UNLOADER SOLENOID WITH LOW PRESSURE CONTROL OR-----t---B---­ HEAD COOLING FAN OR�B--� � P �---OR---©-B BL� B _______J R � BL 6 2 CH � CH HEATER CONNECTION LOCATED IN COMPRESSOR STATOR BOX �a--{D-, - - - - - - - - PRESSURE CONlROL LOW L1 <>-->------ R �: I RAM REV BY -----------B B y WITHOUT OIL FAILURE CONTROL � IS CAP OFF BROWN WIRE AND SPLICE BLUE TO ORANGE INJECTION SOLENOID A o>-----1 DEMAND COOLING MODULE REVISION DESCRIPTION H-DIAGRAM MAJOR RE-DESIGN. ADDED SHEET DWG #3010445 FOR DETAIL BLOCKS. REVISION HISTORY y--e---Y BL: R � fil ----BL� y DATE B ,------------------oR� B --------->-----' LIQUID LINE SOLENOID VALVE ECN ECN-CAP--000 2691--A 30SEP16 R-§-R_:_J PUMPDOWN SWITCH i; LLS B r-----------------8--------------_J R� �B B OL AUX � os CONTACTOR SOLENOID �--------------------------------------8-------------------------------------� SECONDARY 208-230V TRANSFORMER PRIMARY 575V/460V/ 380V FUSES 60 HERTZ R POWER SUPPLY VOLT 575 ' � !:� PHASE MONITOR CONT. I'° R o-----' r I I UNIT COOLERS I TERM BLOCKS -, LFT X! L _J� L _J DEFR TERMINATION T'STAT H REV �p / 1 MATERIAL- ---I MODEL BY / DWG BY- RAM CHECKED BYWAYNE REF- SUPERSEDES APPROVED BYCRAIG DATE DRAWN -30SEPl6 SHEET I OF 1 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE THIRD r,{\ � I ANGLE DECIMALS .xx ±.03, .xxx ±.0 IO \ ° ANGLES ± 2 '-V � PROJECTION 27 Condensing Unit Installation and Operation Manual 28 MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 1 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING HE OUTDOOR UNIT 208V-3PH ® 28 Condensing Unit Installation and Operation Manual PN 0708232_K 29 PN 0708232_K MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 2 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING FAN 2 & 4 208V-3PH ® 29 Condensing Unit Installation and Operation Manual 30 MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 3 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING FAN 6 208V-3PH ® 30 Condensing Unit Installation and Operation Manual PN 0708232_K 31 PN 0708232_K MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 4 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING HE OUTDOOR UNIT 380/460/575V-3PH ® 31 Condensing Unit Installation and Operation Manual 32 MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 5 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING FAN 2 & 4 380/460/575V-3PH ® 32 Condensing Unit Installation and Operation Manual PN 0708232_K 33 PN 0708232_K MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 6 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING FAN 6 380/460/575V-3PH ® 33 Condensing Unit Installation and Operation Manual 34 MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 7 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING HE OUTDOOR UNIT 208V-1PH ® 34 Condensing Unit Installation and Operation Manual PN 0708232_K 35 PN 0708232_K MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 8 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING FAN 2 & 4 208V-1PH ® 35 Condensing Unit Installation and Operation Manual 36 MATERIAL- ---MODEL BY / DWG BY- KARTHIK CHECKED BY- KARTHIK REF- SUPERSEDES: APPROVED BYKH DATE DRAWN -26SEPT19 SHEET 9 OF 9 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES. TOLERANCES ARE: THIRD DECIMALS .XX ±.03, .XXX u.010 ANGLE ANGLES ± 2° PROJECTION 0 CONDENSER FAN WIRING FAN 6 208V-1PH ® 36 Condensing Unit Installation and Operation Manual PN 0708232_K 37 PN 0708232_K DIAG INSERT COPELAND DISCUS , SEMI HERMITIC (COPELAMETIC), SCROLL y FOR - COPruND - -RECP, -COMPRESSOR. - FOR IIIZER - WITHOllf OI.CK1 MOOUl£: 8-TOL.2 TERM BLOCK SCROLL COMPRESSOR 0MB (IF USED) OR l y NO VOLTAGE MUST COME IN CONTACT WITH TERMINALS 1, 2, 3, 4, 81, 82 �1 -8 BLOCK 208-230/24V TRANSFORMER IS t 8 LIQUID INJECTOR SOUENOID BL y 2 OR MORE CON. FANS OR & p � � BITZER ECOLINE COMPRESSOR FAN/OIL RELAY 208V TO "M" ON OIL FAIUJRE OR DC � CASES R UNIT COOUER FAN DELAY T'STAT HEATER SAFETY UNIT COOLER t--¢Ej:--ffiI - FROM "I!" ON PHASE MONITOR TO L1 !ERM. BLOCK B NO TO L2 !ERM. BLOCK ---I 2 TIME DELAY RELAY AUXILIARY PROTECTOR / SE-83 OR BLOCK DESCRIPTION A-COMPRESSOR TERMINAL WIRING B-SOLID STATE MODULE WIRING C-TRAX-OIL WIRING D-UNIT COOLER FAN CONNECTION E-SCROLL LIQUID INJECTION F-HEAT TAPE WIRING G-LIQUID INJECTION - COPELAND RECIP H-CONDENSER FAN I-UNIT COOLER - FAN DELAY T'STAT J-UNIT COOLER - HEATER SAFETY K-PHASE MONITOR TIME DELAY RELAY L-COPELAND SCROLL ZL/ZB**K5E WITH NEW CORESENSE DIAGNOSTICS N-CONDENSER FAN WIRING P-ECM MOTOR WIRING A2(L2) 18 EATON TIMER A 1 (L 1) J.. I B1 ADJUSTABLE 16 {NC) TIME DELAY 15 C B TO L2 LINE ON AUXILIARY PROTECTOR STANDARD APPLICATION ORANGE WIRE TO LM TERMINAL BLOCK SSPC1, XPRT1 & CPC IPC JR RED WIRE CONNECT TO MOTOR CONTACTOR SCROLL COMPRESSORS STANDARD TIMER, SPPC1 XPRT1 AND CPC IPC JR RED WIRE TO DISCHARGE T-STAT OR IF NO T-STAT RUN RED WIRE TO CONNECT WITH BROWN WIRE FROM TRAXOIL NON SCROLL COMPRESSORS REFERANCE-EATON ADJUSTABLE TIME DELAY ORANGE WIRE CONNECT TO BLUE WIRE FROM HIGH PRESSURE CONTROL OR IF OIL FAILURE CONTROL IS USED CUT INTO ORANGE WIRE FROM "M" CONNECTION. SSPC1, XPRT1 & CPC IPC JR RED WIRE CONNECT TO BLUE WIRE FROM HIGH PRESS. CTL. (COM) TO L1<>--- 81� -t@/� REFERENCE HEAT RECLAIM WIRING #3 #4 #5 #6 208V 460V 575V = = = L1 BLACK BROWN RED L2 RED ORANGE BLACK L3 BLUE YELLOW BLUE p BR COPELAND SCROLL ZF/ZB**K5E WITH NEW CORESENSE DIAGNOSTICS (WHEN USED) Liquid Injection Shut-Off �µ��µ� CONDENSER FAN WIRING NOTES: 1 . Remove demand signal wire from terminal "D" when E2 Controller is applied. (Demand Thru RS-485) 17 7 7 7 :;I FROM CONDENSER FAN CONTACTOR r , , , ,1 WIRING NORMALl.Y CLOSED CONTACTS NORMALLY OPEN CONTACTS #1H81161001, #1H81162001, #1H81163001 LEGEND: o. � CONTROL RELAY COIL PRESSURE CONTROL OPEN ON RISE o-H-o -- -- ---- 0 T D FIELD WIRING - - FACTORY WIRING -HOUSE WIRING - HW FIELD OR HOUSE WIRING POWER DISTRIBUTION L 1 L2 L3 BLOCK (PDB) � TERMINAL BLOCK 0 BROKEN LINE INDICATES FIELD INSTAUATION O'XrO POWER WIRING • � 0-;tfo 0 WIRE COLOR CODE RED Y = YELLOW BLUE W = WHITE ORANGE BR= BROWN PURPLE B = BLACK GR= GRAY PINK � FAN FAN FAN FAN FAN FAN * FOR THIS APPLICATION SINGLE CONDENSER FAN REQUIRES CONTACTOR ALSO. NOTE: FOR FAN CYCLE CONTROL SEE FAN CYCLING DRAWINGS R = BL= OR= P = PK= PRESSURE CONTROL °);-? CLOSE ON RISE COMPRESSOR MOTOR CONTACTOR COIL COMPRESSOR COOLING § FAN MOTOR RELAY OR CONTR COIL TERMINAL BLOCK COIL IDENTIFICATION B MC = COMPRESSOR FUSE �SHOWN :: R� MC l FC = COND FAN S 24V YELLOW THERMAL CH = CRANKCASE HEATER PUMP HEAT RECLAIM OVERLOAD r = HEAT RECLAIM LOCKOUT R 230V RED SOLENOID SOLENOID UCF = UNIT COOLER FANS SPLICE DC • DEFROST DT = DEFROST THERMOSTAT WIRE CAP C ONDENSER VOLTAGE PHASE TAPE OR R = HEAT RECLAIM LOCKOUT B REAKER RELAY CONTACTS MINIMUM CIRCUIT CONDUCTOR COLOR '\ NORMAl.l.Y CLOSED WIRE SIZE BREAKER FANS (AWG) SIZE (A) 15 #2 r CONTROL s1�f o;rfi B BREAKER CONDENSER FAN �-------GRAY HEAD COOLING FAN "t-1 -1 (WHEN REQ'D) PDB c, � � PDB or Terminal Blackl � L!:!J..!!J T....... Blackl c,. nooded) c,. nooded) NOTES: USE ONLY WHEN USING 4 OR MORE ECM FANS. ONLY USED ON SINGLE POINT 208V POWER SUPPLY OR 380V WITH 120V CONTROL - -- � 1�-0-1 SINGLE CON. FAN � TO L1 SIDE OF MOTOR COIITACTOR R REFER TO TERMINAL BOX & TERMINAL PLATE FOR MOTOR CONNECTION BASED ON MOTOR VOLTAGE. OL R ��1 �--+-B BLOCK ��-��� (IF USED) UNIT COOLER FAN CONNECTION TO TR TERMINAL BLOCK COPELAND SCROLL 3-6 HP LIQUID INJECTION SOLENOID B p p LIQUID INJECTOR CURRENT SENSING RELAY SOLENOID (WHEN REQ'D) COPELAND SCROLL 7 1/2 HP AND UP LIQUID INJECTION