Basic Configuration Section 2-1
2-1 Basic Configuration
The basic configuration of the PC is shown below. With the C200HX/
C200HG/C200HE, up to two or up to three Expansion I/O Racks (depending on the CPU Unit) can be connected to the CPU Rack, depending on the number of
I/O points required in the system.
CPU Rack
I/O Connecting Cables
Expansion I/O Racks
2-1-1 CPU Rack
An example of a CPU Rack is shown below. The CPU Rack consists of a CPU
Backplane, CPU Unit, Power Supply Unit, I/O Units, and other special Units.
CPU Unit
Power Supply Unit
CPU Backplane
Other Units
10
Basic Configuration Section 2-1
Power Supply Units The Power Supply Unit supplies power to the CPU Rack. The Power Supply
Units listed in the following table are available. Refer to 2-2-4 Power Supply
Units for further details.
Model
C200HW-PA204
C200HW-PA204S
Supply voltage
100 to 120 VAC, ,
200 240 VAC
C200HW-PA204R/PA209R
(See note.)
C200HW-PD024 24 VDC
Remarks
---
Provides 24-VDC output terminals.
Equipped with RUN output contacts.
---
Note The C200HW-PA204R/PA209R cannot be used with all combinations of CPU
Units and Backplanes. Refer to page 23, Restrictions for the C200HW-PA204R/
PA209R , for details.
CPU Units
Model
C200HX-CPU65-ZE
C200HX-CPU85-ZE
The CPU Units listed in the following tables are available. Refer to 2-2-1 CPU
Units for further details on the CPU Units.
User program memory
C200HE-CPU11-E/ZE 3.2K words
C200HE-CPU32-E/ZE 7.2K words
C200HE-CPU42-E/ZE 7.2K words
C200HG-CPU33-E/ZE 15.2K words
C200HG-CPU43-E/ZE 15.2K words
C200HG-CPU53-E/ZE 15.2K words
C200HG-CPU63-E/ZE 15.2K words
C200HX-CPU34-E/ZE 31.2K words
C200HX-CPU44-E/ZE 31.2K words
C200HX-CPU54-E/ZE 31.2K words
C200HX-CPU64-E/ZE 31.2K words
63.2K words
63.2K words
Data memory
4K words
6K words
6K words
6K words
6K words
6K words
6K words
6K words
6K words
6K words
6K words
6K words
6K words
Extended data memory
(EM)
---
---
---
6K words
6K words
6K words
6K words
6K words x 3
(18K words)
6K words x 3
(18K words)
6K words x 3
(18K words)
6K words x 3
(18K words)
6K words x 8
(48K words)
6K words x 16
(96K words)
Instruction processing time (basic instructions)
0.3 µ s min.
0.3 µ s min.
0.3 µ s min.
0.15 µ s min.
0.15 µ s min.
0.15 µ s min.
0.15 µ s min.
0.1 µ s min.
0.1
0.1
0.1
0.1
0.1
µ
µ
µ
µ
µ s min.
s min.
s min.
s min.
s min.
Max. real I/O points supported
640 points
880 points
880 points
880 points
880 points
1,184 points
1,184 points
880 points
880 points
1,184 points
1,184 points
1,184 points
1,184 points
Max. No. of
Expansion
I/O Racks
2 Racks
2 Racks
2 Racks
2 Racks
2 Racks
3 Racks
3 Racks
2 Racks
2 Racks
3 Racks
3 Racks
3 Racks
3 Racks
11
Basic Configuration Section 2-1
Model Max. No. of Group-2
High-density I/O Units
64-point Units
(see note 1)
Max. No. of
(see note 2)
C200HE-CPU11-E/ZE Not supported Not supported 10 Units
C200HE-CPU32-E/ZE 10 Units 5 Units 10 Units
C200HE-CPU42-E/ZE 10 Units
C200HG-CPU33-E/ZE 10 Units
C200HG-CPU43-E/ZE 10 Units
C200HG-CPU53-E/ZE 16 Units
C200HG-CPU63-E/ZE 16 Units
5 Units
5 Units
5 Units
8 Units
8 Units
10 Units
10 Units
10 Units
16 Units
16 Units
C200HX-CPU34-E/ZE 10 Units
C200HX-CPU44-E/ZE 10 Units
C200HX-CPU54-E/ZE 16 Units
C200HX-CPU64-E/ZE 16 Units
C200HX-CPU65-ZE
C200HX-CPU85-ZE
16 Units
16 Units
5 Units
5 Units
8 Units
8 Units
8 Units
8 Units
10 Units
10 Units
16 Units
16 Units
16 Units
16 Units
RS-232C Clock
No
Yes
No
Yes
Yes
Yes
No
No
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Communications
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Note 1. Each 64 I/O Unit is treated as two Units.
2. Special I/O Units like the C200H-NC211 that are allocated the words for two
Units are treated as two Units.
3. Unit number settings for Group-2 Units for the following CPU Units must be between 0 and 9:
C200HE-CPU32/42-E/ZE
C200HG-CPU33/43-E/ZE
C200HX-CPU34/44-E/ZE
CPU Backplane The CPU Backplane is required to mount the CPU Unit and other Units composing the CPU Rack. The following CPU Backplanes are available depending on the number of slot required for Units. Refer to 2-2-5 Backplanes for further details.
Model
C200HW-BC031
C200HW-BC051
3
5
Number of slots
C200HW-BC081-V1 8
C200HW-BC101-V1 10
Other Units
Note When using the C200HW-PA209R Power Supply Unit with an 8-slot or 10-slot
CPU Backplane or Expansion I/O Backplane, be sure to use the C200HW-
BC081-V1 or C200HW-BC101-V1.
The other Units that can be mounted to the CPU Rack include the Standard I/O
Units, High-density I/O Units, and Special I/O Units.
12
Basic Configuration Section 2-1
2-1-2 Expansion I/O Racks
An example of an Expansion I/O Rack is shown in the following diagram. Expansion I/O Racks consist of and I/O Backplane, Power Supply Unit, I/O Units, and other Units. Expansion I/O Racks are connected to the CPU Rack to increase the number of I/O Units and other Units that can be used by the PC. You can connect up to 2 or up to 3 Expansion I/O Racks to a CPU Rack, the number depending on the CPU Unit that is used.
Power Supply Unit
I/O Backplane
Other Units
Power Supply Unit
I/O Backplane
Other Units
The Power Supply Unit supplies power to the Expansion I/O Rack. The Power
Supply Units listed in the following table are available. Refer to 2-2-4 Power Supply Units for further details.
Model
C200HW-PA204
C200HW-PA204S
Supply voltage
100 to 120 VAC, ,
200 240 VAC
Remarks
---
Provides 24-VDC output terminals.
C200HW-PD204R
C200HW-PD209R
C200HW-PD024 24 VDC output contacts.
Note RUN output contacts cannot be used with Expansion I/O Racks.
The I/O Backplane is required to mount the Power Supply Unit and other Units composing the Expansion I/O Rack. The following I/O Backplanes are available depending on the number of slot required for Units. Refer to 2-2-5 Backplanes for further details.
Model
C200HW-BI031 3
C200HW-BI051 5
C200HW-BI081-V1 8
Number of slots
C200HW-BI101-V1 10
Note When using the C200HW-PA209R Power Supply Unit with an 8 or 10-slot Backplane, be sure to use the C200HW-BC081-V1 or C200HW-BC101-V1.
The other Units that can be mounted to an Expansion I/O Rack include the Standard I/O Units, High-density I/O Units, and Special I/O Units.