Model Number Description
4 = Clogged Filter Switch and Fan
5 = Clogged Filter Switch and
6 = Fan Failure Switch and Discharge
7 = Clogged Filter Switch, Fan Failure
Switch and Discharge Air
A = Condensate Drain Pan Overflow
Switch
B = Clogged Filter Switch and
Condensate Drain Pan Overflow
C = Fan Failure Switch and
Condensate Drain Pan Overflow
D = Discharge Air Sensing and
Condensate Drain Pan Overflow
E = Clogged Filter Switch, Fan Failure
Switch and Condensate Drain Pan
Overflow Switch
F = Clogged Filter Switch, Discharge
Air Sensing Tube and Condensate
Drain Pan Overflow Switch
G = Fan Failure Switch, Discharge Air
Sensing Tube and Condensate
Drain Pan Overflow Switch
H = Clogged Filter Switch, Fan Failure
Switch, Discharge Air Sensing and Condensate Drain Pan
Overflow Switch
Digit 26 - System Monitoring
Controls
0 = No Monitoring Controls
A = Demand Control Ventilation
(CO
2
)
B = FDD (Fault Detection and
Diagnostics)
C = FDD (Fault Detection Diagnostics)
& Demand Control Ventilation
(CO
2
)
Digit 27 - Unit Hardware
Enhancements
0 = No Enhancements
1 = Stainless Steel Drain Pan
Digit 28 - Short Circuit Current
Rating
0 = Standard SCCR
A = 65kA SCCR Option
Digit 31 - Advanced Unit
Controls
0 = Standard Unit Controls
1 =
Note: Most Factory Installed Options available for Downflow Air
Discharge units only. Please verify with ordering system for availability.
Model Number Notes
1.
Some field set up required.
2. Requires ReliaTel Options Module.
3. Requires Economizer.
4. All 22 nd digit model numbers for reheat coil (B) require additional factory installed options: Frostat, and 2” pleated filters.
5. Must be ordered with Throughthe-Base Electrical option or
Horizontal-Side Access and either
Unit Mounted Disconnect or
Circuit Breaker.
6. Available factory installed on downflow AND horizontal units.
Verify with ordering system.
7.
Cannot be fused.
8. Must be factory installed when using Through-the-Base Options.
9. ReliaTel Options Module is required when ordering the following accessories: 4 Stage
Cooling, Clogged Filter Switch,
Fan Fail Switch, Condensate
Overflow Switch, Discharge Air
Sensing Kit, Frostat, Ventilation
Override, Smoke Detector,
Dehumidification and Modulating
Gas Heat Furnace.
10. Option cannot be ordered in conjunction with field installed economizer on downflow units.
Must be factory installed. The return air smoke detector may not fit up or work properly on the
Voyager units when used in conjunction with 3 rd party accessories (such as bolt on heat wheels, economizers, and power exhaust). Do not order the return air smoke detectors when using this type of accessory.
11. Unit mounted disconnect and circuit breakers are mutually exclusive of each other.
12. Through-the-base electrical option or Horizontal-Side Access must be ordered with either unit mounted disconnect or circuit breaker. When adding heat, you must order American Standard
Electric Heat.
13. Available on high efficiency units only.
RT-PRC043AC-EN
14. All Factory Installed Options are
Built-to-Order. Check order services for estimated production cycle.
15. For use with multi-speed and
SZVAV units only.
16. Demand Control Ventilation
Option includes wiring only. The
C0
2
sensor is a field-installed only option.
17. Frostat is standard on VAV and high efficiency units.
18. Supply and/or return smoke detector may not be used with the plenum smoke detector.
19. Only available where MOP is above 60A.
20. 575 VAC option is 25kA.
21. Standard filters are not available with Low Leak Economizers.
22. Human Interface is standard with
FDD (Fault Detection Diagnostics).
23
General Data
Table 3.
General data—cooling 12½–15 tons standard efficiency
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TS*150G3,4,W,K YS*150G3,4,W,K TS*180G3,4,W,K YS*180G3,4,W,K
150,000
11
5,000 / 4,000
140,000
12.4/13.5
66/100
12.73
2 / Scrolls
9.2
Microchannel
0.71
25.9
1/23
Microchannel
1.00
17.30
2/16
TXV
1/1.00 NPT
150,000
11
5,000 / 4,000
140,000
12.2/13.5
66/100
12.73
2 / Scrolls
9.2
Microchannel
0.71
25.9
1/23
Microchannel
1.00
17.30
2/16
TXV
1/1.00 NPT
186,000
11
6,000 / 5,400
176,000
12.4/13.2
67/100
16.00
2 / Scrolls
9.2
Microchannel
0.71
35.2
1/23
Microchannel
0.81
23.00
2/16
TXV
1/1.00 NPT
186,000
11
6,000 / 5,400
176,000
12.2/13.2
67/100
16.00
2 / Scrolls
9.2
Microchannel
0.71
35.2
1/23
Microchannel
0.81
23.00
2/16
TXV
1/1.00 NPT
Propeller
2 / 26
Propeller
2 / 26
Propeller
2 / 26
Propeller
2 / 26
Direct / 1 Direct / 1 Direct / 1 Direct / 1
11,000 11,000 11,000 11,000
2 / 0.50
2 / 0.50
2 / 0.50
2 / 0.50
1,100 1,100 1,100 1,100
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized) (e)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
FC Centrifugal
1 / 15x15
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
56HZ / 56HZ
FC Centrifugal
1 / 15x15
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
56HZ / 56HZ
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0 or 7.5
(f)
1,740 / 3,450
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0 or 7.5
1,740 / 3,450
184TZ / 56HZ/184TZ 56HZ / 56HZ/184TZ
24 RT-PRC043AC-EN
General Data
Table 3.
General data—cooling 12½–15 tons standard efficiency
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TS*150G3,4,W,K YS*150G3,4,W,K TS*180G3,4,W,K YS*180G3,4,W,K
Filters
Type Furnished (g)
Number Size Recommended
Throwaway Throwaway Throwaway Throwaway
Downflow
Horizontal
(2)20x20x2
(4)20x25x2
(2)20x20x2
(4)20x25x2
(2)20x20x2
(4)20x25x2
(2)20x20x2
(4)20x25x2
(4)20x20x2
(4)20x25x2
(8)20x25x2
(4)20x20x2
(4)20x25x2
(8)20x25x2
Refrigerant Charge
(Pounds of R-410A) (h)
Cir#1 / Cir#2 (DF)
Cir#1 / Cir#2 (HZ)
8.1/5.1
8.1/5.2
8.1/5.1
8.1/5.2
9.0/5.0
9.2/5.1
9.0/5.0
9.2/5.1
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(f) Offered only as a field installed accessory.
(g)An optional 2-inch pleated filter is also available.
(h)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 4.
General data—heating—12½–15 tons standard efficiency
Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
1st Stage (Btu)
Steady State Efficiency%
No. Burners
No. Stages
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.)
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating
Turn Down
= 2.5:1 Low High
Modulating
Turn Down
= 2.5:1
150,000
100,000
120,000
80,000
80
1
250,000
175,000
200,000
140,000
80
1
2
2.5/14.0
2
2.5/14.0
Natural or LP Natural or LP
1/2 1/2
350,000
140,000
280,000
112,000
80
1
N/A
2.5/14.0
Natural Only
3/4
250,000
175,000
200,000
140,000
80
1
350,000
250,000
280,000
200,000
80
1
2
2.5/14.0
2
2.5/14.0
Natural or LP Natural or LP
1/2 3/4
350,000
140,000
280,000
112,000
80
1
N/A
2.5/14.0
Natural Only
3/4
(a) Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards
Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
RT-PRC043AC-EN 25
General Data
Table 5.
General data—17½–20 tons standard efficiency
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized) (e)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TS*210G3,4,W,K YS*210G3,4,W,K TS*240G3,4,W,K YS*240G3,4,W,K
210,000
11
7,000 / 6,125
196,000
12.4/13.2
67/100
17.82
2 / Scrolls
9.4
Microchannel
1.00
35.2
1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
14,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
56HZ / 184T
210,000
11
7,000 / 6,125
196,000
12.2/13.2
67/100
17.82
2 / Scrolls
9.4
Microchannel
1.00
35.2
1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
14,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
56HZ / 184T
259,000
10
8,000 / 6,400
240,000
11.6/12.4
67/100
24.00
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
15,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
56HZ / 184T
259,000
10
8,000 / 6,400
240,000
11.4/12.4
67/100
24.00
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
15,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
56HZ / 184T
26 RT-PRC043AC-EN
General Data
Table 5.
General data—17½–20 tons standard efficiency
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TS*210G3,4,W,K YS*210G3,4,W,K TS*240G3,4,W,K YS*240G3,4,W,K
Filters
Type Furnished (f)
Number Size Recommended
Throwaway Throwaway Throwaway Throwaway
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A)
Cir#1/Cir#2 (DF)
Cir#1/Cir#2 (HZ)
(4)20x20x2
(4)20x25x2
(8)20x25x2
12.6/6.8
12.0/6.8
(4)20x20x2
(4)20x25x2
(8)20x25x2
12.6/6.8
12.0/6.8
(4)20x20x2
(4)20x25x2
(8)20x25x2
12.4/7.2
11.7/6.8
(4)20x20x2
(4)20x25x2
(8)20x25x2
12.4/7.2
11.7/6.8
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 6.
General data—17½ standard efficiency
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
17½ Tons Downflow & Horizontal Units
TS*211G3,4,W YS*211G3,4,W
210,000
11
7,000 / 6,125
196,000
11.8/12.9
73/100
17.82
2 / Scrolls
9.4
210,000
11
7,000 / 6,125
196,000
11.8/12.9
73/100
17.82
2 / Scrolls
9.4
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Microchannel
1.00
35.2
1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Microchannel
1.00
35.2
1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
RT-PRC043AC-EN 27
General Data
Table 6.
General data—17½ standard efficiency
17½ Tons Downflow & Horizontal Units
TS*211G3,4,W YS*211G3,4,W
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized) (e)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters
Type Furnished (f)
Number Size Recommended
Propeller
2 / 26
Direct / 1
14,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
Throwaway
Propeller
2 / 26
Direct / 1
14,500
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
Throwaway
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A)
Cir#1/Cir#2 (DF)
Cir#1/Cir#2 (HZ)
(4)20x20x2
(4)20x25x2
(8)20x25x2
14.4/7.4
14.4/7.4
(4)20x20x2
(4)20x25x2
(8)20x25x2
14.4/7.4
14.4/7.4
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb.
Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard
340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or
340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data.
(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
28 RT-PRC043AC-EN
General Data
Table 7.
General data—heating—17½–20 tons standard efficiency
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating
Turn
Down = 2.5:1 Low High
Modulating
Turn
Down =
2.5:1 Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
1st Stage (Btu)
Steady State Efficiency%
No. Burners
250,000
175,000
200,000
140,000
80
1
2
350,000
250,000
280,000
200,000
80
1
2
350,000
140,000
280,000
112,000
80
1
N/A
250,000
175,000
200,000
140,000
80
1
2
400,000
300,000
320,000
240,000
80
1
2
350,000
140,000
280,000
112,000
80
1
N/A No. Stages
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
2.5/14.0
Natural or LP
1/2
2.5/14.0
Natural or LP
3/4
2.5/14.0
Natural Only
3/4
2.5/14.0
2.5/14.0
2.5/14.0
Natural or LP Natural or LP Natural Only
1/2 3/4 3/4 Gas Connection Pipe Size (in.)
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards
Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
RT-PRC043AC-EN 29
General Data
Table 8.
General data—25 ton standard efficiency
25 Tons Downflow & Horizontal Units
TS*300G3,4,W,K YS*300G3,4,W,K
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
296,400
10
10,000 / 7,750
270,000
11.6/12.4
66/100
27
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 28
Direct / 1
16,100
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5 / N/A
3,470 / N/A
184T / N/A
296,400
10
10,000 / 7,750
270,000
11.4/12.4
66/100
27
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
Propeller
2 / 28
Direct / 1
16,100
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5 / N/A
3,470 / N/A
184T / N/A
30 RT-PRC043AC-EN
RT-PRC043AC-EN
General Data
Table 8.
General data—25 ton standard efficiency
25 Tons Downflow & Horizontal Units
TS*300G3,4,W,K YS*300G3,4,W,K
Filters
Type Furnished (e)
Number Size Recommended
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A) (f)
Cir#1/Cir#2 (DF)
Cir#1/Cir#2 (HZ)
Throwaway
(4)20x20x2 (4)20x25x2
(8)20x25x2
Throwaway
(4)20x20x2 (4)20x25x2
(8)20x25x2
12.5/6.7
11.7/6.7
12.5/6.7
11.7/6.7
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)An optional 2-inch pleated filter is also available.
(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 9.
General data—25 tons standard efficiency
25 Tons Downflow & Horizontal Units
TS*301G3,4,W YS*301G3,4,W
Cooling Performance (a)
Gross Cooling Capacity
EER (Downflow/Horizontal) (b)
Nominal Airflow CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (d)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI (DF/HZ)
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
296,400
10
10,000 / 8,000
272,000
10.4/12.0
50/100
27.20
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
296,400
10
10,000 / 8,000
272,000
10.4/12.0
50/100
27.20
2 / Scrolls
9.4
Microchannel
1.0
35.2
1/23 / 1/20
Microchannel
1.00
23.00
2 / 16
TXV
1/1.00 NPT
31
General Data
Table 9.
General data—25 tons standard efficiency
25 Tons Downflow & Horizontal Units
TS*301G3,4,W YS*301G3,4,W
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters
Type Furnished (e)
Number Size Recommended
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A) (f)
Cir#1/Cir#2 (DF)
Cir#1/Cir#2 (HZ)
Propeller
2 / 28
Direct / 1
16,100
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5 / N/A
3,470 / N/A
184T / N/A
Throwaway
(4)20x20x2 (4)20x25x2
(8)20x25x2
Propeller
2 / 28
Direct / 1
16,100
2 / 1.0
1125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5 / N/A
3,470 / N/A
184T / N/A
Throwaway
(4)20x20x2 (4)20x25x2
(8)20x25x2
10.5
10.5
10.5
10.5
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(e)An optional 2-inch pleated filter is also available.
(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
32 RT-PRC043AC-EN
RT-PRC043AC-EN
General Data
Table 10. General data—heating—25 tons
25 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating Turn
Down = 2.5:1 Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
250,000
175,000
200,000
400,000
300,000
320,000
350,000
140,000
280,000
1st Stage (Btu)
Steady State Efficiency%
No. Burners
No. Stages
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.)
140,000
80
1
2
2.5 / 14.0
Natural or LP
½
240,000
80
1
2
2.5 / 14.0
Natural or LP
¾
112,000
80
1
N/A
2.5 / 14.0
Natural Only
¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
33
General Data
Table 11. General data—12½–15 ton high efficiency
Cooling Performance (a)
Gross Cooling Capacity
EER (b)
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2/Stage 3) (d)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (e)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TH*150G3,4,W YH*150G3,4,W TH*180G3,4,W YH*180G3,4,W
152,400
12.1
5,000 / 4,000
144,000
13.5/15.0
30/70/100
11.90
2 / Scrolls
9.2
Microchannel
1.0
35.2
1 / 20
Hi-Performance
0.3125
26.00
4 / 15
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
2 / 0.50
1,100
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
145T / 145T
152,400
12.1
5,000 / 4,000
144,000
13.5/15.0
30/70/100
11.90
2 / Scrolls
9.2
Microchannel
1.0
35.2
1 / 20
Hi-Performance
0.3125
26.00
4 / 15
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
2 / 0.50
1,100
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
145T / 145T
180,500
12.1
6,000 / 5,250
174,000
14.0/15.0
32/68/100
14.38
2 / Scrolls
9.2
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
2 / 0.50
1,100
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
145T / 145T
180,500
12.1
6,000 / 5,250
174,000
14.0/15.0
32/68/100
14.38
2 / Scrolls
9.2
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
Propeller
2 / 26
Direct / 1
2 / 0.50
1,100
FC Centrifugal
1 / 18x18
Belt / 1
1
3.0 / 5.0
1,740 / 3,450
145T / 145T
34 RT-PRC043AC-EN
General Data
Table 11. General data—12½–15 ton high efficiency
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
TH*150G3,4,W YH*150G3,4,W TH*180G3,4,W YH*180G3,4,W
Filters
Type Furnished (f)
Number Size Recommended
Throwaway Throwaway Throwaway Throwaway
Downflow
Horizontal
Refrigerant Charge (Pounds of
R-410A) (g)
Downflow & Horizontal (Cir#1/Cir#2)
Optional Hot Gas Reheat Coil (Cir#1/Cir#2)
(4)20x20x2 (4)20x25x2 (4)20x20x2 (4)20x25x2
(8)20x25x2
12.5/7.1
9.2 / 6.9
(8)20x25x2
12.5/7.1
9.2 / 6.9
(8)20x20x2
(4)20x16x2
(12)20x20x2
13.0/8.5
10.9 / 8.9
(8)20x20x2
(4)20x16x2
(12)20x20x2
13.0/8.5
10.9 / 8.9
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)3 stages not available with Reheat models.
(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(f) An optional 2 inch pleated filter is also available.
(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 12. General data—heating—12½-15 ton high efficiency
12½ Tons Downflow & Horizontal Units 15 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating
Turn Down
= 2.5:1 Low High
Modulating
Turn Down
= 2.5:1 Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
1st Stage (Btu)
Steady State Efficiency%
No. Burners
No. Stages
150,000 250,000 350,000
100,000 175,000 140,000
120,000 200,000 280,000
80,000 140,000 112,000
80 80 80
1 1 1
Gas Supply Line Pressure (in. wc) 2.5 / 14.0
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.) ½
2.5 / 14.0
½
2.5 / 14.0
Natural Only
¾
250,000 350,000 350,000
175,000 250,000 140,000
200,000 280,000 280,000
140,000 200,000 112,000
80 80 80
1 1 1
2 2 N/A
2.5 / 14.0
2.5 / 14.0
2.5 / 14.0
½ ¾
Natural Only
¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards
Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
RT-PRC043AC-EN 35
General Data
Table 13. General data—17½–20 ton high efficiency
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TH*210G3,4,W YH*210G3,4,W TH*240G3,4,W YH*240G3,4,W
Cooling Performance (a)
Gross Cooling Capacity
EER (b)
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2/Stage 3) (d)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (e)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard/Oversized)
Motor rpm (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
214,800
11.8
7,000 / 5,600
204,000
13.0/14.0
31/69/100
17.29
2 / Scrolls
9.2
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
214,800
11.8
7,000 / 5,600
204,000
13.0/14.0
31/69/100
17.29
248,500
11.0
8,000 / 6,400
234,000
12.4/14.0
30/70/100
21.27
248,500
11.0
8,000 / 6,400
234,000
12.4/14.0
30/70/100
21.27
Propeller
2 / 26
Direct / 1
Propeller
2 / 26
Direct / 1
Propeller
2 / 28
Direct / 1
Propeller
2 / 28
Direct / 1
15,800 15,800 16,500 16,500
2 / 1.0
1,125
2 / 1.0
1,125
2 / 1.0
1,125
2 / 1.0
1,125
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
2 / Scrolls
9.2
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
2 / Scrolls
9.4
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
2 / Scrolls
9.4
Microchannel
1.0
42.6
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
FC Centrifugal
1 / 18x18
Belt / 1
1
5.0 / 7.5
3,450 / 3,470
145T / 184T
36 RT-PRC043AC-EN
General Data
Table 13. General data—17½–20 ton high efficiency
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
TH*210G3,4,W YH*210G3,4,W TH*240G3,4,W YH*240G3,4,W
Filters
Type Furnished (f)
Number Size Recommended
Throwaway Throwaway Throwaway Throwaway
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A) (g)
Downflow & Horizontal (Cir#1/Cir#2)
Optional Hot Gas Reheat Coil (Cir#1/Cir#2)
(8)20x20x2
(4)20x16x2
(12)20x20x2
14.0 / 7.3
12.2/8.9
(8)20x20x2
(4)20x16x2
(12)20x20x2
14.0 / 7.3
12.2/8.9
(8)20x20x2
(4)20x16x2
(12)20x20x2
15.5 / 7.5
11.9 / 9.6
(8)20x20x2
(4)20x16x2
(12)20x20x2
15.5 / 7.5
11.9 / 9.6
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)3 stages not available with Reheat models.
(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(f) An optional 2 inch pleated filter is also available.
(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 14. General data—heating—17½–20 ton high efficiency
Heating Models
Heating Input (Btu/h)
17½ Tons Downflow & Horizontal Units 20 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating
Turn
Down = 2.5:1
250,000 350,000 350,000
175,000 250,000 140,000
Heating Output (Btu/h) 200,000 280,000 280,000
140,000 200,000 112,000
Steady State Efficiency%
No. Burners
No. Stages
80 80 80
1 1 1
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.)
2 2 N/A
2.5 / 14.0
½
2.5 / 14.0
¾
2.5/14.0
Natural Only
¾
Low High
Modulating
Turn
Down = 2.5:1
250,000 400,000 350,000
175,000 300,000 140,000
200,000 320,000 280,000
140,000 240,000 112,000
80 80 80
1 1 1
2 2 N/A
2.5 / 14.0
2.5 / 14.0
2.5/14.0
½ ¾
Natural Only
¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards
Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
RT-PRC043AC-EN 37
General Data
Table 15. General data—25 ton high efficiency
25 Tons Downflow & Horizontal Units
TH*300G3,4,W YH*300G3,4,W
Cooling Performance (a)
Gross Cooling Capacity
EER (b)
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Energy Efficiency Ratio (IEER) (One
Speed Fan / Multi or Variable Speed Fan) (c)
Percent Capacity @ part load
(Stage 1/Stage 2/Stage 3/Stage 4) (d)
System Power (kW)
Compressor
Number/Type
Sound
Outdoor Sound Rating (BELS) (e)
Outdoor Coil
Type
Coil Width (in.)
Face Area (sq. ft.)
Rows/FPI
Indoor Coil
Type
Tube Size (in.) ID
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)
Outdoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds cfm
Number Motors/hp
Motor rpm
Indoor Fan
Type
Number Used/Diameter (in.)
Drive Type/No. Speeds
Number Motors
Motor hp (Standard)
Motor rpm (Standard)
Motor Frame Size (Standard)
292,300
10.6
10,000 / 8,000
274,000
12.4/15.0
25/50/75/100
25.85
3 / Scrolls
9.4
Microchannel
1.0
42.58
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
292,300
10.6
10,000 / 8,000
274,000
12.4/15.0
25/50/75/100
25.85
Propeller
2 / 28
Direct / 1
Propeller
2 / 28
Direct / 1
16,500 16,500
2 / 1.0
1,125
2 / 1.0
1,125
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5
3,470
184T
3 / Scrolls
9.4
Microchannel
1.0
42.58
1 / 20
Hi-Performance
0.3125
31.42
4 / 15
TXV
1/1.00 NPT
FC Centrifugal
1 / 18x18
Belt / 1
1
7.5
3,470
184T
38 RT-PRC043AC-EN
RT-PRC043AC-EN
General Data
Table 15. General data—25 ton high efficiency
25 Tons Downflow & Horizontal Units
TH*300G3,4,W YH*300G3,4,W
Filters
Type Furnished (f)
Number Size Recommended
Downflow
Horizontal
Refrigerant Charge
(Pounds of R-410A) (g)
Downflow & Horizontal (Cir#1/Cir#2)
Optional Hot Gas Reheat Coil (Cir#1/Cir#2)
Throwaway
(8)20x20x2 (4)20x16x2
(12)20x20x2
Throwaway
(8)20x20x2 (4)20x16x2
(12)20x20x2
11.8 / 10.6
13.2 / 11.4
11.8 / 10.6
13.2 / 11.4
(a)Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360.
(b)EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 340/360.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(d)3 and 4 stages not available with Reheat models.
(e)Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
(f) An optional 2-inch pleated filter is also available.
(g)Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
* Indicates both downflow and horizontal units.
Table 16. General data—heating—25 ton high efficiency
Heating Models
Heating Input (Btu/h)
1st Stage (Btu)
Heating Output (Btu/h)
1st Stage (Btu)
Steady State Efficiency%
No. Burners
No. Stages
Gas Supply Line Pressure (in. wc)
Natural or LP (minimum/maximum)
Gas Connection Pipe Size (in.)
25 Tons Downflow & Horizontal Units
Heating Performance (a) (Gas/Electric Only)
Low High
Modulating Turn
Down = 2.5:1
250,000 400,000 350,000
175,000 300,000 140,000
200,000 320,000 280,000
140,000 240,000 112,000
80 80 80
1 1 1
2.5 / 14.0
2.5 / 14.0
2.5/14.0
Natural Only
¾ ½ ¾
(a)Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
39
Performance Data
Table 17. Gross cooling capacities 12½ tons three phase standard efficiency T/YS*150G3,4,W,K
Air
Flow cfm
4000
4500
5000
5500
6000
Air
Flow cfm
4000
Ent
DB
(°F)
75
80
85
90
75
75
80
85
90
85
90
75
80
85
80
85
90
75
80
90
Ent
DB
(°F)
61
153
161
142
147
156
164
157
161
159
159
158
164
85
67
157
161
105
138
158
164
173
172
173
174
174
173
73
124
154
63
97
130
163
61
Ambient Temperature
95
Entering Wet Bulb
67 73 61
105
67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
135
135
140
148
137
138
145
153
139
141
149
157
141
144
153
161
142
147
156
164
113
134
140
148
121
137
145
153
129
141
149
157
137
144
152
152
151
151
154
154
154
154
156
156
156
157
158
158
115
87
109
131
151
92
117
141
154
96
124
151
157
101
131
166
166
166
166
168
169
169
169
170
171
171
171
172
172
59
81
104
126
60
85
110
135
61
89
117
144
62
93
128
128
134
142
131
131
139
147
132
135
143
151
133
138
110
128
134
142
118
131
139
147
126
144
144
144
144
146
146
146
147
148
135 148
143 148
151 151
133 150
138 149
84
106
128
144
89
113
138
147
93
121
147
151
97
128
157
158
158
158
160
160
160
160
161
162
162
162
162
163
56
78
101 128.7 128.7 136.1 124.8 148.9 97.4
123 136.0 136.0 136.2 136.1 148.8 119.4
57
82
58
121.3 107.0 136.2 81.0 148.3 52.7
121.5 121.4 136.2 103.0 148.6 75.1
123.3 114.8 138.2 85.4 150.0 53.7
125.1 125.1 138.1 110.2 150.4 78.9
107 133.0 133.0 137.8 134.5 150.7 104.0
132 140.3 140.3 140.5 140.5 150.5 128.7
124.7 122.3 139.7 89.7 151.4 54.7
86 128.6 128.6 139.6 117.2 151.9 82.7
114 136.5 136.5 139.2 138.9 152.1 110.5
141 143.7 143.7 143.9 143.9 151.9 137.9
59 125.8 125.6 140.9 94.1 152.4 55.7
90 131.5 131.5 140.8 124.2 153.1 86.5
146
154
135
141
149
146 149
154 154
134 151
141 150
149 150
149
154
102
135
150
163
163
163
164
164
121 139.4 139.4 140.3 140.1 153.6 117.0
151 146.4 146.4 146.5 146.5 152.8 147.1
60 126.8 126.5 141.9 98.4 153.3 56.6
94 134.0 134.0 141.6 131.2 154.2 90.3
127 141.9 141.9 142.0 142.0 153.9 123.8
157
61
157 157 157 164
Ambient Temperature
120
Entering Wet Bulb
67 73
160 148.9 148.9 149.0 149.0 153.3 152.9
61
125
67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 114.1 103.8 127.9 77.7 138.5 49.3 110.4 102.1 123.6 76.0 133.4 47.5 106.5 100.4 119.0 74.1 127.9 45.6
80 115.3 115.3 127.9 99.7 138.9 71.7 112.3 112.3 123.6 98.0 133.7 69.9 109.1 109.1 119.1 96.2 128.3 68.1
85 122.6 122.6 127.8 121.5 139.2 94.0 119.3 119.3 123.3 119.7 134.1 92.3 115.7 115.7 118.7 117.8 128.8 90.4
90 129.4 129.4 129.5 129.5 139.2 116.0 125.8 125.8 125.9 125.9 134.1 114.3 121.9 121.9 122.0 122.0 128.7 112.4
4500
5000
75 115.8 111.5 129.6 82.0 140.0 50.3 111.8 109.7 125.1 80.3 134.6 48.4 107.8 107.6 120.4 78.5 128.9 46.5
80 119.0 119.0 129.5 106.8 140.4 75.5 115.8 115.8 125.0 105.0 135.1 73.7 112.3 112.3 120.3 103.2 129.5 71.8
85 126.4 126.4 129.2 129.0 140.7 100.6 122.8 122.8 124.7 124.5 135.3 98.7 119.0 119.0 120.0 119.8 129.7 96.8
90 133.1 133.1 133.2 133.2 140.5 125.2 129.1 129.1 129.3 129.3 135.2 123.4 124.9 124.9 125.0 125.0 129.5 121.5
75 116.9 116.7 130.9 86.4 141.0 51.2 113.0 112.8 126.3 84.6 135.5 49.4 108.9 108.7 121.4 82.8 129.7 47.5
80 122.1 122.1 130.8 113.8 141.7 79.3 118.7 118.7 126.1 112.0 136.3 77.5 114.9 114.9 121.3 110.2 130.6 75.6
85 129.5 129.5 130.4 130.2 141.8 107.0 125.7 125.7 125.9 125.8 136.3 105.2 121.6 121.6 121.7 121.7 130.5 103.3
90 135.9 135.9 136.0 136.0 141.5 134.4 131.6 131.6 131.7 131.7 135.9 132.4 127.0 127.0 127.1 127.1 130.0 129.5
75 118.0 117.8 131.9 90.7 141.8 52.1 114.0 113.8 127.2 88.9 136.2 50.3 109.9 109.8 122.2 87.1 130.3 48.4
80 124.7 124.7 131.7 120.8 142.7 83.0 121.0 121.0 127.0 119.0 137.3 81.2 117.1 117.1 121.9 117.1 131.5 79.4
5500
6000
85 132.0 132.0 132.1 132.1 142.6 113.5 127.9 127.9 128.0 128.0 137.0 111.6 123.6 123.6 123.7 123.7 131.1 109.7
90 138.2 138.2 138.3 138.3 142.0 141.6 133.7 133.7 133.8 133.8 136.3 135.9 128.8 128.8 128.9 128.9 130.3 130.0
75 118.9 118.8 132.7 94.9 142.5 53.1 115.3 115.3 127.8 93.1 136.8 51.2 111.6 111.6 122.8 91.3 130.8 49.3
80 126.8 126.8 132.4 127.7 143.7 86.9 123.0 123.0 127.4 125.8 138.0 85.1 118.9 118.9 122.2 121.9 132.0 83.1
85 134.0 134.0 134.1 134.1 143.2 119.9 129.7 129.7 129.8 129.8 137.5 118.1 125.2 125.2 125.3 125.3 131.5 116.2
90 140.3 140.3 140.3 140.3 142.4 142.0 135.5 135.5 135.6 135.6 136.7 136.4 130.4 130.4 130.4 130.4 130.8 130.5
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
* Stands for both downflow and horizontal unit.