SOLENOID W/0 PROJECTION W7 PROTECTION INSERT NEUTRAL WHITE WIRE INTO NEUTRAL LUG ON BREAKER 37 Condensing Unit Installation and Operation Manual 38 STARTUP WARNING Know whether a circuit is open at the power supply or not. Remove all power before opening control panels. Note: Some equipment has more than one power supply. Always use a pressure regulator with a nitrogen tank. Do not exceed 2 pounds of pressure and vent lines when brazing. Do not exceed 350 pounds of pressure for leak testing high side. Do not exceed 150 pounds of pressure for leak testing low side. Always follow current EPA regulations and guidelines. STARTUP Leak Testing - Visually inspect all lines and joints for proper piping practices. Isolate - Compressors – Front Seat Service Valves on Suction and Discharge WARNING Always recapture test charge in approved recovery vessel for recycling. Pressure Transducers - Close Angle Valves. Oil Levels Check oil levels for the compressor: Compressor sight glass 1/8 to 1/2 full. Open - Valves – to condenser, heat reclaim and receiver. Note: Check the oil sticker on the condensing unit before adding oil. Liquid Line Solenoid Valve - Solenoid should be energized. Test Charge Using properly regulated dry nitrogen and R22 pressurize the system with vapor only. Add dry nitrogen to bring the system pressure up to 150 psig. Using an electronic leak detector inspect all connections. If a leak is found, isolate, repair, and retest. Be sure system is at 150 psig and all valves closed to isolate the leak are opened. After the last leak is repaired and retested, the system must stand unaltered for 12 hours with no pressure drop from 150 psig. Compressors Shipped Dry Disconnect - Defrost Time Clock – Disconnect power to the clock. Verify - Refrigerant requirements for System, Compressors, and TEV’s in merchandisers and coolers. Electrical supply and component requirements. Compressors with Pre-Charged Oil as Standard H-Series Condensing Units Krack C Series Condensing Units *H-Series Condensing Units with Bitzer Compressors *Any H-Series Condensing Units selected with Bitzer Compressors will not have oil pre-charged or included as standard, but can be ordered as an option (ship loose). PN 0708232_K Condensing Unit Installation and Operation Manual 38 PN 0708232_K 39 Evacuation Nitrogen and moisture will remain in the system unless proper evacuation procedures are followed. Nitrogen left in the system may cause head pressure problems. Moisture causes TEV ice blockage, wax build up, acid oil, and sludge formation. WARNING Never trap liquid refrigerant between closed valves. A hydraulic explosion may result. Do not simply purge the system – this procedure is expensive, harmful to the environment, and may Pre-Charge Check List While the system is being evacuated preparation leave moisture and nitrogen behind. for charging can begin. During any of the pull Do not run the compressors to evacuate – downs check: this procedure introduces moisture into the compressor’s crankcase oil and does not produce Check controller Program if applicable. adequate vacuum to remove moisture from the rest of the system at normal temperatures. Merchandisers Electrical requirements and power supply Setup Electrical connections tight and clean Using all copper lines and packless valves, connect Proper fan operation an 8 CFM or larger vacuum pump to suction or Thermostat setting. liquid line. Connect one-micron vacuum gauge at the pump. Plan procedures so breaking the vacuum with refrigerant will not introduce Walk-in coolers and freezers Electrical requirements and power supply contaminates into the system. The vacuum pump Electrical connections tight and clean must be in good condition filled with fresh oil to Proper fan operation achieve desired results. Thermostat setting. Procedure Pull a vacuum to 1500 microns. If the vacuum Condensing Unit Electrical requirements and power supply fails to hold, determine the cause and correct. Electrical connections tight and clean Begin again with the first of the three required Proper fan operation evacuations. Pressure settings Defrost settings Break the vacuum with refrigerant vapor to Adjust head pressure valve a pressure of about 2 psig. Do not exceed the micron gauge transducer’s maximum pressure limit. Liquid refrigerant may cause damage to To obtain maximum energy efficiency, the ORI components through thermal shock or a pressure flooding valve should be field-adjusted to allow the minimum condensing temperature permitted surge to the transducer of the micron gauge. for the application in question, based on the compressor operating envelope. Repeat first two steps. Install the suction and liquid drier cores, if applicable. Pull a vacuum to 500 microns. Close vacuum header valves and allow system to stand for a minimum of 12 hours. Due to variations in equipment designs and installations, the ORI flooding valve may need to be adjusted to a slightly higher pressure setting to achieve proper operation of the refrigeration system.” The temperature control setpoints should be If the 500-micron vacuum holds, charging may field-adjusted to cycle off half the fans at ambient begin. If not the cause must be determined and temperatures below 40°F. corrected. Repeat the entire evacuation procedure from the first step. Condensing Unit Installation and Operation Manual 39 40 Air Cooled Condenser Electrical requirements and power supply Electrical connections tight and clean Proper fan operation Thermostat or pressure settings Damper operation, if equipped. Water Cooled Condenser Flush water lines before connecting them to water-cooled condenser. Heat Reclaim and other systems Electrical requirements and power supply Electrical connections tight and clean Component operation. Note: Remember to reinstate control to unit components jumpered to make test. Set all mechanical pressure controls. Compressor should still be isolated from the rest of the system. During the last evacuation look up and make a list of the required control settings for the system. High and low pressure, heat reclaim lockout, winter control settings, and other controls on the system should be noted. Charging Use standard procedures for charging while watching for possible problems. Check: Suction and discharge pressure Oil level Voltage differential and balance Ampere draw and balance Shut down the unit at first indication of unusual operation, locate and correct cause. Leak testing, evacuation and initial charging are now completed. Note: With non-azeotropic refrigerants, it is best to charge the entire contents of the cylinder to prevent fractionalization of the refrigerant when charging vapor. Winter Charge When charging the condensing unit equipped with winter head pressure control valve, additional refrigerant is required for winter operation. [See Table Below] Compressor Motor Rotation (Scroll) To check compressor rotation, use the following procedure: Install gauges on suction and discharge side of compressor. A momentary compressor run should cause a drop in suction header and a rise in discharge header pressure. With main disconnect OFF, switch OFF all breakers or fuses in the control panel. Turn ON main disconnect. Condenser Size Summer Charge (pounds) Winter Charge (pounds) A 1 6 B 3 13 C 3 13 D 4 17 E 6 26 F 8 34 J 13 56 K 7 30 *Charges Based on R407A PN 0708232_K Condensing Unit Installation and Operation Manual 40 PN 0708232_K 41 Look for the light on the single phase protector. If it is not lit, turn OFF the main disconnect. Have