Entry Delay. PARADOX ESPRIT 728 ULT, 738ULT 56 Pages
advertisement
7.8
7.9
Entry Delay 1
Decimal Programming
D
Address 050
Default: 45 seconds
Any zone that has not been identified as either Instant Zones, Follow Zones, Entry Delay 2, or 24Hr and Fire Zones will automatically default to Delay 1. You can program the Delay 1 period between 001 and 255 seconds into address 050. If a zone defined as Delay 1 opens in an armed system, the control panel will wait the pre-programmed period of time before generating an alarm. This provides users with the time required to disarm the system when entering the protected area.
[ ENTER ] + Installer code + [0] [5] [0] + 3-digit decimal value (001 to 255) + [ ENTER ]
Entry Delay 2
728 Ultra: Feature Select Programming
D
Address 112; Keys [1] to [10 (0)]
738 Ultra: Feature Select Programming
D
Addresses 112 and 114; Keys [1] to [10 (0)], [ STAY ]/[11] and [ FORCE ]/[ AWAY ]/[12] )
before generating an alarm. This provides users with the time required to disarm the system when entering the protected area.
7.9.1
Entry Time Delay 2
Decimal Programming
D
Address 051
Default: 45 seconds
seconds.
[ ENTER ] + Installer code + [0] [5] [1] + 3-digit decimal value (001 to 255) + [ ENTER ]
7.10
Partitioning
Feature Select Programming
D
Address 086; Key [8]
Default: Disabled
This feature divides the alarm system into two distinct systems, identified as System A and System B. You can assign each zone to System A, System B, both systems, or neither system. Partitioning works as follows:
• Zones assigned to System A will arm/disarm when the system is System A Armed/Disarmed.
• Zones assigned to System B will arm/disarm when the system is System B Armed/Disarmed.
• Zones assigned to both systems (dual area) will arm when the system is either System A Armed, System B Armed or when both systems are armed and will disarm only when both systems disarm.
• Zones not associated with any system (common area) will arm only when the system is both System A Armed and System B
Armed and will only disarm when at least one of the two systems disarms.
For more information on arming or disarming partitions, see
Arming/Disarming Partitions on page 41. Also see
7.10.1
System A/Stay Zones
728 Ultra: Feature Select Programming
D
Address 116; Keys [1] to [10 (0)]
738 Ultra: Feature Select Programming
D
Addresses 116 and 118; Keys [1] to [10 (0)], [ STAY ]/[11] and [ FORCE ]/
[ AWAY ]/[12] )
partitioned, which zones will be identified as stay zones. For details on System A zones refer to
Stay Arming on page 41 for more information.
7.10.2
System B Zones
728 Ultra: Feature Select Programming
D
Address 120; Keys [1] to [10 (0)]
738 Ultra: Feature Select Programming
D
Addresses 120 and 122; Keys [1] to [10 (0)], [ STAY ]/[11] and [ FORCE ]/
[ AWAY ]/[12] )
System B zones, refer to Partitioning above.
7.11
Bypass Enabled Zones
728 Ultra: Feature Select Programming
D
Address 124; Keys [1] to [10 (0)]
738 Ultra: Feature Select Programming
D
Addresses 124 and 126; Keys [1] to [10 (0)], [ STAY ]/[11] and [ FORCE ]/[ AWAY ]/[12] )
bypass enabled can be used for manual zone bypassing (see
Manual Zone Bypassing on page 42) or during Auto Zone
Contact ID (All Codes) on page 19 for more information.
Esprit 728 Ultra & 738 Ultra 29
7.11.1
Auto Zone Shutdown
Feature Select Programming
D
Address 086; Key [ TBL ] or [ TRBL ]
Default: Auto Zone Shutdown Disabled
The control panel will automatically bypass any bypass enabled zones which initiate 5 consecutive alarms in the samearmed period. Therefore, the zone will no longer generate an alarm. After the control panel has bypassed a zone, it will report an event code to the monitoring station if programmed at addresses 448 to 457 (728 Ultra) or 465 (738 Ultra).
The Auto Zone Shutdown counter resets when the system is disarmed.
restore on bell cut-off, the zone will only be bypassed after the bell or siren has cut off 5 consecutive times in the same armed period. While if the option is set for report zone on zone closure, the zone will be bypassed when the zone has opened and closed 5 consecutive times in one armed period.
Key [ TBL ]/[ TRBL ] OFF: Auto Zone Shutdown Disabled
Key [ TBL ]/[ TRBL ] ON: Auto Zone Shutdown Enabled
[ ENTER ] + Installer code + [0] [8] [6] + [ TBL ]/[ TRBL ] ON/OFF + [ ENTER ]
7.12
EOL Zones (Enabled/Disabled)
Feature Select Programming
D
Address 088; Key [ MEM ]
Default: Enabled (No EOL)
If the system requires the use of 1k
9
end of line resistors on zone input terminals, disable this feature (see Keypad Zone
Single Zone Input Terminal Connections on page 6).
Key [ MEM ] OFF: Input Zones use EOL Resistors
Key [ MEM ] ON: Input Zones do not use EOL Resistors
[ ENTER ] + Installer code + [0] [8] [8] + [ MEM ] ON/OFF + [ ENTER ]
7.13
Keypad Zone 1 Supervision
Feature Select Programming
D
Address 090; Key [ STAY ]
Default: Disabled
When using a keypad defined as Keypad Zone 1, enable this feature. When enabled, the control panel will verify the presence of
a keypad and the keypad zone. For more information see Keypad Zone Connections on page 5.
Key [ STAY ] OFF: Keypad Zone 1 Disabled
Key [ STAY ] ON: Keypad Zone 1 Enabled
[ ENTER ] + Installer code + [0] [9] [0] + [ STAY ] ON/OFF + [ ENTER ]
7.14
Keypad Zone 2 Supervision
Feature Select Programming
D
Address 090; Key [ AWAY ]/[ FORCE ]
Default: Disabled
When using a keypad defined as Keypad Zone 2, enable this feature. When enabled, the control panel will verify for the presence
of a keypad and the keypad zone. For more information see Keypad Zone Connections on page 5.
Key [ AWAY ]/[ FORCE ] OFF: Keypad Zone 2 Disabled
Key [ AWAY ]/[ FORCE ] ON: Keypad Zone 2 Enabled
[ ENTER ] + Installer code + [0] [9] [0] + [ AWAY ]/[ FORCE ] ON/OFF + [ ENTER ]
30 Reference & Installation Manual
Arm/Disarm Related
Features
Part 8: Arm/Disarm and Alarm Options
Figure 29: Arming/Disarming Related Features
Auto Arm Time
Addresses 044 and 045
Timed Auto Arming
Address 086; key [5]
Auto Arming Options
Address 090; key [2]
No Movement Auto
Arming
Address 086; key [6]
No Movement Time
Address 055
Code Priority
Define which users can
System A/Stay Arm,
System B/Away (Force) Arm or Bypass zones
System A/Stay Arm
Priority
Addresses 062, 064 and
066; all keys
System B/Away Arm
Priority
Addresses 068, 070 and
072; all keys
Bypass Access
Addresses 074, 076 and
078; all keys
One Key Regular Arming
Address 088; key [7]
One Key System A/
Stay Arming
Address 088; key [8]
Keyswitch Arming
Address 086; keys [2] & [3]
Bell Squawk
Address 086; [ MEM ] key
Exit Delay
Address 049
Alarm Transmission
Delay
Address 059
Bell Cut-Off Time
Address 052
Beep on Exit Delay
Address 088; key [ AWAY ]/[ FORCE ]
Esprit 728 Ultra & 738 Ultra 31
8.1
8.2
8.3
Timed Auto Arming
Feature Select Programming
D
Address 086; Key [5]
Default: Timed Auto Arming Disabled
The alarm system will automatically arm itself at a specified time every day. Please note that as with Regular arming, the system will not arm if a zone is open, but will always report a "late to close" to the monitoring station. If this occurs, the system will not arm until the next day. If arming is successful, the arming report codes and a “late to close” are both transmitted to the monitoring station. If arming is unsuccessful, only the “late to close” is sent to the monitoring station. The type of arming is dependent on the
Auto Arming Options (see
Auto Arming Options on page 32). Program the Auto Arm Time as described below:
8.1.1
8.1.2
Auto Arm Time
The control panel will automatically arm itself at the specified time if timed auto arming (see above) is enabled. The time is programmed using the 24-hour clock (i.e. 8:00 p.m. = 20:00). There are two methods of programming the auto arm time as described below.
Decimal Programming
D
Addresses 044 and 045
Program the Auto Arm Time in hours into address 044 and the Auto Arm Time in minutes into address 045.
[ ENTER ] + Installer code + [0] [4] [4] + 3-digit decimal value (hours) + [0] [4] [5] + 3-digit decimal value (minutes) + [ ENTER ]
Key Access Programming
D
Key [9]
The User 1, Master, or Installer can program the Auto Arm Time using this method.
[ ENTER ] + (Installer, Master or User code 1) + [9] + 2 digits representing hours + 2 digits representing minutes + [ ENTER ]
Auto Arming Options
Feature Select Programming
D
Address 090; Key [2]
Default: Regular Arming
The Auto Arm feature will arm the system as described in Table 11.
