- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Trane
- YSD150G3RHA23X6
- User manual
Variety of Options. Trane YSD240G4RHA0000, TSH210G3R0A0000, TSD210G3R0A0000, YSD150G3RLA0000, TSH150G4R0A0000, YSH240G4RHA0000, TSH300G3R0A0000, YSD210G3RLA0000, YSH210G3RLA0000, YSD180G3RLA0000 162 Pages
Variety of Options. Trane YSD240G4RHA0000, TSH210G3R0A0000, TSD210G3R0A0000, YSD150G3RLA0000, TSH150G4R0A0000, YSH240G4RHA0000, TSH300G3R0A0000, YSD210G3RLA0000, YSH210G3RLA0000, YSD180G3RLA0000
Add to My manuals162 Pages
advertisement
Features and Benefits
Quick-Access Panels
Remove three or more screws for access to the standardized internal components and wiring.
Quick-Adjust Slider Plate
With the Quick-Adjust Slider Plate (pictured right), the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.
Single Point Power
A single electrical connection powers the unit.
Single Side Service
Single side service is standard on all units.
Sloped Drain Pans
Every Voyager unit has a non-corrosive, sloped drain pan made of pre-painted steel and standard on all units.
Standardized Components
Components are placed in the same location on all Voyager units. Familiarize yourself with one
Voyager and you are familiar with every Voyager. Due to standardized components throughout the
Voyager line, contractors/owners can stock fewer parts.
U-Shaped Airflow Pattern
The U-shaped airflow allows for improved static capabilities.
Variable Frequency Drives - VFD (Multispeed Indoor Fan, VAV, and SZ VAV
Only)
Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation. VFDs on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. All VFDs are designed to allow bypass if required. Bypass control will simply provide full nominal airflow in the event of drive failure.
Bypass mode is indicated in the unit wiring manual. Modulating gas heat models with SZVAV allow tighter space temperature control with less temperature swing.
Variety of Options 1
Factory Installed Options
CO
2
Sensor Wiring
This is the unit wiring for field installed C0
2
sensors. Factory-installed C0
2
sensor wiring saves time and ensures proper unit connections for the field installed C0
2
sensor kits.
Complete Coat™ Condenser Coil
The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of different types of heat exchangers. The coating is selected to provide excellent resistance and durability to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive environments. This coating is available for microchannel coils only.
1 Refer to
“Model Number Description,” p. 22 for option availability.
RT-PRC043AC-EN 9
Features and Benefits
Circuit Breaker (Required with Through-the-Base Electrical)
This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. Available on all models.
Condensate Overflow Switch
A condensate overflow switch is available to shut the unit down in the event that the condensate drain line becomes clogged. This option protects the unit from water overflowing from the drain pan and entering the base of the units.
Dehumidification (Hot Gas Reheat)
This option allows for increased outdoor air ventilation. It reduces humidity levels while increasing comfort level in the air space. Cooling can operate without a demand for dehumidification. The hot gas reheat coil is designed to deliver maximum reheat temperature.
Disconnect Switch (Required with Through-the-Base Electrical)
Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available.
Available on all models.
Codes require a method of assured unit shutdown for servicing. Field-installed disconnects sometimes interfere with service access. Factory installation of unit disconnects reduces costs, assures proper mounting and provides the opportunity to upgrade to unit circuit breaker protection.
Fault Detection & Diagnostics (FDD)
This offering meets the mandatory requirement of CA Title 24 of fully configurable diagnostics allowing fault history and reading fault codes at the unit.This option provides detection of the following faults: Air temperature sensor failure/fault and notification of acceptable economizer mode.The FDD system shall be certified by the Energy Commission as meeting the requirements.
High Efficiency Filtration
Voyager units offer a variety of high efficiency filtration options. MERV 8 and MERV 13 filters provide additional filtration beyond the capabilities of typical 2” throwaway filters. Also, when
MERV 8 or MERV 13 filters are ordered, units come equipped with a filter removal tool.
High Efficiency Motors
High efficiency motors are available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.
High Short Circuit Current Rating (SCCR)
Voyager rooftop units now have an optional high short circuit current rated electrical subsystem for units with an MOP above 60A. This option is a perfect fit for applications that need protection against high potential fault currents. This option also includes individual over current protection for each compressor and the indoor fan, as well as a dedicated over current protection to the condenser fan motor(s). When the high SCCR is ordered, the control box will have components separated into two sections - high and low voltage components.
Hinged Access Doors
10 RT-PRC043AC-EN
Features and Benefits
These doors permit easy access to the filter, fan/ heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.