the field connections to the main breaker of the unit corrected so the phase protector indicates phase alignment (The light is lit). • Winter controls • TEV superheat adjustment • High and low pressure controls Turn ON the main disconnect. • Thermostat settings Momentarily turn ON the compressor and verify correct pumping direction. If the compressor is rotating backwards, change two legs on the load side of the compressor contactor. • Adjustments to electronic controls • Inlet / Outlet water temperature (water cooled units only) Note: DO NOT run compressors for more than 10 seconds during test. • Reinstall the wire grille on the front side of the unit enclosure. Final Checks Once the system is up and running it is the responsibility of the installer to see that all the fine adjustments are made so the Condensing Unit delivers maximum temperature performance and efficiency for the customer. These include: • Make sure electrical enclosure is properly grounded, and reinstall panel door after service. • Confirm ORI flooding valve setpoint (when applied). • Confirm fan-cycling temperature-control setpoint (outdoor High-Efficiency units). • Confirm factory-installed scroll compressor terminal rain cover (when supplied) is properly re-installed on outdoor units after service. The black ABS cover is secured to the compressor shell with heat-resistant webbing and a squeezerelease buckle. • Thoroughly inspect all field piping while the equipment is running and add supports where line vibration occurs. Be sure additional supports do not conflict with pipe expansion and contraction. When condition space is completely stocked, check the operation of the system again. At 48 hours of operation, replace the liquid drier and suction filter cores (if applicable). At 90 days, recheck the entire system, including all field wiring. Defrost scheduling and timing Condenser controls Condensing Unit Installation and Operation Manual 41 42 MAINTENANCE This Procedure is not designed to cover system Remove bolts from suction and discharge service changeover to a different refrigerant. valves. COMPRESSOR REPLACEMENT Since each machine room tends to be unique, plan carefully as to how you will move the compressor without harming personnel, equipment or the building. Before beginning removal of old compressor make replacement unit ready to install: Verify: Replacement compressor Electrical requirements Refrigerant application Capacity Piping hookup location and design Suction and discharge gaskets Mounting requirements Remove mounting bolts. When moving the compressor, use a come-along, hoist or hydraulic lift to carry the weight. Do not use the piping or panel to support a hoist or come-along. Do not use ceiling trusses to support a hoist or come-along. The rear support channel on the rack or a properly constructed ceiling rail may be used to support a hoist or come-along. To make hookup and lifting easier, an eyebolt may be installed in the rear top of the compressor head. Have compressor in an easily accessible position, uncrated and unbolted from shipping pallets. If a compressor removal table is used, slide the compressor fully on to the table, then roll table to Disconnect Electrical Supply: overhead hoist or hydraulic lift area. Turn off motor and control panel power supplies to the Condensing Unit. When the old compressor has been removed, clean the suction and discharge service valve Turn off control circuit and open all compressor gasket surfaces to shiny metal. Clean the gasket circuit breakers or fuses. surfaces on the new compressor to shiny metal. Be careful not to groove or round the surfaces. Tag and remove electrical wires and conduit from Gasket surfaces must be clean to prevent leaking. the compressor. Install the new compressor in reverse order of Isolate Compressor: removal. Do not open the new compressor to the Front seat Suction and Discharge Service Valves. system until after it has been leak tested and triple Close oil supply and equalizing lines. evacuated. Bleed compressor pressure through both discharge REPLACING DRIER AND FILTER CORES and suction access ports into an approved recovery vessel. Shut down the system. Isolate the core to be replaced and bleed off pressure into an approved Remove externally mounted components which recovery vessel. Open housing, replace core and will be re-used on the replacement compressor. close up. Pressurize, leak test and bring back into line. Plug holes to compressor manufacturer’s specifications. PN 0708232_K Condensing Unit Installation and Operation Manual 42 PN 0708232_K 43 APPENDIX A – DIMENSION DRAWINGS Condensing Unit Installation and Operation Manual 43 44 HIGH EFFICIENCY H-SERIES SMALL SIZE INDOOR UNIT STANDARD BASE "HxSx-xxxxxxx-xx-x" WEIGHT: 400 LBS CONTROL PANEL FACING LEFT END OF UNIT 40.2 MOUNTING DIMENSIONS TOP VIEW 38.0 41.7 45.9 FRONT VIEW 28.0 MOUNTING DIMENSIONS O .50 MOUNTING HOLES 4 PLACES PIPING 24.4 EXTENSION 6.0 MAX. INFORMATION SUBJECT TO CHANGE DOC REV R PD-000000004 E HIGH EFFICIENCY H-SERIES SMALL INDOOR STD BASE RIGHT SIDE VIEW DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 3 44 Condensing Unit Installation and Operation Manual PN 0708232_K 32.1 LEFT SIDE VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 45.9 L X 32.1 W X 24.4 H. SWN 1.0 SUBMITTAL SHEET SIZE D 45 PN 0708232_K LIQUID LINE OUTLET LOCATION 13.5 14.6 PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT MAIN POWER CONNECTION BACK SIDE OF CONTROL PANEL RECEIVER DOC REV R PD-000000004 E HIGH EFFICIENCY H-SERIES SMALL INDOOR STD BASE LIQUID LINE OUTLET LOCATION ACCUMULATOR SUCTION LINE INLET LOCATION CONDENSER (ELECTROFIN COATING OPTIONAL) BASE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 2 OF 3 45 Condensing Unit Installation and Operation Manual CONTROL PANEL 5.4 SUCTION LINE INLET LOCATION 5.2 COMPRESSOR (VARIOUS MODELS OPTIONAL) ISO VIEW INFORMATION SUBJECT TO CHANGE SUCTION FILTER NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 45.9 L X 32.1 W X 24.4 H. SWN 1.0 SUBMITTAL SHEET SIZE D 46 48.0 42.0 LOUVERED WALL 30.0 SHEET 3 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES 30.0 30.0 CLEARANCE BETWEEN INLET OF CONDENSER AND INSIDE OF LOUVERED WALL MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. LIVE PANEL WALL CONTROL PANEL FACING LEFT END OF UNIT INFORMATION SUBJECT TO CHANGE DOC HIGH EFFICIENCY H-SERIES SMALL INDOOR STD BASE REV R PD-000000004 E 46 Condensing Unit Installation and Operation Manual PN 0708232_K 42" CLEARANCE BETWEEN CONTROL PANEL & ANY WALL. 48" CLEARANCE BETWEEN CONTROL PANEL & ANY LIVE PANEL. NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 45.9 L X 32.1 W X 24.4 H. SWN 1.0 SUBMITTAL SHEET SIZE D 47 PN 0708232_K CONTROL PANEL FACING LEFT END OF UNIT HIGH EFFICIENCY H-SERIES MEDIUM SIZE INDOOR UNIT STANDARD BASE "HxSx-xxxxxxx-xx-x" WEIGHT: 650 LBS. 34.9 LEFT SIDE VIEW 28.2 MOUNTING DIMENSIONS 41.9 O .50 MOUNTING HOLES 4 PLACES PIPING EXTENSION 6.0 MAX. SHEET 1 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES RIGHT SIDE VIEW ISO VIEW INFORMATION SUBJECT TO CHANGE DOC HIGH EFFICIENCY H-SERIES MEDIUM INDOOR STD BASE REV R PD-000000005 E 47 Condensing Unit Installation and Operation Manual 45.8 MOUNTING DIMENSIONS TOP VIEW 44.0 48.0 52.0 FRONT VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 52.0 L X 34.9 W X 41.9 H. SWN 1.0 SUBMITTAL SHEET SIZE D 48 13.5 14.7 5.3 CONTROL PANEL RECEIVER LIQUID LINE OUTLET LOCATION 5.5 SUCTION FILTER COMPRESSOR (VARIOUS MODELS OPTIONAL) CONDENSER (ELECTROFIN COATING