Table 11: Auto Arming Options
Key [2]
OFF
OFF
ON
ON
Partitioning Options
OFF Regular Arming
ON Systems A and B Arming
OFF
ON
Stay Arming
System A Arming
[ ENTER ] + Installer code + [0] [9] [0] + [2] ON/OFF+ [ ENTER ]
No Movement Auto Arming
Feature Select Programming
D
Address 086; Key [6]
Default: Disabled
If the control panel does not detect any movement (zone openings) for a specified period, the panel will arm the system and transmit the event code programmed at address 517. Please note that the type of arming is dependent on the Auto Arming
Options (see section 8.1.2). Program the No Movement Auto Arm Time as described below.
Key [6] OFF: No Movement Auto Arm Disabled
Key [6] ON: No Movement Auto Arm Enabled
[ ENTER ] + Installer code + [0] [8] [6] + [6] ON/OFF + [ ENTER ]
8.2.1
No Movement Auto Arm Time
Decimal Programming
D
Address 055
Default: Disabled
000 = disabled; (001 to 255) x 15 minutes
transmit the event code programmed at address 517 if no movement is detected during the programmed period.
[ ENTER ] + Installer code + [0] [5] [5] + 3-digit decimal value (001 to 255) + [ ENTER ]
One-Key Regular Arming
Feature Select Programming
D
Address 088; Key [7]
Default: Disabled
A user can Regular arm the system by pressing and holding the [0] or [ ARM ] key for 2 seconds.
Key [7] OFF: One Key Regular Arming Disabled
Key [7] ON: One Key Regular Arming Enabled
[ ENTER ] + Installer code + [0] [8] [8] + [7] ON/OFF + [ ENTER ]
32 Reference & Installation Manual
8.4
8.5
8.6
8.7
8.8
8.9
One-Key Stay/System A Arming
Feature Select Programming
D
Address 088; Key [8]
Default: Disabled
Press and hold the [ STAY ] key for 2 seconds to Stay arm the system if partitioning is disabled. If the system is partitioned, the control panel will arm System A.
Key [8] OFF: One Key Stay/System A Arming Disabled
Key [8] ON: One Key Stay/System A Arming Enabled
[ ENTER ] + Installer code + [0] [8] [8] + [8] ON/OFF + [ ENTER ]
Arming Using a Keyswitch
Feature Select Programming
D
Address 086; Keys [2] and [3]
Default: Disabled
The user can use a keyswitch to Stay arm or Regular arm/disarm the system. If the system is ready and the button is pressed, the system will arm. Pressing the button again will disarm the system. The keyswitch will not disarm a Stay armed system in alarm.
Refer to
Keypad and Keyswitch Connections on page 4 for installation of a keyswitch.
Table 12: Keyswitch Arming Table
Key [2]
OFF
ON
OFF
ON
Key [3] Function
OFF
OFF
ON
ON
Disabled
Disabled
Full Arming
Stay Arming *
* If partitioning is enabled, the keyswitch will arm System A only.
[ ENTER ] + Installer code + [0] [8] [6] + [2] and [3] ON/OFF + [ ENTER ]
Bell Squawk
Feature Select Programming
D
Address 086; Key [ MEM ]
Default: Disabled
With this feature enabled, the bell or siren will emit a half-second squawk upon arming and two half-second squawks upon disarming.
Key [ MEM ] OFF: Bell Squawk Disabled
Key [ MEM ] ON: Bell Squawk Enabled
[ ENTER ] + Installer code + [0] [8] [6] + [ MEM ] ON/OFF + [ ENTER ]
Exit Delay
Decimal Programming
D
Address 049
Default: 60 seconds
The exit delay applies to all zones. This option determines how much time the user has to leave the protected area after entering a valid access code and before the system arms. You can program the exit delay from 001 to 255 sec.
[ ENTER ] + Installer code + [0] [4] [9] + 3 digit decimal value (001 to 255) + [ ENTER ]
Beep on Exit Delay
Feature Select Programming
D
Address 088; Key [ AWAY ]/[ FORCE ]
Default: Disabled
With this feature enabled, the keypad will emit an intermittent beep during the programmed exit delay period (except when Stay arming). The frequency of intermittent beeps increases during the last 10 seconds of the exit delay period. For more information
about the exit delay refer to section 8.7.
Key [ AWAY ]/[ FORCE ] OFF: Beep on Exit Delay Disabled
Key [ AWAY ]/[ FORCE ] ON: Beep on Exit Delay Enabled
[ ENTER ] + Installer code + [0] [8] [8] + [ AWAY ]/[ FORCE ] ON/OFF + [ ENTER ]
Alarm Transmission Delay
Decimal Programming
D
Address 059
Default: Disabled
This time limit, set between 5 and 63 seconds, is the delay period before reporting an alarm to the monitoring station after an alarm condition. During this period, disarming the system will cancel all pending alarms and send the restore codes.
Programming 000 to 004 in this address disables this feature (Maximum 30 seconds on UL listed systems).
[ ENTER ] + Installer code + [0] [5] [9] + 3-digit decimal value (005 to 063) + [ ENTER ]
Esprit 728 Ultra & 738 Ultra 33
8.10
Silent Zones and Silent Panics Option
Feature Select Programming
D
Address 086; Key [9]
Default: Generate a Silent Alarm
If the [9] key is on, silent zones or silent panics only transmit a report to the monitoring station. The system will not indicate an alarm and will not have to be disarmed. The control panel can still activate a PGM. If a keypad panic has been defined as audible, the control panel will override this option.
Key [9] OFF: Silent Zones and Silent Panics generate a silent alarm
Key [9] ON: Silent Zones and Silent Panics generate a report only
[ ENTER ] + Installer code + [0] [8] [6] + [9] ON/OFF + [ ENTER ]
8.11
Bell Cut-Off Time
Decimal Programming
D
Address 052
Default: 5 minutes
After an audible alarm, the bell or siren will stop after the programmed time has elapsed.
[ ENTER ] + Installer code + [0] [5] [2] + 3-digit decimal value (001 to 255) minutes + [ ENTER ]
8.12
Code Priority
Feature Select Programming
D
Addresses 062 to 078; [all] keys
In order for a user to arm a partitioned system, to Stay arm, to Force/Away arm or to manually bypass zones, the user must be given code priority. Using the
Feature Select Programming on page 13, identify which arming method each user can use. For
728 Ultra & 738
Ultra System Programming Guide for additional information.
Partitioning Disabled:
Addresses 062 to 066: Selected keys indicate which user codes can Stay arm.
Addresses 068 to 072: Selected keys indicate which user codes can Force/Away arm.
Addresses 074 to 078: Selected keys indicate which user codes can bypass zones.
Partitioning Enabled:
Addresses 062 to 066: Selected keys indicate which user codes can arm System A.
Addresses 068 to 072: Selected keys indicate which user codes can arm System B.
Addresses 074 to 078: Selected keys indicate which user codes can bypass zones.
8.13
Closing Delinquency Timer
Decimal Programming
D
Address 061 (Default: Disabled)
Feature Select Programming
D
Address 090; Key [3] (Default: OFF)
At midnight everyday, the 728 Ultra and the 738 Ultra will verify when the system was last armed. If the last time the system was armed is greater than the programmed Closing Delinquency timer, the control panel will transmit a Closing Delinquency event (see
page 23) to the monitoring station. Depending on whether address 090 key
[3] is ON or OFF, the timer can be in days or hours.
The Closing Delinquency timer will be in days if address 090 key [3] is OFF and in hours if address 090 key [3] is ON. Enter 000 to disable the Closing Delinquency timer. Please note that the Closing Delinquency timer and event apply only to System A.
[ ENTER ] + Installer code + [0] [6] [1] + 3-digit decimal value (000 to 255) days/hours + [ ENTER ]
8.14
Restrict Arming on Battery Failure
Feature Select Programming
D
Address 090; Key [4]
Default: Disabled
If this option is enabled, the control panel will not arm the system if the control panel detects that the backup battery is disconnected, the fuse is blown or the battery voltage drops below 10.5V. The control panel will not arm the system until all battery trouble conditions are rectified.
[ ENTER ] + Installer code + [0] [9] [0] + [4] ON/OFF+ [ ENTER ]
8.15
Restrict Arming on Tamper Trouble
Feature Select Programming
D
Address 090; Key [5]
Default: Disabled
If this option is enabled, the control panel will not arm the system if the control panel detects a tamper trouble on one or more zones. The control panel will not arm the system until all tamper trouble conditions are rectified. The trouble can only be cleared by the installer entering programming mode.
[ ENTER ] + Installer code + [0] [9] [0] + [5] ON/OFF+ [ ENTER ]
clear the “Restrict Arming on Tamper” Trouble.
34 Reference & Installation Manual
Part 9: PGMs (Programmable Outputs)
9.1
9.2
We strongly suggest using the Espload software to program the PGM(s).
PGM Types
Streamline - Sections 09
D
Hex Programming - Address 039
The 728 Ultra and 738 Ultra control panels have either one (728 Ultra) or two (738 Ultra) programmable outputs (PGMs). When a
PGM closes, a ground is supplied to activate any device or relay connected to it, providing up to a maximum of 50mA (UL 30mA).
When a PGM opens, the circuit is opened from ground, therefore not providing any power to devices connected to it. To program a PGM you must define the PGM state (normally open or normally closed), the timing (regular or timed) and you must define the type of logic ("OR", "AND", "EQUAL").
digit programmed corresponds to the PGM. Press the [2 ND ] key for the second digit. For the 738 Ultra, use Table 13 to determine which hex digit to program into address 039, where the first hex digit programmed corresponds to PGM1 and the second hex digit corresponds to PGM2.
Regular N.O./N.C.