40 RT-PRC043AC-EN
Performance Data
Table 18. Gross cooling capacities 15 tons three phase standard efficiency T/YS*180G3,4,W,K
Air
Flow cfm
4800
5400
6000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 163.2 138.4 185.0 107.5 206.8 74.7 155.6 134.9 176.1 103.9 195.7
70.7
147.4 131.1 166.3
99.8
183.0
66.1
80 162.9 162.6 185.1 134.2 206.9 101.8 155.4 155.2 176.2 130.5 195.8
97.7
147.3 147.0 166.3 126.5 183.1
93.1
85 164.5 164.4 185.0 160.7 206.9 128.7 157.8 157.7 176.0 157.1 195.9 124.6 151.2 151.2 166.2 152.9 183.2 120.0
90 173.3 173.3 184.6 184.2 207.0 155.3 167.1 167.1 175.7 175.4 195.9 151.3 160.1 160.1 166.1 165.8 183.2 146.7
75 167.9 148.7 190.1 113.9 211.1 76.6 159.8 145.1 180.5 110.0 198.9
72.2
150.9 141.1 170.0 105.8 185.0
67.4
80 167.5 167.2 190.1 143.8 211.2 107.0 159.6 159.3 180.5 140.0 199.0 102.7 151.0 150.7 170.0 135.8 185.2
97.8
85 170.5 170.5 189.9 173.5 211.3 137.2 164.2 164.2 180.3 169.6 199.1 132.9 157.1 157.1 169.8 165.4 185.3 128.0
90 180.7 180.7 189.4 189.1 211.3 167.2 174.0 174.0 180.0 179.7 199.2 162.9 166.3 166.3 169.8 169.5 185.4 158.0
75 171.7 158.9 194.2 120.0 214.3 78.2 163.1 155.1 184.1 115.9 201.1
73.6
153.9 151.0 173.0 111.6 186.5
68.6
80 171.3 171.0 194.2 153.2 214.4 112.0 162.8 162.6 184.1 149.2 201.3 107.4 154.0 153.9 173.0 144.9 186.6 102.3
85 176.6 176.6 193.8 186.2 214.4 145.5 169.8 169.8 183.6 181.7 201.4 141.0 162.2 162.2 172.5 172.1 186.7 135.9
6600
7200
Air
Flow cfm
4800
90 187.2 187.2 193.3 192.9 214.5 178.8 179.9 179.9 183.4 183.2 201.4 174.3 171.6 171.6 172.9 172.8 186.6 169.2
75 174.9 168.9 197.5 125.9 216.5 79.6 165.9 164.6 187.0 121.7 202.5
74.8
156.2 155.8 175.3 117.2 188.2
70.0
80 174.4 174.2 197.5 162.5 216.7 116.8 165.8 165.7 186.9 158.3 202.6 112.0 156.7 156.6 175.2 153.8 188.3 107.1
85 181.9 181.9 196.9 196.4 216.8 153.7 174.7 174.7 186.3 185.8 202.7 148.9 166.5 166.5 174.7 174.3 188.4 144.0
90 192.8 192.8 196.4 196.1 216.8 190.3 184.9 184.9 186.5 186.3 202.9 185.5 176.0 176.0 176.1 176.1 188.3 180.6
75 177.6 177.1 200.3 131.7 218.1 80.9 168.3 167.8 189.3 127.4 204.3
76.2
158.2 157.8 177.1 122.8 189.5
71.3
80 177.2 177.0 200.3 171.5 218.3 121.4 168.5 168.3 189.2 167.3 204.4 116.8 160.2 160.2 177.0 162.6 189.7 111.8
85 186.6 186.6 199.4 198.9 218.4 161.7 178.9 178.9 188.4 187.9 204.5 157.0 170.3 170.3 176.4 175.9 189.8 152.1
90 197.7 197.7 199.4 199.2 218.4 201.7 189.3 189.3 189.4 189.2 204.2 196.9 179.6 179.6 179.6 179.6 189.5 188.8
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 138.6 127.2 155.7 95.6 168.4 61.0 134.2 125.2 150.1 93.3 160.9
58.4
144.2
91.0
153.4
55.8
80 138.8 138.5 155.7 122.2 168.6 88.0 134.5 134.3 150.1 120.0 161.0
85.4
144.3 117.7 153.5
82.8
85 144.0 144.0 155.6 148.6 168.7 114.9 140.2 140.2 150.0 146.4 161.1 112.3 136.3 136.3 144.2 143.7 153.6 109.7
90 152.4 152.4 155.7 155.5 168.8 141.6 148.2 148.2 150.3 150.0 161.1 138.9 143.8 143.8 144.8 144.7 153.7 136.4
75 141.6 137.0 158.7 101.3 170.1 62.3 136.9 134.9 152.6 99.0 162.5
59.7
132.1 131.8 146.3
96.6
154.4
57.0
80 142.0 141.9 158.7 131.3 170.2 92.7 137.6 137.4 152.7 128.9 162.6
90.1
133.1 132.9 146.4 126.5 154.6
87.4
5400
6000
6600
85 149.3 149.3 158.4 158.0 170.3 122.8 145.2 145.2 152.5 152.1 162.7 120.3 140.8 140.8 146.3 145.9 154.7 117.6
90 157.8 157.8 159.0 158.8 170.4 152.8 153.1 153.1 153.3 153.1 162.8 150.3 147.9 147.9 148.0 148.0 154.8 147.6
75 144.0 143.6 160.9 106.9 171.6 63.5 139.0 138.6 154.5 104.5 163.5
60.9
134.0 133.6 147.8 102.0 155.0
58.1
80 144.8 144.8 160.9 140.2 171.7 97.3 140.7 140.7 154.5 137.7 163.7
94.6
136.5 136.5 147.8 135.2 155.2
91.8
85 153.8 153.8 160.6 160.3 171.8 130.9 149.2 149.2 154.4 154.0 163.8 128.2 144.4 144.4 147.9 147.5 155.4 125.4
90 162.2 162.2 162.3 162.3 171.8 164.2 156.8 156.8 156.9 156.9 163.8 161.5 150.8 150.8 150.8 150.8 155.6 154.8
75 146.0 145.6 162.6 112.4 172.5 64.8 140.8 140.4 155.9 109.9 164.1
62.0
135.4 135.1 148.9 107.3 155.2
59.1
80 148.4 148.4 162.6 149.0 172.7 101.9 144.1 144.1 155.9 146.5 164.3
99.2
139.6 139.6 148.9 143.9 155.5
96.3
85 157.5 157.5 162.3 161.9 172.9 138.8 152.6 152.6 155.6 155.2 164.5 136.1 147.2 147.2 148.8 148.5 155.8 133.2
90 165.5 165.5 165.6 165.6 172.9 172.2 159.3 159.3 159.4 159.4 164.7 164.0 152.2 152.2 152.2 152.2 156.1 155.5
7200
75 147.6 147.2 163.9 117.8 173.2 66.0 142.2 141.8 156.9 115.2 164.5
63.2
136.6 136.2 149.6 112.5 155.3
60.2
80 151.6 151.6 163.8 157.7 173.4 106.5 147.0 147.0 156.9 155.1 164.7 103.6 142.1 142.1 149.6 149.0 155.5 100.7
85 160.6 160.6 163.3 163.0 173.6 146.7 155.2 155.2 156.6 156.4 165.0 143.9 149.4 149.4 149.7 149.4 156.0 141.1
90 167.9 167.9 167.9 167.9 173.7 173.0 160.7 160.7 160.8 160.8 165.2 164.6 153.9 153.9 154.0 154.0 156.4 155.7
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
RT-PRC043AC-EN 41
Performance Data
Table 19. Gross cooling capacities 17½ tons three phase standard efficiency T/YS*210G3,4,W,K
Air
Flow cfm
5600
6300
7000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 186.0 161.1 210.2 124.5 233.8 85.5 176.4 156.7 199.5 120.1 221.1 80.9 166.4 152.2 188.0 115.4 207.2 76.0
80 185.1 184.9 209.9 155.7 233.8 117.2 175.8 175.6 199.3 151.4 221.1 112.6 166.2 166.1 187.8 146.7 207.3 107.7
85 191.8 191.8 209.4 186.6 233.7 148.7 184.3 184.3 198.6 182.2 221.0 144.1 176.1 176.1 187.1 177.5 207.2 139.2
90 203.1 203.1 208.5 208.2 233.5 180.1 195.2 195.2 198.0 197.7 220.9 175.5 186.5 186.5 187.0 186.9 207.0 170.5
75 189.9 172.8 214.5 131.5 237.5 87.3 179.9 168.3 203.2 126.9 224.3 82.7 169.5 163.7 191.1 122.1 209.7 77.6
80 189.1 188.9 214.2 166.6 237.5 123.0 179.8 179.7 203.0 162.1 224.3 118.4 171.3 171.3 190.9 157.3 209.8 113.3
85 199.0 199.0 213.3 201.1 237.4 158.5 191.0 191.0 202.1 196.4 224.2 153.8 182.3 182.3 190.0 189.1 209.8 148.9
90 210.7 210.7 212.4 212.2 237.1 193.7 202.2 202.2 202.4 202.4 223.9 189.0 192.8 192.8 193.0 193.0 209.5 183.9
75 193.1 184.2 218.0 138.3 240.3 89.1 182.8 179.0 206.3 133.6 226.6 84.4 171.9 171.4 193.7 128.7 211.5 79.2
80 193.0 193.0 217.6 177.2 240.4 128.8 185.0 185.0 205.9 172.6 226.7 124.0 176.3 176.3 193.3 167.7 211.7 118.9
85 205.2 205.2 216.5 213.8 240.3 168.2 196.7 196.7 204.5 204.1 226.7 163.5 187.4 187.4 191.9 191.6 211.8 158.4
7700
8400
Air
Flow cfm
5600
90 217.3 217.3 217.5 217.5 239.8 207.1 208.2 208.2 208.4 208.4 226.2 202.4 198.2 198.2 198.3 198.3 211.4 197.3
75 195.7 193.8 220.8 144.9 242.6 90.8 184.9 184.5 208.7 140.2 228.4 86.0 173.6 173.2 195.7 135.3 212.8 80.7
80 198.1 198.1 220.4 187.8 242.7 134.4 189.7 189.7 208.3 183.1 228.6 129.6 180.5 180.5 195.3 178.1 213.2 124.4
85 210.5 210.5 218.6 218.1 242.7 177.8 201.6 201.6 206.5 206.2 228.6 173.0 191.7 191.7 193.7 193.4 213.2 167.8
90 222.9 222.9 223.1 223.1 242.0 220.6 213.4 213.4 213.5 213.5 228.1 215.8 202.6 202.6 202.7 202.7 212.8 208.8
75 197.6 197.1 223.2 151.5 244.3 92.4 186.5 186.0 210.7 146.8 229.8 87.6 175.1 174.8 197.6 141.9 213.8 82.3
80 202.5 202.5 222.6 198.2 244.5 140.0 193.8 193.8 210.2 193.5 230.1 135.2 184.2 184.2 196.9 188.5 214.3 129.9
85 215.2 215.2 220.4 220.0 244.5 187.3 205.9 205.9 208.2 207.8 230.1 182.5 195.6 195.6 195.7 195.7 214.3 177.2
90 227.8 227.8 228.0 228.0 243.9 234.0 217.7 217.7 217.8 217.8 229.5 226.5 206.2 206.2 206.3 206.3 213.4 212.7
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 156.8 147.9 176.0 110.7 192.2 70.7 152.4 145.9 170.0 108.3 184.3 68.0
164.1 106.0 176.1 65.2
80 157.8 157.8 175.8 141.9 192.3 102.5 154.1 154.1 169.9 139.6 184.5 99.8
164.0 137.3 176.5 97.0
85 167.6 167.6 175.3 171.8 192.4 134.1 163.4 163.4 169.2 167.8 184.7 131.4 159.1 159.1 163.2 162.9 176.8 128.7
90 177.1 177.1 177.2 177.2 192.2 165.3 172.1 172.1 172.2 172.2 184.5 162.6 166.9 166.9 167.0 167.0 176.5 159.9
75 159.4 157.6 178.6 117.2 193.9 72.2 154.5 154.1 172.3 114.8 185.6 69.4 150.2 149.9 166.1 112.5 177.1 66.6
80 163.0 163.0 178.4 152.4 194.2 108.0 158.9 158.9 172.1 149.9 186.0 105.2 154.9 154.9 165.9 147.6 177.7 102.4
6300
7000
7700
85 173.0 173.0 177.3 177.0 194.3 143.5 168.3 168.3 171.1 170.8 186.2 140.8 163.4 163.4 164.9 164.6 177.9 138.0
90 182.5 182.5 182.7 182.7 194.1 178.6 177.0 177.0 177.2 177.2 186.0 175.9 171.1 171.1 171.2 171.2 177.7 172.5
75 161.1 160.8 180.6 123.7 195.1 73.7 156.2 155.9 174.2 121.3 186.5 70.8 151.7 151.4 167.8 118.9 177.7 67.9
80 167.4 167.4 180.3 162.7 195.6 113.5 162.9 162.9 173.8 160.2 187.2 110.7 158.5 158.5 167.3 157.8 178.6 107.8
85 177.4 177.4 179.1 178.7 195.7 152.9 172.2 172.2 172.7 172.5 187.3 150.1 166.8 166.8 166.9 166.9 178.6 147.2
90 187.0 187.0 187.1 187.1 195.4 190.8 180.9 180.9 181.0 181.0 187.0 185.9 174.4 174.4 174.5 174.5 178.1 177.5
75 162.7 162.4 182.3 130.3 195.9 75.2 157.6 157.3 175.7 127.8 187.1 72.3 153.1 152.9 169.2 125.3 178.1 69.3
80 171.1 171.1 181.8 173.0 196.6 118.9 166.3 166.3 175.1 170.3 188.1 116.1 161.5 161.5 168.5 166.3 179.4 113.3
85 181.2 181.2 181.3 181.3 196.6 162.3 175.6 175.6 175.7 175.7 188.0 159.4 169.7 169.7 169.8 169.8 179.1 156.8
90 190.5 190.5 190.6 190.6 196.0 195.3 183.8 183.8 183.9 183.9 187.2 186.7 176.6 176.6 176.7 176.7 178.2 177.7
8400
75 164.1 163.9 183.9 136.8 196.5 76.6 159.1 159.1 177.0 134.2 187.5 73.7 154.9 154.9 170.1 131.7
80 174.2 174.2 183.2 181.5 197.6 124.4 169.1 169.1 176.0 175.3 188.9 121.6 164.0 164.0 169.0 168.5
85 184.4 184.4 184.5 184.5 197.3 171.6 178.5 178.5 178.6 178.6 188.5 169.2 172.2 172.2 172.2 172.2
90 193.2 193.2 193.3 193.3 196.3 195.8 185.9 185.9 186.0 186.0 187.3 186.8 177.9 177.9 177.9 177.9
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
42 RT-PRC043AC-EN
Performance Data
Table 20. Gross cooling capacities 17½ tons three phase standard efficiency T/YS*211G3,4,W
Air
Flow cfm
5600
6300
7000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 186.0 161.1 210.2 124.5 233.8 85.5 176.4 156.7 199.5 120.1 221.1 80.9 166.4 152.2 188.0 115.4 207.2 76.0
80 185.1 184.9 209.9 155.7 233.8 117.2 175.8 175.6 199.3 151.4 221.1 112.6 166.2 166.1 187.8 146.7 207.3 107.7
85 191.8 191.8 209.4 186.6 233.7 148.7 184.3 184.3 198.6 182.2 221.0 144.1 176.1 176.1 187.1 177.5 207.2 139.2
90 203.1 203.1 208.5 208.2 233.5 180.1 195.2 195.2 198.0 197.7 220.9 175.5 186.5 186.5 187.0 186.9 207.0 170.5
75 189.9 172.8 214.5 131.5 237.5 87.3 179.9 168.3 203.2 126.9 224.3 82.7 169.5 163.7 191.1 122.1 209.7 77.6
80 189.1 188.9 214.2 166.6 237.5 123.0 179.8 179.7 203.0 162.1 224.3 118.4 171.3 171.3 190.9 157.3 209.8 113.3
85 199.0 199.0 213.3 201.1 237.4 158.5 191.0 191.0 202.1 196.4 224.2 153.8 182.3 182.3 190.0 189.1 209.8 148.9
90 210.7 210.7 212.4 212.2 237.1 193.7 202.2 202.2 202.4 202.4 223.9 189.0 192.8 192.8 193.0 193.0 209.5 183.9
75 193.1 184.2 218.0 138.3 240.3 89.1 182.8 179.0 206.3 133.6 226.6 84.4 171.9 171.4 193.7 128.7 211.5 79.2
80 193.0 193.0 217.6 177.2 240.4 128.8 185.0 185.0 205.9 172.6 226.7 124.0 176.3 176.3 193.3 167.7 211.7 118.9
85 205.2 205.2 216.5 213.8 240.3 168.2 196.7 196.7 204.5 204.1 226.7 163.5 187.4 187.4 191.9 191.6 211.8 158.4
7700
8400
Air
Flow cfm
5600
90 217.3 217.3 217.5 217.5 239.8 207.1 208.2 208.2 208.4 208.4 226.2 202.4 198.2 198.2 198.3 198.3 211.4 197.3
75 195.7 193.8 220.8 144.9 242.6 90.8 184.9 184.5 208.7 140.2 228.4 86.0 173.6 173.2 195.7 135.3 212.8 80.7
80 198.1 198.1 220.4 187.8 242.7 134.4 189.7 189.7 208.3 183.1 228.6 129.6 180.5 180.5 195.3 178.1 213.2 124.4
85 210.5 210.5 218.6 218.1 242.7 177.8 201.6 201.6 206.5 206.2 228.6 173.0 191.7 191.7 193.7 193.4 213.2 167.8
90 222.9 222.9 223.1 223.1 242.0 220.6 213.4 213.4 213.5 213.5 228.1 215.8 202.6 202.6 202.7 202.7 212.8 208.8
75 197.6 197.1 223.2 151.5 244.3 92.4 186.5 186.0 210.7 146.8 229.8 87.6 175.1 174.8 197.6 141.9 213.8 82.3
80 202.5 202.5 222.6 198.2 244.5 140.0 193.8 193.8 210.2 193.5 230.1 135.2 184.2 184.2 196.9 188.5 214.3 129.9
85 215.2 215.2 220.4 220.0 244.5 187.3 205.9 205.9 208.2 207.8 230.1 182.5 195.6 195.6 195.7 195.7 214.3 177.2
90 227.8 227.8 228.0 228.0 243.9 234.0 217.7 217.7 217.8 217.8 229.5 226.5 206.2 206.2 206.3 206.3 213.4 212.7
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 156.8 147.9 176.0 110.7 192.2 70.7 152.4 145.9 170.0 108.3 184.3 68.0
164.1 106.0 176.1 65.2
80 157.8 157.8 175.8 141.9 192.3 102.5 154.1 154.1 169.9 139.6 184.5 99.8
164.0 137.3 176.5 97.0
85 167.6 167.6 175.3 171.8 192.4 134.1 163.4 163.4 169.2 167.8 184.7 131.4 159.1 159.1 163.2 162.9 176.8 128.7
90 177.1 177.1 177.2 177.2 192.2 165.3 172.1 172.1 172.2 172.2 184.5 162.6 166.9 166.9 167.0 167.0 176.5 159.9
75 159.4 157.6 178.6 117.2 193.9 72.2 154.5 154.1 172.3 114.8 185.6 69.4 150.2 149.9 166.1 112.5 177.1 66.6
80 163.0 163.0 178.4 152.4 194.2 108.0 158.9 158.9 172.1 149.9 186.0 105.2 154.9 154.9 165.9 147.6 177.7 102.4
6300
7000
7700
85 173.0 173.0 177.3 177.0 194.3 143.5 168.3 168.3 171.1 170.8 186.2 140.8 163.4 163.4 164.9 164.6 177.9 138.0
90 182.5 182.5 182.7 182.7 194.1 178.6 177.0 177.0 177.2 177.2 186.0 175.9 171.1 171.1 171.2 171.2 177.7 172.5
75 161.1 160.8 180.6 123.7 195.1 73.7 156.2 155.9 174.2 121.3 186.5 70.8 151.7 151.4 167.8 118.9 177.7 67.9
80 167.4 167.4 180.3 162.7 195.6 113.5 162.9 162.9 173.8 160.2 187.2 110.7 158.5 158.5 167.3 157.8 178.6 107.8
85 177.4 177.4 179.1 178.7 195.7 152.9 172.2 172.2 172.7 172.5 187.3 150.1 166.8 166.8 166.9 166.9 178.6 147.2
90 187.0 187.0 187.1 187.1 195.4 190.8 180.9 180.9 181.0 181.0 187.0 185.9 174.4 174.4 174.5 174.5 178.1 177.5
75 162.7 162.4 182.3 130.3 195.9 75.2 157.6 157.3 175.7 127.8 187.1 72.3 153.1 152.9 169.2 125.3 178.1 69.3
80 171.1 171.1 181.8 173.0 196.6 118.9 166.3 166.3 175.1 170.3 188.1 116.1 161.5 161.5 168.5 166.3 179.4 113.3
85 181.2 181.2 181.3 181.3 196.6 162.3 175.6 175.6 175.7 175.7 188.0 159.4 169.7 169.7 169.8 169.8 179.1 156.8
90 190.5 190.5 190.6 190.6 196.0 195.3 183.8 183.8 183.9 183.9 187.2 186.7 176.6 176.6 176.7 176.7 178.2 177.7
8400
75 164.1 163.9 183.9 136.8 196.5 76.6 159.1 159.1 177.0 134.2 187.5 73.7 154.9 154.9 170.1 131.7
80 174.2 174.2 183.2 181.5 197.6 124.4 169.1 169.1 176.0 175.3 188.9 121.6 164.0 164.0 169.0 168.5
85 184.4 184.4 184.5 184.5 197.3 171.6 178.5 178.5 178.6 178.6 188.5 169.2 172.2 172.2 172.2 172.2
90 193.2 193.2 193.3 193.3 196.3 195.8 185.9 185.9 186.0 186.0 187.3 186.8 177.9 177.9 177.9 177.9
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
RT-PRC043AC-EN 43
Performance Data
Table 21. Gross cooling capacities 20 tons three phase standard efficiency T/YS*240G3,4,W,K
Air
Flow cfm
6400
7200
8000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 230.4 187.9 260.3 147.4 287.7 103.3 219.7 182.8 247.5 142.0 271.7 97.5 208.2 177.5 233.5 136.2 253.6 91.0
80 229.9 221.9 260.2 182.1 287.8 138.7 219.2 216.9 247.4 176.7 271.9 132.8 207.8 207.5 233.4 170.9 253.9 126.3
85 231.6 231.5 260.0 216.6 287.9 173.7 222.2 222.2 247.2 211.2 272.0 167.9 213.1 213.1 233.1 205.4 254.1 161.4
90 244.0 244.0 259.2 250.6 287.9 208.5 235.1 235.1 246.5 245.2 272.1 202.7 225.2 225.2 232.8 232.5 254.4 196.3
75 236.0 200.9 265.9 154.9 292.1 105.1 224.6 195.6 252.3 149.4 275.0 99.0 212.2 190.0 237.4 143.4 255.9 92.3
80 235.3 234.9 265.7 193.9 292.3 144.8 224.0 223.7 252.1 188.4 275.2 138.7 211.9 211.7 237.3 182.4 256.1 132.0
85 239.6 239.6 265.4 232.7 292.4 184.2 230.6 230.6 251.7 227.1 275.5 178.2 220.6 220.6 236.9 221.1 256.5 171.5
90 253.6 253.6 264.7 264.3 292.5 223.4 244.0 244.0 251.2 250.9 275.7 217.4 233.1 233.1 236.8 236.5 256.6 211.2
75 240.4 213.5 270.2 162.2 295.3 106.7 228.3 208.1 256.0 156.5 277.2 100.4 215.3 202.4 240.4 150.4 258.3 93.9
80 239.6 239.3 270.0 205.6 295.5 150.8 227.9 227.6 255.7 199.9 277.6 144.5 215.6 215.4 240.3 193.8 258.6 138.0
85 247.4 247.4 269.5 248.5 295.8 194.6 237.8 237.8 255.2 242.8 278.0 188.4 227.0 227.0 239.7 236.7 258.8 181.7
8800
9600
Air
Flow cfm
6400
90 261.8 261.8 268.9 268.5 295.9 238.2 251.4 251.4 255.0 254.7 278.1 232.0 239.5 239.5 240.4 240.2 258.4 225.6
75 243.8 225.9 273.8 169.4 297.6 108.2 231.2 220.4 258.9 163.6 279.5 101.9 217.8 214.6 242.7 157.3 260.1 95.4
80 243.2 242.9 273.5 217.1 298.0 156.7 231.5 231.3 258.8 211.5 279.5 150.4 219.1 219.1 242.7 205.1 260.4 143.9
85 254.2 254.2 272.7 264.2 298.3 204.9 243.9 243.9 258.0 257.1 279.9 198.5 232.4 232.4 242.1 241.6 260.5 192.0
90 268.8 268.8 272.5 272.3 298.4 252.8 257.6 257.6 258.7 258.4 279.8 246.5 244.7 244.7 244.9 244.9 260.4 239.8
75 246.6 238.2 276.6 176.5 299.5 109.6 233.8 232.7 261.3 170.6 281.4 103.5 219.9 219.4 244.6 164.2 261.5 96.9
80 246.7 246.5 276.5 228.6 299.8 162.5 234.7 234.7 261.3 222.7 281.7 156.4 223.6 223.6 244.5 216.3 261.9 149.8
85 260.1 260.1 275.5 274.8 300.3 215.2 249.2 249.2 260.3 259.7 281.7 209.0 237.0 237.0 243.7 243.3 262.2 202.4
90 274.9 274.9 276.0 275.8 300.2 267.3 262.9 262.9 263.1 263.1 281.3 260.9 249.0 249.0 249.2 249.2 261.8 254.3
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 196.3 172.1 218.4 130.1 234.3 84.1 190.2 169.3 210.4 126.9 224.3 80.6
202.2 123.7 214.0 77.1
80 196.0 195.8 218.4 164.8 234.5 119.4 190.1 189.9 210.5 161.7 224.6 116.0
85 203.1 203.1 218.1 199.3 234.6 154.4 198.0 198.0 210.2 196.1 224.9 151.0
-
-
-
-
202.4 158.5 214.4 112.4
202.2 192.9 214.8 147.5
90 214.2 214.2 218.0 217.8 234.7 189.3 208.2 208.2 210.3 210.1 225.0 185.9
202.5 202.3 214.9 182.4
75 199.5 184.4 221.4 137.1 236.4 85.5 193.1 181.5 213.0 133.8 226.0 82.0 186.8 178.8 204.4 130.4 215.2 78.4
80 199.6 199.5 221.4 176.2 236.7 125.3 193.6 193.5 213.1 172.9 226.4 121.7 187.8 187.8 204.6 169.6 215.7 118.1
7200
8000
8800
85 209.8 209.8 221.0 214.8 237.0 164.7 203.9 203.9 212.8 210.3 226.8 161.2 197.8 197.8 204.4 203.4 216.3 157.6
90 220.8 220.8 221.5 221.3 237.0 203.9 214.0 214.0 214.1 214.1 226.7 200.3 206.6 206.6 206.7 206.7 216.2 196.8
75 202.1 196.5 223.6 143.9 237.9 87.0 195.4 193.3 214.9 140.6 227.0 83.3 188.8 187.8 205.9 137.2 215.8 79.6
80 203.3 203.3 223.7 187.4 238.3 131.1 197.8 197.8 215.0 184.0 227.6 127.5 192.1 192.1 206.0 180.6 216.6 123.8
85 215.2 215.2 223.3 222.8 238.5 174.9 208.8 208.8 214.6 214.3 228.2 171.5 202.0 202.0 205.8 205.4 217.2 167.8
90 225.9 225.9 226.1 226.1 238.6 218.3 218.3 218.3 218.4 218.4 228.0 214.8 209.9 209.9 210.0 210.0 217.0 210.6
75 204.1 203.6 225.4 150.7 239.0 88.4 197.3 196.8 216.3 147.3 227.7 84.7 190.4 189.9 207.1 143.8
-
80 207.8 207.8 225.4 198.5 239.5 136.9 201.8 201.8 216.3 195.1 228.5 133.3 195.7 195.7 207.1 191.6
85 219.7 219.7 224.9 224.5 240.0 185.2 212.7 212.7 215.9 215.5 229.0 181.6 205.2 205.2 206.8 206.4
90 229.8 229.8 229.9 229.9 239.7 232.8 221.2 221.2 221.3 221.3 228.9 224.7 212.2 212.2 212.3 212.3
-
-
-
-
-
-
9600
75 205.8 205.3 226.7 157.5 239.7 89.8 198.5 198.1 217.4 154.0 228.2 86.0 191.4 191.0
80 211.6 211.6 226.6 209.5 240.4 142.7 205.2 205.2 217.3 206.0 229.1 139.1 198.5 198.5
85 223.3 223.3 226.1 225.7 240.9 195.4 215.8 215.8 216.9 216.5 229.6 191.7 207.7 207.7
90 232.6 232.6 232.7 232.7 240.7 239.0 223.6 223.6 223.7 223.7 229.5 228.8 214.5 214.5
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