RT-PRC043AC-EN
Human Interface
The 5 inch Color Touchscreen Human Interface provides an intuitive user interface to the rooftop unit that speeds up unit commissioning, shortens unit troubleshooting times, and enhances preventative maintenance measures. The human interface includes several features such as:
• Data trending capabilities by means of time series graphs
• Historical alarm messages
• Real-time sensor measurements
• On board system setpoints
• USB port that enables the downloading of component runtime information as well as trended historical sensor data
• Customizable reports
Modulating Gas Heat with a 2.5:1 Turndown Ratio
Upon receiving a call for heat, modulating gas heat units with a 2.5:1 turndown ratio light their burner at full fire (100%). After the burner is lit, the unit controls will monitor the discharge air temperature and modulate the input rate down to match the load.
Note: Modulating gas heat units are equipped with a stainless steel heat exchanger as standard.
Multi-Speed Indoor Fan System
Multi-speed indoor fan system is designed for use in applications for meeting the minimum requirement of CA Title 24. This system incorporates a multi-speed fan control to change the speed of the fan to 67% of full airflow based off compressor stages.
Multiple-Zone VAV Control
A multiple-zone VAV (MZVAV) system consists of a packaged rooftop unit that serves several individually controlled zones. Each zone is equipped with a VAV terminal unit that varies the quantity of air delivered to maintain the desired temperature in that zone. The rooftop unit controller varies the speed of the indoor fan to maintain the static pressure in the supply ductwork at a setpoint, ensuring that all zones receive the necessary quantity of air. In addition, cooling capacity is cycled to maintain the supply air temperature at the desired setpoint.
For decades, Trane has been an industry leader in rooftop VAV systems. Now, multiple-zone VAV control is available in Trane’s light commercial rooftop platform (3-25 tons).
Novar Unit Controls
Novar 3051 and 2024 are available for Voyager Cooling and Gas/Electric models.
11
Features and Benefits
12
Powered or Unpowered Convenience Outlet
This option is a GFCI, 120V/15amp, 2-plug, convenience outlet, either powered or unpowered. This option can only be ordered when Through the Base Electrical with either the Disconnect Switch or
Circuit Breaker option is ordered. This option is available on all models.
Single Zone VAV - One Zone Variable Air Volume Mode
Note: Single Zone VAV is designed to be used with a zone sensor. If a unit is configured for Single
Zone VAV operation but is connected to a thermostat, the control will revert to multi-speed
(2-Speed) indoor fan control. (See "Multi-Speed Indoor Fan System" above.)
Single zone VAV is designed for use in single zone applications like gymnasiums, auditoriums, manufacturing facilities, retail box stores, and any large open spaces, where there is a lot of diversity in the load profile. Single Zone VAV (SZ VAV) is an ideal replacement to "yesterday's" constant volume (CV) systems, by reducing operating costs while improving occupant comfort.
SZ VAV systems combine American Standard application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition. American Standard algorithms meet/exceed ASHRAE 90.1- 2010, SZ VAV energy-saving recommendations, and those of CA Title 24. The result is an optimized balance between zone temperature control and system energy savings. Depending on your specific application, energy savings can be as much as 20%.
Note: Building system modeling in energy simulation software like TRACE is recommended to evaluate performance improvements for your application.
SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides the simplest and fastest commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control modules, logic and sensors are factory installed, and tested to assure the highest quality and most reliable system available. This means no special programming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need to be installed in the field.
Stainless Steel Drain Pan
For excellent corrosion and oxidation resistance, the optional stainless steel drain pan provides a cleanable surface that complement other IAQ solutions such as high efficiency filtration (MERV 8 or 13), demand control ventilation (CO
2
), and hot gas reheat.
Stainless Steel Heat Exchanger
The optional stainless steel heat exchanger is constructed of 304 stainless steel. It is resistant to corrosion and oxidation and easy to clean. The high strength to weight ratio allows for high ventilation rates with gas units and comes standard with a modulating gas heat option. With this option, a 10-year stainless steel heat exchanger warranty is standard.
Supply, Return, and Plenum Air Smoke Detector
With this option (pictured right) installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models.
Supply and/or Return Smoke Detectors may not be used with the Plenum Smoke Detector.
Through-the-Base Electrical Utility Access
An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.
RT-PRC043AC-EN
Features and Benefits
Factory provided through the base openings simplify wiring and piping. Because these utility openings frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.
Through-the-Base Gas Piping (Gas/Electric Only)
This option (pictured right) shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and union. This assembly will require minor field labor to install.
Factory or Field Installed Options 1
BACnet™ Communications Interface
The BACnet communications interface allows the unit to communicate directly with a generic open protocol BACnet MS/TP Network Building Automation System Controls.
Barometric Relief
Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These sensors allow a zone sensor service light to indicate a dirty filter or a fan that’s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment.
Discharge Air Temperature Sensing Kit
Provides true discharge air temperature sensing in heating models. The kit is functional only with the ReliaTel Options Module.
Economizer - Standard, Downflow
Economizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings. Factory-installed economizers save time and ensure proper installation.
Note: Factory-installed economizers require some field set-up.