A triggered PGM will switch to its opposite state (i.e. closed to open or opened to closed). The PGM will return to its original state once the event(s) that triggered it have terminated.
Timed N.O./N.C.
A triggered PGM will switch to its opposite state (i.e. closed to open or opened to closed). The PGM will remain in its opposite state for the period programmed at address 056 (see
PGM Timer Setting on page 35). If the PGM is triggered again before the
period has elapsed, the PGM will remain in its opposite state and reset the timer.
"OR" Logic
Will trigger a PGM when at least one event occurs from a specific group of events (e.g. key [1] and/or key [2] is pressed on the keypad).
"AND" Logic
The "AND" logic will trigger a PGM when all events, or more, occur from a specific group of events (e.g. Keys [1] and [2] are pressed simultaneously. Note that pressing those two keys in conjunction with any other key will also trigger the PGM).
"EQUAL" Logic
The "EQUAL" logic will trigger a PGM only when the events from a specific group of events occur (e.g. Key [1] and [2] are pressed. Note the PGM will only trigger when pressing keys [1] and [2] simultaneously, if any other key is pressed at the same time (e.g. [1] , [2] and [3] ) the PGM will not trigger).
Table 13: PGM Type Selection
Key
[2 ND ] : OR
[1] : AND
[2] : EQUAL
Reg. N.O.
Key
[8]
[9]
[0]
: OR
: AND
: EQUAL
Reg. N.C.
[4]
[5]
: OR
: AND Timed N.O.
[6] : EQUAL
(For timed PGM, see address 056 in section 9.2.)
[ AWAY / FORCE ] : OR
[ BYP ] : AND
[ MEM ] : EQUAL
Timed N.C.
728 Ultra: [ ENTER ] + Installer code + [0] [3] [9]
+ first digit (see Table 13 above) +
[2 ND ] + [ ENTER ]
738 Ultra: [ ENTER ] + Installer code + [0] [3] [9] + first digit (PGM1) + second digit (PGM2) + [ ENTER ]
PGM Timer Setting
Decimal Programming
D
Address 056
Default: 5 seconds
You can program the PGM Timer from 1 to 127 seconds or from 1 to 127 minutes. The PGM timer applies to both PGMs. To determine the 3-digit decimal value, do the following:
• To program seconds, the required time is respective to the decimal value
1 second = 001, 55 seconds = 055, 127 seconds = 127.
• To program the minutes add the required minutes to 128:
5 minutes: 128 + 5 = 133
127 minutes: 128 +127 = 255
[ ENTER ] + Installer code + [0] [5] [6] + 3-digit decimal value (001 to 255) + [ ENTER ]
Esprit 728 Ultra & 738 Ultra 35
9.3
PGM Options
Streamline - Section 10
D
Hex Programming - Addresses 040 to 043
The PGM options define which sequence of events will trigger the PGM. The PGM options are virtually endless. Therefore, to list
required 2-digit data for each address. If other options are required, you can fax your requests to Paradox Technical Support, you can visit our website at www.paradox.ca, or the 2-digit data can be derived using the Espload Software as follows:
1. Select Accounts from the Main Menu
2. Select a current Account or create a new one
3. Press the [ PAGE DOWN ] key from the keyboard until page 9 appears
4. Using the arrow keys and space bar select the PGM options, state, logic and type for the PGM
5. Press the [F8] key from the keyboard to view the Hexadecimal Mode. This mode will display the 2-digit data for addresses 039 to 043.
6. Record these numbers and program them into the control panel or use the Espload Software to download the data directly to the control panel.
If you do not have a copy of the Espload Software, you can obtain a free copy from your local Paradox distributor.
State Option
Table 14: Commonly Used PGM Options
PGM1
1st digit add. 039
[5] add. 040
[5] / [2] Timed N.O.
Output enabled for 3 seconds before communication attempt*
Regular N.O. Output enabled when keys [1] and [2] are pressed simultaneously
Regular N.O. Output enabled when system armed
Regular N.O. Output enabled during an alarm
Timed N.O.
Output enabled for 2 minutes upon fail to communicate
Regular N.O. Output enabled after one failed communication attempt
Timed N.O.
Output enabled for 3 seconds after signal received at monitoring station
[2
[2
[2
[1]
ND
ND
[5]
ND
[5]
]
]
]
[5] / [8]
[2] / [9]
[2] / [12]
[2] / [6]
[7] / [0]
[7] / [ BYP ]
[2 add. 042
[2
[2
[2
[2
[2
[2
ND
ND
ND
ND
ND
ND
] / [8]
] / [6]
] / [3]
] / [2]
] / [4]
] / [
ND
MEM
] / [8]
]
[2
[2
[2
[5]
[1]
ND
ND
[5]
ND
[5]
PGM2 (738 Ultra only)
2nd digit add. 039
]
]
] add. 041
[5] / [2]
[5] / [8]
[2] / [9]
[2] / [12]
[2] / [6]
[7] / [0]
[7] / [ BYP ]
[2 add. 043
[2
[2
ND ] / [8]
] / [6]
[2 ND ] / [3]
[2 ] / [2]
[2 ND ] / [4]
ND
[2
ND
ND
] / [
ND
MEM
] / [8]
]
36 Reference & Installation Manual
Part 10: Other Options
10.1
Telephone Line Monitoring (TLM)
Feature Select Programming
D
Address 086; Keys [2 ND ] and [1]
Default: TLM Disabled
When enabled, the system verifies the existence of a telephone line every 4 seconds. If the system detects a trouble, the LED will flash ON for 1 second and OFF for 1 second. TLM will activate a trouble when less than 3 volts is detected in four consecutive tests.
Please note that when the dialer detects a telephone ring, the TLM test stops for 1 minute. There are three TLM options, which
are set as indicated in Table 15 below:
Table 15: Telephone Line Monitoring (TLM)
Key
[2 ND ]
OFF
OFF
[1]
OFF
ON
- TLM is disabled (default)
- TLM generates a trouble only
ON
ON
OFF
ON
- generates an alarm if armed
- silent alarm becomes audible
(address 086, key [9] has to be OFF)
1.
OFF/ON: Line test failure will generate a trouble indication; key [0] will illuminate on the keypad (LED keypad only).
2.
ON/OFF: Line test failure will generate a trouble indication and an alarm if the system is armed.
3.
ON/ON: Line test failure will generate a trouble indication and cause a silent zone or a silent panic alarm to switch to audible mode.
[ ENTER ] + Installer code + [0] [8] [6] + [2 ND ] and [1] ON/OFF + [ ENTER ]
10.2
Dialing Options
Feature Select Programming
D
Address 086; Key [7]
Default: Pulse Dialing
You can program the control panel to use the pulse dialing or tone/DTMF dialing format.
Key [7] OFF: Pulse Dialing
Key [7] ON: Tone/DTMF Dialing
[ ENTER ] + Installer code + [0] [8] [6] + [7] ON/OFF+ [ ENTER ]
10.3
Dialing Pulse Rates
Feature Select Programming
D
Address 086; Key [0]
Default: Pulse Europe 1:2
This selection determines the ratio between "pulse" time and "quiet" time. Select Pulse Europe for a 1:2 ratio and select Pulse
USA for 1:1.5. Must be set to pulse dialing mode, refer to Dialing Options .
Key [0] OFF: Pulse Europe 1:2
Key [0] ON: Pulse USA 1:1.5
[ ENTER ] + Installer code + [0] [8] [6] + [0] ON/OFF + [ ENTER ]
10.4
Keypad Panic Options
Feature Select Programming
D
Address 088; Keys [1] to [6]
Default: Disabled
This feature will generate an alarm when the user presses two specific keys on the keypad simultaneously for 2 seconds as follows:
Key [1] ON = Panic 1 (keys [1] and [3] ) enabled
Key [2] ON = Panic 2 (keys [4] and [6] ) enabled
Key [3] ON = Panic 3 (keys [7] and [9] ) enabled
Keypad panic options:
Key [4] OFF = Panic 1 silent
Key [4] ON = Panic 1 audible
Key [5] OFF = Panic 2 silent
Key [5] ON = Panic 2 audible
Key [6] OFF = Panic 3 silent
Key [6] ON = Panic 3 fire alarm
[ ENTER ] + Installer code + [0] [8] [8] + [1] to [6] ON/OFF + [ ENTER ]
Esprit 728 Ultra & 738 Ultra 37
Silent operation:
When using the panic keys, the control panel will emit a single confirmation beep. The control panel will transmit the event codes programmed at addresses 513, 514 and 515. The alarm will latch (no audible alarm) and the light on the keypad will flash until the system is disarmed by a valid user code.
Audible operation:
Audible operation is the same as silent operation, except the alarm output (bell/siren) will activate until the system is disarmed by
a valid user code or until the Bell Cut-Off Time (see page 34) elapses.
Fire operation:
Fire operation is the same as audible operation except that bell/siren output will be pulsed (intermittent ON/OFF).
10.5
Panel Time
Key Access Programming
D
Key [ MEM ]
To program the current time into the control panel press:
[ ENTER ] + (Installer, Master, or User code 1) + [ MEM ] + 2 digits representing hours (00 to 23) + 2 digits representing minutes (00 to 59)
10.6
Time Correction
Streamline - Section 09
D
Hex Programming - Address 037 (2nd digit)
If you notice a gain or loss in the control panel time, calculate the average gain or loss per day; select the "opposite" amount from the Time Correction table in order to automatically correct the time setting every 24 hours.
Example: The control panel loses 4 minutes per month, representing an average loss of 8 seconds per day. Therefore, program
[2] (plus 8 seconds) as the second digit in address 037 to compensate for the 8-second loss.