OPTIONAL) LIQUID LINE OUTLET LOCATION DOC REV R PD-000000005 E HIGH EFFICIENCY H-SERIES MEDIUM INDOOR STD BASE SUCTION LINE INLET LOCATION ACCUMULATOR SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES BASE MAIN POWER CONNECTION BACK SIDE OF CONTROL PANEL ISO VIEW INFORMATION SUBJECT TO CHANGE 48 Condensing Unit Installation and Operation Manual PN 0708232_K SUCTION LINE INLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 52.0 L X 34.9 W X 41.9 H. SWN 1.0 SUBMITTAL SHEET SIZE D 49 PN 0708232_K LOUVERED WALL 30.0 30.0 CLEARANCE BETWEEN INLET OF CONDENSER AND INSIDE OF LOUVERED WALL 48.0 42.0 CONTROL PANEL FACING LEFT END OF UNIT SHEET 3 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES 30.0 INFORMATION SUBJECT TO CHANGE DOC REV R PD-000000005 E HIGH EFFICIENCY H-SERIES MEDIUM INDOOR STD BASE 49 Condensing Unit Installation and Operation Manual MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. LIVE PANEL WALL 42" CLEARANCE BETWEEN CONTROL PANEL & ANY WALL. 48" CLEARANCE BETWEEN CONTROL PANEL & ANY LIVE PANEL. NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 52.0 L X 34.9 W X 41.9 H. SWN 1.0 SUBMITTAL SHEET SIZE D 50 HIGH EFFICIENCY H-SERIES LARGE SIZE INDOOR UNIT STANDARD BASE "HxSx-xxxxxxx-xx-x" WEIGHT: 1,250 LBS. CONTROL PANEL FACING LEFT END OF UNIT 81.8 MOUNTING HOLES TOP VIEW 80.0 84.0 88.0 28.2 MOUNTING HOLES 42.0 O .50 MOUNTING HOLES 4 PLACES PIPING EXTENSION 6.0 MAX. INFORMATION SUBJECT TO CHANGE DOC REV R PD-000000006 D HIGH EFFICIENCY H-SERIES LARGE INDOOR STD BASE RIGHT SIDE VIEW DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 3 50 Condensing Unit Installation and Operation Manual PN 0708232_K 34.9 LEFT SIDE VIEW FRONT VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 88.0 L X 34.9 W X 42.0 H. SWN 1.0 SUBMITTAL SHEET SIZE D 51 PN 0708232_K SUCTION LINE INLET LOCATION LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT 13.5 14.8 CONTROL PANEL 6.2 5.4 RECEIVER DOC REV R PD-000000006 D HIGH EFFICIENCY H-SERIES LARGE INDOOR STD BASE LIQUID LINE OUTLET LOCATION SUCTION LINE INLET LOCATION ACCUMULATOR CONDENSER (ELECTROFIN COATING OPTIONAL) BASE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 2 OF 3 51 Condensing Unit Installation and Operation Manual MAIN POWER CONNECTION BACK SIDE OF CONTROL PANEL SUCTION FILTER INFORMATION SUBJECT TO CHANGE ISO VIEW COMPRESSOR (VARIOUS MODELS OPTIONAL) NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 88.0 L X 34.9 W X 42.0 H. SWN 1.0 SUBMITTAL SHEET SIZE D 52 42.0 48.0 LOUVERED WALL 30.0 30.0 CLEARANCE BETWEEN INLET OF CONDENSER AND INSIDE OF LOUVERED WALL MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. LIVE PANEL WALL CONTROL PANEL FACING LEFT END OF UNIT 30.0 INFORMATION SUBJECT TO CHANGE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC REV R PD-000000006 D HIGH EFFICIENCY H-SERIES LARGE INDOOR STD BASE 52 Condensing Unit Installation and Operation Manual PN 0708232_K 42" CLEARANCE BETWEEN CONTROL PANEL & ANY WALL. 48" CLEARANCE BETWEEN CONTROL PANEL & ANY LIVE PANEL. NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 88.0 L X 34.9 W X 42.0 H. SWN 1.0 SUBMITTAL SHEET SIZE D 53 PN 0708232_K MAIN ELECTRICAL CONNECTION CONTROL PANEL FACING LEFT END OF UNIT HIGH EFFICIENCY H-SERIES EXTRA LARGE SIZE INDOOR UNIT STANDARD BASE "HxSx-xxxxxxx-xx-x" WEIGHT: 1,575 LBS. 34.9 LEFT HAND VIEW 96.8 MOUNTING DIMENSIONS TOP VIEW 95.0 99.0 103.0 FRONT VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 103.0 L X 34.9 W X 54.4 H. 28.2 MOUNTING DIMENSIONS PIPING EXTENSION 54.4 6.00 MAX. INFORMATION SUBJECT TO CHANGE RIGHT SIDE VIEW DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 3 REV R PD-000000007 D HIGH EFFICIENCY H-SERIES EXTRA LARGE INDOOR STD BASE DOC SWN 1.0 SUBMITTAL SHEET SIZE D 53 Condensing Unit Installation and Operation Manual 54 SUCTION LINE INLET LOCATION 12.8 14.8 DOC REV R PD-000000007 D HIGH EFFICIENCY H-SERIES EXTRA LARGE INDOOR STD BASE LIQUID LINE OUTLET LOCATION CONDENSER (ELECTROFIN COATING OPTIONAL) MAIN POWER CONNECTION BACK SIDE OF CONTROL PANEL COMPRESSOR (VARIOUS MODELS OPTIONAL) SUCTION FILTER ACCUMULATOR RECEIVER CONTROL PANEL 5.5 6.7 ISO VIEW SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES SUCTION LINE INLET LOCATION INFORMATION SUBJECT TO CHANGE 54 Condensing Unit Installation and Operation Manual PN 0708232_K LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 103.0 L X 34.9 W X 54.4 H. SWN 1.0 SUBMITTAL SHEET SIZE D 55 PN 0708232_K 48.0 42.0 CONTROL PANEL FACING LEFT END OF UNIT LOUVERED WALL SHEET 3 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES 30.00 CLEARANCE BETWEEN INLET OF CONDENSER AND INSIDE OF LOUVERED WALL 30.0 INFORMATION SUBJECT TO CHANGE 30.0 REV R PD-000000007 D HIGH EFFICIENCY H-SERIES EXTRA LARGE INDOOR STD BASE DOC 55 Condensing Unit Installation and Operation Manual MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. LIVE PANEL WALL 42" CLEARANCE BETWEEN CONTROL PANEL & ANY WALL. 48" CLEARANCE BETWEEN CONTROL PANEL & ANY LIVE PANEL. NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 103.0 L X 34.9 W X 54.4 H. SWN 1.0 SUBMITTAL SHEET SIZE D 56 HIGH EFFICIENCY H-SERIES SMALL SIZE INDOOR UNIT HEAVY DUTY BASE "HxHx-xxxxxxx-xx-x" WEIGHT: 400 LBS. MAIN ELECTRICAL CONNECTION BEHIND CONTROL PANEL TOP VIEW 39.0 44.9 FRONT VIEW PIPING EXTENSION 32.1 6.0 MAX. 26.2 MOUNTING DIMENSIONS .625 MOUNTING HOLES 4 PLACES RIGHT SIDE VEW INFORMATION SUBJECT TO CHANGE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 3 DOC HIGH EFFICIENCY H-SERIES SMALL INDOOR HD BASE REV R PD-000000009 D 56 Condensing Unit Installation and Operation Manual PN 0708232_K 29.6 LEFT SIDE VIEW RECEIVER 35.7 MOUNTING DIMENSIONS BOTTOM VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 44.9 L X 29.6 W X 32.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 57 PN 0708232_K 11.8 A A 14.0 11.0 LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT CONTROL PANEL 13.1 CONDENSER (ELECTROFIN COATING OPTIONAL) HIGH EFFICIENCY H-SERIES SMALL INDOOR HD BASE REV PD-000000009 D R ACCUMULATOR SUCTION LINE INLET LOCATION LIQUID LINE OUTLET LOCATION FRONT TO BACK DOC BASE ASSEMBLY SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES ISO VIEW MAIN POWER CONNECTION BACK SIDE OF CONTROL PANEL SUCTION FILTER COMPRESSOR (VARIOUS MODELS OPTIONAL) 1.0 5.1 INFORMATION SUBJECT TO CHANGE 57 Condensing Unit Installation and Operation Manual SUCTION LINE INLET LOCATION RECEIVER 5.1 SECTION A-A NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 44.9 L X 29.6 W X 32.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 58 MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. LOUVERED WALL 42" CLEARANCE BETWEEN CONTROL PANEL & ANY WALL. 30.0 30.0 CLEARANCE BETWEEN INLET OF CONDENSER AND INSIDE OF LOUVERED WALL 30.0 CONTROL PANEL 48.0 48" CLEARANCE BETWEEN CONTROL PANEL & ANY LIVE PANEL. INFORMATION SUBJECT TO CHANGE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC HIGH EFFICIENCY H-SERIES SMALL INDOOR HD BASE REV R PD-000000009 D 58 Condensing Unit Installation and Operation Manual PN 0708232_K 42.0 WALL LIVE PANEL NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 44.9 L X 29.6 W X 32.