Features and Benefits
Table 2.
Voyager™ Light Commercial features - standard and optional
Single Side Service
Single Zone Variable Air Volume (SZ VAV)
Stainless Steel Drain Pan
Stainless Steel Heat Exchanger with 10 Year Warranty
Standardized Components
Supply and/or Return Air Smoke Detector
Thermal Expansion Valve
Through the Base Electrical Access
Through the Base Electrical with Circuit Breaker
Through the Base Electrical with Disconnect Switch
Through the Base Gas Piping
Tool-less Hail Guards
U-shaped Airflow Pattern
Variable Frequency Drive (Multispeed Indoor Fan, VAV, and Single Zone VAV)
Ventilation Override Accessory
(a)Refer to model number description for option availability.
Standard
Features
X
X
X
X
X
X
X
X
X
X
Factory
Installed
X
X
X
Options (a)
Factory or
Field
Installed
Field
Installed
X
X
Note: Most Factory Installed Options (FIOPS) available for Downflow Air Discharge units only.
Please verify with ordering system for availability.
6
Standard Features
Anti-Short Cycle Timer
Provides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhance compressor reliability by assuring proper oil return.
Colored and Numbered Wiring
Save time and money tracing wires and diagnosing the unit.
Compressors
Voyager contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models and allow for efficient cooling utilizing three stages of compressor operation (high efficiency 12½–20 Tons models only). 25 tons high efficiency units have 4 stages of cooling with a single compressor and tandem set (similar to variable speed).
Controls—ReliaTel™
ReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel also provides outputs for building automation systems and expanded diagnostics. For a complete list of ReliaTel offerings, refer to
.
RT-PRC043AC-EN
Features and Benefits
Conversionless Units
The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.
Crankcase Heaters
These band or insertion heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.
Discharge Line Thermostat
A bi-metal element discharge line thermostats installed as a standard feature on the discharge line of each system. This standard feature provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher.
Efficiencies
Standard or High Efficiency Cooling available.
Easy Access Low Voltage Terminal Board
Foil Faced Insulation
RT-PRC043AC-EN
Voyager’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire and test operation of all unit functions. This is another cost and time saving installation feature.
All panels in the evaporator section of the unit have cleanable foil-faced insulation. All edges are either captured or sealed to ensure no insulation fibers get into the airstream.
Fork Pocket Access
Voyager™ has the ability to be forked from 3 sides.
Heat Exchanger—Drum and Tube
The cabinet features a drum and tube heat exchanger (pictured right) that is manufactured using aluminized steel with stainless steel components for maximum durability.
The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47.
This is the standard required by both UL and
AGA for cycle test requirements.
For c ed Com b ust i on Blower
Ne ga t i ve Pressure Ga s V a lve
Hot Surf ac e I g n i tor
American Standard requires the design to be tested to 2½ times this current standard. The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current
7
Features and Benefits
ANSI cycling requirements. The negative pressure gas valve is used in the standard furnaces. This is one of our unique safety features. Modulating heaters use a pressure switch to ensure that the blower motor is operating before the gas valve is allowed to open.
The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system. Modulating furnaces contain a metal fiber material to ensure proper flame distribution at low fire. The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability. Our gas/electric rooftops exceed all California seasonal efficiency requirements and perform even better than the California NO x
emission requirements.
Low Ambient Cooling
All Voyager microprocessor units have cooling capabilities down to 0°F as standard.
Low Voltage Connections
The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.
8
Microchannel Coils
Air Inlet
Slit Fins and Braze Contact for Improved Heat Transfer and Strength
Microchannels for Refrigerant
Air Outlet
Microchannel coils are all-aluminum coils with fullybrazed construction. This design reduces risk of leaks and provides increased coil rigidity — making them more rugged on the jobsite. Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow for exceptional heat transfer.
Microchannel all-aluminum construction provides several additional benefits:
• Light weight (simplifies coil handling)
• Easy to recycle
• Minimize galvanic corrosion
Motors
All indoor fan motors are belt drive as standard.
Pressure Cutouts
Low and high pressure cutouts are standard on all Voyager models.
Phase Monitor
Voyager features a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.
RT-PRC043AC-EN
advertisement
Related manuals
advertisement
Table of contents
- 4 Features and Benefits
- 4 Standard Features and Available Options
- 6 Standard Features
- 9 Variety of Options
- 9 Factory Installed Options
- 13 Factory or Field Installed Options
- 14 Field Installed Options
- 16 Other Benefits
- 18 Application Considerations
- 20 Selection Procedure
- 20 Cooling Capacity
- 21 Heating Capacity
- 21 Air Delivery Selection
- 22 Model Number Description
- 23 Model Number Notes
- 24 General Data
- 40 Performance Data
- 124 Controls
- 124 Economizer Controls
- 124 Zone Sensors
- 127 Communication Interfaces
- 128 Electrical Data
- 140 Jobsite Connections
- 141 Dimensional Data
- 150 Weights
- 153 Mechanical Specifications
- 155 Factory Installed Options
- 157 Factory or Field Installed Options
- 159 Field Installed Options