Table 16: Time Correction Table
(address 037 2nd digit)
[2 ND ] - No adjustment
[1] - Plus 4 seconds
[2] - Plus 8 seconds
[3] - Plus 12 seconds
[4] - Plus 16 seconds
[5] - Plus 20 seconds
[6] - Plus 24 seconds
[7] - Plus 28 seconds
[8] - Minus 4 seconds
[9] - Minus 8 seconds
[0] - Minus 12 seconds
[ STAY ] - Minus 16 seconds
[ AWAY ]/[ FORCE ] - Minus 20 seconds
[ BYP ]
[ MEM ]
[ TBL / TRBL ]
- Minus 24 seconds
- Minus 28 seconds
- Minus 32 seconds
10.7
Tamper/Wire Fault Recognition Options
Feature Select Programming
D
Address 088; Keys [0] and [ STAY ]
Default: Disabled
If the control panel detects an open or a short on a zone when the system is armed, regardless of the tamper/wire settings it will always generate an alarm and trouble indicator (key [9] ). Alarms will be audible or silent depending on individual zone definitions.
If an open or short occurs on a disarmed system, the control panel will generate an incident depending on the following settings.
Table 17: Tamper Recognition Option
Key [10 (0)] Key [ STAY ]
OFF OFF
OFF
ON
ON
ON
OFF
ON
- Tamper/Wire Fault disabled
- Trouble Indicator enabled
- Silent Alarm enabled
- Audible Alarm enabled
Tamper/Wire disabled
Tamper/wiring failure recognition is disabled. Not permitted on UL listed systems.
Trouble enabled
Tamper/wiring failure will generate a trouble indicator (key [9]
) and a trouble report code (see Tamper Codes on page 22) when
the system is disarmed.
Silent alarm enabled
Tamper/wiring failure will generate a trouble indicator (key [9]
), a trouble report code (see Tamper Codes on page 22) and a silent
alarm (no bells/sirens).
Audible alarm enabled
Tamper/wiring failure will generate a trouble indicator (key [9] ), a trouble report code (see
Tamper Codes on page 22) and an
audible alarm.
When the zone definition is 24Hr, the tamper definition follows the audible/silent alarm definition of the 24Hr zone.
38 Reference & Installation Manual
10.8
Tamper Bypass Options
Feature Select Programming
D
Address 090; Key [6]
Default: Generate alarm on bypassed zone tamper
With this option enabled, the control panel will not generate an alarm if a tamper is detected on a bypassed zone while the system is armed. With this option disabled, the control panel will generate an alarm if a tamper is detected on a bypassed zone while the system is armed.
Key [6] OFF: Generates an alarm if a tamper is detected on a bypassed zone
Key [6] ON: Ignores tamper if detected on a bypassed zone
[ ENTER ] + Installer code + [0] [9] [0] + [6] ON/OFF + [ ENTER ]
10.9
Installer Test Mode
Key Access Programming
D
Key [8]
The Test Mode will allow you to perform walk tests where the bell or siren will squawk to indicate opened zones. To enter or exit the control panel Test Mode press:
[ ENTER ] + Installer code + [8] to enable (confirmation beep); press [8] again to disable (rejection beep)
10.10
Exclude Power Failure From Trouble Display
Feature Select Programming
D
Address 090; Key [2 ND ]
Default: Disabled
Excludes the Power Failure, key [2]
, from the Trouble Display (see Trouble Display Monitoring on page 43).
10.11
Audible Trouble Warning
Feature Select Programming
D
Address 090; Key [9]
Default: Disabled
Trouble conditions will cause the keypad to emit an intermittent beep. To silence the trouble warning, press the [ TBL ] / [ TRBL ] key.
10.12
Power Down Reset
Performing a power down reset will set the Installer and Master codes to factory default. Values entered at addresses 008 to 043,
062 to 124, 300 to 527 and all user codes will be set to factory defaults. Programmed values at addresses 003 to 007 do not change. To perform a reset, the installer lock must be disabled. To perform a power down reset perform the following:
1. Verify installer lock is disabled (see
2. Remove the battery and AC power from the control panel.
3. Remove all connected wires and devices from the PGM (PGM1 for 738 Ultra) and zone 1 terminals.
4. Short the PGM (PGM1 for 738 Ultra) and zone 1 terminals with a wire.
5. Reconnect the AC and battery power to the control panel.
6. Wait for 10 seconds and remove the wire.
Figure 30: Power Down Reset
1. Remove Power.
2. Remove all connected wires and devices from the PGM
(PGM1 for 738 Ultra) and zone 1 terminals.
3. Short the PGM (PGM1 for 738 Ultra) and zone 1 terminals.
4. Reconnect power.
5. Wait 10 seconds and remove wire.
Esprit 728 Ultra & 738 Ultra 39
Part 11: User/Keypad Functions
The innovative Esprit keypads take a new approach to security features and functions. Each numeral from 1 to 10 (728 Ultra) or 12 (738
Ultra) on the LED keypad represents each zone, from 1 to 10 (or 1 to 12) respectively, on the control panel. When using the LED keypad with the 738 Ultra, if the [2 ND ] key flashes, press the [2 ND ] key to view the status of zones 13 to 18 which are represented by keys [1] to [6].
When the zone light is OFF, the status in the protected zone is normal. If the zone light is ON, this means the zone is open. An LCD keypad will display the open zone numbers on the screen.
The light on the keypad will illuminate when the status of all the zones is normal (zones are closed). Therefore, all protected windows and doors must be closed and motion detectors must not detect any movement except those zones that have been bypassed.
Confirmation Beep: an intermittent series of beeps ("beep-beep-beep") indicates a successful keypad entry or system operation.
End/Rejection Beep: one long tone ("beeeeeeep") indicates incorrect keypad entry or unsuccessful system operation.
11.1
Programming Master and User Codes
The Esprit Ultra control panels have one Master code (00) and up to 48 user codes (01 to 48). The default Master code is
474747. The Master code can arm the system using any arming method, create/modify user codes and perform Key Access
access code consists of either 4- or 6-digits and each digit can be any value from 0 to 9.
Do not enter [2 ND ] when programming the Master code as this will invalidate the Master code.
[ ENTER ] + Master or User code 1 + 2-digit code number (00 to 48) + 4 or 6-digit access code + [ ENTER ]
11.2
Regular Arming
This method, commonly used for day-to-day arming, will arm all the zones in the system. To Regular arm, the light must be illuminated, indicating that all zones are closed. All doors and windows must be closed, and there can be no movement in areas monitored by motion detectors. Once the light is on, a valid user access code must be entered. If a mistake is made entering the code or if the light is not on when the code was entered, the keypad will emit a rejection beep.
When the correct user access code is entered, the keypad will emit a confirmation beep and the light will illuminate. The
seconds of the exit delay, the keypad will beep and the light will flash at a faster rate. At the end of the exit delay, the keypad will emit a confirmation beep, the light will extinguish and the light will remain illuminated to indicate that the system is armed.
11.2.1
One-Key Regular Arming
To use this feature, enable the One-Key Regular Arming option (see page 32). When the
light is on, pressing and holding the [0] or [ ARM ] key for 2 seconds will arm all zones in the system. This feature can be used to allow specific individuals like service personnel (i.e. cleaners, maintenance) to arm the system when leaving the protected area, without giving them access to any other control panel operations. The use of a valid access code is still required to
disarm the system. For more information, see Regular Arming on page 40.
11.3
Force/Away Arming
To rapidly arm the system without having to wait for the light, simply press the [ FORCE ]/[ AWAY ] key followed by a valid access code. Once the exit delay expires, any open zones will be considered "deactivated" by the control panel. Therefore, these zones will not generate an alarm. If, while the system is armed, a "deactivated" zone closes, the control panel will change that zone to active status, generating an alarm if the zone is breached.
728 Ultra: If a mistake is made entering the code, the keypad will emit a rejection beep. When the correct user code is entered, the keypad will emit a confirmation beep and the light will illuminate. The light will flash and the keypad will beep during the exit delay period (see
light will flash at a faster rate. At the end of the exit delay, the light will extinguish and the light will remain illuminated. If programmed at address 518, the control panel will send a partial arm report code to the monitoring station.
738 Ultra: If a mistake is made entering the code, the keypad will emit a rejection beep. When the correct user code is entered, the keypad will emit a confirmation beep and the light will illuminate. The light will flash and the keypad will beep during the exit delay period (see
Beep on Exit Delay on page 33). For the LED keypad, the
[ AWAY ] key will flash during the exit delay. During the final 10 seconds of the exit delay, the keypad will beep and the light will flash at a faster rate (LED keypad: the [ AWAY ] key will flash at a faster rate). At the end of the exit delay, the light will extinguish and the light will remain illuminated (LED keypad: the [ AWAY ] key will flash). If programmed at address 518, the control panel will send a partial arm report code to the monitoring station.
To use this method, the user must have force arming priority (see
40 Reference & Installation Manual
11.4
Stay Arming
Stay arming allows the user to remain in the protected area while partially arming the system. This means that the user can stay in and move around the establishment, while certain designated zones are armed. For example, entry/exit points like doors or windows, the basement, or perhaps all the zones on the perimeter of the establishment may be armed when going to sleep at
System A/Stay Zones on page 29.