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 59 PN 0708232_K MAIN ELECTRICAL CONNECTION HIGH EFFICIENCY H-SERIES MEDIUM SIZE INDOOR UNIT HEAVY DUTY BASE "HxHx-xxxxxxx-xx-x" WEIGHT: 650 LBS. 37.3 LEFT SIDE VIEW RECEIVER 49.6 PIPE EXTENSION 6.00 MAX. 34.0 MOUNTING DIMENSIONS O .05 MOUNTING HOLES 4 PLACES RIGHT SIDE VIEW INFORMATION SUBJECT TO CHANGE DOC HIGH EFFICIENCY H-SERIES MEDIUM INDOOR HD BASEREV R PD-000000010 D ISO VIEW DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 3 59 Condensing Unit Installation and Operation Manual TOP VIEW 46.9 47.0 53.0 FRONT VIEW 43.7 MOUNTING DIMENSIONS BOTTOM VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 53.0 L X 37.3 W X 49.6 H. SWN 1.0 SUBMITTAL SHEET SIZE D 60 14.0 A A SUCTION FILTER COMPRESSOR (VARIOUS MODELS OPTIONAL) CONTROL PANEL SUCTION LINE INLET LOCATION RECEIVER 13.2 5.1 1.0 5.1 ISO VIEW DOC ACCUMULATOR SUCTION LINE INLET LOCATION R PD-000000010 D HIGH EFFICIENCY H-SERIES MEDIUM INDOOR HD BASEREV INLET LINE OUTLET LOCATION FRONT TO BACK RECEIVER CONDENSER (ELECTROFIN COATING OPTIONAL) SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES BASE ASSEMBLY INFORMATION SUBJECT TO CHANGE 60 Condensing Unit Installation and Operation Manual PN 0708232_K 14.8 LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT SECTION A-A NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 53.0 L X 37.3 W X 49.6 H. SWN 1.0 SUBMITTAL SHEET SIZE D 61 PN 0708232_K MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. LOUVERED WALL 30.0 42" CLEARANCE BETWEEN CONTROL PANEL & ANY WALL. 48" CLEARANCE BETWEEN CONTROL PANEL & ANY LIVE PANEL. INFORMATION SUBJECT TO CHANGE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC HIGH EFFICIENCY H-SERIES MEDIUM INDOOR HD BASEREV R PD-000000010 D 61 Condensing Unit Installation and Operation Manual 30.0 CLEARANCE BETWEEN INLET OF CONDENSER AND INSIDE OF LOUVERED WALL 30.0 48.0 CONTROL PANEL 42.0 WALL LIVE PANEL NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 53.0 L X 37.3 W X 49.6 H. SWN 1.0 SUBMITTAL SHEET SIZE D 62 HIGH EFFICIENCY H-SERIES LARGE SIZE INDOOR UNIT HEAVY DUTY BASE "HxHx-xxxxxxx-xx-x" WEIGHT: 1,250 LBS. MAIN ELECTRICAL CONNECTION TOP VIEW 46.9 53.7 FRONT VIEW PIPING EXTENSION 6.0 MAX. 34.0 MOUNTING DIMENSIONS O .56 MOUNTING HOLES 4 PLACES 90.7 RIGHT SIDE VIEW INFORMATION SUBJECT TO CHANGE DRAWN: DEC 2019 DOC R PD-000000011 D HIGH EFFICIENCY H-SERIES LARGE INDOOR HD BASEREV ISO VIEW DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 2 62 Condensing Unit Installation and Operation Manual PN 0708232_K 37.5 LEFT SIDE VIEW 43.7 MOUNTING DIMENSIONS NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 53.7 L X 37.5 W X 90.7 H. SWN 1.0 SUBMITTAL SHEET SIZE D 63 PN 0708232_K MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. LOUVERED WALL 30.0 42" CLEARANCE BETWEEN CONTROL PANEL & ANY WALL. 48" CLEARANCE BETWEEN CONTROL PANEL & ANY LIVE PANEL. INFORMATION SUBJECT TO CHANGE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 2 OF 2 DOC HIGH EFFICIENCY H-SERIES LARGE INDOOR HD BASEREV R PD-000000011 D 63 Condensing Unit Installation and Operation Manual 30.0 CLEARANCE BETWEEN INLET OF CONDENSER AND INSIDE OF LOUVERED WALL 30.0 48.0 CONTROL PANEL 42.0 WALL LIVE PANEL NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 53.7 L X 37.5 W X 90.7 H. SWN 1.0 SUBMITTAL SHEET SIZE D 64 HIGH EFFICIENCY H-SERIES EXTRA LARGE SIZE INDOOR UNIT HEAVY DUTY BASE "HxHx-xxxxxxx-xx-x" WEIGHT: 1,575 LBS. MAIN ELECTRICAL CONNECTION TOP VIEW 95.0 101.1 FRONT VIEW PIPING EXTENSION 6.0 MAX. 31.5 MOUNTING DIMENSIONS 62.1 RIGHT SIDE VIEW O .562 MOUNTING HOLES 6 PLACES INFORMATION SUBJECT TO CHANGE ISO VIEW DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 3 REV R PD-000000012 D HIGH EFFICIENCY H-SERIES EXTRA LARGE INDOOR HD BASE DOC 64 Condensing Unit Installation and Operation Manual PN 0708232_K 34.8 LEFT SIDE VIEW RECEIVER 44.5 MOUNTING DIMENSIONS BOTTOM VIEW 47.4 MOUNTING DIMENSIONS NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 101.1 L X 34.8 W X 62.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 65 PN 0708232_K A A 14.0 14.6 SUCTION LINE INLET LOCATION RECEIVER LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT 14.4 1.0 5.1 ACCUMULATOR COMPRESSOR (VARIOUS MODELS OPTIONAL) ISO VIEW DOC REV R PD-000000012 D HIGH EFFICIENCY H-SERIES EXTRA LARGE INDOOR HD BASE SUCTION LINE INLET LOCATION LIQUID LINE OUTLET LOCATION FRONT TO BACK SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES BASE ASSEMBLY CONDENSER (ELECTROFIN COATING OPTIONAL) INFORMATION SUBJECT TO CHANGE 65 Condensing Unit Installation and Operation Manual CONTROL PANEL 5.1 SECTION A-A NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 101.1 L X 34.8 W X 62.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 66 MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. LOUVERED WALL 42" CLEARANCE BETWEEN CONTROL PANEL & ANY WALL. 30.0 CLEARANCE BETWEEN INLET OF CONDENSER AND INSIDE OF LOUVERED WALL 48.0 CONTROL PANEL 42.0 48" CLEARANCE BETWEEN CONTROL PANEL & ANY LIVE PANEL. 30.00 INFORMATION SUBJECT TO CHANGE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 REV R PD-000000012 D HIGH EFFICIENCY H-SERIES EXTRA LARGE INDOOR HD BASE DOC 66 Condensing Unit Installation and Operation Manual PN 0708232_K 30.0 WALL LIVE PANEL NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 101.1 L X 34.8 W X 62.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 67 PN 0708232_K MAIN ELECTRICAL CONNECTION LOCATION CONTROL PANEL FACING LEFT END OF UNIT HIGH EFFICIENCY H-SERIES SMALL SIZE OUTDOOR UNIT STANDARD BASE "HxSx-xxxxxxx-xx-x" WEIGHT: 400 LBS. 32.6 LEFT SIDE VIEW TOP VIEW 40.2 MOUNTING DIMENSIONS 38.00 41.7 45.9 FRONT VIEW HINGED TOP FRONT PANEL REV R PD-000000013 D HIGH EFFICIENCY H-SERIES SMALL OUTDOOR STD BASE BASE RIGHT END PANEL FIXED TOP REAR PANEL DOC 67 Condensing Unit Installation and Operation Manual CONTROL PANEL 28.0 MOUNTING DIMENSIONS FRONT GRILLE ISO VIEW SHEET 1 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES RIGHT SIDE VIEW INFORMATION SUBJECT TO CHANGE 24.4 O .500 MOUNTING HOLES 4 PLACES PIPING EXTENSION NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 45.9 L X 32.6 W X 24.4 H. SWN 1.0 SUBMITTAL SHEET SIZE D 68 13.5 14.6 CONTROL PANEL 5.4 SUCTION LINE INLET LOCATION 5.2 RECEIVER COMPRESSOR (VARIOUS MODELS OPTIONAL) SUCTION FILTER SUCTION LINE INLET LOCATION CONDENSER (ELECTROFIN COATING OPTIONAL) DOC REV R PD-000000013 D HIGH EFFICIENCY H-SERIES SMALL OUTDOOR STD BASE LIQUID LINE OUTLET LOCATION ACCUMULATOR BASE SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES ISO VIEW WITH OUTDOOR HOUSING REMOVED FOR CLARITY INFORMATION SUBJECT TO CHANGE 68 Condensing Unit Installation and Operation Manual PN 0708232_K LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 45.9 L X 32.6 W X 24.4 H. SWN 1.0 SUBMITTAL SHEET SIZE D 69 PN 0708232_K EXHAUST 48.0 INTAKE EXHAUST 48.0 EXHAUST EXHAUST INTAKE EXHAUST EXHAUST EXHAUST INTAKE EXHAUST EXHAUST DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC REV R PD-000000013 D HIGH EFFICIENCY H-SERIES SMALL OUTDOOR STD BASE CLEARANCE ON MULTIPLE UNIT APPLICATION PROVIDE CLEARANCES AS SHOWN TO ENSURE ADEQUATE AIRFLOW, REDUCE THE POTENTIAL FOR AIR RECIRCULATION AND FACILITATE SERVICE ACCESSIBILITY. 60.00 CLEARANCE BETWEEN MULTIPLE UNIT SIDE EXHAUSTS INTAKE EXHAUST 180.00 CLEARANCE BETWEEN REAR UNIT EXHAUST AND FRONT UNIT INTAKE EXHAUST EXHAUST INFORMATION SUBJECT TO CHANGE 69 Condensing Unit Installation and Operation Manual MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. 