44 RT-PRC043AC-EN
Performance Data
Table 22. Gross cooling capacities 25 tons three phase standard efficiency T/YS*300G3,4,W,K
Air
Flow cfm
7000
8000
9000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.5 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1
80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 274.8 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0
85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7
90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2
75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7
80 263.5 263.0 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3
85 270.1 270.1 295.0 264.3 322.1 207.6 259.9 259.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7
90 285.1 285.1 294.2 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7
75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8
80 268.4 268.1 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0
85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9
10000
11000
Air
Flow cfm
7000
90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 284.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6
75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9
80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8
85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4
90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4
75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.0
80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5
85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8
90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8
236.0 85.9
80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7
85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3
90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7
75 223.7 210.5 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 248.8 91.5
80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
236.2 125.8
236.6 165.5
236.8 204.9
227.8 148.2 236.9 87.5
228.0 193.2 237.3 133.1
8000
9000
10000
85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4
90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3
75 226.8 224.9 249.1 164.3 261.8 97.2 219.3 218.6 239.4 160.7 249.9 93.3
80 230.0 230.0 249.1 214.9 262.2 148.5 223.5 223.5 239.5 211.2 250.3 144.6
85 242.4 242.4 248.5 248.1 262.5 199.5 234.9 234.9 238.9 238.5 250.7 195.6
-
-
-
-
-
-
-
-
-
-
227.6 227.1 238.0 178.6
231.1 231.1 238.0 223.4
229.5 156.9
229.6 207.4
229.1 228.7
-
-
-
-
-
-
90 252.9 252.9 253.0 253.0 262.4 249.9 243.8 243.8 243.9 243.9 251.0 246.1
233.9 233.9
75 229.3 228.7 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7
80 235.2 235.2 250.9 229.2 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7
85 247.3 247.3 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.8 230.3 230.3 230.4 230.4
90 256.6 256.6 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2
-
-
-
-
-
-
-
-
-
-
11000
75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1
80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.8 224.1 224.1
85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5
90 258.7 258.7 258.8 258.8 264.6 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
RT-PRC043AC-EN 45
Performance Data
Table 23. Gross cooling capacities 25 tons three phase standard efficiency T/YS*301G3,4,W
Air
Flow cfm
7000
8000
9000
Ambient Temperature
Ent
DB
(°F)
85 95
Entering Wet Bulb
105
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 257.6 212.0 289.0 165.3 317.0 114.6 245.8 206.5 274.9 159.4 299.4 108.2 233.1 200.6 259.5 153.1 279.6 101.1
80 257.0 250.5 288.9 204.5 317.1 154.5 245.3 244.2 274.8 198.7 299.5 148.1 232.7 232.3 259.5 192.4 279.8 141.0
85 259.2 259.1 288.8 243.6 317.2 194.2 249.7 249.7 274.6 237.7 299.7 187.7 239.4 239.4 259.2 231.3 280.1 180.7
90 273.4 273.4 287.9 282.0 317.2 233.5 263.5 263.5 274.1 273.6 299.8 227.1 252.3 252.3 258.7 258.4 280.4 220.2
75 264.4 228.7 295.5 175.0 321.8 116.8 251.7 223.0 280.5 168.9 302.9 110.1 238.0 216.8 264.2 162.4 281.8 102.7
80 263.5 263.0 295.4 219.8 322.0 162.4 250.9 250.6 280.4 213.7 303.1 155.7 237.6 237.4 264.1 207.3 282.0 148.3
85 270.1 270.1 295.0 264.3 322.1 207.6 259.9 259.9 279.9 258.2 303.4 201.0 248.6 248.6 263.6 251.6 282.5 193.7
90 285.1 285.1 294.2 293.7 322.2 252.7 274.1 274.1 279.3 279.0 303.6 246.1 261.6 261.6 263.6 263.4 282.7 238.7
75 269.4 245.0 300.5 184.4 325.2 118.8 256.0 239.1 284.8 178.2 305.1 111.8 241.7 232.8 267.6 171.5 284.3 104.8
80 268.4 268.1 300.4 234.8 325.4 170.0 255.7 255.5 284.7 228.6 305.4 163.1 242.3 242.1 267.6 222.1 284.5 156.0
85 279.4 279.4 299.7 284.7 325.7 221.0 268.4 268.4 283.9 278.5 305.9 214.1 256.1 256.1 267.0 266.2 284.7 206.9
10000
11000
Air
Flow cfm
7000
90 294.7 294.7 299.1 298.8 325.8 271.6 282.6 282.6 284.2 284.0 306.1 264.8 268.8 268.8 269.0 269.0 284.4 257.6
75 273.3 261.1 304.4 193.6 327.7 120.8 259.5 255.0 288.0 187.3 307.8 114.0 244.7 244.0 270.1 180.4 286.4 106.9
80 273.1 272.9 304.3 249.8 328.0 177.7 260.3 260.3 288.1 243.4 307.8 170.8 248.3 248.3 270.2 236.5 286.7 163.8
85 287.3 287.3 303.3 302.5 328.3 234.3 275.4 275.4 287.0 286.2 307.9 227.3 262.1 262.1 269.1 268.5 286.9 220.4
90 302.6 302.6 303.8 303.5 328.2 290.4 289.5 289.5 289.7 289.7 307.7 283.6 274.4 274.4 274.5 274.5 286.4 276.4
75 276.5 275.7 307.6 202.8 330.2 122.9 262.3 261.6 290.6 196.3 310.1 116.2 247.0 246.2 272.1 189.3 288.1 109.0
80 277.6 277.6 307.6 264.5 330.3 185.5 266.1 266.1 290.6 258.0 310.3 178.8 253.4 253.4 272.0 251.0 288.4 171.5
85 293.9 293.9 306.1 305.3 331.2 247.7 281.3 281.3 289.1 288.4 310.4 241.0 267.1 267.1 270.8 270.4 288.6 233.8
90 309.2 309.2 309.4 309.4 330.3 309.3 295.0 295.0 295.2 295.2 309.5 302.3 278.5 278.5 278.7 278.7 288.1 286.9
Ambient Temperature
Ent
DB
(°F)
115 120
Entering Wet Bulb
125
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 219.7 194.5 243.0 146.4 258.2 93.6 212.8 191.4 234.3 143.0 247.2 89.8
236.0 85.9
80 219.4 219.2 243.0 185.7 258.2 133.4 212.8 212.5 234.3 182.3 247.5 129.7
85 228.2 228.2 242.7 224.7 258.5 173.0 222.2 222.2 234.1 221.2 247.8 169.3
90 239.8 239.8 242.5 242.2 258.7 212.5 233.0 233.0 234.1 233.9 247.9 208.7
75 223.7 210.5 246.5 155.4 260.3 95.4 216.5 207.3 237.3 151.9 248.8 91.5
80 224.1 224.0 246.6 200.4 260.5 140.9 217.8 217.8 237.4 196.8 249.1 137.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
236.2 125.8
236.6 165.5
236.8 204.9
227.8 148.2 236.9 87.5
228.0 193.2 237.3 133.1
8000
9000
10000
85 236.1 236.1 246.2 243.9 260.9 186.2 229.4 229.4 237.1 236.4 249.6 182.4
90 247.4 247.4 247.6 247.6 260.9 231.2 239.5 239.5 239.7 239.7 249.6 227.3
75 226.8 224.9 249.1 164.3 261.8 97.2 219.3 218.6 239.4 160.7 249.9 93.3
80 230.0 230.0 249.1 214.9 262.2 148.5 223.5 223.5 239.5 211.2 250.3 144.6
85 242.4 242.4 248.5 248.1 262.5 199.5 234.9 234.9 238.9 238.5 250.7 195.6
-
-
-
-
-
-
-
-
-
-
227.6 227.1 238.0 178.6
231.1 231.1 238.0 223.4
229.5 156.9
229.6 207.4
229.1 228.7
-
-
-
-
-
-
90 252.9 252.9 253.0 253.0 262.4 249.9 243.8 243.8 243.9 243.9 251.0 246.1
233.9 233.9
75 229.3 228.7 251.0 173.2 263.2 99.2 221.2 220.7 241.0 169.4 250.7 95.1 213.2 212.8 230.8 165.7
80 235.2 235.2 250.9 229.2 263.6 156.2 228.2 228.2 240.9 225.5 251.4 152.2 220.9 220.9 230.7 221.7
85 247.3 247.3 250.1 249.6 263.9 212.8 239.1 239.1 240.3 240.0 251.7 208.8 230.3 230.3 230.4 230.4
90 256.6 256.6 256.7 256.7 263.7 262.7 246.2 246.2 246.3 246.3 251.6 250.6 236.1 236.1 236.2 236.2
-
-
-
-
-
-
-
-
-
-
11000
75 230.8 230.4 252.4 182.0 264.0 101.1 222.7 222.3 242.1 178.2 251.2 97.0 214.6 214.1
80 239.4 239.4 252.2 243.6 264.7 163.8 232.0 232.0 242.0 238.9 252.1 159.8 224.1 224.1
85 251.0 251.0 251.7 251.3 264.9 226.1 242.1 242.1 242.2 242.2 252.4 222.0 232.5 232.5
90 258.7 258.7 258.8 258.8 264.6 263.8 248.7 248.7 248.8 248.8 252.1 251.4 237.7 237.7
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Stands for both downflow and horizontal unit.
-
-
-
-
46 RT-PRC043AC-EN
Performance Data
Table 24. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (stage 1)
Air
Flow cfm
Ent
DB
(°F)
Ambient Temperature
85 95
Entering Wet Bulb
61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2000
2500
3000
3500
4000
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
42.0 39.3 45.3 31.2 49.8 15.0 39.2 37.2 42.3 29.4 46.7 13.6
44.2 43.5 46.2 39.1 50.3 29.0 41.5 41.2 43.3 37.1 47.2 27.2
46.9 46.6 48.0 44.3 50.7 38.0 44.1 44.1 45.1 42.1 47.6 36.1
49.6 49.3 50.4 48.1 52.2 44.1 46.9 46.8 47.5 45.8 49.1 42.1
43.3 41.5 46.2 33.6 50.4 17.5 40.4 39.2 43.1 31.6 47.1 15.9
45.7 45.7 47.4 41.6 51.1 31.5 42.8 42.8 44.3 39.3 47.9 29.6
48.5 48.5 49.5 46.9 51.8 40.7 45.6 45.6 46.4 44.6 48.6 38.6
51.5 51.5 52.0 50.9 53.5 47.0 48.5 48.5 48.9 48.4 50.3 44.7
44.4 43.3 46.9 35.5 50.8 19.5 41.3 40.8 43.7 33.3 47.3 17.7
47.0 47.0 48.4 43.6 51.7 33.6 44.0 44.0 45.1 41.2 48.3 31.6
50.0 50.0 50.6 49.1 52.7 42.9 46.9 46.9 47.4 46.5 49.3 40.6
53.0 53.0 53.3 53.2 54.6 49.3 49.9 49.9 50.1 50.1 51.2 46.9
45.2 44.7 47.4 37.0 50.9 21.1 42.0 42.0 44.0 34.6 47.7 19.1
48.1 48.1 49.1 45.2 52.1 35.3 44.8 44.8 45.7 42.6 48.5 33.0
51.2 51.2 51.6 50.8 53.3 44.7 48.1 47.9 48.2 48.0 49.8 42.2
54.3 54.3 54.4 54.4 55.4 51.3 50.6 50.6 51.0 51.0 51.9 48.6
45.8 45.6 47.6 38.0 51.3 22.3 42.4 42.4 44.3 35.4 48.4 20.0
48.9 48.9 49.6 46.3 52.2 36.6 45.5 45.5 46.0 43.5 48.7 34.1
52.1 52.1 52.3 52.1 53.7 46.1 48.6 48.6 48.7 48.7 50.0 43.4
54.8 54.8 55.2 55.2 56.0 52.8 51.2 51.2 51.7 51.7 52.3 49.9
4375
75
80
85
90
46.1 46.0 47.6 38.5 51.9 22.8 42.6 42.6 44.6 35.8 48.7 20.5
49.3 49.3 49.8 46.9 52.4 37.2 45.8 45.8 46.1 43.9 48.9 34.6
52.3 52.3 52.6 52.6 53.9 46.8 48.8 48.8 49.0 49.0 50.3 44.0
55.2 55.2 55.7 55.7 56.3 53.6 52.0 52.0 52.1 52.1 52.5 50.6
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
RT-PRC043AC-EN 47
Performance Data
Table 25. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (stage 2)
Air
Flow cfm
Ent
DB
(°F)
Ambient Temperature
85 95
Entering Wet Bulb
61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2000
2500
3000
3500
4000
75
80
85
90
87.1 69.1 97.7 56.8 108.4 33.8 83.2 66.7 92.6 54.8 102.7 32.4
88.4 76.3 98.3 68.1 110.1 52.4 84.5 73.5 93.8 65.7 104.8 50.5
91.0 81.9 99.1 76.1 110.6 65.0 87.1 78.9 94.7 73.5 105.5 62.7
94.6 86.6 101.5 82.3 111.0 73.9 90.6 83.5 97.0 79.4 106.0 71.4
75
80
92.4 75.4 101.4 62.0 112.8 37.9 88.1 72.7 96.9 59.7 105.9 36.2
94.3 83.2 103.5 74.1 114.0 57.5 90.1 80.3 98.7 71.6 109.8 55.3
85 97.5 89.5 105.0 83.0 115.8 71.0 93.3 86.3 100.2 80.1 110.4 68.5
90 101.5 94.7 107.9 89.7 116.8 80.7 97.3 91.3 103.2 86.6 111.5 77.9
75
80
96.8 80.9 107.7 66.4 114.3 41.2 92.3 78.0 102.4 64.0 113.2 39.3
99.4 89.5 107.8 79.5 118.5 61.9 94.9 86.3 102.7 76.7 114.1 59.5
85 103.1 96.3 110.0 89.1 120.1 76.2 98.6 92.9 105.0 86.0 114.4 73.5
90 107.6 102.0 113.5 96.4 121.8 86.7 103.1 98.4 108.5 93.1 116.2 83.7
75 100.3 85.7 110.4 70.2 120.2 43.8 95.6 82.5 104.8 67.5 115.7 41.7
80 103.6 95.0 111.4 84.2 123.3 65.5 98.9 91.6 106.0 81.1 117.2 62.9
85 107.9 102.4 114.2 94.5 123.6 80.8 103.2 98.8 108.9 91.1 117.7 77.8
90 112.9 108.7 118.3 102.4 126.0 92.0 108.1 104.9 112.9 98.9 120.1 88.7
75 103.1 89.8 112.3 73.3 121.4 45.7 98.0 86.4 106.5 70.4 116.8 43.3
80 107.0 99.8 114.1 88.1 125.2 68.5 102.0 96.2 108.4 84.9 118.8 65.7
85 111.9 107.9 117.5 99.1 126.3 84.6 106.9 104.0 112.0 95.6 120.0 81.5
90 117.4 114.6 122.2 107.7 129.3 96.5 112.3 110.6 116.6 103.9 123.2 93.1
4375
75 104.6 92.4 113.2 75.1 122.6 46.7 99.3 88.8 107.1 72.0 117.4 44.1
80 109.0 103.0 115.5 90.6 126.1 70.3 103.8 99.1 109.7 87.2 119.4 67.3
85 114.3 111.5 119.5 102.2 127.7 87.1 109.1 107.4 113.7 98.5 121.3 83.7
90 120.1 118.6 124.6 111.2 131.3 99.5 114.8 114.4 118.8 107.3 124.9 95.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
48 RT-PRC043AC-EN
Performance Data
Table 26. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (full load)
Air
Flow cfm
2500
3000
3500
4000
4500
5000
5500
6000
Ent
DB
(°F)
85
Ambient Temperature
95 105
Entering Wet Bulb
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 125.0 96.9 138.0 75.5 153.6 38.3 118.3 92.7 130.4 72.3 145.1 36.2 111.1 88.1 122.3 68.7 136.2 33.8
80 127.7 109.0 139.6 94.4 154.2 68.6 121.0 104.1 132.0 90.4 145.7 65.6 113.8 98.9 123.9 86.0 136.7 62.2
85 132.0 118.4 141.2 108.0 154.7 89.5 125.1 113.0 133.5 103.4 146.2 85.7 117.8 107.3 125.5 98.4 137.2 81.5
90 137.2 126.3 144.6 118.4 155.2 104.6 130.0 120.5 136.8 113.3 146.7 100.1 122.5 114.3 128.6 107.7 137.8 95.3
75 131.2 104.5 143.4 82.5 158.2 44.6 124.1 99.9 135.4 78.9 149.3 42.1 116.5 94.9 126.9 74.9 140.0 39.3
80 134.4 117.1 145.5 102.0 159.3 75.6 127.3 111.8 137.5 97.6 150.4 72.2 119.7 106.2 129.0 92.9 141.0 68.4
85 139.1 127.0 147.6 116.2 160.4 97.2 131.8 121.2 139.6 111.1 151.4 93.0 124.1 115.1 131.1 105.7 142.1 88.4
90 144.6 135.3 151.5 127.1 161.4 112.8 137.1 129.1 143.3 121.5 152.5 107.9 129.1 122.5 134.6 115.6 143.1 102.7
75 136.7 111.4 148.1 88.8 162.1 50.2 129.2 106.4 142.1 84.8 152.8 47.4 121.2 101.0 133.1 80.4 143.1 44.2
80 140.5 124.5 150.7 108.9 163.7 82.0 132.9 118.8 142.3 104.1 154.4 78.2 124.9 112.8 133.4 99.0 144.6 74.0
85 145.6 134.9 153.4 123.6 165.3 104.2 137.8 128.7 144.9 118.2 156.0 99.5 129.7 122.2 136.0 112.4 146.2 94.6
90 151.4 143.6 157.6 135.0 166.9 120.3 143.4 137.0 149.0 129.0 157.6 115.1 135.0 130.0 140.0 122.7 147.8 109.5
75 141.5 117.6 154.6 94.4 165.3 55.2 133.5 112.2 145.6 90.0 155.6 51.9 125.1 106.4 136.1 85.3 145.4 48.3
80 145.8 131.3 155.2 115.2 167.4 87.7 137.8 125.2 146.4 110.0 157.7 83.4 129.4 118.8 137.0 104.5 147.5 78.9
85 151.3 142.1 158.4 130.4 169.6 110.5 143.2 135.5 149.5 124.6 159.8 105.5 134.6 128.6 140.2 118.4 149.6 100.1
90 157.4 151.2 163.1 142.3 171.7 127.2 149.1 144.2 154.0 135.9 161.9 121.5 140.2 136.9 144.6 129.2 151.7 115.5
75 145.6 123.2 157.7 99.4 173.0 59.4 137.2 117.4 148.3 94.6 162.6 55.8 128.4 111.2 138.4 89.4 151.7 51.8
80 150.4 137.3 159.0 120.8 173.0 92.7 142.0 130.9 149.7 115.2 162.7 88.1 133.2 124.1 140.0 109.3 152.0 83.1
85 156.3 148.7 162.7 136.6 173.1 116.1 147.8 141.7 153.4 130.3 162.9 110.7 138.8 134.4 143.7 123.7 152.3 105.0
90 162.8 158.2 167.8 148.9 175.8 133.4 154.0 150.8 158.4 142.1 165.6 127.3 144.7 143.1 148.5 135.0 155.0 120.9
75 149.0 128.0 160.1 103.7 174.5 63.1 140.2 121.8 150.2 98.5 163.6 59.0 130.9 115.3 139.9 92.9 152.3 54.6
80 154.3 142.8 162.1 125.7 175.2 97.0 145.5 135.9 152.4 119.7 164.5 92.0 136.2 128.7 142.2 113.4 153.3 86.7
85 160.6 154.5 166.3 142.0 175.9 121.1 151.6 147.2 156.6 135.4 165.3 115.3 142.2 139.5 146.5 128.4 154.3 109.1
90 167.4 164.5 171.8 154.8 179.1 138.9 158.2 156.7 162.0 147.6 168.5 132.4 148.5 148.5 151.7 140.1 157.5 125.6
75 151.6 132.3 161.8 107.3 175.2 66.0 142.4 125.7 151.5 101.7 164.0 61.5 132.7 118.7 140.8 95.8 152.8 56.8
80 157.5 147.5 164.5 129.9 176.6 100.7 148.2 140.3 154.3 123.6 165.5 95.3 138.6 132.7 143.8 116.8 153.9 89.5
85 164.2 159.7 169.2 146.8 178.0 125.4 154.8 152.0 159.1 139.8 167.0 119.2 145.0 143.9 148.5 132.4 155.6 112.6
90 171.3 170.1 175.1 160.0 181.8 143.7 161.7 161.7 164.9 152.5 170.7 136.9 151.6 151.6 154.2 144.6 159.3 129.7
75 153.6 135.8 162.8 110.2 175.3 68.2 143.9 128.8 152.1 104.2 164.5 63.4 133.8 121.5 140.9 97.9 153.2 58.2
80 160.0 151.6 166.1 133.5 177.4 103.7 150.3 144.0 155.6 126.7 165.8 97.9 140.2 136.0 144.6 119.6 154.5 91.7
85 167.1 164.3 171.4 150.9 179.4 129.0 157.3 156.1 160.9 143.5 168.0 122.4 147.0 147.0 149.9 135.7 156.2 115.5
90 174.5 174.5 177.7 164.6 183.7 147.9 164.4 164.4 167.1 156.7 172.3 140.6 154.0 154.0 155.9 148.4 160.4 133.1
RT-PRC043AC-EN 49
Performance Data
Table 26. Gross cooling capacities 12½ tons three phase high efficiency T/YH*150G3,4,W (full load)
Air
Flow cfm
2500
Ent
DB
(°F)
115
Ambient Temperature
120 125
61 67 73 61
Entering Wet Bulb
67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 103.5 83.2 113.8 64.9 126.9 31.1 99.5 80.7 109.4 62.8 122.0 29.6 95.5 78.0 104.9 60.6 117.0 28.0
80 106.2 93.3 115.4 81.4 127.4 58.5 102.2 90.4 110.9 78.9 122.5 56.5 98.1 87.5 106.4 76.4 117.5 54.4
85 110.0 101.2 116.9 93.0 127.9 77.0 105.9 98.1 112.5 90.3 123.0 74.7 101.8 94.8 107.9 87.4 118.0 72.2
90 114.5 107.9 119.9 101.9 128.4 90.2 110.3 104.5 115.4 98.8 123.5 87.5 106.0 101.1 110.8 95.7 118.5 84.7
75 108.5 89.6 118.0 70.6 130.2 36.2 104.3 86.8 113.3 68.4 125.1 34.5 100.0 84.0 108.6 66.0 120.0 32.7
3000
3500
4000
4500
5000
80 111.7 100.3 120.0 87.8 131.2 64.3 107.5 97.2 115.4 85.1 126.2 62.1 103.2 94.0 110.7 82.4 121.0 59.9
85 115.9 108.6 122.1 100.0 132.3 83.5 111.6 105.3 117.5 97.0 127.2 80.9 107.3 101.8 112.7 94.0 122.0 78.3
90 120.7 115.7 125.5 109.3 133.3 97.2 116.3 112.1 120.8 106.1 128.2 94.3 111.8 108.5 116.0 102.7 123.1 91.3
75 112.7 95.3 123.6 75.8 132.9 40.6 108.3 92.4 118.7 73.3 127.6 38.7 103.8 89.3 113.7 70.8 122.2 36.8
80 116.4 106.5 124.0 93.5 134.4 69.5 112.0 103.2 119.2 90.7 129.1 67.1 107.5 99.8 114.2 87.7 123.8 64.7
85 121.1 115.3 126.6 106.3 136.0 89.3 116.6 111.8 121.8 103.1 130.7 86.5 112.0 108.2 116.8 99.8 125.3 83.7
90 126.2 122.8 130.5 116.1 137.6 103.5 121.6 119.0 125.5 112.6 132.3 100.4 116.9 115.2 120.5 109.1 126.9 97.3
75 116.3 100.4 126.2 80.2 134.8 44.4 111.7 97.2 121.0 77.5 129.3 42.3 107.0 94.0 115.8 74.8 123.7 40.1
80 120.5 112.1 127.3 98.6 136.9 74.0 115.9 108.6 122.2 95.5 131.4 71.4 111.2 105.0 117.1 92.4 125.8 68.8
85 125.6 121.4 130.4 111.9 139.0 94.4 120.9 117.6 125.4 108.5 133.5 91.5 116.1 113.8 120.2 105.1 127.9 88.4
90 131.0 129.2 134.7 122.1 141.1 109.2 126.2 125.3 129.5 118.5 135.6 105.9 121.3 121.2 124.3 114.8 130.0 102.5
75 119.1 104.7 128.0 84.0 140.3 47.5 114.3 101.4 122.7 81.1 134.5 45.2 109.4 97.9 117.3 78.2 128.6 42.8
80 123.9 117.0 129.8 103.0 140.8 77.8 119.0 113.3 124.5 99.7 135.0 75.1 114.1 109.6 119.2 96.4 129.2 72.2
85 129.3 126.7 133.5 116.8 141.3 98.9 124.4 122.8 128.2 113.3 135.6 95.7 119.4 118.8 122.8 109.6 129.8 92.5
90 135.1 135.0 138.1 127.6 143.9 114.2 130.0 130.0 132.8 123.7 138.2 110.7 124.9 124.9 127.4 119.8 132.4 107.1
75 121.2 108.4 129.2 87.1 140.6 49.9 116.2 104.9 123.6 84.0 134.5 47.4 111.1 101.2 118.0 80.9 129.0 44.9
80 126.5 121.2 131.6 106.7 141.7 81.0 121.5 117.4 126.2 103.3 135.7 78.0 116.4 113.4 120.6 99.7 129.6 75.0
85 132.4 131.4 135.8 121.1 142.8 102.7 127.3 127.3 130.4 117.3 136.9 99.3 122.1 122.1 124.8 113.5 130.9 95.9
90 138.4 138.4 140.9 132.3 146.0 118.5 133.2 133.2 135.4 128.3 140.1 114.8 127.9 127.9 129.7 124.1 134.1 111.1
75 122.6 111.5 129.6 89.5 141.0 51.7 117.4 107.7 123.9 86.3 134.8 49.0 112.1 103.9 118.0 82.9 130.0 46.2
5500
80 128.4 124.8 132.7 109.8 141.9 83.5 123.2 120.7 127.1 106.1 136.2 80.3 117.9 116.6 121.3 102.4 130.7 77.1
85 134.7 134.7 137.5 124.7 143.7 105.8 129.4 129.4 131.8 120.7 137.6 102.2 124.0 124.0 126.0 116.7 131.4 98.6
90 141.1 141.1 143.0 136.4 147.4 122.2 135.7 135.7 137.2 132.1 141.3 118.3 130.1 130.1 131.4 127.8 135.1 114.3
75 123.3 113.8 130.0 91.3 142.0 52.7 117.9 109.9 125.0 87.8 135.3 49.9 112.3 105.8 119.0 84.3 130.2 46.9