Unlike Regular arming, the light does not have to be illuminated. Only doors and windows programmed as stay zones must be closed, and there can be no movement in areas monitored by motion detectors in stay zones. To Stay arm the system, press the
[ STAY ] key followed by a valid access code. If a mistake is made entering the code or if a stay zone is open when entering the code, the keypad will emit a rejection beep.
728 Ultra: After entering the correct user access code, the keypad will emit a confirmation beep, the light will flash and the
[ STAY ] key will illuminate (LED keypad only) during the exit delay period. During the final 10 sec. of the exit delay, the light will flash at a faster rate and the [ STAY ] key will remain illuminated (LED keypad only). At the end of the exit delay, the keypad will the ] key will remain illuminated (LED keypad only).
738 Ultra: After entering the correct user access code, the keypad will emit a confirmation beep, the light will flash and the
[ STAY ] key will flash during the exit delay period (LED keypad only). During the final 10 sec. of the exit delay, the light will flash at a faster rate and the [ STAY ] key will flash at a faster rate (LED keypad only). At the end of the exit delay, the keypad will emit a confirmation beep, the and lights and the [ STAY ] key will flash (LED keypad only).
To use this method, the user must be given Stay arming priority (see Code Priority on page 34).
11.4.1
One-Key Stay Arming
pressing and holding the [ STAY ] key for 2 seconds will arm only zones programmed as stay zones. For more information, refer to
11.4.2
One-Key Instant Arming
During the Stay arming exit delay (see Stay Arming on page 41), press and hold the
[ STAY ] key for 2 seconds until you hear a single beep. This will switch all entry delay zones to instant zones (see
,
waiting a pre-determined period.
11.4.3
Fast Exit
user to exit premises while the system is already armed and keep the system armed. This can be done one of two ways:
• With the system already Stay armed (after the exit delay), press and hold the [ STAY ] key for 2 seconds. The system will switch to exit delay mode ( light flashes), allowing time for the user to exit the premises. At the end of the exit delay period, the system will return to Stay arm mode.
• With the system already Stay armed, press and hold the [0] or [ ARM ] key for 2 seconds. The system will switch to exit delay mode ( light flashes). At the end of the exit delay period, the system will Regular arm the system (see
11.5
Arming/Disarming Partitions
Thanks to the partitioning feature, two distinct systems (A and B) can be created and controlled by the control panel. Partitioning can be used in installations where shared security systems are more practical, such as office/warehouse buildings, or apartment/ condominium complexes. Each zone can be assigned to System A, System B, both systems or given no system assignment.
User access codes can also be programmed to arm/disarm one system or both systems simultaneously (see
Code Priority on page 34). Unlike Regular arming, the
light does not have to be illuminated. All doors and windows pertaining to the desired system must be closed, and there can be no movement in areas monitored by motion detectors in the desired system.
1. If a user is not given any code priorities, the user will never be able to arm or disarm the system when partitioned.
2. If a user is given code priority to one of the two systems, entering the correct access code will arm or disarm the system to which the user was given priority.
3. If a user is given code priority to arm/disarm both systems A & B, it will function as follows:
• If the user enters the correct access code when Systems A and B are disarmed, it will completely arm both systems.
• If the user enters the correct access code when Systems A and B are armed, it will completely disarm both systems.
• When the system is partially armed, (i.e. only System A or only System B is armed) entering the correct access code will arm the other system.
• To arm/disarm each system separately, do the following:
Press [ STAY ] + [ VALID ACCESS CODE ] to arm/disarm System A.
Press [ AWAY ]/[ FORCE ] + [ VALID ACCESS CODE ] to arm/disarm System B.
Esprit 728 Ultra & 738 Ultra 41
If a mistake is made entering the code or if a zone in the desired system is open when entering the code, the keypad will emit a rejection beep. When the access code is correctly entered, the keypad will emit a confirmation beep. The keypad can display the status of both systems. For the LED keypad, when System A is armed, the [ STAY ] key and light will remain on. If System B is armed, the [ AWAY ]/[ FORCE ] key and light will remain on. When both systems are armed, all three lights will remain on. The
LCD keypad will directly display the partition status.
11.5.1
One-Key System A Arming
This feature allows the user to arm System A without the use of an access code. To use this feature, enable the One-
[ STAY ] key for 2 seconds to arm System A. This feature can be used to allow specific individuals like service personnel
(i.e. cleaners, maintenance) to arm the system when leaving the protected area, without giving them access to any
11.6
System Disarming
The user must enter the protected area through a designated entry/exit point. The keypad will beep during the entry delay reminding the user to disarm the system. Upon entry of a valid access code, the light will extinguish and the keypad will emit a confirmation beep indicating that the system has been disarmed. If an incorrect access code is entered, the keypad will emit a rejection beep. Press the [ CLEAR ] key at any time to clear data and re-enter another access code. If an alarm was generated from a fire or 24Hr zone while the system was armed, entering a valid user code will silence the siren. However, you should then check the zone and eliminate the cause of the alarm. If you are unable to pinpoint the reason for the alarm, call your installer.
11.7
Alarm Memory
If an alarm condition occurs when the system is armed, the [ MEM ] key will turn on. A record of all alarm situations that occur is stored in memory. After disarming the system, pressing once on the [ MEM ] key will display which zones were open during the alarm period by illuminating the corresponding zone indicator(s) or by displaying it on the LCD screen depending on the type of keypad used. Please note that if the [ MEM ] key is pressed again when using LED keypads (636 and 646*) you will enter the event display which can only be decoded with a 642 LCD keypad. To exit the alarm memory display, press the [ CLEAR ] key. If using a
642* LCD keypad press the [ MEM ] key followed by the [ INFO ] key and use the [
S
] and [
T
] keys to scroll through the event list in memory. The alarms will remain in memory until the system is armed and disarmed without generating an alarm.
* Do not use the 646 LED and 642 LCD keypads for UL installations. Both the 646 LED keypad and the 642 LCD keypad are not UL listed.
11.8
Keyswitch or Pushbutton Arming/Disarming
A keyswitch or push button can be used to Stay (see
Stay Arming on page 41) or Regular (see
Regular Arming on page 40) arm/
disarm the system. If the system is ready and the button is pressed, the system will arm. Pressing the button again will disarm the system. If a Stay armed system is in entry delay or if an alarm has been generated while Stay armed, the keyswitch or push button cannot be used to disarm the system (if the keyswitch is programmed to Stay arm/disarm). In this case, only a keypad can disarm the system. In a partitioned system the keyswitch or push button will arm/disarm System A regardless of the System B
11.9
Manual Zone Bypassing
When a zone is bypassed it will no longer be monitored by the control panel, and hence, will not generate an alarm. A user may wish to bypass certain zones when, for example, workers are renovating part of the establishment or if a component in the system is damaged. Manual bypass arming instructs the control panel to ignore ("deactivate") specified zones in order to arm the remainder of the system. Verify that the following options are set in the control panel so that a user can manually bypass zones:
be bypassed.
• Only users with the appropriate Code Priority (see page 34) can bypass zones.
• Please note, the control panel cannot bypass fire zones.
To bypass zones, press the [ BYP ] key followed by a valid access code. If the wrong code or a code without bypass priority is entered, the keypad will emit a rejection beep. If the correct code is entered, the [ BYP ] key will flash to indicate that you are now in bypass mode. If there are any currently bypassed zones, their respective zone indicators will turn on. Press the key corresponding to the zone you wish to bypass until their respective zone indicator turns on. If the zone you wish to bypass has not been programmed as bypass enabled, the corresponding zone indicator will never turn on. Press the [ CLEAR ] key to erase the current zone bypass entries and exit the bypass mode. If you have entered the correct bypass entries, press the [ ENTER ] key to accept these entries. The [ BYP ] key will remain on, denoting that zones in the system are currently bypassed, and hence, the next time the system is armed, certain zones will be bypassed. When the system is disarmed, the bypass entries will be erased.
11.10
Bypass Recall
This feature permits users to reinstate the last zone bypass entries saved in memory. When the system is disarmed, the bypass entries will be erased. To recall the previous bypass entries, while in the bypass mode, press the [ BYP ] and [ ENTER ] keys and the
42 Reference & Installation Manual
previous bypass status will be re-established. This eliminates the need to re-enter the bypass entries every time the system is armed. If a user is in the process of entering new bypass entries on the keypad, pressing the [ BYP ] key will override new information and reinstate previous bypass entries.
11.11
Keypad Chime Zones (on LED Keypads)
A chimed zone advises you when a zone is opened by creating a rapid intermittent beep tone (beep-beep-beep-beep-beep). Up to six zones plus the local keypad zone can be programmed as chime zones. To turn on the chime zone feature, press and hold the key corresponding to the desired zone ( [1] to [6] ) for three seconds until the intermittent chime beep is heard. This means that the chime feature has been activated. If a continuous beep is heard, this means that the chime beep has been deactivated.
To enable the chime feature on the keypad zone, press and hold the [8] key for three seconds. To mute the keypad's alarm sounder, press and hold the [9] key for three seconds until the intermittent chime beep is heard. This means that the muting feature has been activated. If a continuous beep is heard, this means that the muting feature has been deactivated. If there is more than one keypad in the system, you must program each keypad’s chime zones separately. Keypad chimes must be reprogrammed if the panel suffers a total power loss.