48.0 CONTROL PANEL INSIDE 48.0 CLEARANCE ON A SINGLE UNIT APPLICATION NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 45.9 L X 32.6 W X 24.4 H. SWN 1.0 SUBMITTAL SHEET SIZE D 70 FIELD LOCATE MAIN ELECTRICAL CONNECTION IN THIS AREA CONTROL PANEL FACING LEFT END OF UNIT TOP VIEW 45.8 MOUNTING DIMENSIONS 44.6 44.0 48.0 52.0 CONTROL PANEL 28.2 MOUNTING DIMENSIONS 42.0 O .500 MOUNTING HOLES 4 PLACES PIPING EXTENSION 6.0 MAX. ISO VIEW FRONT GRILLE DOC BASE HIGH EFFICIENCY H-SERIES MEDIUM OUTDOOR STD BASE REV PD-000000014 E R RIGHT END PANEL HINGED TOP FRONT PANEL FIXED TOP REAR PANEL SHEET 1 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES RIGHT SIDE VIEW INFORMATION SUBJECT TO CHANGE 70 Condensing Unit Installation and Operation Manual PN 0708232_K HIGH EFFICIENCY H-SERIES MEDIUM SIZE OUTDOOR UNIT STANDARD BASE "HxSx-xxxxxxx-xx-x" WEIGHT: 650 LBS. 35.0 LEFT SIDE VIEW FRONT VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 52.0 L X 35.0 W X 42.0 H. SWN 1.0 SUBMITTAL SHEET SIZE D 71 PN 0708232_K SUCTION LINE INLET LOCATION 13.5 14.8 PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT RECEIVER CONDENSER (ELECTROFIN COATING OPTIONAL) LIQUID LINE OUTLET LOCATION SUCTION LINE INLET LOCATION ACCUMULATOR DOC REV R PD-000000014 E HIGH EFFICIENCY H-SERIES MEDIUM OUTDOOR STD BASE BASE ASSEMBLY DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 2 OF 3 71 Condensing Unit Installation and Operation Manual CONTROL PANEL 5.5 LIQUID LINE OUTLET LOCATION 5.3 COMPRESSOR (VARIOUS MODELS OPTIONAL) SUCTION FILTER INFORMATION SUBJECT TO CHANGE ISO VIEW WITH OUTDOOR HOUSING REMOVED FOR CLARITY NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 52.0 L X 35.0 W X 42.0 H. SWN 1.0 SUBMITTAL SHEET SIZE D 72 INTAKE 48.0 EXHAUST EXHAUST 48.0 MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. EXHAUST 48.0 CONTROL PANEL FACING LEFT END OF UNIT EXHAUST INTAKE EXHAUST EXHAUST 60.00 INTAKE EXHAUST EXHAUST CLEARANCE ON MULTIPLE UNIT APPLICATION CLEARANCE BETWEEN MULTIPLE UNIT SIDE EXHAUSTS EXHAUST INTAKE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC REV R PD-000000014 E HIGH EFFICIENCY H-SERIES MEDIUM OUTDOOR STD BASE PROVIDE CLEARANCES AS SHOWN TO ENSURE ADEQUATE AIRFLOW, REDUCE THE POTENTIAL FOR AIR RECIRCULATION AND FACILITATE SERVICE ACCESSIBILITY. EXHAUST 180.00 CLEARANCE BETWEEN REAR UNIT EXHAUST AND FRONT UNIT INTAKE EXHAUST EXHAUST INFORMATION SUBJECT TO CHANGE 72 Condensing Unit Installation and Operation Manual PN 0708232_K 48.0 CLEARANCE ON A SINGLE UNIT APPLICATION NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 52.0 L X 35.0 W X 42.0 H. SWN 1.0 SUBMITTAL SHEET SIZE D 73 PN 0708232_K FIELD LOCATE MAIN ELECTRICAL CONNECTION IN THIS AREA CONTROL PANEL FACING LEFT END OF UNIT HIGH EFFICIENCY H-SERIES LARGE SIZE OUTDOOR UNIT STANDARD BASE "HxSx-xxxxxxx-xx-x" WEIGHT: 1,250 LBS 35.0 LEFT SIDE VIEW 81.8 MOUNTING DIMENSIONS TOP VIEW 80.0 84.0 88.0 FRONT VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 88.0 L X 35.0 W X 41.9 H. CONTROL PANEL HINGED TOP FRONT PANEL BASE RIGHT END PANEL FIXED TOP REAR PANEL ISO VIEW REV R PD-000000015 D HIGH EFFICIENCY H-SERIES LARGE OUTDOOR STD BASE DOC 73 Condensing Unit Installation and Operation Manual 28.2 MOUNITING DIMENSIONS 41.9 FRONT GRILLE O .500 MOUNTING HOLES 6 PLACES PIPING EXTENSION 6.0 MAX. SHEET 1 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES RIGHT SIDE VIEW INFORMATION SUBJECT TO CHANGE SWN 1.0 SUBMITTAL SHEET SIZE D 74 13.5 14.8 CONTROL PANEL 5.4 6.2 RECEIVER COMPRESSOR (VARIOUS MODELS OPTIONAL) CONDENSER (ELECTROFIN COATING OPTIONAL) DOC REV R PD-000000015 D HIGH EFFICIENCY H-SERIES LARGE OUTDOOR STD BASE LIQUID LINE OUTLET LOCATION SUCTION LINE INLET LOCATION ACCUMULATOR BASE SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES ISO VIEW WITH OUTDOOR HOUSING REMOVED FOR CLARITY INFORMATION SUBJECT TO CHANGE 74 Condensing Unit Installation and Operation Manual PN 0708232_K SUCTION LINE INLET LOCATION LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 88.0 L X 35.0 W X 41.9 H. SWN 1.0 SUBMITTAL SHEET SIZE D 75 PN 0708232_K 48.0 INTAKE EXHAUST 48.0 EXHAUST EXHAUST INTAKE EXHAUST INTAKE 180.0 CLEARANCE BETWEEN REAR UNIT EXHAUST AND FRONT UNIT INTAKE EXHAUST EXHAUST EXHAUST 60.0 CLEARANCE BETWEEN MULTIPLE UNIT SIDE EXHAUSTS INTAKE EXHAUST DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC EXHAUST REV R PD-000000015 D HIGH EFFICIENCY H-SERIES LARGE OUTDOOR STD BASE CLEARANCE ON MULTIPLE UNIT APPLICATION PROVIDE CLEARANCES AS SHOWN TO ENSURE ADEQUATE AIRFLOW, REDUCE THE POTENTIAL FOR AIR RECIRCULATION AND FACILITATE SERVICE ACCESSIBILITY. EXHAUST INFORMATION SUBJECT TO CHANGE 75 Condensing Unit Installation and Operation Manual MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. EXHAUST 48.0 CONTROL PANEL FACING LEFT END OF UNIT 48.0 CLEARANCE ON A SINGLE UNIT APPLICATION EXHAUST NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 88.0 L X 35.0 W X 41.9 H. SWN 1.0 SUBMITTAL SHEET SIZE D 76 HIGH EFFICIENCY H-SERIES EXTRA LARGE SIZE OUTDOOR UNIT STANDARD BASE "HxSx-xxxxxxx-xx-x" WEIGHT: 1,575 LBS. CONTROL PANEL FACING LEFT END OF UNIT FIELD LOCATE MAIN ELECTRICAL CONNECTION IN THIS AREA TOP VIEW 95.6 95.0 99.0 103.0 HINGED TOP FRONT PANEL CONTROL PANEL 54.5 FRONT GRILLE PIPING EXTENSION ISO VIEW SHEET 1 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES RIGHT SIDE VIEW INFORMATION SUBJECT TO CHANGE FIXED TOP REAR PANEL RIGHT END PANEL REV R PD-000000016 D HIGH EFFICIENCY H-SERIES EXTRA LARGE OUTDOOR STD BASE DOC 76 Condensing Unit Installation and Operation Manual PN 0708232_K 35.1 LEFT SIDE VIEW FRONT VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 103.0 L X 35.1 W X 54.5 H. SWN 1.0 SUBMITTAL SHEET SIZE D 77 PN 0708232_K SUCTION LINE INLET LOCATION 12.8 14.8 PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT 6.7 LIQUID LINE OUTLET LOCATION 5.5 DOC ACCUMULATOR INLET LINE OUTLET LOCATION SUCTION LINE INLET LOCATION REV R PD-000000016 D HIGH EFFICIENCY H-SERIES EXTRA LARGE OUTDOOR STD BASE CONDENSER (ELECTROFIN COATING OPTIONAL) BASE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 2 OF 3 77 Condensing Unit Installation and Operation Manual CONTROL PANEL RECEIVER COMPRESSOR (VARIOUS MODELS OPTIONAL) INFORMATION SUBJECT TO CHANGE ISO VIEW WITH OUTDOOR HOUSING REMOVED FOR CLARITY NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 103.0 L X 35.1 W X 54.5 H. SWN 1.0 SUBMITTAL SHEET SIZE D 78 INTAKE 48.0 EXHAUST EXHAUST 48.0 MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. 48.0 EXHAUST CONTROL PANEL FACING LEFT END OF UNIT EXHAUST INTAKE EXHAUST INTAKE 180.0 CLEARANCE BETWEEN REAR UNIT EXHAUST AND FRONT UNIT INTAKE EXHAUST EXHAUST EXHAUST 60.0 CLEARANCE BETWEEN MULTIPLE UNIT SIDE EXHAUSTS INTAKE EXHAUST DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC EXHAUST REV R PD-000000016 D HIGH EFFICIENCY H-SERIES EXTRA LARGE OUTDOOR STD BASE CLEARANCE ON MULTIPLE UNIT APPLICATION PROVIDE CLEARANCES AS SHOWN TO ENSURE ADEQUATE AIRFLOW, REDUCE THE POTENTIAL FOR AIR RECIRCULATION AND FACILITATE SERVICE ACCESSIBILITY. EXHAUST INFORMATION SUBJECT TO CHANGE 78 Condensing Unit Installation and Operation Manual PN 0708232_K 48.0 CLEARANCE ON A SINGLE UNIT APPLICATION EXHAUST NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 103.0 L X 35.1 W X 54.5 H. SWN 1.0 SUBMITTAL SHEET SIZE D 79 PN 0708232_K CONTROL PANEL FACING LEFT END OF UNIT MAIN ELECTRICAL CONNECTION LOCATION TOP VIEW 38.2 44.1 FRONT VIEW PIPING EXTENSION 6.0 MAX. 28.7 MOUNTING DIMENSIONS 32.1 O .56 MOUNTING HOLES 4 PLACES HINGED TOP FRONT PANEL FRONT GRILLE CONTROL PANEL RIGHT SIDE VIEW INFORMATION SUBJECT TO CHANGE DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 3 FIXED TOP REAR PANEL R RIGHT END PANEL BASE ASSEMBLY REV PD-000000017 D HIGH EFFICIENCY H-SERIES SMALL OUTDOOR HD BASE DOC 79 Condensing Unit Installation and Operation Manual HIGH EFFICIENCY H-SERIES SMALL SIZE OUTDOOR UNIT HEAVY DUTY BASE "HxHx-xxxxxxx-xx-x" WEIGHT: 400 LBS 32.4 LEFT SIDE VIEW RECEIVER 34.9 MOUNTING DIMENSIONS BOTTOM VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 44.1 L X 32.4 W X 32.