6000
80 129.7 127.7 133.2 112.2 143.0 85.3 124.2 123.4 127.3 108.3 137.0 81.9 118.7 118.7 124.0 104.4 131.6 78.5
85 136.4 136.4 138.4 127.6 143.8 108.2 130.8 130.8 132.5 123.5 139.0 104.5 125.2 125.2 126.5 119.2 133.0 100.6
90 143.0 143.0 144.3 139.8 148.1 125.2 137.4 137.4 138.4 135.3 141.8 121.1 131.6 131.6 132.3 130.8 135.3 116.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
50 RT-PRC043AC-EN
Performance Data
Table 27. Gross cooling capacities 12½ tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD150G3,4,W (Digit 22 = B)
Air
Flow cfm
2500 (a)
3250
4000
4500
5000
5500
6000
Ent
DB
(°F)
85
Ambient Temperature
95 105
61 67 73 61
Entering Wet Bulb
67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 119.6 86.9 135.0 60.0 154.5 54.1 112.4 82.4 127.1 56.5 145.9 51.1 104.7 77.6 118.6 52.7 136.8 47.9
80 121.1 102.6 134.0 82.6 151.3 52.9 114.0 97.4 126.2 78.4 142.8 50.0 106.3 92.0 117.9 74.0 133.7 46.8
85 123.7 114.7 134.3 101.6 149.2 75.1 116.7 108.9 126.6 96.8 140.8 71.4 109.2 102.8 118.4 91.7 131.9 67.4
90 127.5 123.2 135.8 116.9 148.3 97.4 120.6 116.7 128.2 111.5 140.0 93.0 113.2 110.0 120.1 105.8 131.2 88.4
75 129.1 96.7 143.2 68.4 161.5 56.5 121.5 91.9 134.9 64.6 152.5 53.4 113.3 86.8 126.0 60.5 142.9 50.0
80 131.4 113.6 143.2 92.1 159.1 57.4 123.9 108.1 134.9 87.7 150.2 54.0 115.8 102.4 126.1 83.0 140.7 50.4
85 134.9 126.9 144.3 112.3 157.9 84.4 127.5 120.8 136.2 107.2 149.1 80.4 119.5 114.4 127.5 101.9 139.7 76.2
90 139.7 136.5 146.7 128.8 157.9 107.9 132.3 129.8 138.6 123.1 149.2 103.2 124.4 122.8 130.0 117.2 139.9 98.3
75 137.1 105.6 149.9 75.8 167.0 58.4 129.0 100.4 141.1 71.7 157.4 55.1 120.3 95.0 131.7 67.4 147.4 51.6
80 140.2 123.6 150.7 100.7 165.4 64.5 132.2 117.8 142.0 96.0 156.0 60.9 123.7 111.8 132.7 91.0 146.1 57.0
85 144.6 138.0 152.7 122.0 165.1 92.7 136.7 131.6 144.1 116.7 155.8 88.5 128.3 124.9 135.0 111.1 145.9 83.9
90 150.2 148.8 156.0 139.7 166.0 117.4 142.4 141.8 147.5 133.7 156.8 112.4 134.0 134.0 138.4 127.5 147.0 107.2
75 141.5 110.9 153.5 80.1 169.7 59.4 133.1 105.5 144.3 75.9 159.9 56.0 124.1 100.0 134.7 71.3 149.5 52.3
80 145.2 129.7 154.9 105.8 168.8 68.7 136.9 123.7 145.8 100.9 159.0 64.9 128.1 117.5 136.3 95.8 148.8 60.8
85 150.2 144.9 157.5 127.9 169.0 97.7 142.0 138.3 148.6 122.4 159.4 93.2 133.2 131.4 139.1 116.6 149.2 88.5
90 156.3 156.3 161.3 146.4 170.5 123.1 148.2 148.2 152.5 140.3 161.0 118.0 139.6 139.6 143.1 133.8 150.9 112.6
75 145.2 115.7 156.3 84.0 171.8 60.1 136.5 110.2 146.9 79.6 161.6 56.6 127.2 104.5 137.0 74.9 151.0 52.8
80 149.5 135.3 158.3 110.5 171.4 72.5 140.9 129.2 149.0 105.4 161.4 68.4 131.7 122.8 139.1 100.1 150.8 64.2
85 155.0 151.3 161.5 133.4 172.2 102.3 146.5 144.5 152.3 127.7 162.3 97.6 137.5 137.5 142.5 121.7 151.8 92.7
90 161.8 161.8 165.9 152.7 174.3 128.4 153.4 153.4 156.8 146.3 164.4 123.1 144.4 144.4 147.1 139.7 154.1 117.6
75 148.2 120.1 158.5 87.5 173.1 60.6 139.2 114.4 148.8 82.9 162.7 56.9 129.6 108.5 138.5 78.0 151.7 53.1
80 153.1 140.5 161.1 114.8 173.3 75.8 144.2 134.2 151.4 109.5 163.0 71.6 134.7 127.6 141.3 104.0 152.1 67.1
85 159.2 157.2 164.8 138.4 174.7 106.3 150.4 150.3 155.3 132.5 164.5 101.5 141.0 141.0 145.3 126.3 153.7 96.4
90 166.5 166.5 169.8 158.5 177.3 133.3 157.8 157.8 160.4 151.9 167.2 127.8 148.6 148.6 150.4 145.1 156.6 122.0
75 150.5 124.1 160.0 90.5 173.7 60.8 141.2 118.2 150.0 85.7 163.0 57.1 131.3 112.1 139.4 80.6 151.7 53.1
80 156.0 145.2 163.1 118.6 174.5 78.6 146.8 138.7 153.2 113.1 163.9 74.2 137.0 131.9 142.7 107.4 152.7 69.6
85 162.7 162.7 167.5 143.0 176.5 110.0 153.6 153.6 157.6 136.9 166.0 104.9 143.9 143.9 147.3 130.5 154.9 99.6
90 170.6 170.6 173.0 163.8 179.7 137.7 161.5 161.5 163.3 157.1 169.3 132.0 152.0 152.0 153.0 150.1 158.3 126.1
RT-PRC043AC-EN 51
Performance Data
Table 27. Gross cooling capacities 12½ tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD150G3,4,W (Digit 22 = B)
Air
Flow cfm
Ent
DB
(°F)
115
Ambient Temperature
120 125
61 67 73 61
Entering Wet Bulb
67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 96.4 72.5 109.7 48.7 127.1 44.5 92.1 69.8 105.0 46.6 122.1 42.7 87.7 67.2 100.2 44.4 116.9 40.9
2500
3250
4000
4500
80 98.2 86.3 109.0 69.4 124.1 43.5 93.9 83.3 104.4 66.9 119.2 41.7 89.5 80.3 99.6 64.4 114.0 39.9
85 101.1 96.4 109.6 86.4 122.4 63.2 96.9 93.2 105.0 83.7 117.5 60.9 92.5 89.8 100.3 80.9 112.4 58.7
90 105.3 103.0 111.4 99.9 121.8 83.5 101.1 99.4 106.9 96.9 116.9 81.0 96.8 95.8 102.2 93.7 111.9 78.4
75 104.6 81.4 116.5 56.2 132.7 46.5 100.0 78.7 111.6 54.0 127.5 44.6 95.3 75.8 106.6 51.7 122.1 42.7
80 107.2 96.4 116.8 78.1 130.7 46.5 102.7 93.3 111.9 75.5 125.4 44.5 98.0 90.2 106.9 72.9 120.1 42.3
85 111.0 107.7 118.3 96.3 129.8 71.6 106.5 104.3 113.4 93.4 124.6 69.3 101.9 100.9 108.5 90.5 119.3 66.9
90 116.0 115.5 120.9 111.0 130.1 93.2 111.6 111.6 116.2 107.8 125.0 90.5 107.1 107.1 111.3 104.5 119.7 87.8
75 111.1 89.4 121.8 62.8 136.8 47.9 106.3 86.5 116.7 60.4 131.3 46.0 101.4 83.5 111.4 57.9 125.7 44.0
80 114.6 105.5 123.0 85.8 135.6 52.8 109.9 102.3 117.9 83.1 130.1 50.6 105.0 99.0 112.7 80.3 124.6 48.4
85 119.3 118.0 125.3 105.2 135.6 79.1 114.6 114.5 120.3 102.2 130.2 76.6 109.8 109.8 115.1 99.1 124.7 74.0
90 125.2 125.2 128.8 121.0 136.7 101.8 120.5 120.5 123.8 117.7 131.4 99.0 115.8 115.8 118.7 114.3 125.9 96.1
75 114.6 94.1 124.5 66.6 138.6 48.5 109.7 91.1 119.2 64.1 133.0 46.5 104.6 88.1 113.8 61.5 127.2 44.5
80 118.7 111.0 126.2 90.4 138.0 56.4 113.8 107.7 121.0 87.6 132.4 54.2 108.8 104.3 115.6 84.7 126.7 51.8
85 123.9 123.9 129.1 110.6 138.6 83.5 119.1 119.1 123.9 107.4 133.0 80.9 114.1 114.1 118.6 104.3 127.3 78.3
90 130.4 130.4 133.2 127.1 140.3 107.0 125.6 125.6 128.1 123.7 134.8 104.1 120.7 120.7 122.8 120.2 129.2 101.1
75 117.4 98.4 126.5 69.9 139.8 48.9 112.3 95.3 121.0 67.4 134.0 46.9 107.1 92.2 115.4 64.7 128.0 44.8
5000
5500
80 122.1 116.1 128.8 94.5 139.7 59.6 117.0 112.7 123.4 91.6 134.0 57.2 111.8 109.2 117.8 88.6 128.1 54.8
85 127.9 127.9 132.2 115.5 140.8 87.5 122.9 122.9 126.9 112.3 135.1 84.8 117.8 117.8 121.4 109.0 129.3 82.0
90 134.9 134.9 136.9 132.8 143.2 111.7 130.0 130.0 131.6 129.3 137.5 108.7 125.0 125.0 126.2 125.7 131.8 105.7
75 119.5 102.3 127.7 72.8 140.2 49.1 114.3 99.1 122.1 70.2 134.2 47.0 108.9 95.8 116.4 67.4 128.2 44.9
80 124.7 120.7 130.6 98.2 140.7 62.3 119.5 117.2 125.0 95.2 134.8 59.9 114.2 113.6 119.4 92.1 128.8 57.4
85 131.1 131.1 134.7 119.9 142.4 91.0 126.0 126.0 129.2 116.6 136.6 88.2 120.7 120.7 123.5 113.2 130.6 85.4
90 138.5 138.5 139.9 138.1 145.4 116.0 133.1 133.1 134.5 134.4 139.6 112.9 128.9 128.9 128.9 128.9 133.6 109.8
75 120.9 105.7 128.3 75.3 139.9 49.0 115.5 102.4 122.5 72.5 133.8 46.8 110.0 99.0 116.7 69.7 127.6 44.7
6000
80 126.7 124.9 131.7 101.4 141.0 64.6 121.4 121.3 126.0 98.3 135.0 62.1 115.9 115.9 120.2 95.2 128.8 59.5
85 133.7 133.7 136.4 123.9 143.3 94.1 128.4 128.4 130.7 120.5 137.3 91.2 123.0 123.0 125.0 117.1 131.2 88.2
90 142.2 142.2 142.2 142.2 146.8 119.9 136.6 136.6 136.6 136.6 140.9 116.7 130.9 130.9 130.9 130.9 134.8 113.4
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
(a)For 2500 and 3250 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.
- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
52 RT-PRC043AC-EN
Performance Data
Table 28. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (stage 1)
Air
Flow cfm
Ent
DB
(°F)
Ambient Temperature
85 95
Entering Wet Bulb
61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2400
3000
3600
4200
4800
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
54.8 51.5 59.2 40.6 65.3 18.6 51.8 49.1 56.0 38.5 60.9 17.0
57.4 56.8 60.0 50.8 65.5 37.2 54.3 54.2 56.8 48.5 62.1 35.2
60.3 60.3 61.9 57.4 65.5 48.8 57.1 57.1 58.6 54.8 62.1 46.6
63.3 63.3 64.3 61.8 66.8 56.5 60.1 60.1 61.0 59.1 63.3 54.1
56.6 54.6 60.5 44.0 66.3 22.4 53.4 52.0 57.1 41.7 61.6 20.5
59.5 59.5 61.7 54.3 66.7 40.9 56.2 56.2 58.2 51.8 63.1 38.7
62.6 62.6 63.8 60.9 67.1 52.6 59.3 59.3 60.4 58.2 63.4 50.2
65.7 65.7 66.4 65.5 68.6 60.4 62.3 62.3 62.9 62.6 64.9 57.7
58.1 57.2 61.5 46.8 66.9 25.5 54.7 54.3 57.9 44.3 62.0 23.4
61.2 61.2 63.0 57.2 67.5 44.0 57.8 57.8 59.4 54.4 63.8 41.6
64.5 64.5 65.4 63.9 68.2 55.8 61.0 61.0 61.8 60.9 64.4 53.1
67.9 67.9 68.3 68.3 70.0 63.7 64.3 64.3 64.6 64.6 66.2 60.7
59.3 59.1 62.2 49.1 67.0 28.1 55.7 55.7 58.4 46.3 62.1 25.7
62.6 62.6 64.0 59.5 68.1 46.6 59.0 59.0 60.2 56.4 64.1 43.9
66.2 66.2 66.7 66.3 69.1 58.4 62.5 62.5 62.9 62.9 65.1 55.5
69.7 69.7 69.7 69.7 71.2 66.3 64.6 64.6 65.9 65.9 67.2 63.2
60.1 60.1 62.5 50.7 67.1 30.0 56.4 56.4 58.6 47.7 62.7 27.4
63.7 63.7 64.7 61.1 68.3 48.5 59.9 59.9 60.7 57.9 64.1 45.6
67.5 67.5 67.6 67.6 69.6 60.4 63.6 63.6 63.6 63.6 65.5 57.3
69.8 69.8 70.9 70.9 72.0 68.5 65.9 65.9 66.8 66.8 67.8 65.1
5250
75
80
85
90
60.5 60.5 62.5 51.6 67.2 31.1 56.6 56.6 58.8 48.4 63.0 28.4
64.3 64.3 65.0 62.0 68.5 49.6 60.4 60.4 60.9 58.6 64.1 46.5
67.8 67.8 68.1 68.1 69.8 61.6 63.8 63.8 64.0 64.0 65.5 58.2
70.7 70.7 71.5 71.5 72.4 69.6 66.7 66.7 67.4 67.4 68.0 66.1
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
RT-PRC043AC-EN 53
Performance Data
Table 29. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (stage 2)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2400
3000
3600
4200
4800
75 102.0 81.9 111.7 65.6 123.0 36.1 96.8 78.4 105.8 62.6 116.0 33.6
80 104.0 90.7 113.0 79.9 123.8 59.7 98.9 86.9 107.3 76.5 117.7 56.7
85 107.1 97.4 114.3 89.8 124.6 75.5 102.0 93.4 108.8 86.1 118.5 72.1
90 111.0 102.8 117.0 97.1 125.4 86.5 105.8 98.6 111.5 93.2 119.3 82.9
75 107.2 88.8 117.9 71.7 126.6 41.1 101.7 85.0 111.7 68.3 120.0 38.3
80 109.8 98.2 118.0 86.6 128.0 65.6 104.4 94.1 112.0 82.9 121.5 62.3
85 113.4 105.4 120.0 97.2 129.4 82.2 108.0 101.1 114.1 93.2 123.0 78.5
90 117.8 111.3 123.2 105.1 130.8 93.9 112.3 106.7 117.3 100.8 124.5 89.9
75 111.5 94.8 121.2 76.7 133.1 45.2 105.7 90.6 114.7 73.0 125.9 42.1
80 114.7 104.8 122.0 92.5 133.2 70.6 109.0 100.4 115.7 88.4 126.2 67.0
85 118.9 112.5 124.7 103.7 133.3 87.9 113.2 107.9 118.5 99.3 126.5 84.0
90 123.7 118.9 128.4 112.1 135.3 100.3 117.8 114.0 122.2 107.5 128.7 96.0
75 114.9 99.8 123.6 80.9 134.5 48.4 108.8 95.3 116.8 76.9 127.0 44.9
80 118.8 110.4 125.2 97.4 135.4 74.7 112.7 105.7 118.6 93.0 128.1 70.7
85 123.5 118.7 128.5 109.2 136.3 92.8 117.4 113.7 122.0 104.6 129.2 88.5
90 128.6 125.5 132.8 118.2 139.0 105.7 122.5 120.3 126.3 113.2 132.0 101.1
75 117.4 103.9 125.1 84.1 135.0 50.6 111.0 99.1 117.9 79.7 128.0 46.8
80 121.9 115.2 127.5 101.4 136.7 77.8 115.6 110.1 120.6 96.7 129.1 73.5
85 127.1 123.9 131.5 113.9 138.4 96.7 120.8 118.6 124.6 108.8 131.0 92.0
90 132.7 131.1 136.3 123.3 141.8 110.3 126.3 125.6 129.4 118.1 134.5 105.3
5250
75 118.7 106.3 125.6 85.9 135.5 51.7 112.0 101.3 118.2 81.3 129.0 47.6
80 123.7 118.1 128.7 103.7 137.1 79.5 117.1 112.7 121.5 98.8 129.3 75.0
85 129.3 127.3 133.1 116.7 139.4 99.0 122.7 121.7 126.0 111.4 131.8 94.1
90 135.2 134.8 138.3 126.6 143.3 113.0 128.5 128.5 131.2 121.1 135.7 107.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 2400, 3000, 3600, and 4200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
54 RT-PRC043AC-EN
Performance Data
Table 30. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (full load)
Air
Flow cfm (a)
3000
3600
4200
4800
5400
6000
6600
7200
Ent
DB
(°F)
85
Ambient Temperature
95 105
Entering Wet Bulb
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 149.8 116.6 163.9 91.6 180.9 48.7 142.5 112.1 155.7 88.3 172.0 46.6 134.3 106.9 146.7 84.2 162.1 43.8
80 153.0 130.6 165.9 113.6 181.8 83.7 145.7 125.4 157.8 109.4 172.9 80.6 137.5 119.5 148.7 104.5 163.1 76.8
85 157.9 141.6 167.9 129.4 182.8 108.0 150.5 135.8 159.8 124.5 173.8 104.0 142.2 129.4 150.8 118.9 164.0 99.3
90 163.8 150.7 171.9 141.5 183.7 125.5 156.2 144.5 163.7 136.0 174.7 120.8 147.7 137.7 154.6 129.9 164.9 115.5
75 156.6 125.2 169.8 99.5 186.1 55.7 148.9 120.2 161.3 95.7 176.7 53.2 140.3 114.6 151.8 91.2 166.5 50.1
80 160.4 139.8 172.4 122.2 187.5 91.6 152.7 134.2 163.9 117.5 178.2 88.1 144.1 127.9 154.4 112.2 168.0 83.9
85 165.7 151.3 175.0 138.6 189.0 116.6 157.9 145.1 166.5 133.2 179.7 112.2 149.2 138.3 157.0 127.2 169.4 107.1
90 172.0 160.9 179.5 151.2 190.5 134.7 163.9 154.2 170.8 145.3 181.2 129.6 155.0 147.0 161.3 138.7 170.9 123.8
75 162.6 133.0 177.9 106.6 190.4 62.0 154.5 127.6 168.8 102.4 180.7 59.1 145.5 121.6 158.9 97.5 170.0 55.5
80 166.9 148.2 178.1 129.9 192.5 98.7 158.8 142.1 169.2 124.9 182.7 94.8 149.8 135.4 159.4 119.1 172.1 90.1
85 172.7 160.2 181.3 147.0 194.5 124.4 164.5 153.6 172.3 141.2 184.8 119.5 155.4 146.3 162.5 134.8 174.1 114.1
90 179.3 170.2 186.2 160.1 196.6 143.1 170.9 163.1 177.2 153.8 186.8 137.6 161.6 155.5 167.2 146.8 176.2 131.4
75 167.9 139.9 182.2 112.8 194.0 67.4 159.3 134.2 172.7 108.2 183.8 64.1 149.9 127.7 162.3 102.9 172.8 60.2
80 172.7 155.7 183.1 136.9 196.6 105.0 164.2 149.3 173.7 131.4 186.5 100.6 154.8 142.2 163.5 125.3 175.4 95.6
85 179.0 168.2 186.8 154.5 199.2 131.4 170.3 161.2 177.5 148.4 189.1 126.1 160.8 153.6 167.2 141.5 178.0 120.2
90 185.9 178.7 192.2 168.2 201.9 150.7 177.1 171.3 182.7 161.4 191.7 144.7 167.3 163.2 172.4 154.0 180.7 138.2
75 172.3 146.1 185.6 118.3 202.7 72.1 163.4 139.9 175.7 113.3 191.8 68.4 153.6 133.1 164.9 107.6 180.1 64.0
80 177.8 162.5 187.3 143.1 202.9 110.5 168.8 155.6 177.5 137.2 192.2 105.7 159.0 148.1 166.9 130.6 180.6 100.3
85 184.4 175.5 191.6 161.3 203.2 137.6 175.4 168.1 181.8 154.7 192.6 131.9 165.5 160.0 171.2 147.5 181.2 125.6
90 191.7 186.4 197.4 175.5 206.4 157.5 182.5 178.6 187.5 168.3 195.8 151.1 172.3 170.1 176.8 160.5 184.4 144.1
75 176.0 151.5 188.3 123.0 204.4 76.0 166.7 144.9 178.0 117.5 193.1 71.9 156.5 137.6 166.8 111.4 181.0 67.1
80 182.0 168.5 190.7 148.5 205.4 115.2 172.7 161.2 180.5 142.2 194.3 110.0 162.5 153.3 169.5 135.2 182.3 104.1
85 189.1 182.0 195.5 167.3 206.3 143.0 179.7 174.2 185.4 160.3 195.4 136.9 169.3 165.7 174.3 152.6 183.5 130.2
90 196.8 193.3 201.8 181.9 210.1 163.5 187.1 185.1 191.5 174.4 199.1 156.7 176.6 176.2 180.4 166.2 187.3 149.3
75 178.9 156.1 190.2 126.9 205.4 79.1 169.2 149.1 179.5 121.0 193.7 74.5 158.6 141.4 167.9 114.5 181.2 69.3
80 185.5 173.7 193.3 153.1 207.0 119.1 175.7 166.0 182.7 146.3 195.5 113.5 165.1 157.6 171.3 139.0 183.1 107.2
85 193.0 187.7 198.7 172.5 208.7 147.6 183.2 179.5 188.2 165.1 197.3 141.1 172.4 170.6 176.7 157.0 185.1 134.0
90 201.0 199.5 205.5 187.6 213.0 168.7 190.9 190.8 194.8 179.7 201.7 161.5 180.0 180.0 183.2 171.1 189.4 153.7
75 181.0 159.9 191.4 130.0 205.6 81.4 170.9 152.5 180.3 123.7 194.3 76.4 159.9 144.4 168.3 116.8 181.3 70.8
80 188.2 178.1 195.2 156.8 207.9 122.2 178.0 170.0 184.2 149.7 196.0 116.2 167.0 161.2 172.3 141.9 183.2 109.5
85 196.1 192.6 201.1 176.9 210.3 151.4 185.9 184.0 190.2 169.0 198.5 144.5 174.7 174.6 178.3 160.6 185.9 137.0
90 204.5 204.5 208.3 192.5 215.2 173.1 194.0 194.0 197.2 184.2 203.4 165.5 182.7 182.7 185.3 175.1 190.8 157.3
RT-PRC043AC-EN 55
Performance Data
Table 30. Gross cooling capacities 15 tons three phase high efficiency T/YH*180G3,4,W (full load)
Air
Flow cfm
3000
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 125.3 101.0 136.8 79.5 151.4 40.4 120.4 97.8 131.5 76.9 145.7 38.5 115.3 94.5 126.0 74.1 139.8 36.4
80 128.5 113.0 138.8 98.9 152.4 72.3 123.6 109.5 133.6 95.9 146.7 69.9 118.5 105.8 128.1 92.7 140.8 67.2
85 133.0 122.3 140.9 112.6 153.3 94.0 128.1 118.5 135.6 109.3 147.6 91.1 122.9 114.6 130.1 105.7 141.7 88.1
90 138.3 130.2 144.6 123.1 154.2 109.5 133.3 126.2 139.2 119.4 148.5 106.2 128.0 122.0 133.7 115.6 142.6 102.8
75 130.9 108.3 141.5 86.1 155.4 46.3 125.8 105.0 138.6 83.3 149.5 44.1 120.5 101.4 132.9 80.4 143.4 41.8
3600
4200
4800
5400
6000
80 134.6 120.9 144.1 106.2 156.8 79.0 129.5 117.2 138.7 103.0 151.0 76.3 124.3 113.3 133.0 99.6 144.9 73.5
85 139.6 130.8 146.7 120.6 158.3 101.4 134.5 126.8 141.3 117.0 152.5 98.3 129.1 122.6 135.6 113.3 146.4 95.0
90 145.2 139.0 150.9 131.5 159.8 117.4 140.0 134.8 145.3 127.7 153.9 113.9 134.5 130.5 139.6 123.6 147.9 110.3
75 135.7 114.9 148.0 92.0 158.5 51.3 130.4 111.3 142.2 88.9 152.4 48.9 124.9 107.5 136.3 85.8 146.1 46.4
80 140.0 128.0 148.7 112.7 160.6 84.8 134.7 124.1 143.0 109.3 154.5 82.0 129.2 120.0 137.1 105.7 148.2 78.9
85 145.4 138.4 151.8 127.7 162.6 107.9 140.1 134.2 146.1 123.9 156.5 104.6 134.5 129.8 140.2 120.0 150.2 101.1
90 151.4 147.1 156.4 139.2 164.7 124.6 145.9 142.7 150.7 135.1 158.6 120.9 140.3 138.1 144.7 130.9 152.3 117.1
75 139.7 120.6 151.0 97.0 160.9 55.5 134.2 116.8 145.1 93.8 159.7 53.0 128.5 112.9 138.9 90.4 153.1 50.2
80 144.6 134.4 152.4 118.5 163.5 89.9 139.1 130.2 146.5 114.8 159.8 86.8 133.4 125.9 140.4 111.0 153.2 83.5
85 150.4 145.3 156.1 134.0 166.1 113.7 144.9 140.8 150.2 130.0 159.8 110.2 139.1 136.3 144.1 125.9 153.3 106.5
90 156.7 154.4 161.2 146.0 168.7 130.9 151.1 149.8 155.2 141.7 162.5 127.0 145.2 145.0 149.1 137.3 156.0 123.0
75 142.9 125.6 153.3 101.2 167.5 59.0 137.3 121.6 147.1 97.8 160.8 56.2 131.4 117.4 140.7 94.2 154.0 53.2
80 148.4 139.9 155.4 123.4 168.2 94.2 142.7 135.6 149.3 119.6 161.6 90.9 136.8 131.1 143.0 115.6 154.8 87.4
85 154.7 151.3 159.7 139.6 168.8 118.6 148.9 146.7 153.6 135.4 162.4 114.9 143.0 141.9 147.3 131.0 155.6 111.0
90 161.3 160.9 165.1 152.1 172.0 136.5 155.5 155.5 159.0 147.6 165.6 132.4 149.4 149.4 152.6 142.9 158.8 128.2
75 145.4 129.7 154.8 104.7 168.0 61.6 139.5 125.5 148.4 101.0 161.2 58.6 133.4 121.1 141.8 97.3 154.1 55.5
80 151.4 144.7 157.6 127.6 169.4 97.6 145.5 140.1 151.3 123.5 162.6 94.1 139.4 135.4 144.8 119.3 155.6 90.5
85 158.1 156.6 162.4 144.3 170.8 122.8 152.2 151.7 156.1 139.9 164.1 118.9 146.0 146.0 149.6 135.4 157.2 114.8
90 165.1 165.1 168.4 157.3 174.6 141.2 159.1 159.1 162.0 152.6 167.9 137.0 152.8 152.8 155.4 147.8 161.0 132.5
75 147.1 133.1 155.5 107.3 168.5 63.4 141.0 128.7 148.9 103.5 161.5 60.3 134.7 124.1 142.1 99.5 154.2 56.9
6600
80 153.6 148.6 159.0 130.9 169.9 100.3 147.6 143.9 152.5 126.7 162.9 96.6 141.3 138.9 145.8 122.2 155.7 92.7
85 160.8 160.8 164.4 148.3 172.0 126.2 154.7 154.7 157.9 143.7 165.1 122.0 148.3 148.3 151.2 138.9 158.0 117.7
90 168.2 168.2 170.8 161.8 176.3 145.2 161.9 161.9 164.2 156.9 169.4 140.7 155.5 155.5 157.5 151.8 162.3 136.1
75 148.0 135.6 156.1 109.2 169.1 64.5 141.7 131.0 149.4 105.1 161.8 61.1 135.2 126.2 142.4 100.9 154.4 57.5
7200
80 155.1 151.8 159.6 133.5 170.3 102.2 148.8 146.8 152.9 129.0 163.2 98.3 142.3 141.7 146.0 124.4 155.8 94.2
85 162.7 162.7 165.6 151.4 172.4 128.8 156.4 156.4 158.9 146.6 165.3 124.4 149.8 149.8 152.0 141.6 158.7 119.9
90 170.4 170.4 172.4 165.4 177.3 148.4 164.0 164.0 165.7 160.4 170.2 143.7 157.3 157.3 158.7 155.1 162.8 138.8
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 3000, 3600, and 4200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.
- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
56 RT-PRC043AC-EN
Performance Data
Table 31. Gross cooling capacities 15 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD180G3,4,W (Digit 22 = B)
Air
Flow cfm (a)
3000
3900
4800
5400
6000
6600
7200
85
61
Ambient Temperature
95
Entering Wet Bulb
67 73
105
Ent
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 149.8 108.9 167.7 71.3 190.8 66.8 141.5 104.7 158.6 68.7 180.8 63.3 132.6 99.7 148.8 65.2 170.1 59.5
80 151.5 129.2 166.7 101.1 187.0 65.5 143.4 124.3 157.7 97.7 177.1 62.0 134.7 118.5 148.1 93.4 166.7 58.3
85 154.6 144.8 167.0 126.0 184.5 89.1 146.7 139.2 158.2 121.9 174.9 86.5 138.1 132.6 148.8 116.9 164.6 83.0
90 159.1 155.7 168.7 146.3 183.5 118.7 151.3 149.2 160.1 141.4 174.0 115.3 143.0 141.9 150.9 135.6 163.9 111.1
75 160.4 120.9 176.9 82.0 198.6 69.5 151.6 116.3 167.3 79.0 188.1 65.8 142.3 110.9 157.1 75.1 177.0 61.9
80 163.1 142.6 176.9 113.1 195.8 68.5 154.6 137.2 167.5 109.3 185.5 64.9 145.4 131.0 157.4 104.6 174.5 61.1
85 167.2 159.5 178.2 139.4 194.4 101.1 158.8 153.4 169.0 134.8 184.2 98.1 149.8 146.4 159.1 129.4 173.5 94.2
90 172.7 171.6 180.9 160.9 194.3 132.0 164.5 164.5 171.9 155.6 184.3 128.2 155.7 155.7 162.2 149.4 173.8 123.5
75 169.3 131.7 184.4 91.5 204.6 71.6 160.0 126.7 174.3 88.0 193.7 67.8 150.2 120.8 163.6 83.7 182.1 63.7
80 173.0 154.7 185.4 123.8 202.8 74.8 164.0 148.9 175.5 119.6 192.1 72.1 154.3 142.3 164.9 114.5 180.7 68.6
85 178.1 172.9 187.7 151.4 202.4 111.8 169.3 166.4 178.0 146.5 191.8 108.4 159.8 159.0 167.7 140.6 180.6 104.0
90 184.6 184.6 191.4 174.3 203.4 144.0 176.0 176.0 181.9 168.5 192.9 139.8 166.7 166.7 171.7 161.9 181.9 134.7
75 174.2 138.2 188.4 97.1 207.7 72.7 164.7 132.9 178.0 93.4 196.4 68.7 154.6 126.8 167.0 88.8 184.5 64.6
80 178.6 162.0 190.0 130.3 206.6 80.4 169.3 156.0 179.8 125.8 195.5 77.4 159.3 149.1 169.0 120.4 183.8 73.6
85 184.4 181.1 193.1 158.8 206.8 118.2 175.3 174.3 183.0 153.5 195.9 114.5 165.5 165.5 172.4 147.4 184.4 109.9
90 191.6 191.6 197.4 182.5 208.4 151.4 182.6 182.6 187.6 176.5 197.7 146.9 173.0 173.0 177.2 169.5 186.4 141.5
75 178.4 144.1 191.6 102.1 210.0 73.5 168.5 138.6 180.9 98.1 198.4 69.4 158.1 132.1 169.6 93.2 186.2 65.2
80 183.5 168.8 193.9 136.2 209.5 85.4 173.8 162.5 183.4 131.4 198.1 82.2 163.6 155.3 172.3 125.8 186.1 78.1
85 189.9 188.8 197.6 165.5 210.4 124.1 180.5 180.5 187.3 160.0 199.2 120.1 170.4 170.4 176.4 153.6 187.4 115.3
90 197.8 197.8 202.7 190.1 212.7 158.1 188.5 188.5 192.6 183.8 201.7 153.4 178.6 178.6 181.8 176.6 190.1 147.7
75 181.8 149.5 194.1 106.6 211.5 74.0 171.6 143.7 183.0 102.3 199.6 69.9 160.9 137.0 171.4 97.1 187.1 65.5
80 187.5 175.0 197.1 141.5 211.7 89.9 177.6 168.5 186.2 136.5 200.0 86.4 167.0 161.0 174.8 130.6 187.7 82.0
85 194.7 194.7 201.4 171.8 213.3 129.5 184.9 184.9 190.8 166.0 201.8 125.2 174.5 174.5 179.5 159.2 189.7 120.0
90 203.2 203.2 207.2 197.2 216.3 164.3 193.6 193.6 196.7 190.6 204.9 159.3 183.4 183.4 185.6 183.2 193.0 153.3
75 184.4 154.3 195.7 110.5 212.2 74.3 173.9 148.2 184.4 105.9 200.0 70.0 162.9 141.2 172.5 100.5 187.2 65.5
80 190.8 180.7 199.4 146.3 213.1 93.8 180.6 173.9 188.3 141.0 201.1 90.0 169.7 166.1 176.5 134.8 188.5 85.3
85 198.7 198.7 204.5 177.4 215.4 134.2 188.6 188.6 193.5 171.3 203.6 129.7 177.9 177.9 181.9 164.3 191.1 124.2
90 207.8 207.8 210.9 203.8 219.0 170.0 198.0 198.0 200.1 196.9 207.4 164.6 188.7 188.7 188.7 188.7 195.1 158.4
RT-PRC043AC-EN 57
Performance Data
Table 31. Gross cooling capacities 15 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD180G3,4,W (Digit 22 = B)
Air
Flow
Ent
DB 61
115
67 73 61
Ambient Temperature
120
Entering Wet Bulb
67 73 61
125
67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
3000
3900
4800
5400
75 123.1 93.8 138.4 60.9 158.9 55.6 118.1 90.5 133.0 58.3 153.0 53.5 112.9 87.0 127.4 55.6 147.0 51.4
80 125.3 111.8 137.9 88.3 155.6 54.5 120.4 108.1 132.6 85.4 149.8 52.4 115.4 104.2 127.1 82.2 143.9 50.4
85 129.0 125.1 138.8 111.0 153.7 78.6 124.2 121.1 133.5 107.7 148.0 76.1 119.2 116.8 128.1 104.1 142.2 73.3
90 134.0 133.7 141.0 128.9 153.1 105.9 129.3 129.2 135.9 125.2 147.6 103.0 124.4 124.4 130.6 121.3 141.8 99.9
75 132.3 104.6 146.2 70.3 165.3 57.8 127.1 101.1 140.6 67.6 159.2 55.7 121.7 97.3 134.7 64.6 152.9 53.5
80 135.6 123.9 146.7 99.0 163.0 57.1 130.5 120.0 141.2 95.9 157.0 54.9 125.2 115.9 135.4 92.6 150.8 52.8
85 140.2 138.5 148.6 123.0 162.1 89.3 135.2 134.2 143.1 119.5 156.2 86.6 130.0 129.7 137.5 115.8 150.1 83.6
90 146.3 146.3 151.9 142.3 162.6 118.0 141.3 141.3 146.5 138.4 156.8 114.8 136.2 136.2 140.9 134.2 150.8 111.5
75 139.8 114.1 152.3 78.5 169.9 59.5 134.3 110.4 146.4 75.5 163.6 57.3 128.7 106.4 140.4 72.4 157.1 55.0
80 144.1 134.7 153.8 108.5 168.7 64.1 138.7 130.6 148.0 105.2 162.4 61.6 133.2 126.3 142.1 101.6 156.0 58.8
85 149.8 149.8 156.7 133.8 168.8 98.8 144.5 144.5 151.0 130.1 162.6 95.9 139.1 139.1 145.1 126.2 156.4 92.7
90 156.8 156.8 161.0 154.4 170.3 128.7 151.6 151.6 155.4 150.3 164.2 125.4 146.3 146.3 149.6 145.9 158.0 121.8
75 143.8 119.7 155.4 83.3 172.0 60.2 138.2 115.9 149.3 80.2 165.6 57.9 132.4 111.8 143.1 76.9 158.9 55.6
80 148.8 141.3 157.6 114.2 171.5 68.9 143.3 137.0 151.6 110.7 165.1 66.2 137.6 132.6 145.5 107.0 158.5 63.3
85 155.1 155.1 161.1 140.3 172.3 104.4 149.7 149.7 155.3 136.5 166.0 101.3 144.1 144.1 149.3 132.4 159.5 98.0
90 162.8 162.8 166.1 161.7 174.4 135.2 157.5 157.5 160.3 157.5 168.2 131.7 152.9 152.0 154.4 153.0 161.9 128.0
6000
6600
75 147.1 124.8 157.7 87.5 173.4 60.7 141.3 120.8 151.5 84.2 166.8 58.4 135.4 116.6 145.1 80.8 160.0 56.0
80 152.7 147.2 160.5 119.2 173.5 73.1 147.0 142.8 154.4 115.6 167.0 70.2 141.2 138.2 148.2 111.8 160.3 67.2
85 159.7 159.7 164.8 146.3 175.0 109.5 154.2 154.2 158.8 142.3 168.5 106.2 148.4 148.4 152.6 138.0 161.9 102.8
90 168.7 168.1 170.4 168.5 177.8 141.1 162.8 162.8 164.5 164.2 171.5 137.5 158.4 158.4 158.4 158.4 165.0 133.7
75 149.5 129.4 159.2 91.1 174.0 60.9 143.6 125.2 152.8 87.7 167.2 58.5 137.6 120.9 146.3 84.1 160.3 56.1
80 155.9 152.6 162.7 123.7 174.8 76.7 150.0 148.1 156.5 120.0 168.1 73.7 144.1 143.4 150.1 116.0 161.2 70.5
85 163.6 163.6 167.7 151.6 176.9 114.0 157.8 157.8 161.5 147.5 170.3 110.6 151.9 151.9 155.2 143.1 163.6 107.0
90 174.0 174.0 174.0 174.0 180.4 146.5 167.9 167.9 167.9 167.9 173.9 142.7 161.7 161.7 161.7 161.7 167.3 138.8
7200
75 151.2 133.3 159.9 94.2 173.8 60.8 145.2 129.0 153.4 90.7 166.9 58.4 138.9 124.6 146.8 86.9 159.8 55.9
80 158.2 157.5 164.2 127.7 175.2 79.7 152.3 152.3 157.8 123.8 168.4 76.6 146.1 146.1 151.2 119.7 161.4 73.3
85 166.6 166.6 169.8 156.5 178.1 117.9 160.7 160.7 163.5 152.2 171.3 114.4 154.7 154.7 157.0 147.7 164.4 110.7
90 176.7 176.7 176.7 176.7 182.3 151.3 170.5 170.5 170.5 170.5 175.6 147.4 164.1 164.1 164.1 164.1 168.8 143.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
(a)For 3000 and 3900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Dehumidification (Hot Gas Reheat) with Frostat and Crankcage heaters are required on applications below 320 cfm/ton.
- Multi-speed or single zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
58 RT-PRC043AC-EN
Performance Data
Table 32. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (stage 1)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2800
3500
4200
4900
5600
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
63.9 60.0 68.3 47.4 74.6 22.7 59.8 56.7 64.0 44.6 70.2 20.3
67.5 66.8 70.0 59.7 75.7 44.0 63.4 63.4 65.8 56.6 71.3 41.4
71.6 71.6 73.0 68.1 76.7 58.1 67.5 67.5 68.8 64.8 72.4 55.2
75.8 75.8 76.7 74.3 79.2 67.9 71.7 71.7 72.5 70.9 74.8 64.8
65.8 63.2 69.7 50.8 75.5 26.3 61.5 59.7 65.2 47.7 70.8 23.7
69.8 69.8 71.9 63.3 77.0 47.8 65.5 65.5 67.4 59.9 72.3 44.9
74.1 74.1 75.2 71.9 78.4 62.1 69.8 69.8 70.8 68.3 73.8 58.9
78.6 78.6 79.1 78.4 81.2 72.1 74.2 74.2 74.7 74.7 76.7 68.7
67.3 65.7 70.6 53.5 76.0 29.2 62.8 61.9 65.9 50.1 71.1 26.3
71.6 71.6 73.2 66.2 77.8 50.9 67.0 67.0 68.5 62.5 73.0 47.7
76.2 76.2 76.9 75.0 79.7 65.4 71.6 71.6 72.2 71.2 74.9 61.9
80.9 80.9 81.1 81.1 82.8 75.6 76.3 76.3 76.4 76.4 78.0 71.9
68.4 67.6 71.1 55.5 76.8 31.5 63.6 63.5 66.2 51.9 71.5 28.2
72.9 72.9 74.1 68.4 77.9 53.3 68.2 68.2 69.2 64.5 73.1 49.7
77.8 77.8 78.1 77.4 80.5 67.9 73.0 73.0 73.2 73.2 75.5 64.1
81.0 81.0 82.6 82.6 84.0 78.3 76.5 75.0 77.7 77.7 79.0 74.4
68.9 68.7 71.2 56.9 77.0 33.0 63.7 63.7 67.0 52.9 72.2 29.5
73.9 73.9 74.6 69.9 78.2 55.0 68.9 68.9 69.5 65.7 73.9 51.1
78.0 78.0 78.9 78.9 80.9 69.8 73.2 71.0 73.8 73.8 75.6 65.7
82.1 82.1 83.7 83.7 84.7 80.4 77.0 77.0 78.6 78.6 79.4 76.1
6125
75
80
85
90
69.1 69.1 71.6 57.4 77.4 33.7 63.9 63.9 68.0 53.2 73.0 30.0
74.3 74.3 74.7 70.5 78.4 55.8 69.1 69.1 71.0 66.1 74.4 51.7
78.6 78.6 79.3 79.3 81.8 70.7 73.5 73.5 74.0 74.0 77.0 66.4
83.5 83.5 84.2 84.2 84.9 81.5 77.2 77.2 78.9 78.9 79.5 77.0
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 2800, 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC043AC-EN 59
Performance Data
Table 33. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (stage 2)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
2800
3500
4200
4900
5600
75 123.5 100.2 134.4 80.1 147.8 44.0 117.3 96.3 127.4 77.0 139.9 41.8
80 126.3 111.0 136.4 97.8 148.9 73.2 120.1 106.7 129.4 94.1 141.1 70.2
85 130.4 119.4 138.3 110.3 150.0 92.9 124.2 114.7 131.3 106.1 142.3 89.4
90 135.4 126.3 141.8 119.6 151.1 106.9 129.0 121.3 134.8 115.0 143.4 102.8
75 129.9 108.5 142.2 87.5 152.2 50.4 123.2 104.2 134.6 84.0 143.9 47.6
80 133.3 120.2 142.4 106.1 154.0 80.6 126.7 115.4 135.0 102.0 145.8 77.2
85 138.0 129.2 145.1 119.4 155.8 101.2 131.3 124.0 137.7 114.7 147.7 97.2
90 143.5 136.7 149.2 129.3 157.7 115.9 136.7 131.2 141.7 124.3 149.6 111.4
75 135.1 115.8 146.3 93.8 160.5 55.6 128.0 111.0 138.3 89.8 151.6 52.4
80 139.3 128.2 147.4 113.3 160.5 86.9 132.2 122.9 139.6 108.7 151.8 83.0
85 144.5 137.8 150.7 127.3 160.6 108.4 137.4 132.2 142.9 122.2 152.0 103.9
90 150.5 145.9 155.4 137.9 163.1 123.8 143.2 139.9 147.6 132.5 154.6 118.9
75 139.2 121.9 149.3 99.0 162.4 59.6 131.7 116.7 140.9 94.5 153.0 56.0
80 144.1 135.1 151.3 119.4 163.3 92.0 136.6 129.4 143.0 114.3 154.1 87.7
85 149.9 145.4 155.3 134.1 164.2 114.4 142.4 139.3 147.1 128.6 155.2 109.5
90 156.3 153.9 160.6 145.4 167.5 130.6 148.6 147.5 152.3 139.5 158.5 125.3
75 142.3 126.9 151.2 103.0 163.2 62.6 134.3 121.2 142.3 98.1 153.4 58.5
80 147.8 140.8 154.1 124.3 165.0 96.0 139.9 134.7 145.3 118.8 155.4 91.2
85 154.2 151.7 158.8 139.8 166.8 119.3 146.3 145.2 150.1 133.8 157.4 114.0
90 161.1 160.8 164.6 151.7 170.7 136.3 152.9 152.9 155.9 145.4 161.4 130.5
6125
75 143.8 129.9 151.9 105.3 164.1 64.0 135.5 123.9 142.7 100.0 154.0 59.6
80 149.9 144.4 155.4 127.3 165.5 98.3 141.7 137.9 146.4 121.4 155.6 93.2
85 156.7 155.8 160.7 143.3 168.0 122.3 148.4 148.4 151.7 137.0 158.2 116.6
90 163.9 163.9 167.0 155.7 172.5 139.8 155.4 155.4 157.9 149.0 162.8 133.6
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 2800, 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
60 RT-PRC043AC-EN
Performance Data
Table 34. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (full load)
Air
Flow cfm (a)
3500
4200
4900
5600
6300
7000
7700
8400
85
Ambient Temperature
95 105
Ent Entering Wet Bulb
DB 61 67 73 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 178.2 140.1 193.8 111.1 207.3 60.7 169.5 134.8 186.6 107.2 204.8 58.4 159.9 128.9 174.5 102.7 183.6 55.5
80 182.3 156.6 197.4 136.9 211.8 102.1 173.6 150.4 187.6 132.0 205.4 98.5 164.0 143.7 177.0 126.4 187.8 94.3
85 188.5 169.5 200.2 155.6 217.6 130.7 179.6 162.7 190.4 149.7 206.7 126.0 169.9 155.2 179.7 143.3 195.0 120.8
90 195.9 180.3 205.3 169.8 219.0 151.3 186.7 172.9 195.3 163.3 208.1 145.8 176.7 164.9 184.5 156.2 196.4 139.7
75 186.2 150.2 194.6 120.2 212.8 68.8 177.0 144.4 193.2 115.8 211.6 66.0 166.9 138.0 183.6 110.8 196.3 62.6
80 191.0 167.4 205.2 147.0 223.4 111.3 181.8 160.8 194.9 141.5 212.2 107.2 171.7 153.5 183.7 135.5 198.7 102.5
85 197.7 181.0 208.6 166.4 225.1 140.8 188.3 173.7 198.3 160.1 213.7 135.6 178.1 165.7 187.1 153.2 201.5 129.9
90 205.5 192.4 214.2 181.3 227.2 162.2 195.9 184.5 203.8 174.3 215.8 156.2 185.3 176.0 192.4 166.7 203.5 149.6
75 193.4 159.4 211.5 128.5 229.7 76.0 183.6 153.0 200.5 123.6 217.5 72.7 173.0 146.1 188.6 118.0 204.6 68.8
80 198.8 177.4 212.0 156.2 230.6 119.6 189.1 170.2 201.2 150.2 218.2 114.9 178.5 162.4 189.5 143.6 205.4 109.7
85 206.0 191.6 216.1 176.3 231.7 150.0 196.1 183.7 205.2 169.5 219.8 144.3 185.4 175.3 193.6 162.1 207.0 138.0
90 214.3 203.5 222.3 191.9 234.4 172.2 204.1 195.1 211.3 184.4 222.5 165.6 193.0 186.1 199.4 176.3 209.8 158.5
75 199.6 167.6 216.7 135.8 236.2 82.3 189.4 160.8 205.1 130.4 223.6 78.5 178.3 153.3 192.7 124.3 206.4 74.0
80 205.7 186.4 218.0 164.4 237.1 126.9 195.5 178.7 206.6 157.9 224.2 121.8 184.4 170.4 194.4 150.8 211.7 116.0
85 213.5 201.3 222.7 185.3 237.4 158.2 203.1 192.9 211.4 178.0 225.0 152.0 191.8 183.9 199.1 170.0 211.7 145.2
90 222.1 213.8 229.4 201.6 240.8 181.2 211.4 204.9 217.9 193.6 228.4 174.2 199.8 195.3 205.5 184.9 215.1 166.5
75 205.0 174.9 220.9 142.2 240.8 87.7 194.2 167.6 208.8 136.2 227.7 83.3 182.6 159.6 195.9 129.7 208.9 78.4
80 211.7 194.5 223.1 171.7 241.7 133.3 201.0 186.3 211.2 164.7 228.6 127.7 189.4 177.4 198.5 157.1 214.6 121.4
85 220.0 210.0 228.4 193.4 242.2 165.6 209.1 201.1 216.6 185.6 229.3 158.8 197.3 191.6 203.8 177.1 215.5 151.5
90 229.1 223.1 235.7 210.4 246.2 189.3 217.8 213.7 223.6 201.8 233.3 181.8 205.7 203.6 210.8 192.6 219.5 173.6
75 209.4 181.3 224.2 147.7 243.2 92.1 198.2 173.4 211.7 141.2 230.3 87.2 186.0 165.0 198.2 134.1 210.2 81.8
80 216.9 201.6 227.2 178.1 244.8 138.8 205.6 192.9 214.8 170.5 231.2 132.7 193.4 183.6 201.6 162.4 216.7 125.9
85 225.6 217.8 233.3 200.6 246.1 172.0 214.2 208.4 220.9 192.2 232.7 164.7 201.9 198.4 207.6 183.2 218.4 156.9
90 235.1 231.5 241.0 218.2 250.8 196.5 223.4 221.5 228.5 209.1 237.4 188.4 210.8 210.8 215.1 199.4 223.1 179.7
75 213.0 186.8 226.7 152.2 245.6 95.6 201.2 178.4 213.6 145.2 231.9 90.2 188.6 169.4 199.6 137.6 210.6 84.2
80 221.1 207.9 230.5 183.5 247.0 143.4 209.3 198.6 217.6 175.5 232.8 136.7 196.6 188.8 203.8 166.8 217.9 129.4
85 230.4 224.7 237.2 206.8 249.1 177.5 218.4 214.8 224.3 197.9 235.2 169.7 205.6 204.3 210.5 188.4 220.4 161.4
90 240.3 238.9 245.5 225.1 254.5 202.8 228.0 228.0 232.4 215.5 240.5 194.2 214.9 214.9 218.5 205.3 225.7 185.0
75 215.7 191.3 228.2 155.8 246.8 98.2 203.4 182.4 214.6 148.3 232.7 92.3 190.2 172.9 200.2 140.2 220.4 85.8
80 224.4 213.2 232.9 188.1 248.3 147.1 212.1 203.4 219.5 179.5 233.6 139.9 199.0 193.1 205.2 170.3 220.8 132.1
85 234.2 230.7 240.2 212.1 251.3 182.0 221.8 220.3 226.8 202.7 236.8 173.8 208.4 208.4 212.6 192.7 221.5 164.9
90 244.5 244.5 249.1 231.1 257.3 208.1 231.8 231.8 235.5 221.0 242.8 199.0 218.1 218.1 221.1 210.2 227.5 189.3
RT-PRC043AC-EN 61
Performance Data
Table 34. Gross cooling capacities 17½ tons three phase high efficiency T/YH*210G3,4,W (full load)
Air
Flow cfm
3500
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 149.5 122.4 158.0 97.6 172.5 52.1 144.0 119.0 155.8 94.8 165.9 50.1 138.2 115.3 148.3 91.9 160.8 48.0
80 153.6 136.3 165.4 120.3 176.7 89.5 148.1 132.4 159.3 117.0 169.4 86.9 142.3 128.4 153.0 113.5 163.4 84.1
85 159.3 147.2 168.2 136.3 182.4 114.9 153.7 143.0 162.1 132.6 175.8 111.8 147.8 138.6 155.8 128.7 169.0 108.4
90 165.8 156.4 172.8 148.5 183.8 133.0 160.1 151.8 166.7 144.4 177.2 129.4 154.1 147.2 160.3 140.2 170.4 125.7
75 156.0 131.0 171.4 105.2 184.6 58.6 150.2 127.2 164.9 102.2 174.8 56.4 144.2 123.3 158.3 99.0 162.4 54.0
4200
4900
5600
6300
7000
80 160.8 145.6 171.6 128.8 186.8 97.2 155.0 141.5 165.3 125.2 175.3 94.3 149.0 137.2 158.7 121.5 168.6 91.2
85 167.0 157.2 175.0 145.6 188.4 123.5 161.1 152.7 168.7 141.6 181.5 120.1 155.0 148.0 162.1 137.5 174.4 116.5
90 173.9 166.9 180.2 158.5 190.4 142.3 167.9 162.1 173.8 154.1 183.6 138.5 161.6 157.2 167.1 149.6 176.5 134.5
75 161.6 138.6 175.9 111.9 190.2 64.3 155.5 134.6 169.2 108.6 180.7 61.8 149.3 130.4 162.3 105.2 175.1 59.2
80 167.0 154.0 176.9 136.4 192.8 103.9 161.0 149.6 170.3 132.6 181.3 100.7 154.7 145.0 163.5 128.6 176.4 97.4
85 173.7 166.2 181.0 154.0 193.4 131.1 167.6 161.4 174.4 149.8 186.3 127.4 161.3 156.5 167.6 145.3 178.9 123.6
90 181.1 176.5 186.7 167.5 196.1 150.7 174.8 171.5 180.0 162.9 189.0 146.6 168.3 166.3 173.1 158.2 181.7 142.4
75 166.3 145.3 179.4 117.7 192.5 69.0 160.0 141.0 172.5 114.1 184.5 66.3 153.5 136.6 165.3 110.4 176.9 63.4
80 172.4 161.5 181.4 143.1 197.4 109.7 166.1 156.8 174.5 139.0 189.9 106.3 159.6 152.0 167.4 134.8 182.2 102.7
85 179.6 174.3 186.1 161.5 197.6 137.8 173.2 169.3 179.2 157.0 190.2 133.9 166.6 164.1 172.1 152.3 182.6 129.8
90 187.4 185.2 192.3 175.7 201.0 158.2 180.9 179.9 185.4 170.8 193.6 153.9 174.1 174.1 178.2 165.8 186.0 149.3
75 170.1 151.0 182.1 122.5 194.1 72.8 163.6 146.5 174.9 118.7 185.6 69.8 156.8 141.9 167.5 114.8 178.3 66.7
80 176.9 168.0 184.9 148.8 199.8 114.6 170.3 163.1 177.8 144.5 192.1 110.9 163.5 158.0 170.4 140.0 184.1 107.1
85 184.6 181.5 190.2 168.0 200.8 143.6 178.0 176.2 183.1 163.2 193.2 139.4 171.1 170.8 175.8 158.3 185.3 135.1
90 192.8 192.8 197.0 182.9 204.9 164.8 186.0 186.0 189.8 177.7 197.2 160.2 179.0 179.0 182.4 172.5 189.4 155.4
75 173.0 155.9 183.9 126.5 194.4 75.7 166.2 151.1 176.5 122.4 186.5 72.4 159.2 146.2 168.8 118.2 178.8 69.0
80 180.4 173.6 187.5 153.7 201.3 118.5 173.6 168.4 180.1 149.1 193.3 114.6 166.6 163.1 172.5 144.3 185.1 110.5
85 188.7 187.8 193.5 173.6 203.2 148.5 181.8 181.8 186.2 168.6 195.3 144.0 174.7 174.7 178.6 163.4 187.2 139.4
90 197.3 197.3 200.8 189.1 207.9 170.4 190.2 190.2 193.4 183.8 200.0 165.5 183.0 183.0 185.7 178.2 191.9 160.5
75 175.1 159.8 184.8 129.4 195.2 77.6 168.0 154.8 177.1 125.1 187.2 74.1 160.7 149.6 169.2 120.7 179.2 70.5
7700
80 183.1 178.3 189.2 157.6 202.0 121.5 176.0 172.9 181.6 152.7 193.7 117.4 168.7 167.3 173.8 147.7 185.3 113.0
85 191.9 191.9 195.9 178.3 204.7 152.4 184.8 184.8 188.3 173.0 196.5 147.7 177.4 177.4 180.4 167.6 188.1 142.8
90 200.9 200.9 203.8 194.5 210.1 175.1 193.6 193.6 196.0 188.8 201.9 170.0 186.1 186.1 188.1 183.1 193.5 164.7
75 176.2 162.8 184.8 131.5 195.6 78.7 168.9 157.5 177.8 126.9 187.9 74.9 161.3 152.0 170.0 122.2 180.3 71.0
8400
80 184.9 182.1 190.1 160.6 202.4 123.6 177.6 176.4 182.2 155.4 194.3 119.2 170.0 170.0 174.1 150.2 184.4 114.6
85 194.2 194.2 197.4 182.1 205.3 155.4 186.8 186.8 189.5 176.5 196.8 150.4 179.2 179.2 181.4 170.8 188.2 145.3
90 203.6 203.6 205.8 198.9 211.3 178.9 196.1 196.1 197.8 193.0 202.9 173.5 188.3 188.3 189.6 187.0 194.2 168.0
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 3500, 4200, and 4900 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
62 RT-PRC043AC-EN
Performance Data
Table 35. Gross cooling capacities 17½ tons three phase dehumidification (hot gas reheat) option high efficiency T/
YHD210G3,4,W (Digit 22 = B)
Air
Flow cfm (a)
3500
4550
5600
6300
7000
7700
8400
85
Ambient Temperature
95 105
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 157.6 122.6 174.5 95.9 196.1 56.8 151.2 119.5 166.8 93.6 187.2 55.2 143.7 115.7 158.2 90.5 177.3 53.0
80 160.6 140.5 174.2 120.6 192.5 88.1 154.0 136.7 166.5 117.6 183.6 85.9 146.5 132.2 157.8 113.8 173.6 83.0
85 165.2 154.7 175.6 141.4 190.7 115.7 158.6 150.2 167.8 137.7 181.7 112.8 151.0 145.0 159.0 133.3 171.6 109.2
90 171.5 165.0 178.7 158.5 190.5 139.5 164.8 159.9 170.8 154.1 181.4 135.9 157.2 154.0 161.9 149.1 171.3 131.6