Key [1] [6] : Turns chime ON or OFF in zones numbered 1-6
Key [8] :
Key [9] :
Turns chime ON and OFF for the local keypad zone
Turns the keypad's alarm sounder muting ON or OFF
11.12
Trouble Display Monitoring
Trouble conditions are continuously monitored by the control panel, which recognizes and displays 10 different trouble conditions on the keypad. When a trouble condition occurs, the [ TBL ]/[ TRBL ] key will illuminate and the keypad will emit an intermittent beep
if the Audible Trouble Warning (see page 39) is enabled. Press the
[ TBL ]/[ TRBL ] key to switch to trouble display mode. The [ TBL ]/
[ TRBL ] key will flash and any illuminated keys correspond to a current trouble condition as described below. Press any key to exit the trouble display mode.
11.12.1 No Battery/Low Battery - Key [1]
The control panel conducts a dynamic battery test under load every 60 seconds. The illumination of the [1] key indicates that the back-up battery is disconnected or that the battery should be replaced, as it will not provide adequate back-up current in case of AC loss. If the control panel is currently running on battery power, the illumination of the [1] key indicates that the battery voltage has dropped to 10.5 volts or lower.
11.12.2 Power Failure - Key [2]
The control panel will detect a power loss if a continuous loss of AC (less than or equal to 12.5V) has occurred during the period between two AC power tests (64 to 116 seconds). If a power loss remains present throughout the Power Failure
[ TBL ]/[ TRBL ] key will flash rapidly indicating a power failure. The trouble indicator is restored if AC is detected during the dynamic battery test and the panel will then transmit the report code programmed at address 507. You can remove the power failure trouble
11.12.3 Bell Disconnected - Key [4]
The illumination of the [4] key indicates that there is no bell or siren connected to the bell output terminals of the panel.
Please note that when connecting a bell or siren to an optional relay output the trouble indicator will always be on. To avoid this, connect a 1k
9
resistor across the bell output. The control panel only recognizes bells or siren connected directly to the bell output of the control panel—not those connected through a relay.
11.12.4 Maximum Bell Current - Key [5]
The bell output is microprocessor controlled and will automatically shut down when the current exceeds 3A. If this occurs, the [5] key will illuminate. After opening the short or reducing the load, the bell current is restored upon the following alarm generation.
This trouble indicator will only appear when the bell is activated (i.e. during an alarm).
11.12.5 Maximum Auxiliary Current - Key [6]
The illumination of the [6] key indicates that the auxiliary current has exceeded 650mA (728 Ultra) or 700mA (738
Ultra). This will cause an automatic shutdown of the auxiliary output. After opening the short or reducing the load, the panel will restore power to the auxiliary output following the dynamic battery test (approximately 60 seconds).
11.12.6 Communicator Report Failure - Key [7]
If the control panel was unsuccessful while attempting to communicate with the monitoring station computer or the
Espload software, the [7] key will illuminate. This trouble is automatically cleared when the [ TBL ]/[ TRBL ] key is pressed and the user has exited from the Trouble Display.
Esprit 728 Ultra & 738 Ultra 43
11.12.7 Timer Loss - Key [8]
The illumination of the [8] key indicates that the control panel’s internal clock must be reprogrammed. To reprogram the timer press:
[ ENTER ] + (Installer, Master or User code 1) + [ MEM ] + 2 digits (00 to 23) representing hours + 2 digits (00 to 59) representing minutes + [ ENTER ]
11.12.8 Tamper/Zone Wiring Failure - Key [9]
If the Tamper/Wire Fault Recognition Options (see page 38) are enabled, the
[9] key will illuminate to indicate a short or cut on a zone input. In order to provide line short recognition the zone connections must have EOL resistors (see
on page 5 to Single Zone Input Terminal Connections on page 6).
11.12.9 Telephone Line Monitoring - Key [0]
If the Telephone Line Monitoring (TLM) feature (see page 37) is enabled, the
[0] key will illuminate to indicate that the control panel has not detected the presence of a telephone line for 30 seconds.
11.12.10 Fire Loop Trouble - Key [
STAY
]
The illumination of the [ STAY ] key indicates a wiring problem (line open) on zone 3 (or zone 5 with 2-wire smoke and
ATZ for 728 Ultra), if identified as a fire zone (see
24Hr and 4-Wire Smoke Detector Fire Zones
and
Detector Recognition (Input 3) on page 28).
11.13
Key Access Programming
This method allows for quick programming of features without entering addresses or section numbers. The following features are programmed using the Installer code as well as the Master code and User code 1.
Key
[9]
[ MEM ]
[ BYP ]
[ TBL ] / [ TRBL ]
[ AWAY ] / [ FORCE ]
[ STAY ]
[8]
Features
Auto Arm Time: for details see page 32
Panel Time: for details see page 38.
Manual Test Report: for details see page 24
Call Espload: for details see page 15
Answer Espload: for details see page 15
Cancel Communication: for details see page 15
Installer Test Mode: for details see page 39.
44 Reference & Installation Manual
Important Information
This equipment complies with Part 68 of the FCC rules subpart D and CS-
03. Inside the cover of this equipment is a label that contains, among other information, the FCC registration number of this equipment.
Notification to Telephone Company
Upon request, customer shall notify telephone company of particular line to which the connection will be made, and provide the FCC registration number and the ringer equivalence of the protective circuit.
FCC Registration Number: 5A7AL01B728ULT
Ringer Equivalence Number: 0.1B (U.S. & Canada)
USOC Jack: RJ31X (USA), CA31A (CANADA)
Telephone Connection Requirements
Except for telephone company provided ringers, all connections to the telephone network shall be made through standard plugs and telephone company provided jacks, or equivalent, in such a manner as to allow for easy, immediate disconnection of terminal equipment. Standard jacks shall be so arranged that, if plug connected thereto is withdrawn, no interference to operation of equipment at customer's premises which remains connected to telephone network shall occur by reason of such withdrawal.
Incidence of Harm
Should terminal equipment/protective circuitry cause harm to telephone network, telephone company shall, where practicable, notify customer that temporary disconnection of service may be required; however, where prior notice is not practicable, the telephone company may temporarily discontinue service if action is deemed reasonable in circumstances. In case of temporary discontinuance, telephone company shall promptly notify customer and will be given opportunity to correct the situation.
Changes in Telephone Company Equipment or Facilities
The telephone company may make changes in its communication facilities, equipment operations or procedures, where such actions are reasonably required and proper in its business. Should any such changes render customer's terminal equipment incompatible with the telephone company facilities, the customer shall be given adequate notice to effect the modifications to maintain uninterrupted service.
General
This equipment shall not be used on coin telephone lines. Connection to party line service is subject to state tariffs.
Ringer Equivalence Number (REN)
The ren is useful to determine the quantity of devices that you may connect to your telephone line and still have all of those devices ring when your telephone number is called. In most, but not all areas, sum of the ren's of all devices connected to one line should not exceed five (5.0). To be certain of the number of devices that you may connect to your line, you may want to contact your local telephone company.
Equipment Maintenance Facility
If you experience trouble with this telephone equipment, please contact facility indicated below for information on obtaining service or repairs. The telephone company may ask that you disconnect this equipment from network until problem is corrected or until you are sure that the equipment is not malfunctioning.
FCC Part 15, Warnings Information to User
This equipment has been tested and found to comply with the limits for
Class B digital devices, pursuant to Part 15 of FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy, and, if not installed and used in accordance with
Warnings
the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to equipment intermittently, the user is encouraged to try to correct the interference by one or more of the following measures: (1) re orient or relocate the receiving antenna; (2) increase the separation between the equipment and receiver; (3) connect the equipment to an outlet on a circuit other than the one to which the receiver is connected, or (4) consult the dealer or an experienced radio/tv technician for assistance.
Caution:
Changes or modifications not expressly approved by PARADOX
SECURITY SYSTEMS could void the user's authority to operate the equipment.
Warranty
Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as specifically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with products not manufactured by Seller , Seller cannot guarantee the performance of the security system and shall not be responsible for circumstances resulting from the product’s inability to operate.
Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the specifications.
Returns must include proof of purchase and be within the warranty period.
In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct or indirect or consequential or incidental, including without limitation, any damages for lost profits stolen goods, or claims by any other party, caused by defective goods or otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold.
Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limited to the purchase price of the defective product. Your use of this product signifies your acceptance of this warranty.
BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional warranties that are binding on the Seller.
Attachment Limitation Notice
The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company.
The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electrical inspection
Esprit 728 Ultra & 738 Ultra 45
authority, or electrician, as appropriate.
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device, to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all of the devices does not exceed 100.
Industry Canada certification is only applicable to installation of devices which include transformers approved by the Canadian Standards
Association (CSA).
Requirements and Guidelines for UL Installations
UL has only evaluated the 728ULT for compatibility with the
Ademco model 685, FBI model CP220FB, SUR-GUARD SG-
MLR2-D6 and Silent Knight model 9000.
UL listed in accordance with standard UL1023 (Household Burglar
- Alarm System Units), standard UL985 (Household Fire Warning
Units) and UL1635 (Digital Alarm Communicator System Units).
Look for the UL mark on the product. Only products bearing this mark are UL listed.
Some operational features are not permitted in UL installations. To respect the standards for household applications, the installer should follow these guidelines when configuring the system.
1. All components of the system should be UL listed for the intended application.
2. If the installation is a FIRE ALARM application, refer to NFPA Standard
74 for details on smoke detector locations. There must be at least one
UL-Listed Indoor Fire Alarm Warning Signalling Appliance.
3. For UL/cUL Burglar Applications:
Maximum entry time = UL 45 seconds/cUL 60 seconds
Maximum exit time = UL 60 seconds/cUL 120 seconds
Minimum bell cutoff time = 5 minutes
4. Keypad Models 639, 642 and 646 are not UL/cUL listed. Do not use the
708 or Esprint with a UL installation--they are not UL listed.