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 80 14.0 A A RECEIVER 13.1 CONDENSER (ELECTROFIN COATING OPTIONAL) ACCUMULATOR SUCTION LINE INLET LOCATION LIQUID LINE OUTLET LOCATION FRONT TO BACK DOC REV R PD-000000017 D HIGH EFFICIENCY H-SERIES SMALL OUTDOOR HD BASE BASE ASSEMBLY SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES ISO VIEW OUTDOOR HOUSING REMOVED FOR CLARITY COMPRESSOR (VARIOUS MODELS OPTIONAL) CONTROL PANEL SUCTION LINE INLET LOCATION 5.1 1.0 5.1 INFORMATION SUBJECT TO CHANGE 80 Condensing Unit Installation and Operation Manual PN 0708232_K 13.5 LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT SECTION A-A NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 44.1 L X 32.4 W X 32.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 81 PN 0708232_K 48.0 INTAKE EXHAUST EXHAUST 48.0 EXHAUST INTAKE EXHAUST EXHAUST 60.00 INTAKE EXHAUST EXHAUST DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC REV R PD-000000017 D HIGH EFFICIENCY H-SERIES SMALL OUTDOOR HD BASE CLEARANCE ON MULTIPLE UNIT APPLICATION PROVIDE CLEARANCES AS SHOWN TO ENSURE ADEQUATE AIRFLOW, REDUCE THE POTENTIAL FOR AIR RECIRCULATION AND FACILITATE SERVICE ACCESSIBILITY. CLEARANCE BETWEEN MULTIPLE UNIT SIDE EXHAUSTS EXHAUST INTAKE EXHAUST 180.00 DISTANCE BETWEEN REAR UNIT EXHAUST AND FRONT UNIT INTAKE EXHAUST EXHAUST INFORMATION SUBJECT TO CHANGE 81 Condensing Unit Installation and Operation Manual MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. 48.0 EXHAUST CONTROL PANEL FACING LEFT END OF UNIT 48.00 CLEARANCE ON A SINGLE UNIT APPLICATION NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 44.1 L X 32.4 W X 32.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 82 HIGH EFFICIENCY H-SERIES MEDIUM SIZE OUTDOOR UNIT HEAVY DUTY BASE "HxHx-xxxxxxx-xx-x" WEIGHT: 650 LBS. CONTROL PANEL FACING LEFT END OF UNIT FIELD LOCATE MAIN POWER CONNECTION IN THIS AREA. TOP VIEW 44.2 50.1 FRONT VIEW PIPING EXTENSION 6.0 MAX. 31.5 MOUNTING DIMENSIONS 49.7 O .562 MOUNTING HOLES 4 PLACES SHEET 1 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES ISO VIEW HINGED TOP FRONT PANEL RIGHT SIDE VIEW INFORMATION SUBJECT TO CHANGE FIXED TOP REAR PANEL R RIGHT END PANEL BASE ASSEMBLY REV PD-000000018 E HIGH EFFICIENCY H-SERIES MEDIUM OUTDOOR HD BASE DOC 82 Condensing Unit Installation and Operation Manual PN 0708232_K 35.0 LEFT SIDE VIEW 40.9 MOUNTING DIMENSIONS BOTTOM VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 50.1 L X 35.0 W X 49.7 H. SWN 1.0 SUBMITTAL SHEET SIZE D 83 PN 0708232_K A A 14.0 RECEIVER 14.8 LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT 5.1 1.0 CONDENSER (ELECTROFIN COATING OPTIONAL) ACCUMULATOR SUCTION LINE INLET LOCATION REV R PD-000000018 E 83 Condensing Unit Installation and Operation Manual CONTROL PANEL DOC HIGH EFFICIENCY H-SERIES MEDIUM OUTDOOR HD BASE LIQUID LINE OUTLET LOCATION FRONT TO BACK SHEET 2 OF 3 THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES BASE ASSEMBLY INFORMATION SUBJECT TO CHANGE ISO VIEW WITH OUTDOOR HOUSING REMOVED FOR CLARITY COMPRESSOR (VARIOUS MODELS OPTIONAL) OIL SEPERATOR SUCTION LINE INLET LOCATION 13.2 5.1 SECTION A-A NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 50.1 L X 35.0 W X 49.7 H. SWN 1.0 SUBMITTAL SHEET SIZE D 84 EXHAUST INTAKE 48.0 EXHAUST EXHAUST 48.0 MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. 48.0 CONTROL PANEL FACING LEFT END OF UNIT EXHAUST INTAKE EXHAUST EXHAUST EXHAUST INTAKE EXHAUST DRAWN: DEC 2019 EXHAUST DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC REV R PD-000000018 E HIGH EFFICIENCY H-SERIES MEDIUM OUTDOOR HD BASE CLEARANCE ON MULTIPLE UNIT APPLICATION PROVIDE CLEARANCES AS SHOWN TO ENSURE ADEQUATE AIRFLOW, REDUCE THE POTENTIAL FOR AIR RECIRCULATION AND FACILITATE SERVICE ACCESSIBILITY. 60.0 CLEARANCE BETWEEN MULTIPLE UNIT SIDE EXHAUSTS INTAKE EXHAUST 180.0 CLEARANCE BETWEEN REAR UNIT EXHAUST AND FRONT UNIT INTAKE EXHAUST EXHAUST INFORMATION SUBJECT TO CHANGE 84 Condensing Unit Installation and Operation Manual PN 0708232_K 48.0 CLEARANCE ON A SINGLE UNIT APPLICATION NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 50.1 L X 35.0 W X 49.7 H. SWN 1.0 SUBMITTAL SHEET SIZE D 85 PN 0708232_K CONTROL PANEL FACING LEFT END OF UNIT TOP VIEW 80.2 86.1 FRONT VIEW 36.0 MOUNTING DIMENSIONS PIPING EXTENSION 6.0 MAX. 31.5 MOUNTING DIMENSIONS 49.6 SHEET 1 OF 3 DOC REV R PD-000000019 D HIGH EFFICIENCY H-SERIES LARGE OUTDOOR HD BASE BASE ASSEMBLY FIXED TOP REAR PANEL THIRD ANGLE PROJECTION DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES ISO VIEW HINGED TOP FRONT PANEL RIGHT SIDE VIEW O .562 MOUNTING HOLES 6 PLACES INFORMATION SUBJECT TO CHANGE 85 Condensing Unit Installation and Operation Manual HIGH EFFICIENCY H-SERIES LARGE SIZE OUTDOOR UNIT HEAVY DUTY BASE "HxHx-xxxxxxx-xx-x" WEIGHT: 1,250 LBS. 35.0 34.7 LEFT SIDE VIEW FIELD LOCATE MAIN POWER CONNECTION IN THIS AREA. 40.9 MOUNTING DIMENSIONS BOTTOM VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 86.1 L X 35.0 W X 49.6 H. SWN 1.0 SUBMITTAL SHEET SIZE D 86 A A 14.0 RECEIVER 14.8 SUCTION LINE INLET LOCATION 13.9 5.1 1.0 CONTROL PANEL ISO VIEW WITH OUTDOOR HOUSING REMOVED FOR CLARITY COMPRESSOR (VARIOUS MODELS OPTIONAL) BASE ASSEMBLY ACCUMULATOR 5.1 INFORMATION SUBJECT TO CHANGE R PD-000000019 D REV SUCTION LINE INLET LOCATION CONDENSER (ELECTROFIN COATING OPTIONAL) DOC HIGH EFFICIENCY H-SERIES LARGE OUTDOOR HD BASE LIQUID LINE OUTLET LOCATION FRONT TO BACK SUCTION FILTER DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 2 OF 3 86 Condensing Unit Installation and Operation Manual PN 0708232_K LIQUID LINE OUTLET LOCATION PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT SECTION A-A NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 86.1 L X 35.0 W X 49.6 H. SWN 1.0 SUBMITTAL SHEET SIZE D 87 PN 0708232_K INTAKE 48.0 EXHAUST 48.0 EXHAUST EXHAUST INTAKE EXHAUST INTAKE 180.00 CLEARANCE BETWEEN REAR UNIT EXHAUST AND FRONT UNIT INTAKE EXHAUST EXHAUST 60.0 EXHAUST CLEARANCE BETWEEN MULTIPLE UNIT SIDE EXHAUSTS INTAKE EXHAUST DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC EXHAUST REV R PD-000000019 D HIGH EFFICIENCY H-SERIES LARGE OUTDOOR HD BASE CLEARANCE ON MULTIPLE UNIT APPLICATION PROVIDE CLEARANCES AS SHOWN TO ENSURE ADEQUATE AIRFLOW, REDUCE THE POTENTIAL FOR AIR RECIRCULATION AND FACILITATE SERVICE ACCESSIBILITY. EXHAUST INFORMATION SUBJECT TO CHANGE 87 Condensing Unit Installation and Operation Manual MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. EXHAUST 48.0 CONTROL PANEL FACING LEFT END OF UNIT 48.0 CLEARANCE ON A SINGLE UNIT APPLICATION EXHAUST NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 86.1 L X 35.0 W X 49.6 H. SWN 1.0 SUBMITTAL SHEET SIZE D 88 CONTROL PANEL FACING LEFT END OF UNIT HIGH EFFICIENCY H-SERIES EXTRA LARGE SIZE OUTDOOR UNIT HEAVY DUTY BASE "HxHx-xxxxxxx-xx-x" WEIGHT: 1,575 LBS. 34.7 LEFT SIDE VIEW TOP VIEW 95.2 101.0 FRONT VIEW 44.5 MOUNTING DIMENSIONS RIGHT SIDE VIEW HINGED TOP FRONT PANEL 62.1 PIPE EXTENSION 6.0 MAX. 31.5 MOUNTING DIMENSIONS O .562 MOUNTING HOLES 6 PLACES INFORMATION SUBJECT TO CHANGE ISO VIEW DRAWN: DEC 2019 DOC REV R PD-000000020 D HIGH EFFICIENCY H-SERIES EXTRA LARGE OUTDOOR HD BASE BASE ASSEMBLY RIGHT END PANEL FIXED TOP REAR PANEL DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 1 OF 3 88 Condensing Unit Installation and Operation Manual PN 0708232_K FIELD LOCATE MAIN ELECTRICAL CONNECTION IN THIS AREA RECEIVER 47.4 MOUNTING DIMENSIONS BOTTOM VIEW NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 101.0 L X 34.7 W X 62.