75 167.1 138.7 182.4 110.5 202.3 69.8 160.1 134.8 174.2 107.4 192.8 67.5 152.2 130.2 164.9 103.5 182.4 64.4
80 171.1 158.1 183.1 136.6 199.7 102.6 164.0 153.5 174.8 132.7 190.2 99.5 156.0 148.2 165.5 128.2 179.7 95.8
85 176.7 173.6 185.5 158.8 198.9 131.5 169.6 168.3 177.1 154.3 189.3 127.8 161.4 161.4 167.7 149.1 178.7 123.4
90 184.0 184.0 189.5 177.3 199.7 156.7 176.8 176.8 181.1 172.1 190.0 152.3 168.6 168.6 171.6 166.2 179.4 147.2
75 174.9 145.5 188.5 116.5 206.7 75.0 167.3 141.2 179.7 113.0 196.7 72.3 158.8 136.2 169.9 108.7 185.7 68.8
80 179.8 165.5 190.1 143.2 205.1 108.5 172.2 160.6 181.3 139.0 195.1 105.0 163.6 154.9 171.5 134.1 184.0 100.9
85 186.4 181.8 193.5 166.2 205.3 138.1 178.7 176.1 184.6 161.3 195.1 134.0 170.0 169.7 174.7 155.7 184.0 129.2
90 194.7 194.2 198.5 185.3 207.0 164.0 186.9 186.9 189.5 179.8 196.8 159.2 178.1 178.1 179.6 173.5 185.7 153.7
75 179.1 151.4 191.5 121.6 208.6 79.4 171.1 146.7 182.4 117.7 198.3 76.2 162.2 141.3 172.3 113.1 187.0 72.4
80 184.6 172.1 193.9 149.1 207.7 113.5 176.6 166.8 184.7 144.5 197.3 109.7 167.7 160.7 174.5 139.1 185.9 105.1
85 191.9 189.1 197.9 172.7 208.5 143.9 183.8 183.0 188.6 167.4 198.0 139.3 174.8 174.8 178.3 161.4 186.5 134.1
90 200.8 200.8 203.5 192.6 210.9 170.4 192.6 192.6 194.2 186.6 200.4 165.2 183.5 183.5 183.9 179.9 188.8 159.3
75 182.4 156.5 193.8 125.9 209.8 82.9 174.2 151.4 184.3 121.6 199.1 79.3 164.9 145.6 173.8 116.6 187.4 75.1
80 188.6 177.9 196.8 154.0 209.5 117.7 180.3 172.1 187.2 149.0 198.8 113.5 171.0 165.6 176.7 143.3 187.0 108.5
85 196.5 195.5 201.4 178.4 211.0 148.7 188.1 188.1 191.8 172.7 200.1 143.8 178.7 178.7 181.2 166.3 188.3 138.2
90 206.1 206.1 207.7 198.9 214.1 176.0 197.6 197.6 198.0 192.5 203.1 170.4 185.5 185.5 187.3 185.5 191.2 164.1
75 185.0 160.6 195.3 129.3 210.2 85.5 176.4 155.2 185.4 124.6 199.1 81.5 166.7 149.0 174.6 119.2 187.0 76.9
80 191.9 182.8 198.9 158.1 210.6 121.0 183.2 176.6 189.0 152.7 199.4 116.4 173.5 169.7 178.0 146.6 187.3 111.0
85 200.4 200.4 204.2 183.1 212.6 152.7 191.6 191.6 194.2 177.1 201.4 147.4 181.9 181.9 183.2 170.3 189.2 141.4
90 210.6 210.6 211.2 204.4 216.4 180.7 201.8 201.8 201.1 197.6 205.1 174.7 190.0 190.0 190.0 190.0 192.8 168.0
75 186.8 164.0 195.9 131.8 209.7 87.2 177.8 158.1 185.7 126.7 198.3 82.9 167.8 151.5 174.5 120.9 185.9 77.8
80 194.3 186.8 200.2 161.3 210.8 123.5 185.2 180.2 189.9 155.6 199.3 118.4 175.2 172.9 178.6 149.0 186.8 112.7
85 203.5 203.5 206.2 187.1 213.5 155.9 194.4 194.4 195.8 180.6 201.9 150.2 184.2 184.2 184.5 173.4 189.3 143.8
90 214.4 214.4 213.8 209.0 217.9 184.5 201.3 201.3 203.4 201.8 206.2 178.1 191.9 191.9 191.9 191.9 193.6 171.1
RT-PRC043AC-EN 63
Performance Data
Table 35. Gross cooling capacities 17½ tons three phase dehumidification (hot gas reheat) option high efficiency T/
YHD210G3,4,W (Digit 22 = B)
115
Ambient Temperature
120 125
Air
Flow
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
3500
4550
5600
6300
75 135.3 111.1 148.5 86.8 166.4 50.0 130.7 108.6 143.3 84.7 160.6 48.2 125.9 105.9 137.9 82.4 154.5 46.3
80 138.0 127.0 148.0 109.4 162.7 79.3 133.4 124.2 142.8 106.9 156.8 77.2 128.5 121.1 137.3 104.3 150.8 75.0
85 142.4 139.2 149.2 128.2 160.6 104.8 137.8 136.0 143.9 125.4 154.8 102.4 132.9 132.6 138.4 122.4 148.6 99.8
90 148.5 147.5 152.1 143.3 160.3 126.6 143.8 143.8 146.8 140.1 154.3 123.8 138.9 138.9 141.2 136.8 148.2 120.9
75 143.2 124.9 154.8 99.0 171.0 60.6 138.3 119.0 149.3 93.8 164.9 56.2 133.2 118.9 143.6 93.8 158.6 56.2
80 146.9 142.2 155.2 123.0 168.2 91.3 142.0 135.6 149.7 117.2 162.1 86.3 136.9 135.5 144.0 117.1 155.8 86.2
85 152.3 152.3 157.4 143.2 167.2 118.3 147.4 147.4 151.9 136.7 161.0 112.5 142.2 142.2 146.1 136.6 154.6 112.4
90 159.6 159.6 161.2 159.6 167.8 141.4 154.4 154.4 155.7 152.4 161.6 134.9 149.8 149.8 149.8 149.8 155.1 134.9
75 149.3 130.5 159.2 103.8 173.8 64.6 144.2 127.4 153.5 101.1 167.4 62.3 138.8 124.1 147.5 98.2 160.8 59.8
80 154.0 148.5 160.7 128.5 172.0 96.1 148.8 145.0 154.9 125.4 165.6 93.4 143.4 141.4 148.9 122.2 159.0 90.5
85 160.4 160.4 163.8 149.4 171.9 123.7 155.2 155.2 158.0 146.0 165.5 120.6 149.7 149.7 151.9 142.4 158.8 117.4
90 168.4 168.4 168.6 166.5 173.5 147.5 162.8 162.8 162.8 162.8 167.0 144.1 156.7 156.7 156.7 156.7 160.3 140.6
75 152.4 135.2 161.2 107.7 174.6 67.8 147.0 131.9 155.2 104.8 168.1 65.3 141.5 128.4 149.1 101.7 161.3 62.5
80 157.7 153.9 163.3 133.1 173.5 99.9 152.4 150.2 157.3 129.9 166.9 97.0 146.8 146.4 151.1 126.4 160.1 94.0
85 164.7 164.7 167.1 154.7 174.1 128.2 159.4 159.4 161.1 151.1 167.5 125.0 153.7 153.7 154.8 147.3 160.6 121.6
90 172.5 172.5 172.5 172.5 176.3 152.7 166.5 166.5 166.5 166.5 169.7 149.2 160.2 160.2 160.2 160.2 162.8 145.4
7000
7700
75 154.6 139.1 162.3 110.8 174.7 70.1 149.1 135.5 156.2 107.7 168.0 67.4 143.4 131.9 149.9 104.4 161.0 64.4
80 160.6 158.4 165.1 136.9 174.2 102.9 155.1 154.6 159.0 133.4 167.5 99.8 149.3 149.3 152.6 129.8 160.5 96.6
85 168.3 168.3 169.6 159.2 175.4 131.9 162.8 162.8 163.4 155.4 168.7 128.5 156.9 156.9 157.0 151.4 161.6 124.9
90 175.7 175.7 175.7 175.7 178.3 157.1 169.4 169.4 169.4 169.4 171.5 153.3 163.0 163.0 163.0 163.0 164.4 149.4
75 156.1 142.0 162.7 113.0 174.0 71.5 150.5 138.3 156.4 109.7 167.1 68.6 144.5 134.4 149.9 106.2 159.9 65.5
80 162.8 162.1 166.1 139.8 174.2 105.0 157.1 157.1 159.8 136.1 167.2 101.7 151.1 151.1 153.3 132.3 160.0 98.3
85 171.1 171.1 171.2 162.8 176.0 134.7 165.4 165.4 164.9 158.8 169.0 131.1 159.4 159.4 158.3 154.6 161.8 127.3
90 178.0 178.0 178.0 178.0 179.5 160.6 171.6 171.6 171.6 171.6 172.5 156.7 165.0 165.0 165.0 165.0 165.3 152.5
8400
75 156.8 144.2 162.3 114.4 172.5 72.1 151.0 140.3 155.8 110.8 165.4 69.0 144.9 136.2 149.1 107.1 158.0 65.6
80 164.1 164.1 166.4 141.8 173.3 106.3 158.2 158.2 159.9 138.0 166.2 102.8 152.1 152.1 153.1 133.9 158.8 99.1
85 173.1 173.1 172.1 165.5 175.8 136.7 167.2 167.2 165.6 161.3 168.6 132.8 157.2 157.2 158.8 156.9 161.2 128.8
90 179.5 179.5 179.5 179.5 180.0 163.3 173.0 173.0 173.0 173.0 172.8 159.1 166.1 166.1 166.1 166.1 165.3 154.8
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
(a)For 3500, and 4550 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
64 RT-PRC043AC-EN
Performance Data
Table 36. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (stage 1)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
3200
4000
4800
5600
6400
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
71.7 67.2 76.0 52.7 82.4 24.7 66.8 63.4 70.9 49.4 77.0 21.9
76.1 75.4 78.6 67.1 84.3 49.4 71.3 71.3 73.5 63.4 78.9 46.1
81.1 81.1 82.5 77.1 86.2 65.8 76.3 76.3 77.4 73.1 80.9 62.2
86.3 86.3 87.1 84.6 89.5 77.4 81.4 81.4 82.0 80.5 84.3 73.6
73.6 70.6 77.4 56.5 83.2 28.8 68.4 66.4 71.9 52.7 79.9 25.6
78.5 78.5 80.4 71.0 85.6 53.6 73.3 73.3 75.0 66.9 79.9 50.0
83.8 83.8 84.8 81.2 88.0 70.2 78.6 78.6 79.4 76.9 82.3 66.3
89.3 89.3 89.8 89.1 91.8 82.0 84.1 84.1 84.4 84.4 86.2 77.9
75.0 73.3 78.2 59.4 85.9 32.1 69.5 68.6 72.5 55.2 80.0 28.5
80.3 80.3 81.8 74.2 86.4 57.1 74.8 74.8 76.1 69.7 80.4 53.0
86.0 86.0 86.6 84.7 89.3 73.9 80.5 80.5 80.9 79.9 83.4 69.6
91.8 91.8 91.9 91.9 93.6 86.0 85.0 85.0 86.2 86.2 87.6 81.4
76.0 75.2 78.6 61.6 86.0 34.7 70.2 70.1 72.5 57.1 80.2 30.7
81.7 81.7 82.7 76.6 86.8 59.8 75.9 75.9 76.7 71.7 80.5 55.4
87.8 87.8 87.9 87.3 90.2 76.8 81.0 81.0 81.9 81.9 83.9 72.1
92.0 92.0 93.6 93.6 94.9 89.2 87.0 88.0 87.6 87.6 88.6 84.2
76.5 76.3 79.0 63.1 87.0 36.5 70.3 70.3 73.0 58.1 81.0 32.1
82.6 82.6 83.2 78.3 88.0 61.8 76.5 76.5 76.8 73.0 82.5 56.9
88.2 88.2 88.8 88.8 90.6 79.0 82.0 82.0 82.4 82.4 84.0 73.9
93.5 93.5 94.8 94.8 95.7 91.6 88.2 88.2 88.5 88.5 89.1 86.2
7000
75
80
85
90
76.5 76.5 81.0 63.7 88.0 37.4 70.2 70.2 75.0 58.4 82.0 32.7
83.0 83.0 83.2 79.0 91.0 62.7 76.6 76.6 78.0 73.4 84.0 57.6
89.0 89.0 89.1 89.1 94.0 80.1 82.2 82.2 82.5 82.5 86.0 74.7
95.0 95.0 95.4 95.4 96.0 92.9 88.4 89.0 88.8 88.8 89.1 87.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 3200, 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC043AC-EN 65
Performance Data
Table 37. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (stage 2)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
3200
4000
4800
5600
6400
75 147.4 116.5 161.9 94.0 179.6 54.5 139.3 111.3 153.0 89.7 169.9 51.2
80 150.8 130.2 164.3 114.7 181.0 87.0 142.8 124.5 155.5 109.7 171.4 82.9
85 155.8 141.5 166.7 130.2 182.4 110.0 147.8 135.4 158.0 124.7 172.9 105.2
90 161.9 151.4 170.9 142.5 183.7 127.2 153.7 144.9 162.2 136.6 174.4 121.9
75 155.6 127.1 171.7 103.0 185.5 61.7 147.0 121.3 162.1 98.1 175.3 57.9
80 160.1 142.0 172.3 125.2 187.9 96.0 151.5 135.8 163.0 119.7 177.7 91.4
85 165.9 154.4 175.7 141.9 190.2 120.5 157.3 147.7 166.4 135.9 180.2 115.2
90 172.5 165.2 180.7 155.4 192.5 138.9 163.9 158.2 171.5 148.9 182.6 133.1
75 162.5 136.3 177.1 110.6 195.7 67.6 153.4 130.0 167.0 105.3 184.6 63.2
80 167.9 152.5 178.9 134.3 196.1 103.6 158.8 145.7 169.0 128.3 185.3 98.5
85 174.5 166.0 183.2 152.3 196.6 129.6 165.4 158.8 173.5 145.8 186.0 123.8
90 181.8 177.7 189.1 166.9 199.9 149.3 172.6 170.2 179.3 159.9 189.4 143.0
75 168.0 144.2 181.2 116.9 198.4 72.1 158.3 137.4 170.5 111.0 186.8 67.2
80 174.3 161.7 184.1 142.1 200.0 109.9 164.7 154.3 173.7 135.6 188.6 104.2
85 181.7 176.2 189.4 161.4 201.6 137.4 172.0 168.4 179.1 154.3 190.5 131.1
90 189.6 188.8 196.1 177.1 205.9 158.4 179.9 179.9 185.7 169.6 194.9 151.5
75 172.1 150.7 183.8 121.9 199.6 75.3 161.8 143.4 172.6 115.5 187.5 69.9
80 179.3 169.5 187.9 148.6 202.4 114.9 169.2 161.6 177.0 141.5 190.5 108.7
85 187.5 185.1 194.2 169.2 205.2 143.9 177.3 176.8 183.3 161.6 193.5 137.0
90 196.0 196.0 201.6 185.9 210.4 166.2 185.8 185.8 190.7 177.9 198.9 158.8
7000
75 174.2 154.7 184.8 124.8 199.6 76.8 163.5 147.0 173.2 117.9 190.8 71.0
80 182.2 174.4 189.9 152.6 203.3 117.8 171.6 166.2 178.5 145.1 191.0 111.1
85 190.9 190.8 196.8 174.1 207.0 147.9 180.3 180.3 185.5 166.1 194.9 140.6
90 199.9 199.9 204.9 191.6 212.9 171.1 189.3 189.3 193.6 183.2 201.0 163.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 3200, 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
66 RT-PRC043AC-EN
Performance Data
Table 38. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (full load)
Air
Flow cfm (a)
4000
4800
5600
6400
7200
8000
8800
9600
85
Ambient Temperature
95 105
Ent Entering Wet Bulb
DB 61 67 73 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 204.7 159.8 224.3 126.6 248.0 69.4 194.8 153.5 213.3 121.7 235.9 66.2 184.1 146.6 201.4 116.3 223.0 62.4
80 209.6 179.2 227.5 156.5 249.7 116.6 199.7 172.0 216.5 150.5 237.6 112.1 189.0 164.2 204.7 143.9 224.8 106.9
85 217.0 194.6 230.8 178.3 251.4 149.6 206.9 186.7 219.8 171.4 239.4 143.9 195.9 178.1 208.0 163.9 226.5 137.7
90 225.7 207.7 236.9 195.3 253.2 173.8 215.3 199.2 225.7 187.6 241.1 167.2 204.1 190.1 213.7 179.4 228.2 160.0
75 214.2 171.5 232.6 137.1 255.1 78.6 203.7 164.6 225.1 131.7 242.5 74.8 192.4 157.1 212.5 125.6 229.0 70.4
80 220.0 191.9 236.7 168.2 257.7 127.2 209.5 184.0 225.1 161.6 245.1 122.0 198.1 175.6 212.7 154.4 231.6 116.3
85 228.0 208.1 240.9 191.0 260.3 161.4 217.3 199.6 229.2 183.5 247.7 155.1 205.7 190.4 216.8 175.4 234.2 148.2
90 237.3 221.9 247.6 208.8 262.9 186.5 226.3 212.8 235.9 200.6 250.2 179.3 214.5 203.1 223.2 191.7 236.7 171.5
75 222.7 182.1 243.9 146.6 261.2 86.7 211.5 174.6 231.5 140.5 248.0 82.3 199.6 166.5 218.3 133.9 233.9 77.4
80 229.3 203.5 244.8 178.8 264.7 136.7 218.1 195.0 232.6 171.6 251.4 130.9 206.2 186.0 219.5 163.8 237.3 124.6
85 237.9 220.6 249.8 202.6 268.1 172.0 226.6 211.4 237.6 194.5 254.8 165.1 214.5 201.7 224.5 185.8 240.7 157.6
90 247.8 235.1 257.3 221.2 271.6 198.1 236.2 225.3 244.9 212.4 258.3 190.3 223.7 215.0 231.6 203.0 244.2 181.9
75 230.0 191.6 249.9 154.9 274.8 93.8 218.3 183.5 236.8 148.3 260.5 88.8 205.7 174.8 223.0 141.0 245.5 83.2
80 237.5 214.0 251.8 188.3 274.8 145.1 225.7 204.9 239.0 180.5 260.7 138.7 213.1 195.3 225.3 172.1 245.9 131.8
85 246.8 231.9 257.6 213.1 274.8 181.6 234.9 222.1 244.8 204.4 260.9 174.1 222.1 211.8 231.1 195.1 246.2 166.0
90 257.2 247.1 265.8 232.6 279.1 208.6 245.0 236.8 252.8 223.1 265.2 200.2 231.9 225.9 239.0 213.1 250.5 191.2
75 236.2 200.1 254.7 162.2 278.3 99.8 223.9 191.4 241.1 155.0 263.4 94.2 210.7 182.0 226.6 147.1 247.8 88.0
80 244.5 223.4 257.7 196.7 279.4 152.5 232.2 213.7 244.3 188.3 264.7 145.5 219.0 203.5 230.0 179.4 249.2 137.9
85 254.6 242.2 264.4 222.5 280.4 190.0 242.0 231.8 250.9 213.2 265.9 181.9 228.7 220.8 236.7 203.3 250.6 173.3
90 265.5 258.1 273.2 242.8 285.6 218.1 252.6 247.2 259.6 232.8 271.1 209.1 239.0 235.6 245.2 222.2 255.8 199.5
75 241.4 207.5 258.4 168.5 280.7 104.7 228.4 198.1 244.2 160.6 265.2 98.5 214.6 188.2 229.1 152.1 249.0 91.7
80 250.5 231.7 262.5 204.1 282.8 158.7 237.6 221.5 248.5 195.1 267.5 151.1 223.8 210.7 233.6 185.5 251.4 143.0
85 261.2 251.3 270.1 230.8 284.9 197.4 248.1 240.4 256.0 220.9 269.8 188.7 234.1 228.8 241.1 210.5 253.9 179.4
90 272.7 268.0 279.6 252.0 291.0 226.5 259.2 256.5 265.4 241.4 275.8 216.9 245.0 244.3 250.3 230.2 259.9 206.7
75 245.4 213.8 261.1 173.6 282.0 108.5 231.9 203.8 246.2 165.1 265.9 101.7 217.5 193.3 230.6 156.1 249.1 94.3
80 255.4 239.0 266.2 210.4 285.2 163.9 241.8 228.2 251.6 200.8 269.3 155.7 227.4 216.7 236.1 190.6 252.6 146.9
85 266.8 259.4 274.6 238.1 288.4 203.8 253.0 247.9 259.9 227.6 272.6 194.4 238.5 235.7 244.4 216.5 256.1 184.6
90 278.8 276.8 284.8 260.1 295.2 233.8 264.7 264.7 270.0 248.9 279.5 223.6 249.9 249.9 254.3 237.1 263.0 212.8
75 248.4 219.0 262.6 177.6 282.2 111.2 234.2 208.4 247.2 168.6 265.5 103.8 219.2 197.3 230.9 158.9 248.1 95.8
80 259.2 245.2 268.8 215.6 286.4 168.0 245.0 233.7 253.6 205.4 270.0 159.2 230.0 221.7 237.5 194.6 252.6 149.8
85 271.3 266.5 278.1 244.3 290.7 209.0 256.9 254.3 262.8 233.2 274.4 199.1 241.7 241.5 246.7 221.5 257.2 188.6
90 283.8 283.8 289.0 267.2 298.4 240.0 269.1 269.1 273.5 255.3 282.1 229.2 253.7 253.7 257.3 242.9 264.9 217.8
RT-PRC043AC-EN 67
Performance Data
Table 38. Gross cooling capacities 20 tons three phase high efficiency T/YH*240G3,4,W (full load)
Air
Flow cfm
4000
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 172.5 139.1 188.8 110.3 209.3 58.1 166.4 135.1 182.1 107.1 202.2 55.7 160.1 131.0 175.3 103.7 194.8 53.1
80 177.4 155.8 192.0 136.8 211.0 101.2 171.3 151.4 185.4 133.0 203.9 98.1 164.9 146.8 178.5 129.1 196.5 94.9
85 184.2 169.0 195.3 155.9 212.8 130.8 178.0 164.3 188.6 151.7 205.6 127.2 171.6 159.4 181.8 147.3 198.2 123.4
90 192.0 180.4 200.9 170.7 214.5 152.2 185.7 175.3 194.2 166.1 207.3 148.1 179.1 170.1 187.2 161.3 199.9 143.9
75 180.2 149.0 199.0 119.0 214.7 65.5 173.8 144.7 192.0 115.5 207.2 62.8 167.2 140.3 184.7 111.8 199.6 60.0
4800
5600
6400
7200
8000
80 185.9 166.6 199.4 146.7 217.3 110.0 179.5 161.9 192.4 142.6 209.8 106.6 172.9 157.1 185.3 138.4 202.1 103.1
85 193.4 180.7 203.5 166.8 219.8 140.7 186.9 175.7 196.5 162.2 212.3 136.8 180.2 170.5 189.4 157.5 204.7 132.7
90 201.8 192.8 209.8 182.4 222.4 163.1 195.2 187.4 202.7 177.5 214.9 158.7 188.3 181.9 195.5 172.4 207.2 154.2
75 186.8 157.8 204.2 126.7 219.0 71.8 180.1 153.2 196.9 122.8 211.2 68.8 173.2 148.5 189.3 118.9 203.2 65.7
80 193.4 176.4 205.6 155.5 222.4 117.6 186.6 171.4 198.4 151.1 214.6 114.0 179.7 166.2 190.9 146.5 206.6 110.1
85 201.5 191.3 210.6 176.5 225.8 149.6 194.7 186.0 203.3 171.7 218.0 145.3 187.7 180.5 195.9 166.7 210.0 141.0
90 210.5 204.1 217.6 193.0 229.2 172.9 203.5 198.5 210.2 187.8 221.4 168.3 196.4 192.7 202.7 182.4 213.4 163.4
75 192.3 165.5 208.3 133.2 229.6 77.1 185.3 160.6 200.7 129.1 221.3 73.8 178.1 155.6 192.8 124.8 212.9 70.3
80 199.7 185.1 210.8 163.2 230.1 124.3 192.7 179.8 203.3 158.5 222.0 120.3 185.5 174.3 195.5 153.7 213.6 116.1
85 208.5 200.9 216.6 185.2 230.7 157.3 201.4 195.2 209.1 180.1 222.6 152.8 194.1 189.4 201.3 174.8 214.3 148.1
90 218.0 214.4 224.3 202.5 235.0 181.7 210.8 208.4 216.7 197.0 226.9 176.7 203.3 202.3 208.8 191.4 218.6 171.5
75 196.7 172.1 211.3 138.7 231.3 81.2 189.4 167.0 203.4 134.3 222.7 77.7 181.9 161.7 195.2 129.7 213.9 73.9
80 205.0 192.7 214.9 169.8 232.9 129.8 197.7 187.1 207.0 164.8 224.4 125.5 190.1 181.4 199.0 159.7 215.7 121.1
85 214.5 209.3 221.6 192.9 234.5 164.0 207.1 203.4 213.7 187.4 226.1 159.2 199.4 197.2 205.6 181.8 217.5 154.2
90 224.5 223.5 229.9 211.0 239.6 189.3 216.9 216.9 222.0 205.2 231.2 184.0 209.2 209.2 213.8 199.2 222.6 178.6
75 200.0 177.7 213.3 143.1 231.9 84.3 192.4 172.2 205.0 138.4 223.0 80.4 184.6 166.6 196.5 133.5 213.9 76.4
80 209.1 199.3 217.9 175.4 234.5 134.2 201.5 193.4 209.7 170.1 225.7 129.6 193.7 187.3 201.3 164.7 216.7 124.9
85 219.3 216.7 225.4 199.4 237.1 169.6 211.6 210.4 217.2 193.6 228.5 164.4 203.7 203.7 208.8 187.8 219.6 159.2
90 229.9 229.9 234.4 218.4 243.1 195.9 222.0 222.0 226.2 212.3 234.4 190.3 214.0 214.0 217.7 206.0 225.5 184.6
75 202.2 182.2 214.1 146.4 231.3 86.3 194.3 176.4 205.5 141.4 222.2 82.2 186.2 170.5 196.7 136.2 213.5 77.8
8800
80 212.2 204.7 219.7 179.9 235.0 137.6 204.3 198.5 211.3 174.3 226.0 132.7 196.1 192.1 202.6 168.5 217.0 127.7
85 223.1 223.0 228.1 204.8 238.7 174.1 215.0 215.0 219.6 198.8 229.7 168.7 206.8 206.8 211.0 192.6 220.5 163.1
90 234.2 234.2 237.8 224.7 245.6 201.4 226.0 226.0 229.3 218.3 236.6 195.5 217.6 217.6 220.5 211.7 227.4 189.5
75 203.4 185.6 216.0 148.7 233.2 87.3 195.1 179.5 207.0 143.3 224.1 82.8 186.7 173.3 198.0 137.9 213.0 78.1
9600
80 214.2 209.1 220.5 183.2 236.2 139.9 205.9 202.6 211.8 177.4 227.0 134.7 197.5 195.9 202.8 171.3 218.0 129.4
85 225.7 225.7 229.8 209.2 239.2 177.5 217.4 217.4 221.0 202.9 229.9 171.8 208.9 208.9 212.0 196.4 223.0 165.9
90 237.4 237.4 240.2 229.9 246.9 205.8 228.9 228.9 231.3 223.2 237.6 199.6 220.2 220.2 222.3 216.3 228.1 193.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 4000, 4800, and 5600 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
68 RT-PRC043AC-EN
Performance Data
Table 39. Gross cooling capacities 20 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD240G3,4,W (Digit 22 = B)
Air
Flow cfm (a)
4000
5200
6400
7200
8000
8800
9600
85
61
Ambient Temperature
95
Entering Wet Bulb
67 73
105
Ent
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 203.7 145.0 228.5 96.2 259.7 90.9 193.4 139.5 217.0 92.5 247.0 86.4 182.4 133.4 204.8 88.3 233.5 81.7
80 206.0 171.4 227.3 134.7 254.8 89.2 195.8 164.9 215.8 130.0 242.1 84.7 184.8 157.8 203.6 124.6 228.6 80.0
85 210.1 191.8 227.8 167.0 251.7 118.8 199.9 184.2 216.3 161.3 239.0 114.9 189.0 176.0 204.1 154.9 225.5 110.4
90 216.1 206.0 230.1 193.2 250.4 157.1 205.9 197.4 218.6 186.5 237.7 152.1 194.9 188.2 206.4 179.1 224.2 146.5
75 218.6 159.9 241.6 108.8 271.0 94.8 207.5 153.9 229.3 104.6 257.4 90.1 195.7 147.3 216.2 99.8 243.0 85.1
80 222.2 188.3 241.6 149.2 267.3 93.6 211.1 181.3 229.3 144.0 253.7 88.8 199.3 173.6 216.2 138.2 239.4 83.8
85 227.6 210.6 243.4 183.5 265.5 133.0 216.5 202.5 231.1 177.3 251.9 128.6 204.7 193.8 218.0 170.4 237.6 123.5
90 234.8 226.8 247.0 211.7 265.4 173.2 223.7 217.7 234.6 204.4 251.9 167.7 211.9 207.9 221.6 196.5 237.5 161.6
75 231.3 173.2 252.5 119.7 280.0 98.0 219.3 166.7 239.3 115.1 265.5 92.9 206.6 159.6 225.3 109.8 250.3 87.6
80 236.2 203.6 253.7 162.1 277.6 97.2 224.2 196.0 240.5 156.4 263.2 93.4 211.5 187.9 226.6 150.1 248.0 88.8
85 242.8 227.8 256.8 198.4 277.0 145.5 230.9 219.3 243.6 191.6 262.6 140.6 218.2 210.0 229.7 184.2 247.4 135.0
90 251.2 245.9 261.6 228.5 278.2 187.7 239.3 236.3 248.4 220.7 263.8 181.7 226.7 226.1 234.5 212.3 248.6 175.1
75 238.5 181.2 258.5 126.2 284.8 99.7 226.0 174.4 244.7 121.2 269.7 94.4 212.7 166.9 230.2 115.5 253.9 88.9