Economizer - Low Leak, Downflow
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief. This option can be paired with or without Fault Detection & Diagnostics (FDD) to meet current mandatory CA Title 24 requirements.
Available on downflow units only. The economizers come with three control options, dry bulb and reference or comparative enthalpy (optional).
Electric Heaters
Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical option with an Electrical Heater, the heater must be factory installed.
1 Refer to
“Model Number Description,” p. 22 for option availability.
RT-PRC043AC-EN 13
Features and Benefits
Frostat™
A capillary bulb embedded in the face of the evaporator coil or a thermostat on the suction line monitors coil temperature to prevent evaporator icing and protect the compressor. Recommended for applications with low leaving air temperatures, low airflow and/or high latent load applications.
Note: Frostat is standard on all Single-Zone VAV, Multiple-Zone VAV, and high efficiency units.
Indoor Fan Motor Shaft Grounding Ring
Shaft grounding rings are used on all VFD driven motors to provide a conductive discharge path away from the motor bearings to ground. Bearing Protection Rings shall be maintenance free circumferential rings of conductive micro fibers that discharge voltages to ground.
Oversized Motors
Factory or field installed oversized motors are available for high static applications.
Reference or Comparative Enthalpy
Measures and communicates humidity while maximizing comfort control.
ReliaTel Options Module (RTOM)
The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, dehumidification setpoint, supply air tempering, Frostat™ and smoke detector.
Note: The RTOM is standard on high efficiency units.
Tool-less Hail Guards
Tool-less, hail protection quality coil guards (pictured right) shall be either factory or field-installed for condenser coil protection. This option protects the condenser coil from vandalism and/or hail damage.
Field Installed Options 1
CO
2
Sensor - Demand Control Ventilation (DCV)
Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand
(need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO
2
sensor measures the concentration (parts per million, ppm) of CO
2
(Carbon
Dioxide) in the air. As the CO
2
concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone. The CO
2
sensor kit is available as a field installed accessory. Two field installed kits are offered; C0
2
sensor and wiring or C0
2
sensor only. The C0
2 sensor only kit should be ordered with factory installed C0
2
sensor wiring. Factory installed C0
2 sensor wiring saves set-up time and ensures proper unit connections for the C0
2
sensor.
Dampers
0–25 percent manual or 0–50 percent motorized outside air dampers are available.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors.
1 Refer to
“Model Number Description,” p. 22 for option availability.
14 RT-PRC043AC-EN
RT-PRC043AC-EN
Features and Benefits
Economizer - Standard, Horizontal
Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing.
These economizers provide free cooling as the outdoor temperature and/or humidity decreases.
Correctly installed, they offer a valuable energy savings.
Economizer - Low Leak, Downflow & Horizontal
This accessory meets low leak requirements for ASHRAE 90.1, IECC, and CA Title 24 standards (3 cfm/ft^2@1" wg exterior air, 4 cfm/ft^2@1" wg return air). This option allows 100% outdoor air supply from 0-100% modulating dampers and is standard with barometric relief. It can be paired with powered exhaust for additional building pressure relief.
Humidity Sensor/Humidistat
Used in conjunction with our Dehumidification (Hot Gas Reheat) units to provide outstanding humidity control and comfort. Humidity sensors can be wall or duct mounted and set for levels between 40% and 60%.
LP Conversion Kit
Provided for field conversion of gas/electric units from natural gas to propane.
Powered Exhaust
This option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems.
Remote Potentiometer
When properly installed in the economizer control circuitry, this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position.
Roof Curbs
Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.
Static Drive Accessories
Available on many models, this high and low static drive accessories extend the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.
Ventilation Override Accessory
With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory.
Wireless Zone Sensor
LCD display that provides heat, cool, auto, or off. Includes two temperature setpoints and a lockable setting with °F or °C indicators.
Zone Sensors/Thermostats
Available in programmable, automatic and manual styles.
Note: Zone sensors required for units configured for Single Zone VAV indoor fan system control to enable Single Zone VAV functionality.
15
advertisement
Related manuals
advertisement
Table of contents
- 4 Features and Benefits
- 4 Standard Features and Available Options
- 6 Standard Features
- 9 Variety of Options
- 9 Factory Installed Options
- 13 Factory or Field Installed Options
- 14 Field Installed Options
- 16 Other Benefits
- 18 Application Considerations
- 20 Selection Procedure
- 20 Cooling Capacity
- 21 Heating Capacity
- 21 Air Delivery Selection
- 22 Model Number Description
- 23 Model Number Notes
- 24 General Data
- 40 Performance Data
- 124 Controls
- 124 Economizer Controls
- 124 Zone Sensors
- 127 Communication Interfaces
- 128 Electrical Data
- 140 Jobsite Connections
- 141 Dimensional Data
- 150 Weights
- 153 Mechanical Specifications
- 155 Factory Installed Options
- 157 Factory or Field Installed Options
- 159 Field Installed Options