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 89 PN 0708232_K A A RECEIVER 14.6 LIQUID LINE OUTLET LOCATION 5.1 1.0 CONTROL PANEL SECTION A-A SUCTION LINE INLET LOCATION 14.4 PIPING CONNECTION LOCATION OUT RIGHT SIDE OF UNIT SUCTION FILTER BASE ASSEMBLY DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 2 OF 3 ACCUMULATOR SUCTION LINE INLET LOCATION DOC REV R PD-000000020 D HIGH EFFICIENCY H-SERIES EXTRA LARGE OUTDOOR HD BASE LIQUID LINE OUTLET LOCATION FRONT TO BACK CONDENSER (ELECTROFIN COATING OPTIONAL) INFORMATION SUBJECT TO CHANGE ISO VIEW WITH OUTDOOR HOUSING REMOVED FOR CLARITY NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 101.0 L X 34.7 W X 62.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D 89 Condensing Unit Installation and Operation Manual 90 48.0 INTAKE EXHAUST EXHAUST 48.0 INTAKE EXHAUST INTAKE 180.00 DISTANCE BETWEEN REAR UNIT EXHAUST AND FRONT UNIT INTAKE MINIMUM CLEARANCE REQUIREMENTS: ACTUAL CLEARANCE REQUIREMENTS ARE DEPENDENT UPON AUTHORITY HAVING EXHAUST JURISDICTION, AND MAY EXCEED DIMENSIONS SHOWN. EXHAUST 48.0 CONTROL PANEL INSIDE EXHAUST EXHAUST EXHAUST 60.00 CLEARANCE BETWEEN MULTIPLE UNIT SIDE EXHAUSTS INTAKE EXHAUST DRAWN: DEC 2019 DIMENSIONS ARE IN INCHES THIRD ANGLE PROJECTION SHEET 3 OF 3 DOC R EXHAUST REV PD-000000020 D HIGH EFFICIENCY H-SERIES EXTRA LARGE OUTDOOR HD BASE CLEARANCE ON MULTIPLE UNIT APPLICATION PROVIDE CLEARANCES AS SHOWN TO ENSURE ADEQUATE AIRFLOW, REDUCE THE POTENTIAL FOR AIR RECIRCULATION AND FACILITATE SERVICE ACCESSIBILITY. EXHAUST INFORMATION SUBJECT TO CHANGE 90 Condensing Unit Installation and Operation Manual PN 0708232_K 48.00 CLEARANCE ON A SINGLE UNIT APPLICATION EXHAUST NOTES: 1. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THE FINAL EQUIPMENT INSTALLATION MEETS ALL APPLICABLE CODE REQUIREMENTS. 2. ILLUSTRATION SHOWN IS FOR GENERAL REPRESENTATION ONLY. ACTUAL PRODUCT WILL VARY DEPENDENT UPON APPLICATION. 3. OVERALL DIMENSIONS: 101.0 L X 34.7 W X 62.1 H. SWN 1.0 SUBMITTAL SHEET SIZE D PN 0708232_K 91 SERVICE TROUBLE SHOOTING INFORMATION SPORLAN http://www.sporlanonline.com EMERSON Fault Finder app http://www.emersonclimate.com/en-us/ Resources/Mobile_Apps/Pages/mobileapps.aspx SQUARED HOTLINE 888-SQUARED (888-778-2733) Tech Support Line. Level One provides product initial Tech Support and can connect the Caller to Level 2, if required. Condensing Unit Installation and Operation Manual 91 PN 0708232_K Replace Components 4 Condensing Unit Installation and Operation Manual Yes Verify System Operation Do Not Replace Components 4 Replace Compressor Does Not Restart No Resolve Application Issues 3 Yes Is the Compressor Properly Applied? Proper Refrigerant, Voltage Application, Temp Range? No Yes Refer to Motor & Basic Wiring Section Correct Voltage Supply Check -- Excessive Cable Length -- Undersized Cable -- Power Supply/Utility Grid -- Loose Electrical Connections -- Bad Transformers -- Worn Electrical Contacts Refer to 3 Phase Voltage Monitor Section of Controls Module 3 Replace Appropriate Components 4 See Complete System Operation Worksheet 5 See Pressure Control Section of Controls Module 6 Check for Blown Gasket or Damaged Discharge Reeds 7 Check for Loss of Charge, Restriction or Faulty Control 8 Check for Dirty Condensers, Defective Condenser, Fan & Motor, Refrigerant Overcharge, etc. 2 1 Verify System Operation Compressor Starts Runs Continuously Verify System Operation 4 Do Not Replace Compressor 4, 8 Backseat It Verify System Operation Troubleshooting Guide Balance System Pressure and Attempt to Restart While Observing Amps Replace Compressor Form No. 2004CC-126 © 2004 Copeland Corporation No Are The Start Components (i.e. Relays, Motor Starters, Contactors, and Capacitors) OK? Verify System Operation Not High Amps Restarts Fix Connections Bad High Amps Fix Replace Wiring Good Inspect/Replace Compressor 6 HPC Is the Discharge Service Valve Back Seated? Do Not Replace Compressor 4, 7 No Verify System Operation Yes Still Short Cycling? Do Not Replace Compressor Fix Voltage Issues 2, 4 Check Electrical Connections Replace Protector (If Accessible) or Compressor Wired Correctly Check Wiring Replace Compressor Wired Incorrectly Proper Resistance Improper Resistance Check Winding Resistance and Resistance to Ground 1 Normal Amps Check Amp Draw Improper Voltage Verify System Operation Proper Voltage DANGER! Do Not Frontseat Suction Service Valve if Doing so will Isolate the LPC from the Compressor! Do Not Replace Compressor4 LPC Frontseat Suction Service Valve Thermostat Protector Which Control is Short Cycling? Compressor Starts Short Cycle Check Voltage at Compressor Terminals 1 High or Excessive Amps Allow Time for Compressor Protector to Reset Compressor Starts Immediately Trips on Protector 92 U.S. & Canada 1-800-922-1919 • Mexico 01-800-890-2900 • WWW.HUSSMANN.COM 92 Condensing Unit Installation and Operation Manual No Yes Do Not Replace Compressor 2 Replace Compressor Verify System Operation Not High Amps High Amps Windings OK Verify System Operation Resolve Application Issues 3 No Is the Compressor Properly Applied? Proper Refrigerant, Voltage Application, Temp Range? Yes 1 2 Refer to Motor & Basic Wiring Module See Complete System Operation Worksheet 3 Replace Appropriate Components 4 Check External Wiring 5 Correct Voltage Supply Check -- Excessive Cable Length -- Undersized Cable -- Power Supply/Utility Grid -- Loose Electrical Connections -- Bad Transformers -- Worn Electrical Contacts Refer to 3 Phase Voltage Monitor Section of Controls Module 6 Check Fuses, Circuit Breakers, Control Circuit/Safety ControlsThermostat, Contactors, etc. 1 Replace Compressor Windings Not OK Check Winding Resistance Using an Ohmmeter No Do Not Replace Compressor Check Components 2, 4 Replace Compressor Troubleshooting Guide Replace Compressor Does Not Restart Balance System Pressure and Attempt to Restart While Observing Amps Verify System Operation Do Not Replace Compressor Replace Components 2 Good Replace Protector (If Accessible) or Compressor Are The Start Components (i.e. Relays, Motor Starters, Contactors, and Capacitors) OK? Verify System Operation Did Not Reset Check Electrical Connections Restarts Fix Connections Bad Fix Replace Reset Wired Correctly Check Wiring Proper Resistance No Voltage6 Do Not Replace Compressor Fix Voltage Issues 4 Improper Voltage 5 Allow Time for Compressor Protector to Reset No Amps Wired Incorrectly Form No. 2004CC-126 © 2004 Copeland Corporation Replace Compressor Improper Resistance Check Winding Resistance and Resistance to Ground 1 High or Excessive Check Amp Draw Proper Voltage Yes Is Compressor Grounded? Allow Time for Compressor Protector to Reset Check Voltage at Compressor Terminals 1 Does Not Start Instantly Blown Fuses Compressor Not Running PN 0708232_K 93 HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. 93 ® To obtain warranty information or other support, contact your Hussmann representative. Please include the model and serial number of the product. Hussmann Corporation, Corporate Headquarters: Bridgeton, Missouri, U.S.A. ">
/

Download
Just a friendly reminder. You can view the document right here. But most importantly, our AI has already read it. It can explain complex things in simple terms, answer your questions in any language, and help you quickly navigate even the longest or most compilcated documents.
Advertisement