5. The upload/download software should not be used on UL listed systems.
6. All outputs are Class 2 or power-limited, except for the battery terminal.
The Class 2 and power-limited fire alarm circuits shall be installed using
CL3, CL3R, CL3P or substitute cable permitted by the National Electrical
Code, ANSI/NFPA 70.
Label: US: 5A7AL01B728ULT
Filing Type: New Filing
Product Identifier: 728ULT
Equipment Code: AL
Network Address Signal Code: E
Country of Origin: CANADA (CAN)
AC Ringer Equivalent Number: 01B
USOC Jacks: RJ31X
Equipment Description: Control panel for residential burglar and fire warning systems
Rechargeable Acid/Lead or Gel Cell Backup Battery: 12Vdc, 4Ah/
7Ah; UL/cUL: 12Vdc, 7Ah only
Transformer: Universal, Model No. UB1640W, 16.5Vac (50-60Hz)
20VA minimum (40VA recommended). Do not connect the transformer to a switch-controlled outlet.
Bell/Siren: UL/cUL Wheelock 46T-12
Aux Power: 450mA (fuseless shutdown at 650mA); UL: 200mA maximum for 24Hr stand-by
Smoke Detector: 2-wire Hochicki model SLR 835BH-2 (see
Warning : For UL installations, the metallic enclosure must be grounded to the cold water pipe or to the grounding rod.
UL/cUL: All outputs are Class 2 or power-limited, except for the battery terminal. The Class 2 or power-limited fire alarm circuits shall be installed using CL3, CL3R, CL3P or substitute cable permitted by the National Electrical Code, ANSI/NFPA 70.
Requirements and Guidelines for AUSTEL Installations
Austel-approved installations: use a transformer approved by the
State Electricity commission, such as "Dyen" PA series 15Vac
22VA. With this transformer, do not exceed the following maximum currents:
- maximum Auxiliary current (including keypads): 300mA
- maximum Bell current: 600mA
Requirements and Guidelines for cUL Installations
When the system controls a fire alarm system, wiring method must correspond to section 32 of the Canadian Electrical Code.
Look for the cUL mark on the product. Only products bearing this mark are cUL listed.738 Ultra is not UL listed.
Rechargeable Acid/Lead or Gel Cell Backup Battery: 12Vdc, 4Ah/
7Ah; UL/cUL: 12Vdc, 7Ah only
Transformer: Universal, Model No. UB1640W, 16.5Vac (50-60Hz)
20VA minimum (40VA recommended). Do not connect the transformer to a switch-controlled outlet.
Bell/Siren: UL/cUL Wheelock 46T-12
Aux Power: 450mA (fuseless shutdown at 650mA); UL: 200mA maximum for 24Hr stand-by
Smoke Detector: 2-wire Hochicki model SLR 835BH-2 (see
© 2003-2005 Paradox Security Systems Ltd. Esprit and Ultra are trademarks or registered trademarks of Paradox Security Systems
Ltd. and its affiliates in Canada, the United States and other countries. All rights reserved. Specifications may change without prior notice. One or more of the following patents may apply:
6215399, 6111256, 5751803, 5721542, 5287111, 5119069,
5077549, 5920259 5886632. Canadian and international patents may also apply.
46 Reference & Installation Manual
Index
Numerics
24Hr Zones
........................................................................28
2-Wire smoke detector
Connections
..................................................................10
Recognition
...................................................................28
4-Wire smoke detector connections
......................................10
A
About this manual
.................................................................1
AC Power
............................................................................2
Access Codes
....................................................................11
Access Programming, Key
...................................................44
Account Codes, System
......................................................19
Alarm Codes
......................................................................22
Alarm Memory
....................................................................42
Alarm Relay Ouputs
..............................................................4
Alarm Transmission Delay
...................................................33
Answer Espload
.................................................................15
Answering Machine Override Options Table
Anti-Tamper Switch
..............................................................6
Arming
Away
...........................................................................40
Codes
..........................................................................22
Force
...........................................................................40
Partitions
......................................................................41
Pushbutton
....................................................................42
Regular
........................................................................40
Stay
............................................................................41
Using a Keyswitch
.....................................................33
ATZ
...................................................................................27
ATZ Connections
..................................................................7
ATZ Parallel Wiring
...............................................................9
Audible Trouble Warning
.....................................................39
Auto Arm Time
...................................................................32
Auto Arming Options
...........................................................32
Auto Arming Options Table
..................................................32
Auto Test Report
................................................................23
Auto Zone Shutdown
..........................................................30
Automatic Event Buffer Transmission
...................................15
Auxiliary Power Terminals
.....................................................3
Away Arming
......................................................................40
B
Backup Battery
.....................................................................2
Battery Test
.........................................................................3
Battery, Backup
....................................................................2
Beep
Confirmation
..................................................................40
On Exit Delay
.................................................................33
Rejection
......................................................................40
Bell Cut-off Time
.................................................................34
Bell Output
...........................................................................4
Bell Squawk
.......................................................................33
Bypass
Enabled Zones
...............................................................29
Manual Zone
.................................................................42
Recall
..........................................................................42
Tamper, Options
.............................................................39
C
Call Back
........................................................................... 15
Call Espload
....................................................................... 15
Cancel Communication
....................................................... 15
Chime Zones, Keypad
......................................................... 43
Closing Delinquency Timer
.................................................. 34
Code Priority
...................................................................... 34
Commonly Used PGM Options Table
...................................36
Communicator Formats
Ademco Contact ID
All Codes
............................................................... 19
Programmable Codes
................................................ 20
Ademco Express
............................................................ 21
Pager
........................................................................... 21
Standard Pulse Formats
................................................... 21
Communicator Formats Table
........................................19
Computer Telephone Number
.............................................. 15
Connecting an Anti-Tamper Switch on an LED Keypad
Connecting Programmable Outputs
........................................ 4
Contact ID Event Codes Table
............................................. 19
Current Consumption Table
................................................... 3
D
Decimal Programming
......................................................... 13
Delinquency Timer
.............................................................. 34
Dialing Options
................................................................... 37
Dialing Pulse Rates
............................................................ 37
Disarming
Partitions
...................................................................... 41
Pushbutton
.................................................................... 42
System
......................................................................... 42
Using a Keyswitch
........................................................... 42
Disarming Codes
................................................................22
Double Reporting
............................................................... 17
Double Zone Input Connections. See ATZ Connections
Duress Code
...................................................................... 11
E
Earth Ground
....................................................................... 2
Entry Delay 1
..................................................................... 29
Entry Delay 2
..................................................................... 29
EOL Zones
........................................................................ 30
Espload Software
............................................................... 12
Event Reporting
................................................................. 16
Exclude Power Failure from Trouble Display
Exit Delay
.......................................................................... 33
F
Fast Exit
............................................................................ 41
Feature Select Programming
............................................... 13
Fire Circuit
Standard Installation
........................................................ 10
UL/ULC Installation
......................................................... 10
Fire Zones
......................................................................... 28
Follow Zones
..................................................................... 28
Force Arming
..................................................................... 40
G
Ground
................................................................................ 2
Esprit 728 Ultra & 738 Ultra 47
H
Hexa Programming
............................................................. 12
Hexa Streamlined Section Programming
............................... 13
I
Input Connections
For Single Zones. See Single Zone Connections
For Zone Doubling. See ATZ Connections
Installer
Code
........................................................................... 11
Lock
............................................................................ 11
Test Mode
.................................................................... 39
Instant Zones
..................................................................... 28
Intellizone Time Delay
......................................................... 27
Intellizones
........................................................................ 27
K
Key Access Programming
................................................... 44
Keypad
Chime Zones
................................................................. 43
Connections
.................................................................... 4
Function Test
................................................................... 3
Panic Options
................................................................ 37
Zone 1 Supervision
......................................................... 30
Zone 2 Supervision
......................................................... 30
Zone Connections
............................................................. 5
Zone Recognition Table
..................................................... 6
Keyswitch
Arming
................................................................... 33 ,
Arming Table
................................................................. 33
Connections
.................................................................... 4
Disarming
..................................................................... 42
L
LED, Status
....................................................................... 11
Location and Mounting
.......................................................... 2
M
Manual Test Report
............................................................ 24
Manual Zone Bypassing
...................................................... 42
Master Code
...................................................................... 11
Lock
............................................................................ 11
Programming
................................................................. 40
Memory, Alarm
................................................................... 42
Monitoring Station Telephone Number 1
............................... 18
Monitoring Station Telephone Number 2
............................... 18
Mounting
............................................................................. 2
N
No Movement Auto Arm Time
.............................................. 32
No Movement Auto Arming
.................................................. 32
O
One-Key
Double Stay Arming
........................................................ 41
Regular Arming
........................................................ 32 ,
Stay Arming
............................................................ 33 ,
System A Arming
...................................................... 33 ,
Other Options
.................................................................... 37
P
Pager
Delay
........................................................................... 21
Format Transmission Options
............................................ 21
Report Event Options
...................................................... 21
48 Reference & Installation Manual
Reporting Format
............................................................ 21
Panel
Answer Options
.............................................................. 14
Identifier
....................................................................... 14
Settings for Espload
........................................................ 14
Time
............................................................................ 38
Panic
Codes
.......................................................................... 23
Keypad Options
............................................................. 37
Silent Option
................................................................. 34
Parallel Wiring, ATZ
.............................................................. 9
Partition Arming / Disarming
................................................ 41
Partitioning
........................................................................ 29
PC Password
..................................................................... 14
PGM Options
..................................................................... 36
PGM Timer Setting
............................................................. 35
PGM Type Selection Table
.................................................. 35
PGM Types
AND Logic
.................................................................... 35
EQUAL Logic
................................................................. 35
OR Logic
...................................................................... 35
Regular N.O. / N.C.