80 244.2 212.9 260.6 169.9 283.2 103.4 231.7 205.0 246.8 163.8 268.2 99.2 218.5 196.5 232.3 157.1 252.4 94.3
85 251.7 238.4 264.4 207.4 283.5 153.0 239.2 229.5 250.7 200.3 268.4 147.7 226.0 220.0 236.2 192.6 252.7 141.8
90 261.0 257.9 270.1 238.9 285.5 196.5 248.5 247.9 256.3 230.7 270.5 190.2 235.3 235.3 241.9 222.0 254.7 183.2
75 244.8 188.5 263.5 131.9 288.6 101.0 231.7 181.3 249.2 126.5 272.9 95.5 217.8 173.5 234.1 120.5 256.6 89.8
80 251.3 221.5 266.4 176.9 287.8 108.9 238.2 213.2 252.1 170.5 272.2 104.3 224.4 204.4 237.0 163.5 255.9 99.1
85 259.6 248.3 271.1 215.8 288.9 159.8 246.5 239.1 256.8 208.3 273.3 154.2 232.7 229.2 241.7 200.2 257.0 147.9
90 269.7 269.0 277.6 248.5 291.8 204.5 256.7 256.7 263.3 240.0 276.2 197.9 242.9 242.9 248.2 230.9 259.9 190.6
75 250.0 195.1 267.5 136.9 291.3 102.0 236.3 187.5 252.6 131.2 275.2 96.3 221.9 179.4 236.9 124.9 258.2 90.4
80 257.4 229.3 271.3 183.2 291.5 113.6 243.7 220.8 256.4 176.5 275.3 108.7 229.3 211.6 240.7 169.1 258.4 103.2
85 266.5 257.5 276.8 223.4 293.4 165.8 252.9 247.9 261.9 215.6 277.2 159.9 238.5 237.7 246.3 207.2 260.3 153.3
90 277.5 277.5 284.1 257.4 297.1 211.9 263.8 263.8 269.2 248.6 280.9 204.9 249.5 249.5 253.6 239.2 264.0 197.3
75 254.3 200.9 270.6 141.2 293.1 102.6 240.0 193.1 255.1 135.2 276.4 96.7 225.0 184.6 238.8 128.5 258.9 90.6
80 262.5 236.5 275.1 188.8 294.1 117.7 248.2 227.6 259.7 181.7 277.4 112.4 233.3 218.1 243.4 174.0 259.9 106.5
85 272.4 266.0 281.5 230.3 296.8 171.2 258.2 256.0 266.0 222.2 280.1 164.9 243.3 243.3 249.8 213.4 262.6 157.9
90 284.2 284.2 289.6 265.7 301.4 218.6 270.0 270.0 274.2 256.5 284.7 211.2 255.1 255.1 258.0 246.7 267.2 203.2
RT-PRC043AC-EN 69
Performance Data
Table 39. Gross cooling capacities 20 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD240G3,4,W (Digit 22 = B)
Air
Flow cfm (b)
Ent
DB 61
115
67 73 61
Ambient Temperature
120
Entering Wet Bulb
67 73 61
125
67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
4000
5200
6400
7200
75 170.7 126.7 191.8 83.3 219.2 76.7 164.5 123.1 185.0 80.6 211.8 74.1 158.2 119.3 178.1 77.8 204.2 71.5
80 173.1 150.0 190.6 118.7 214.4 75.0 166.9 145.9 183.8 115.5 207.0 72.4 160.6 141.6 176.8 112.1 199.4 69.8
85 177.3 167.2 191.1 147.9 211.3 105.2 171.1 162.6 184.4 144.2 203.9 102.4 164.8 157.7 177.4 140.3 196.3 99.4
90 183.2 178.3 193.5 171.0 210.0 140.3 177.1 173.1 186.7 166.8 202.6 137.0 170.8 167.8 179.8 162.3 195.1 133.5
75 183.1 140.0 202.3 94.4 227.9 79.8 176.5 136.2 195.1 91.4 220.1 77.0 169.7 132.1 187.7 88.3 212.0 74.2
80 186.7 165.3 202.4 131.7 224.3 78.5 180.1 160.9 195.2 128.2 216.5 75.8 173.4 156.4 187.8 124.6 208.4 73.0
85 192.1 184.5 204.2 162.9 222.5 117.8 185.6 179.6 197.0 158.9 214.7 114.7 178.8 174.5 189.6 154.7 206.7 111.5
90 199.4 197.5 207.8 187.9 222.5 154.9 192.8 192.1 200.6 183.4 214.6 151.3 186.1 186.1 193.2 178.7 206.6 147.5
75 193.2 151.8 210.6 103.8 234.3 82.0 186.2 147.7 203.0 100.6 226.1 79.1 179.0 143.4 195.2 97.2 217.6 76.2
80 198.1 179.1 211.9 143.1 232.0 83.6 191.1 174.4 204.3 139.3 223.7 80.8 183.9 169.6 196.5 135.4 215.3 77.8
85 204.8 200.2 215.0 176.2 231.4 128.8 197.8 195.0 207.4 172.0 223.2 125.5 190.6 189.7 199.5 167.5 214.8 122.0
90 213.3 213.3 219.8 203.2 232.7 167.8 206.3 206.3 212.2 198.5 224.4 164.0 199.1 199.1 204.4 193.5 216.0 160.0
75 198.7 158.8 214.9 109.2 237.4 83.1 191.4 154.5 207.0 105.8 228.9 80.1 183.9 150.0 198.9 102.3 220.1 77.0
80 204.4 187.3 217.0 149.8 235.9 88.8 197.2 182.5 209.1 145.9 227.4 85.8 189.7 177.5 201.0 141.8 218.6 82.6
85 212.0 209.8 220.9 184.2 236.2 135.3 204.7 204.4 213.0 179.8 227.6 131.7 197.2 197.2 204.9 175.2 218.9 128.1
90 221.3 221.3 226.6 212.5 238.2 175.6 214.0 214.0 218.7 207.6 229.7 171.6 206.6 206.6 210.6 202.5 221.0 167.4
8000
8800
75 203.2 165.0 218.2 113.9 239.5 83.8 195.7 160.6 210.0 110.3 230.6 80.7 187.9 155.9 201.6 106.6 221.6 77.6
80 209.8 194.9 221.2 155.8 238.8 93.2 202.2 189.9 213.0 151.7 230.0 90.1 194.5 184.7 204.6 147.5 221.0 86.7
85 218.2 218.2 225.9 191.5 239.9 141.0 210.6 210.6 217.7 186.9 231.1 137.3 202.9 202.9 209.3 182.2 222.1 133.5
90 228.3 228.3 232.4 221.2 242.8 182.7 220.8 220.8 224.2 216.0 234.0 178.4 213.0 213.0 215.9 210.8 225.0 174.1
75 206.8 170.6 220.5 117.9 240.6 84.2 198.9 165.9 212.0 114.2 231.4 81.0 190.9 161.1 203.3 110.3 222.1 77.7
80 214.2 201.7 224.3 161.1 240.7 97.0 206.3 196.6 215.8 156.8 231.6 93.6 198.3 191.2 207.1 152.4 222.3 90.1
85 223.4 223.4 229.9 198.1 242.7 146.0 215.5 215.5 221.4 193.3 233.6 142.2 207.5 207.5 212.7 188.4 224.3 138.1
90 234.3 234.3 237.2 229.1 246.4 189.0 226.5 226.5 228.8 223.8 237.3 184.6 217.9 217.9 220.1 218.3 228.0 180.1
9600
75 209.3 175.4 221.8 121.2 240.6 84.2 201.2 170.6 213.0 117.3 231.2 80.9 192.8 165.6 204.1 113.2 221.6 77.6
80 217.5 207.9 226.4 165.6 241.6 100.0 209.4 202.5 217.7 161.2 232.2 96.5 201.1 197.0 208.7 156.6 222.6 92.8
85 227.6 227.6 232.8 204.0 244.4 150.4 219.4 219.4 224.1 199.1 235.0 146.3 211.1 211.1 215.1 194.0 225.4 142.1
90 239.4 239.4 241.0 236.2 249.0 194.6 230.0 230.0 232.3 230.8 239.6 190.1 223.3 223.3 223.3 223.3 230.0 185.3
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity (a)
(a)For 4000, and 5200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)For 4000, and 5200 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
70 RT-PRC043AC-EN
Performance Data
Table 40. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 1)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
4000
5000
6000
7000
8000
75
80
85
90
75
80
85
90
75
80
80.5 78.0 85.7 62.9 93.7 32.5 75.1 73.7 80.0 59.3 87.7 29.5
85.2 85.2 87.8 78.2 94.6 59.2 79.7 79.7 82.1 74.1 88.6 55.8
90.1 90.1 91.3 88.2 95.4 76.5 84.6 84.6 85.6 83.8 89.4 72.6
94.9 94.9 95.3 95.3 97.8 88.2 89.3 89.3 89.5 89.5 91.8 83.9
83.0 82.1 87.6 67.4 95.0 37.4 77.3 77.3 81.6 63.4 88.7 34.1
88.1 88.1 90.2 82.7 96.3 64.2 82.3 82.3 84.2 78.3 90.0 60.3
93.3 93.3 94.0 92.9 97.6 81.6 87.5 87.5 88.0 88.0 91.3 77.2
98.3 98.3 98.3 98.3 100.3 93.3 92.0 92.0 92.2 92.2 94.0 88.7
85.1 85.1 89.0 71.1 95.7 41.5 79.1 79.1 82.7 66.7 89.2 37.8
90.5 90.5 92.0 86.5 97.5 68.3 84.5 84.5 85.8 81.6 90.9 64.1
85
90
75
80
96.0 96.0 96.2 96.2 99.2 85.8 89.9 89.9 89.9 89.9 92.7 81.1
99.8 99.8 100.8 100.8 102.3 97.7 94.0 94.0 94.4 94.4 95.8 92.6
86.6 86.6 89.8 74.0 96.0 44.9 80.3 80.3 83.3 69.2 89.5 40.7
92.4 92.4 93.4 89.5 98.2 71.7 86.1 86.1 86.8 84.2 91.3 67.0
85 96.0 96.0 97.9 97.9 100.4 89.2 91.0 91.0 91.3 91.3 93.6 84.1
90 101.0 101.0 102.8 102.8 103.8 101.2 95.8 95.8 96.1 96.1 97.0 95.8
75
80
87.7 87.7 90.2 76.1 98.2 47.4 81.1 81.1 83.3 70.9 91.0 42.9
93.8 93.8 94.2 91.6 98.4 74.2 87.2 87.2 87.3 86.0 92.0 69.1
85 98.4 98.4 99.1 99.1 101.0 91.8 92.0 92.0 92.2 92.2 93.9 86.3
90 103.7 103.7 104.2 104.2 104.8 104.0 96.0 96.0 97.3 97.3 97.7 97.7
8750
75
80
88.1 88.1 91.0 77.1 98.5 48.8 81.3 81.3 84.0 71.6 92.0 43.9
94.0 94.0 94.5 92.7 99.0 75.6 87.3 87.3 87.4 86.7 93.5 70.2
85 99.0 99.0 99.7 99.7 101.2 93.2 92.4 92.4 92.6 92.6 95.0 87.4
90 104.0 104.0 105.0 105.0 105.2 105.2 97.0 97.0 97.8 97.8 97.9 97.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC043AC-EN 71
Performance Data
Table 41. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 2)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
4000
5000
6000
7000
8000
75 135.6 118.7 146.9 92.7 156.4 43.8 127.9 113.4 138.5 88.3 147.4 40.5
80 140.7 132.3 148.2 116.5 159.0 84.6 132.9 126.3 139.8 111.3 150.0 80.4
85 146.9 142.2 152.0 132.5 161.5 111.5 138.9 135.7 143.6 126.7 152.5 106.4
90 153.5 150.3 157.2 144.1 164.1 129.8 145.3 143.4 148.6 137.8 155.0 124.2
75 141.2 127.5 151.3 101.4 165.2 52.4 133.0 121.6 142.4 96.4 155.5 48.5
80 147.0 141.5 153.5 125.6 165.8 93.7 138.7 134.9 144.5 119.9 156.2 88.8
85 153.7 151.8 157.9 142.1 166.4 121.0 145.2 144.8 149.0 135.7 156.8 115.4
90 160.7 160.3 163.6 154.1 169.7 139.7 152.0 152.0 154.5 147.2 160.0 133.5
75 145.8 134.8 154.6 108.6 167.3 59.5 137.0 128.2 145.1 103.0 157.1 55.0
80 152.2 149.2 157.6 133.2 168.7 101.2 143.4 142.0 148.2 126.9 158.6 95.8
85 159.4 159.4 162.7 150.1 170.2 128.9 150.4 150.4 153.3 143.2 160.1 122.7
90 166.8 166.8 169.0 162.6 174.1 148.1 157.6 157.6 159.3 155.1 164.0 141.3
75 149.2 140.5 156.8 114.2 168.3 65.0 140.0 133.4 146.9 108.1 157.6 59.9
80 156.3 155.3 160.7 139.3 170.6 107.2 147.0 147.0 150.8 132.4 160.0 101.2
85 164.0 164.0 166.5 156.7 172.9 135.4 154.6 154.6 156.5 149.1 162.3 128.6
90 171.8 171.8 173.2 169.5 177.5 155.0 162.1 162.1 163.1 161.4 166.8 147.6
75 151.6 144.7 158.0 118.3 169.0 69.0 141.9 137.0 147.5 111.6 158.0 63.4
80 159.4 159.4 162.7 143.9 171.4 111.7 149.6 149.6 152.2 136.4 160.3 105.1
85 167.6 167.6 169.1 161.6 174.5 140.3 157.6 157.6 158.7 153.5 163.5 132.9
90 175.7 175.7 176.4 174.9 179.8 160.3 165.5 165.5 165.7 165.7 168.6 152.3
8750
75 152.7 146.8 158.1 120.4 171.3 71.0 142.6 138.7 147.9 113.2 159.6 64.9
80 161.0 161.0 163.4 146.3 172.0 114.0 150.8 150.8 152.7 138.3 161.0 107.0
85 169.5 169.5 170.4 164.3 175.1 142.9 159.2 159.2 159.6 155.8 163.6 135.1
90 178.0 178.0 178.0 177.9 180.8 163.3 166.0 167.4 167.0 167.0 169.3 154.9
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
72 RT-PRC043AC-EN
Performance Data
Table 42. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (stage 3)
Air
Flow cfm (a)
Ambient Temperature
85 95
Ent Entering Wet Bulb
DB 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
4000
5000
6000
7000
8000
75 188.9 150.3 205.8 121.4 226.6 71.4 179.7 145.2 195.3 117.2 214.8 68.3
80 193.3 167.2 208.8 147.0 228.3 111.8 184.1 161.3 198.4 142.0 216.6 107.6
85 199.5 180.7 211.8 165.8 230.0 140.0 190.3 174.2 201.4 160.0 218.4 135.0
90 207.0 192.0 217.1 180.3 231.7 160.6 197.5 185.0 206.7 174.0 220.2 154.9
75 199.5 162.2 218.5 131.4 234.4 79.3 189.4 156.2 206.9 126.4 221.8 75.4
80 204.9 180.5 219.0 158.8 237.2 121.8 194.9 173.8 207.8 153.0 224.7 116.9
85 212.0 195.3 223.1 179.1 240.0 151.8 202.0 188.0 211.9 172.5 227.6 146.0
90 220.2 207.7 229.3 194.9 242.7 173.9 209.9 199.9 218.0 187.7 230.4 167.4
75 208.4 172.8 225.7 140.2 247.8 86.1 197.5 166.0 213.4 134.4 234.0 81.4
80 214.8 192.7 227.6 169.4 248.1 130.7 204.1 185.1 215.6 162.7 234.6 124.9
85 222.8 208.7 232.7 191.2 248.3 162.4 212.0 200.6 220.8 183.8 235.1 155.8
90 231.7 222.2 239.8 208.3 252.1 186.0 220.6 213.6 227.8 200.3 239.0 178.7
75 215.6 182.2 231.3 147.8 251.9 91.6 204.0 174.6 218.2 141.2 237.3 86.1
80 223.2 203.6 234.5 178.8 253.4 138.3 211.6 195.2 221.7 171.3 239.1 131.7
85 232.0 220.9 240.7 202.1 255.0 171.8 220.4 211.9 228.0 193.8 241.0 164.4
90 241.6 235.5 248.7 220.5 259.9 197.0 229.7 226.1 235.9 211.7 246.0 188.8
75 221.2 190.4 235.3 154.2 254.3 96.0 208.8 181.9 221.3 146.7 238.9 89.6
80 229.8 213.3 239.8 187.0 257.1 144.7 217.5 204.1 226.2 178.6 242.0 137.3
85 239.6 231.8 247.1 211.8 260.0 180.0 227.1 222.1 233.5 202.7 245.2 171.7
90 249.9 247.6 255.9 231.5 266.0 206.7 237.2 237.2 242.3 221.8 251.3 197.7
8750
75 224.3 195.7 237.2 158.2 255.0 98.4 211.3 186.6 222.6 150.1 239.0 91.4
80 233.7 219.7 242.7 192.3 258.9 148.8 220.8 209.9 228.5 183.3 243.1 140.7
85 244.1 239.3 250.8 218.2 262.7 185.4 231.1 228.9 236.6 208.5 247.3 176.5
90 255.0 255.0 260.3 238.9 269.5 213.2 241.7 241.7 246.1 228.6 254.2 203.5
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 4000, 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and
YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC043AC-EN 73
Performance Data
Table 43. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (full load)
Air
Flow cfm (a)
5000
6000
7000
8000
9000
10000
11000
85
Ambient Temperature
95 105
Ent Entering Wet Bulb
DB 61 67 73 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 244.4 192.5 271.7 152.0 293.2 82.9 232.4 184.9 257.9 146.3 278.4 79.2 219.4 176.7 243.2 139.9 262.5 74.8
80 250.0 215.3 270.3 187.5 295.4 139.2 238.0 206.6 256.8 180.3 280.5 133.8 225.0 197.3 242.2 172.5 264.5 127.7
85 258.5 233.2 274.2 213.2 297.6 178.4 246.2 223.6 260.6 204.8 282.6 171.4 232.8 213.3 246.0 195.8 266.5 163.9
90 268.6 248.1 281.3 232.8 299.8 206.6 255.9 237.7 267.4 223.5 284.7 198.6 242.1 226.7 252.6 213.6 268.6 189.9
75 255.4 206.3 281.1 164.5 301.6 93.9 242.7 198.1 266.6 158.1 286.0 89.5 228.9 189.1 251.1 150.9 269.3 84.3
80 262.0 230.2 280.9 201.3 304.7 151.7 249.2 220.8 266.6 193.4 289.1 145.6 235.5 210.7 251.4 184.8 272.3 138.7
85 271.2 249.0 285.7 228.0 307.8 192.1 258.2 238.7 271.4 219.0 292.1 184.5 244.1 227.7 256.1 209.2 275.3 176.2
90 282.0 264.7 293.6 248.6 311.0 221.4 268.5 253.6 279.0 238.6 295.1 212.7 253.9 241.8 263.4 227.9 278.3 203.3
75 265.0 218.8 289.1 175.7 308.5 103.5 251.6 209.8 273.9 168.5 292.2 98.3 237.1 200.1 257.7 160.6 274.8 92.5
80 272.6 243.7 290.1 213.7 312.6 162.9 259.1 233.6 275.1 205.1 296.2 156.0 244.6 222.8 259.1 195.8 278.8 148.4
85 282.6 263.5 295.9 241.5 316.7 204.5 268.8 252.4 280.9 231.7 300.2 196.1 254.0 240.6 264.8 221.2 282.7 187.1
90 293.9 279.9 304.6 263.0 320.8 234.9 279.7 268.1 289.2 252.2 304.2 225.4 264.4 255.6 272.9 240.8 286.7 215.3
75 273.3 229.9 295.7 185.4 324.1 111.8 259.1 220.1 279.8 177.5 306.4 105.9 243.9 209.7 262.8 168.9 287.8 99.3
80 281.8 255.9 298.0 224.7 324.2 172.6 267.6 245.0 282.2 215.4 306.7 165.0 252.3 233.5 265.5 205.3 288.3 156.6
85 292.5 276.6 304.7 253.7 324.2 215.6 278.0 264.7 288.9 243.1 307.0 206.4 262.5 252.2 272.1 231.9 288.7 196.7
90 304.5 293.8 314.1 276.0 329.2 247.0 289.5 281.2 298.1 264.5 311.9 236.8 273.5 268.0 281.0 252.4 293.6 225.9
75 280.1 239.6 301.0 193.8 327.8 118.7 265.2 229.1 284.3 185.2 309.4 112.0 249.3 218.0 266.6 175.8 290.0 104.7
80 289.6 266.7 304.4 234.4 329.1 181.0 274.7 255.1 288.0 224.3 310.9 172.6 258.7 242.8 270.5 213.5 291.7 163.6
85 301.1 288.3 312.1 264.4 330.3 225.2 285.9 275.7 295.6 253.1 312.3 215.4 269.6 262.5 278.1 241.2 293.3 204.9
90 313.7 306.3 322.3 287.7 336.3 257.8 297.9 293.0 305.5 275.5 318.3 246.8 281.2 279.0 287.7 262.6 299.2 235.1
75 285.6 247.9 304.9 200.8 330.2 124.2 270.0 236.7 287.4 191.4 311.0 116.8 253.3 224.8 269.0 181.3 290.9 108.7
80 296.1 276.1 309.5 242.7 332.6 188.0 280.4 263.8 292.3 231.9 313.7 178.9 263.6 250.7 274.1 220.3 293.7 169.1
85 308.3 298.6 318.2 273.8 335.0 233.5 292.3 285.3 300.9 261.7 316.3 222.9 275.3 271.3 282.6 249.0 296.6 211.7
90 321.4 317.4 329.1 298.0 342.0 267.1 305.0 303.3 311.6 285.0 323.2 255.4 287.5 287.5 293.0 271.4 303.4 243.0
75 289.7 254.9 307.3 206.5 331.1 128.3 273.3 243.0 289.2 196.3 311.2 120.2 255.9 230.3 270.0 185.5 291.5 111.3
80 301.1 284.2 313.2 249.6 334.7 193.7 284.7 271.1 295.2 238.0 315.1 183.8 267.2 257.3 276.3 225.8 294.4 173.2
85 314.1 307.6 322.8 281.8 338.3 240.4 297.4 293.5 304.8 269.0 318.9 229.1 279.6 278.8 285.8 255.6 298.4 217.1
90 327.9 327.1 334.5 306.9 346.3 275.1 310.7 310.7 316.3 293.2 326.8 262.7 292.5 292.5 297.0 278.8 306.2 249.5
74 RT-PRC043AC-EN
Performance Data
Table 43. Gross cooling capacities 25 tons three phase high efficiency T/YH*300G3,4,W (full load)
Air
Flow cfm
5000
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 205.4 167.9 227.4 132.8 245.5 69.7 198.0 163.2 219.2 129.0 236.7 66.9 190.4 158.3 210.7 125.0 227.6 64.0
80 210.9 187.2 226.7 164.0 247.5 120.9 203.5 182.0 218.5 159.5 238.6 117.2 195.9 176.5 210.1 154.8 229.5 113.4
85 218.5 202.3 230.4 186.2 249.5 155.7 211.0 196.6 222.2 181.1 240.6 151.3 203.2 190.7 213.8 175.8 231.4 146.8
90 227.3 215.0 236.7 202.9 251.5 180.5 219.5 208.8 228.4 197.4 242.5 175.5 211.5 202.5 219.8 191.6 233.4 170.4
75 214.2 179.5 234.6 143.1 251.7 78.5 206.5 174.4 226.0 138.9 242.5 75.3 198.5 169.2 217.1 134.6 233.0 72.0
6000
7000
8000
9000
10000
80 220.7 199.9 235.1 175.6 254.6 131.2 212.9 194.3 226.6 170.7 245.4 127.1 204.9 188.5 217.8 165.6 235.9 122.9
85 229.0 216.0 239.7 198.8 257.5 167.2 221.1 209.8 231.2 193.3 248.3 162.5 213.0 203.6 222.4 187.7 238.8 157.6
90 238.4 229.3 246.8 216.5 260.5 193.1 230.3 222.9 238.1 210.6 251.2 187.8 221.9 216.2 229.2 204.5 241.6 182.3
75 221.7 189.7 240.4 152.0 256.4 85.9 213.6 184.3 231.5 147.5 246.8 82.4 205.2 178.7 222.2 142.8 237.0 78.7
80 229.1 211.3 242.1 185.8 260.3 140.1 220.9 205.2 233.2 180.5 250.7 135.7 212.6 199.1 224.1 175.1 240.8 131.1
85 238.2 228.2 247.7 210.1 264.2 177.4 229.9 221.7 238.8 204.3 254.6 172.3 221.4 215.1 229.6 198.2 244.7 167.0
90 248.2 242.4 255.6 228.7 268.1 204.4 239.7 235.5 246.5 222.4 258.4 198.7 230.9 228.5 237.2 215.9 248.5 192.8
75 227.7 198.6 244.9 159.6 268.2 92.0 219.2 192.8 235.5 154.6 258.0 88.1 210.5 186.8 225.9 149.6 247.5 84.0
80 236.1 221.2 247.7 194.6 268.8 147.6 227.6 214.8 238.5 189.0 258.7 142.8 218.8 208.3 229.0 183.2 248.4 137.9
85 245.9 239.0 254.3 220.0 269.5 186.2 237.3 232.2 245.0 213.8 259.5 180.8 228.4 225.2 235.5 207.4 249.2 175.1
90 256.5 254.0 262.9 239.5 274.3 214.3 247.7 246.8 253.5 232.9 264.3 208.2 238.5 238.5 243.9 226.0 254.0 202.0
75 232.4 206.1 247.9 165.7 269.7 96.6 223.5 200.0 238.2 160.5 259.1 92.4 214.4 193.6 228.2 155.0 248.3 87.9
80 241.7 229.8 252.0 202.0 271.5 153.8 232.8 223.0 242.4 196.0 261.0 148.6 223.7 216.1 232.5 189.9 250.3 143.3
85 252.3 248.5 259.5 228.5 273.4 193.7 243.3 241.3 249.9 221.9 263.0 187.8 234.1 233.9 240.0 215.2 252.4 181.8
90 263.5 263.5 268.9 249.0 279.2 222.8 254.3 254.3 259.1 241.9 268.8 216.4 244.8 244.8 249.1 234.7 258.1 209.8
75 235.6 212.3 249.6 170.5 269.8 99.9 226.4 205.7 239.5 164.9 260.5 95.3 217.0 199.0 229.2 159.1 249.2 90.5
80 245.9 237.0 254.9 208.1 272.8 158.6 236.7 229.9 244.9 201.7 262.0 153.1 227.2 222.6 234.6 195.2 250.9 147.4
85 257.3 256.6 263.3 235.7 275.9 199.7 247.9 247.9 253.3 228.7 265.1 193.5 238.3 238.3 243.1 221.6 254.1 187.1
90 269.1 269.1 273.5 257.1 282.7 229.9 259.5 259.5 263.4 249.6 271.9 223.2 249.6 249.6 253.0 242.0 260.9 216.2
75 237.5 217.0 249.9 174.0 271.0 101.8 228.0 210.1 240.5 167.9 261.3 96.8 218.1 203.0 229.8 161.7 252.3 91.6
11000
80 248.8 242.8 256.3 212.8 274.0 162.0 239.2 235.3 246.0 206.1 263.6 156.1 229.3 227.7 235.4 199.2 253.4 150.1
85 260.9 260.9 265.8 241.4 277.0 204.4 251.2 251.2 255.4 234.1 265.9 197.9 241.2 241.2 244.8 226.6 254.5 191.1
90 273.3 273.3 276.7 263.8 284.7 235.7 263.3 263.3 266.2 256.0 273.6 228.5 253.1 253.1 255.4 248.0 262.2 221.2
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC043AC-EN 75
Performance Data
Table 44. Gross cooling capacities 25 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD300G3,4,W (Digit 22 = B)
Air
Flow cfm (a)
5000
6500
8000
9000
10000
10500
11000
85
Ambient Temperature
95 105
Ent Entering Wet Bulb
DB 61 67 73 61 67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 237.6 170.2 266.9 137.2 298.3 101.7 226.6 164.3 254.2 130.9 284.0 95.4 215.0 158.1 241.1 124.7 269.5 89.1
80 237.8 197.2 266.6 164.6 298.3 130.4 226.8 191.3 254.2 158.7 284.5 124.4 215.2 184.8 241.2 152.8 269.5 117.9
85 238.0 223.6 266.8 192.2 298.3 157.9 227.3 217.6 254.4 186.3 284.5 150.8 216.0 211.0 241.3 180.0 269.3 145.0
90 244.4 244.4 267.0 219.3 298.3 185.7 235.5 235.5 254.6 213.1 284.2 179.6 226.0 225.9 241.7 206.9 269.5 173.2
75 251.7 194.9 281.3 151.1 313.6 103.1 239.4 188.7 267.3 144.8 297.7 96.7 226.4 182.1 252.8 138.0 281.0 90.0
80 252.2 230.1 281.5 185.9 313.9 142.8 239.8 223.7 267.7 179.8 299.0 134.7 227.0 216.7 253.1 173.7 281.5 129.6
85 257.9 257.7 282.0 223.2 313.7 176.7 248.0 247.9 268.2 217.0 297.6 170.9 237.2 237.2 253.6 210.5 281.8 163.8
90 272.5 272.4 282.5 258.1 314.3 213.5 262.0 261.9 268.8 251.7 298.7 207.5 250.8 250.7 254.4 244.6 282.3 201.7
75 260.7 217.8 290.3 162.9 322.7 103.2 247.6 211.8 276.0 155.2 305.8 96.6 233.7 205.3 260.1 149.5 288.2 90.1
80 262.3 259.5 291.1 207.3 323.0 153.7 249.7 247.8 276.3 201.2 306.2 146.9 238.4 236.1 260.8 195.0 288.7 139.6