......................................................... 35
Timed N.O. / N.C.
........................................................... 35
PGMs, Programming
.......................................................... 35
Power
................................................................................. 2
Power Down Reset
............................................................. 39
Power Failure Report Delay
................................................. 24
Programmable Outputs
Connecting
..................................................................... 4
Programming Master and User Codes
.................................. 40
Programming Methods
Espload Software
........................................................... 12
Keypad
Decimal Programming
............................................... 13
Feature Select Programming
....................................... 13
Hexa Programming
................................................... 12
Hexa Streamlined Section Programming
Programming PGMs
........................................................... 35
Programming, Key Access
.................................................. 44
Pulse Rates, Dialing
........................................................... 37
Pushbutton Arming / Disarming
............................................ 42
R
Recent Close Delays
.......................................................... 24
Regular Arming
.................................................................. 40
Regular Reporting
.............................................................. 17
Report Code Disarming Options
........................................... 24
Report Zone Restore Options
.............................................. 24
Reporting Disabled
............................................................. 17
Reporting Event Codes
Alarm Codes
................................................................. 22
Arming Codes
................................................................ 22
Disarming Codes
............................................................ 22
Restore Codes
............................................................... 22
Special Codes
............................................................... 23
Tamper Trouble Codes
.................................................... 22
Trouble / Trouble Restore Codes
........................................ 23
Zone Shutdown Codes
..................................................... 22
Reporting Options
Bypass Reporting
........................................................... 19
Double Reporting
............................................................ 17
Regular Reporting
........................................................... 17
Reporting Disabled
......................................................... 17
Split Reporting
............................................................... 17
Reporting Options Table
..................................................... 17
Reset to default
.................................................................. 39
Restore Codes
...................................................................22
Restrict Arming
On Battery Failure
...........................................................34
On Tamper Trouble
.........................................................34
S
Serial Output Connector
......................................................10
Shutdown Codes, Zone
.......................................................22
Silent Panics Option
............................................................34
Silent Zone Options
............................................................34
Silent Zones
.......................................................................27
Single Zone Connections
.......................................................6
Siren Output
.........................................................................4
Smoke detector connections
2-wire
..........................................................................10
4-wire
..........................................................................10
Special Codes
....................................................................23
Specifications
.......................................................................1
Split Reporting
...................................................................17
Squawk, Bell
......................................................................33
Status LED
........................................................................11
Stay Arming
.......................................................................41
System A / Stay Zones
........................................................29
System Account Codes
.......................................................19
System B Zones
.................................................................29
System Disarming
..............................................................42
T
Tamper / Wire Fault Recognition Options
..............................38
Tamper Bypass Options
......................................................39
Tamper Codes
...................................................................22
Tamper Fault Recognition Options
.......................................38
Tamper Recognition Table
...................................................38
Telephone Line Connection
...................................................3
Telephone Line Monitoring (TLM)
.........................................37
Telephone Line Monitoring Table
.........................................37
Telephone Number Special Instructions Table
Test
Battery
...........................................................................3
Keypad Function
...............................................................3
Test Report
Auto
............................................................................23
Manual
.........................................................................24
Test Transmission, Timed
...................................................24
Time Correction
..................................................................38
Time Correction Table
.........................................................38
Timed Auto Arming
.............................................................32
Timed Test Transmission
....................................................24
Trouble Codes
...................................................................23
Trouble Display Monitoring
..................................................43
Trouble Restore Codes
.......................................................23
Troubles
Bell Disconnected
...........................................................43
Communicator Report Failure
............................................43
Fire Trouble
...................................................................44
Maximum Auxiliary Current
................................................43
Maximum Bell Current
......................................................43
No Battery / Low Battery
...................................................43
Power Failure
................................................................43
Tamper / Zone Wiring Failure
.............................................44
Telephone Line Monitoring (TLM)
........................................44
Timer Loss
....................................................................44
U
User / Access Code Length
.................................................11
User / Keypad Functions
..................................................... 40
User Code Programming
..................................................... 40
User Codes
........................................................................ 11
W
Wire Fault Recognition Options
............................................ 38
Z
Zone 4
............................................................................... 28
Zone Bypassing, Manually
................................................... 42
Zone Definitions
................................................................. 25
Zone Recognition Table, Keypad
............................................ 6
Zone Shutdown Codes
........................................................ 22
Zone Speed
....................................................................... 27
Esprit 728 Ultra & 738 Ultra 49
Notes
For technical support in Canada or the U.S., call 1-800-791-1919 for English or 1-866-912-0600 for French, Monday to Friday, 8:00 a.m. to 8:00 p.m. EST.
For technical support outside Canada and the U.S., call 00-1-450-491-7444, Monday to Friday from 8:00 a.m. to 8:00 p.m. EST.
Please feel free to visit our website at www.paradox.ca.
780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADA
Tel.: (450) 491-7444 Fax: (450) 491-2313 www.paradox.ca
PRINTED IN CANADA - 03/2005 7X8ULT-EI01
advertisement
Related manuals
advertisement
Table of contents
- 5 Introduction
- 5 About This Manual
- 5 New Features
- 5 Main Features
- 5 Specifications
- 6 Installation
- 6 Location and Mounting
- 6 Earth Ground
- 6 AC Power
- 6 Backup Battery
- 7 Auxiliary Power Terminals
- 7 Battery Test
- 7 Keypad Function Test
- 7 Telephone Line Connection
- 8 Bell/Siren Output
- 8 Alarm Relay Outputs (738 Ultra; Optional)
- 8 Programmable Outputs (PGMs)
- 8 Keypad and Keyswitch Connections
- 9 Keypad Zone Connections
- 10 Connecting an Anti-Tamper Switch on an LED Keypad
- 10 Single Zone Input Terminal Connections
- 10 N.C. Contacts, Without EOL Resistor
- 11 N.O. and N.C. Contacts, With EOL Resistor (UL/cUL)
- 11 Recognition
- 11 Wire Fault Recognition (UL/cUL)
- 11 Advanced Technology Zone (ATZ) Connections
- 12 N.C. Contacts, Without EOL Resistor, ATZ Series
- 13 Recognition, ATZ Series
- 13 Wire Fault Recognition (UL/cUL), ATZ Series
- 13 N.C. Contacts, With ATZ Parallel Wiring
- 14 Fire Circuit
- 14 4-Wire Smoke Detector Connections (Standard Installation)
- 14 4-Wire Smoke Detector Connections (UL/cUL Installation)
- 14 2-Wire Smoke Detector Connections
- 14 Serial Output Connector
- 15 Status LED
- 15 Access Codes
- 15 Installer Code
- 15 Master and User Codes
- 15 User/Access Code Length
- 15 Duress
- 15 Installer Lock
- 15 Master Code Lock
- 16 Programming Methods
- 16 Espload Software
- 16 Keypad
- 16 Hex Programming
- 17 Hex Streamlined Section Programming
- 17 Decimal Programming
- 17 Feature Select Programming
- 18 Panel Settings for Espload
- 18 Panel Answer Options
- 18 Panel Identifier
- 18 PC Password
- 19 Computer Telephone Number
- 19 Call Espload
- 19 Answer Espload
- 19 Cancel Communication
- 19 Call Back
- 19 Automatic Event Buffer Transmission
- 20 Event Reporting
- 21 Reporting Options
- 21 Reporting Disabled
- 21 Regular Reporting
- 21 Split Reporting
- 21 Double Reporting
- 22 Monitoring Station Telephone Number 1 (MSTN1)
- 22 Monitoring Station Telephone Number 2 (MSTN2)
- 23 System Account Codes
- 23 Communicator Formats
- 23 Ademco Contact ID (All Codes)
- 24 Ademco Contact ID (Programmable Codes)
- 25 Ademco Express
- 25 Pager Reporting Format
- 25 Standard Pulse Formats
- 25 Pager Delay
- 25 Pager Format Transmission Options
- 25 Pager Report Event Option
- 26 Reporting Event Codes
- 26 Arming Codes
- 26 Disarming Codes
- 26 Alarm Codes
- 26 Restore Codes
- 26 Zone Shutdown Codes
- 26 Tamper Codes
- 27 Trouble/Trouble Restore Codes
- 27 Special Codes
- 27 Auto Test Report
- 28 Timed Test Transmission (738 Ultra only)
- 28 Manual Test Report
- 28 Power Failure Report Delay
- 28 Recent Close Delay
- 28 Report Zone Restore Options
- 28 Report Code Disarming Options
- 29 Zone Definitions
- 31 Zone Speed
- 31 Advanced Technology Zoning (ATZ)
- 31 ATZ Parallel Wiring
- 31 Intellizones
- 31 Intellizone Time Delay
- 31 Silent Zones
- 32 24Hr and 4-Wire Smoke Detector Fire Zones
- 32 Enable/Disable Zone 4 (728 Ultra) or Zone 11 (738 Ultra)
- 32 2-Wire Smoke Detector Recognition (Input 3)
- 32 2-Wire Smoke Detector Reset
- 32 Instant Zones
- 32 Follow Zones
- 33 Entry Delay
- 33 Entry Time Delay
- 33 Partitioning
- 33 System A/Stay Zones