85 277.8 277.7 291.9 252.8 324.9 192.8 266.3 266.3 277.0 246.3 307.1 188.1 254.2 254.2 261.6 239.2 289.8 182.0
90 293.7 293.6 293.9 292.8 324.5 241.9 281.8 281.8 280.5 277.0 307.8 235.5 269.1 269.1 269.3 268.3 290.6 229.1
75 265.2 233.5 294.9 170.4 326.8 103.2 251.5 226.7 279.5 163.8 309.5 97.1 237.2 219.2 263.4 156.9 291.4 90.9
80 269.5 264.6 294.7 223.9 328.3 159.2 259.7 259.5 280.4 215.9 310.2 152.6 247.7 247.6 264.4 209.5 292.4 145.4
85 288.2 288.1 296.6 271.4 328.6 206.7 276.1 275.9 281.4 264.7 311.4 201.1 263.2 263.2 265.9 256.5 293.6 196.0
90 302.2 301.5 303.9 299.6 329.4 260.3 292.3 292.2 292.9 292.7 311.8 255.6 278.9 278.9 279.6 279.5 294.5 248.5
75 268.8 247.3 298.4 178.1 330.1 104.0 254.7 240.1 282.6 171.2 312.4 98.0 240.0 233.0 266.2 164.6 293.6 91.6
80 279.8 279.8 299.5 236.4 331.3 165.7 267.6 267.5 284.2 228.6 313.0 159.1 254.0 254.5 267.3 223.1 295.4 151.0
85 297.2 297.2 300.7 289.4 332.4 221.0 284.4 284.3 285.0 281.9 314.7 215.8 270.9 270.7 269.0 265.0 296.6 209.8
90 315.0 315.0 315.6 315.6 333.5 279.6 301.5 301.5 302.1 301.9 316.4 271.6 287.3 287.2 287.9 287.6 297.7 265.0
75 270.3 254.1 300.1 181.8 332.2 103.2 256.1 246.9 283.8 175.0 313.4 98.3 241.2 239.6 267.4 168.8 294.6 91.9
80 283.5 283.4 301.2 243.4 332.8 168.0 271.0 270.7 285.1 236.6 314.6 149.6 257.8 257.6 268.5 229.6 296.6 153.9
85 301.2 301.2 302.5 297.8 334.1 228.5 287.5 287.2 286.5 283.2 316.3 222.6 274.3 274.2 271.3 263.2 297.9 216.4
90 319.3 319.3 320.0 319.8 335.2 288.2 305.5 305.3 306.2 305.9 317.5 280.7 291.0 290.9 291.6 291.5 299.1 272.8
75 271.7 260.7 301.5 185.8 332.6 105.1 257.3 253.5 285.1 179.1 314.5 98.9 242.4 239.2 268.5 173.1 295.9 92.6
80 287.0 286.7 302.6 250.0 334.2 170.7 273.9 273.7 286.4 243.2 316.9 162.5 260.6 260.6 269.7 235.9 297.6 156.7
85 305.1 304.9 304.5 304.2 335.6 235.1 291.3 291.2 288.4 280.2 317.6 229.0 277.4 277.4 274.0 262.8 299.1 222.8
90 323.4 323.3 324.1 323.8 336.7 295.8 309.2 309.1 309.9 309.7 318.9 288.2 294.5 294.5 295.1 295.0 300.4 280.4
76 RT-PRC043AC-EN
Performance Data
Table 44. Gross cooling capacities 25 tons three phase dehumidification (hot gas reheat) option high efficiency
T/YHD300G3,4,W (Digit 22 = B)
Air
Flow cfm
5000
115
Ambient Temperature
120 125
Ent
DB 61 67 73 61
Entering Wet Bulb
67 73 61 67 73
(°F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 202.6 151.6 227.5 118.5 253.9 82.4 196.1 148.2 220.0 114.8 245.8 79.0 189.5 144.9 212.3 111.2 237.3 75.6
80 202.9 178.2 227.2 145.7 253.8 111.3 196.5 175.0 220.0 142.3 245.6 107.9 189.8 171.5 212.6 138.9 237.3 104.5
85 204.6 203.6 227.5 173.3 253.9 138.4 199.2 199.2 220.4 170.0 245.9 135.1 193.9 193.9 213.0 166.6 237.6 131.8
90 215.9 215.9 227.9 200.1 254.2 166.7 210.6 210.6 220.7 196.6 246.2 163.4 205.0 204.9 213.3 193.2 237.9 160.1
75 212.7 175.3 237.9 130.0 264.1 83.1 205.6 171.9 229.7 127.2 255.2 79.7 198.4 168.5 221.5 123.5 246.0 76.1
6500
8000
9000
10000
10500
80 214.0 209.1 238.0 167.4 264.3 122.8 207.2 205.4 230.1 164.0 255.6 119.4 200.5 199.9 222.1 160.6 246.4 116.0
85 225.8 225.7 238.7 203.5 265.1 157.2 219.7 219.6 230.7 199.9 256.2 153.7 213.5 213.5 222.7 196.3 247.2 150.4
90 238.9 238.9 240.2 236.6 265.6 195.5 232.7 232.6 232.7 232.0 256.8 192.1 226.1 226.1 226.1 225.3 247.8 188.5
75 219.2 198.0 244.4 141.6 269.9 83.7 211.7 194.1 235.6 139.0 260.8 80.6 204.1 190.2 227.1 135.5 251.1 77.2
80 227.1 227.0 244.7 188.9 271.1 132.5 220.8 220.8 236.4 185.6 261.6 128.7 214.1 214.1 227.9 182.0 252.2 125.1
85 241.4 241.3 245.6 232.1 271.9 176.3 234.7 234.6 237.3 228.3 262.7 173.5 227.8 227.7 228.8 224.1 253.2 170.8
90 255.9 255.8 256.4 256.2 272.7 223.1 248.8 248.8 249.4 249.3 263.5 219.9 241.6 241.6 242.1 242.1 254.1 216.4
75 222.3 211.8 247.1 150.1 272.7 84.4 214.6 208.1 238.5 146.8 263.2 81.0 206.8 204.1 229.7 143.2 253.2 77.4
80 234.7 234.5 247.9 202.7 274.0 137.8 228.0 227.7 239.4 199.2 265.6 132.5 220.9 220.7 230.7 195.4 255.1 130.9
85 249.7 249.5 249.2 248.6 275.2 190.4 242.6 242.5 241.3 238.4 265.8 187.3 235.2 235.1 233.6 228.6 256.1 184.1
90 264.8 264.8 265.3 265.1 276.2 241.1 257.5 257.3 258.0 257.7 266.8 237.2 249.8 249.7 250.3 250.1 257.1 233.0
75 224.8 224.5 249.4 158.3 274.8 84.8 217.2 214.2 240.6 155.1 265.0 81.9 209.8 204.0 231.7 152.2 254.7 80.2
80 241.0 241.0 250.5 215.8 277.5 141.3 233.9 233.9 241.8 212.1 267.0 140.3 226.6 226.4 232.8 208.4 257.0 136.7
85 256.6 256.6 254.1 246.2 277.8 203.4 249.2 249.2 247.5 240.9 268.3 200.1 241.5 241.4 241.8 241.5 258.3 196.6
90 272.5 272.5 272.9 272.9 279.0 256.9 264.7 264.7 265.2 265.1 269.4 252.9 256.6 256.6 257.1 256.9 259.5 249.1
75 226.2 222.1 250.4 162.6 275.7 85.3 218.8 211.8 241.5 159.9 265.6 83.7 211.7 204.3 232.6 157.1 255.4 82.4
80 243.8 243.8 251.6 222.3 277.7 147.0 236.6 236.4 242.8 218.6 268.0 143.5 229.1 228.8 234.2 213.6 258.0 140.1
85 259.7 259.7 258.1 251.8 279.0 209.7 252.1 251.9 252.5 252.2 269.3 206.4 244.3 244.1 244.7 244.3 259.3 203.0
90 275.9 275.8 276.3 276.2 280.7 263.7 267.9 267.8 268.4 268.1 270.5 261.0 259.7 259.6 260.1 259.8 260.6 257.1
75 227.7 219.7 251.2 167.7 276.4 87.2 220.8 212.4 242.4 164.9 266.3 86.0 214.6 210.1 233.3 161.8 256.1 84.1
11000
80 246.4 246.2 252.6 228.5 278.6 149.9 239.1 238.8 243.7 224.6 268.8 146.8 231.5 231.3 234.6 220.7 259.6 141.2
85 262.6 262.4 263.0 262.6 280.5 214.9 254.8 254.6 255.2 254.9 270.2 212.8 246.9 246.7 247.2 246.9 260.2 209.1
90 279.0 278.9 279.5 279.2 281.4 272.9 270.9 270.8 271.3 271.0 271.6 269.0 262.5 262.4 263.0 262.8 261.5 258.0
Notes:
1.
All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes.
2.
MBh = Total Gross Capacity
3.
SHC = Sensible Heat Capacity
4.
*Indicates both downflow and horizontal units.
(a)For 5000, 6000, and 7000 cfm-Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC043AC-EN 77
Performance Data
Table 45. Evaporator fan performance 12½ tons TSD150G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4000 461 0.60
522 0.79
575 0.98
624 1.18
667 1.37
707 1.56
743 1.75
773 1.90
802 2.05
4500 410 0.51
485 0.74
545 0.95
598 1.17
645 1.39
688 1.60
728 1.82
765 2.04
800 2.25
833 2.47
5000 437 0.64
509 0.89
569 1.14
621 1.38
667 1.62
710 1.86
749 2.10
786 2.34
821 2.58
853 2.82
5500 465 0.79
535 1.08
593 1.35
644 1.62
690 1.88
732 2.14
771 2.41
807 2.67
842 2.94
874 3.20
6000 493 0.97
561 1.28
618 1.58
668 1.87
713 2.16
754 2.45
793 2.75
829 3.03
863 3.31 896 (a)
3-hp Standard Motor & High Static Drive
3.60
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive
4000 826 2.17
856 2.33
880 2.47
902 2.60
923 2.72
944 2.84
963 2.96
982 3.08 1002 3.20
1021 3.32
4500 858 2.64
888 2.82
909 2.96
932 3.11
958 3.29
981 3.46 1000 3.59 1020 3.73 1038 3.87
1056 4.00
5000 885 3.06
916 3.31
941 3.51
963 3.69
991 3.89 1010 4.06 1029 4.22 1051 4.40 1074 4.60
1094 4.78
5500 906 3.46
936 3.73
965 4.00
993 4.26 1019 4.53 1040 4.73 1061 4.93 1087 5.15 1104 5.34
1122 5.52
6000 927 3.89
957 4.18
986 4.47 1014 4.76 1041 5.06 1066 5.34 1091 5.64
-
5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
8.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)5-hp Oversized Motor & Drive
78 RT-PRC043AC-EN
Performance Data
Table 46. Evaporator fan performance 12½ tons TSH150G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
4000
4500
-
-
3-hp Standard Motor & Low Static Drive
-
-
3-hp Standard Motor & Drive
3 hp
Standard
Motor & High
Static Drive
494 0.80
558 1.02
613 1.23
662 1.44
707 1.64
749 1.84
787 2.04
824 2.24
851 2.40
521 1.00
584 1.26
638 1.50
686 1.74
731 1.98
772 2.21
811 2.43
847 2.66
882 2.88
5000 475 0.92
549 1.24
610 1.53
663 1.80
711 2.08
756 2.34
797 2.61
835 2.86
871 3.12
905 3.37
5500 506 1.15
578 1.50
637 1.83
690 2.15
737 2.45
781 2.75
821 3.04
859 3.34
895 3.62
929 3.91
6000 538 1.42
607 1.81
666 2.18
717 2.53
764 2.87
807 3.20
846 3.52
884 3.85
920 4.17
953 4.48
5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive
4000 882 2.63
909 2.80
935 2.99
961 3.19
991 3.42 1017 3.65 1043 3.88 1069 4.12 1093 4.35
1116 4.58
4500 915 3.10
941 3.27
968 3.53
994 3.75 1016 3.94 1042 4.18 1063 4.36 1090 4.62 1117 4.89
1139 5.13
5000 938 3.62
969 3.86
999 4.11 1029 4.36 1049 4.52 1074 4.82 1100 5.10 1118 5.28 1141 5.54
1162 5.77
5500 961 4.18
993 4.46 1022 4.73 1051 5.00 1080 5.28 1107 5.55
-
6000 986 4.79 1016 5.09 1046 5.40 1076 5.71
-
5-hp Oversized Motor & Drive
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
8.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
RT-PRC043AC-EN 79
Performance Data
Table 47. Evaporator fan performance 12½ tons with gas heat YSD150G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4000 511 0.75
559 0.92
601 1.08
639 1.24
673 1.40
706 1.56
736 1.71
763 1.85
793 2.00
816 2.12
4500 562 1.02
607 1.21
647 1.40
683 1.58
717 1.76
748 1.94
777 2.11
805 2.29
831 2.46
854 2.61
5000 614 1.35
656 1.56
694 1.77
729 1.98
761 2.18
791 2.38
820 2.57
847 2.77
873 2.97
898 3.17
5500 667 1.74
706 1.98
742 2.21
776 2.44
807 2.67
836 2.89
863 3.11
890 3.32
915 3.55
940 3.76
6000 720 2.21
757 2.48
791 2.73
823 2.98
853 3.23
881 3.47
908 3.72
934 3.96
959 4.20
982 4.43
3-hp Standard Motor & High Static Drive 5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive
4000 844 2.27
868 2.41
889 2.52
910 2.64
929 2.76
948 2.87
967 2.98
986 3.10 1003 3.21
1020 3.32
4500 883 2.78
905 2.93
926 3.07
951 3.24
973 3.40
993 3.54 1011 3.67 1028 3.79 1047 3.93
1064 4.06
5000 921 3.36
942 3.52
967 3.72
990 3.89 1009 4.05 1027 4.20 1051 4.39 1072 4.59 1091 4.75
1107 4.89
5500 962 3.97
985 4.19 1006 4.40 1027 4.60 1046 4.79 1069 5.00 1090 5.18 1108 5.37 1123 5.53
1144 5.72
6000 1005 4.67 1026 4.90 1048 5.14 1069 5.38 1089 5.61
-
5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
8.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
80 RT-PRC043AC-EN
Performance Data
Table 48. Evaporator fan performance 12½ tons with gas heat YSH150G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low
Static Drive
3-hp Standard Motor & Drive
3-hp
Standard
Motor & High
Static Drive
4000 562 1.04
610 1.22
653 1.40
692 1.57
727 1.74
760 1.90
791 2.06
820 2.22
842 2.34
875 2.58
4500 619 1.42
665 1.63
705 1.84
742 2.03
776 2.23
808 2.42
838 2.60
866 2.78
893 2.95
920 3.14
5000 678 1.88
720 2.13
758 2.36
793 2.58
826 2.80
857 3.02
886 3.23
914 3.43
940 3.64
966 3.84
5500 737 2.45
776 2.72
813 2.98
846 3.23
877 3.48
907 3.72
935 3.96
963 4.19
988 4.42
1013 4.64
6000 796 3.12
834 3.42
868 3.71
900 3.99
930 4.26
959 4.53
986 4.79 1012 5.05 1037 5.31
1062 5.56
5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive
4000 900 2.74
926 2.93
952 3.11
981 3.34 1008 3.56 1032 3.78 1057 4.01 1079 4.22 1102 4.45
1127 4.70
4500 939 3.26
967 3.53
992 3.74 1014 3.92 1037 4.13 1060 4.34 1085 4.57 1110 4.82 1134 5.07
1156 5.33
5000 990 4.03 1014 4.23 1035 4.41 1051 4.54 1079 4.89 1102 5.12 1121 5.31 1142 5.54
-
5500 1037 4.87 1060 5.08 1082 5.30 1104 5.52 1125 5.73
6000 -
-
-
-
-
-
-
5-hp Oversized Motor & Drive
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
8.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
RT-PRC043AC-EN 81
Performance Data
Table 49. Evaporator fan performance 15 tons TSD180G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor Drive
4800
5400
-
-
-
-
385 0.83
419 0.95
455 1.11
486 1.28
517 1.48
545 1.63
571 1.78
596 1.92
620 2.05
415 1.06
450 1.25
478 1.39
510 1.57
538 1.75
565 1.98
592 2.18
616 2.35
640 2.51
6000 387 1.03
447 1.38
477 1.59
507 1.75
533 1.92
562 2.12
588 2.30
613 2.55
637 2.82
660 3.02
6600 411 1.28
472 1.71
507 1.94
536 2.19
562 2.36
585 2.55
612 2.77
635 2.97
658 3.19
681 3.49
7200 436 1.58
496 2.05
539 2.41
564 2.64
591 2.89
614 3.07
635 3.28
659 3.51
682 3.74
703 3.96
5-hp Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Drive 3HP Standard Motor & High Static Drive
4800 643 2.19
664 2.32
685 2.44
705 2.57
724 2.69
743 2.81
761 2.93
779 3.05
797 3.16
813 3.27
5400 662 2.67
683 2.82
704 2.98
724 3.12
743 3.27
762 3.41
780 3.55
798 3.70
816 3.84
832 3.97
6000 682 3.20
704 3.38
724 3.56
744 3.73
763 3.91
782 4.07
800 4.24
817 4.40
835 4.57
851 4.73
6600 703 3.78
724 3.99
744 4.19
764 4.40
783 4.59
802 4.79
819 4.98
836 5.16
853 5.35
871 5.54
7200 725 4.24
745 4.56
765 4.89
784 5.11
803 5.34
822 5.56
840 5.78
857 6.00
873 6.20
890 6.42
5-hp Oversized Motor & Drive 7.5hp OS Motor & High Static Drive (a)
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 121 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)7.5HP high static oversized motor offering is field installed only.
82 RT-PRC043AC-EN
Performance Data
Table 50. Evaporator fan performance 15 tons TSH180G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4800 420 0.77
453 0.91
481 1.05
508 1.18
532 1.31
563 1.47
587 1.61
614 1.77
638 1.93
658 2.08
5400 464 1.06
494 1.22
521 1.37
546 1.52
570 1.67
592 1.81
619 2.00
642 2.15
664 2.32
687 2.50
6000 509 1.41
537 1.59
562 1.76
586 1.93
609 2.09
629 2.26
649 2.42
669 2.58
695 2.80
716 2.97
6600 554 1.83
580 2.03
604 2.22
627 2.41
648 2.59
668 2.78
687 2.96
706 3.14
724 3.32
745 3.53
7200 599 2.34
624 2.56
647 2.77
668 2.97
689 3.18
708 3.38
727 3.58
744 3.77
762 3.97
778 4.17
5-hp Oversized Motor & Standard Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor &
Drive
3HP Standard Motor & High Static Drive
4800 678 2.23
698 2.39
719 2.55
738 2.71
756 2.88
774 3.05
791 3.22
808 3.38
825 3.56
841 3.73
5400 709 2.67
728 2.84
747 3.02
764 3.19
782 3.37
800 3.55
818 3.73
835 3.91
851 4.10
868 4.30
6000 735 3.16
757 3.36
777 3.55
796 3.75
812 3.93
828 4.12
844 4.32
860 4.52
877 4.73
893 4.92
6600 767 3.75
785 3.93
804 4.14
822 4.35
841 4.57
860 4.79
876 5.00
891 5.20
907 5.42
920 5.63
7200 794 4.36
815 4.61
835 4.86
852 5.05
869 5.27
886 5.50
902 5.73
921 5.98
937 6.20
952 6.43
5-hp Oversized Motor & Standard Drive 7.5hp OS Motor & High Static Drive (a)
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 121 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)7.5HP high static oversized motor offering is field installed only.
RT-PRC043AC-EN 83
Performance Data
Table 51. Evaporator fan performance 15 tons with gas heat YSD180G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4800 379 0.80
415 0.93
449 1.08
484 1.26
513 1.46
544 1.63
573 1.79
600 1.94
627 2.09
651 2.24
5400 417 1.07
450 1.25
480 1.41
512 1.58
543 1.79
568 2.01
596 2.21
623 2.39
648 2.57
673 2.74
6000 456 1.43
486 1.64
515 1.80
542 1.98
571 2.18
599 2.41
622 2.65
645 2.89
671 3.10
695 3.30
6600 496 1.86
524 2.11
550 2.28
576 2.47
600 2.67
626 2.89
653 3.13
674 3.40
695 3.68
718 3.93
7200 535 2.39
562 2.61
587 2.86
610 3.05
633 3.26
655 3.47
679 3.71
705 3.97
726 4.26
745 4.57
5hp Oversized Motor & Low
Static Drive
5hp Oversized Motor & Standard Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Drive 3-hp Standard Motor & High Static Drive
4800 674 2.38
697 2.52
719 2.66
739 2.78
759 2.92
779 3.04
797 3.16
816 3.29
834 3.41
851 3.52
5400 696 2.92
718 3.08
740 3.24
760 3.40
780 3.55
799 3.71
819 3.86
837 4.01
854 4.15
872 4.29
6000 718 3.50
740 3.70
761 3.89
782 4.08
801 4.25
821 4.44
840 4.61
857 4.78
876 4.96
893 5.13
6600 740 4.15
762 4.38
783 4.59
803 4.81
824 5.02
842 5.22
861 5.44
880 5.64
896 5.83
914 6.03
7200 764 4.87
785 5.13
806 5.38
826 5.61
846 5.86
864 6.09
883 6.32
901 6.55
918 6.78
935 7.00
5-hp Oversized Motor & Standard Drive 7.5hp Oversized Motor & High Static Drive (a)
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 121 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating ranges.
(a)7.5HP high static oversized motor offering is field installed only.
84 RT-PRC043AC-EN
Performance Data
Table 52. Evaporator fan performance 15 tons with gas heat YSH180G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive 3-hp Standard Motor & Drive
4800 419 0.77
455 0.92
487 1.07
515 1.22
548 1.39
578 1.55
607 1.73
634 1.90
659 2.08
681 2.26
5400 462 1.05
496 1.22
526 1.39
553 1.56
578 1.72
603 1.89
635 2.10
661 2.29
687 2.49
711 2.68
6000 506 1.39
537 1.59
566 1.78
592 1.97
616 2.15
639 2.33
661 2.52
690 2.76
713 2.95
736 3.17
6600 550 1.81
579 2.03
606 2.24
631 2.45
654 2.65
677 2.86
698 3.06
717 3.25
738 3.46
766 3.74
7200 595 2.30
622 2.54
648 2.77
671 3.00
694 3.23
715 3.46
735 3.68
755 3.89
773 4.11
791 4.33
5hp Oversized Motor & Low Static Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor &
Drive
3-hp Standard Motor & High Static Drive
4800 704 2.44
728 2.63
750 2.83
772 3.03
793 3.23
813 3.43
833 3.64
852 3.85
872 4.07
890 4.28
5400 732 2.88
753 3.08
774 3.29
795 3.49
815 3.70
835 3.92
855 4.15
874 4.38
892 4.60
911 4.84
6000 761 3.40
783 3.61
803 3.82
822 4.04
841 4.27
859 4.50
877 4.73
896 4.95
914 5.18
933 5.44
6600 787 3.95
809 4.20
830 4.45
850 4.68
870 4.92
887 5.15
905 5.39
921 5.64
939 5.90
955 6.15
7200 814 4.60
838 4.88
856 5.11
876 5.37
896 5.64
916 5.91
934 6.16
951 6.42
968 6.68
983 6.93
5-hp Oversized Motor & Standard Drive 7.5hp Oversized Motor & High Static Drive (a)
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 89, p. 119
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 91, p. 121 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating ranges.
(a)7.5HP high static oversized motor offering is field installed only.
RT-PRC043AC-EN 85
Performance Data
Table 53. Evaporator fan performance 17½ tons TSD210/211G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory
5600 424 1.01
474 1.31
509 1.52
540 1.72
567 1.87
594 2.08
620 2.26
643 2.43
664 2.60
6300 392 001 450 1.27
498 1.60
541 1.93
572 2.16
599 2.39
622 2.55
648 2.75
671 2.99
695 3.20
7000 421 001 477 1.56
524 1.93
566 2.30
603 2.67
631 2.93
656 3.16
679 3.40
700 3.57
723 3.80
7700 451 001 505 1.90
551 2.31
591 2.72
628 3.12
662 3.53
689 3.84
711 4.06
733 4.37
752 4.58
8400 482 002 533 2.30
578 2.75
617 3.20
653 3.64
687 4.09
718 4.53
745 4.91
764 5.13
785 5.42
5-hp Standard Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive
5600 685 2.77
705 2.93
724 3.09
743 3.26
761 3.42
778 3.58
795 3.73
812 3.90
828 4.06
843 4.20
6300 715 3.39
734 3.58
753 3.76
772 3.96
790 4.14
807 4.33
824 4.51
840 4.69
856 4.87
871 5.04
7000 744 4.08
765 4.31
784 4.52
802 4.74
820 4.95
837 5.16
853 5.37
870 5.58
885 5.78
901 5.98
7700 772 4.77
792 5.02
812 5.34
831 5.60
850 5.85
867 6.09
884 6.32
900 6.56
914 6.78
930 7.01
8400 805 5.76
822 5.96
841 6.17
860 6.45
878 6.77
895 7.09
913 7.37
930 7.64
945 7.88
961 8.15
7.5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
86 RT-PRC043AC-EN
Performance Data
Table 54. Evaporator fan performance 17½ tons TSH210/211G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive
5600 439 1.10
487 1.40
530 1.68
568 1.98
591 2.10
614 2.32
634 2.53
654 2.76
673 2.98
692 3.20
6300 477 1.45
531 1.85
567 2.15
603 2.46
637 2.80
658 2.91
678 3.15
698 3.40
716 3.64
734 3.89
7000 517 1.87
571 2.36
605 2.70
641 3.05
672 3.39
703 3.78
725 3.97
742 4.15
760 4.42
777 4.69
7700 557 2.38
609 2.92
649 3.38
676 3.73
710 4.12
738 4.49
765 4.90
790 5.28
805 5.32
822 5.61
8400 598 2.97
647 3.57
690 4.16
719 4.54
745 4.95
776 5.38
801 5.78
826 6.20
852 6.67
868 6.88
5-hp Standard Motor & Drive 7.5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive
5-hp Standard Motor &
High Static Drive
5600 709 3.42
726 3.65
743 3.88
759 4.11
774 4.34
789 4.57
803 4.81
817 5.05
831 5.28
845 5.54
6300 751 4.14
767 4.39
783 4.64
798 4.89
814 5.15 829 (a) 5.41
843 5.67
857 5.92
870 6.18
884 6.46
7000 794 4.97
810 5.24
825 5.51
840 5.79
855 6.07
870 6.35
884 6.63
897 6.92
911 7.20
924 7.48
7700 838 5.92
854 6.22
869 6.52
883 6.81
898 7.13
912 7.43
925 7.72
939 8.04
952 8.34
8400 883 7.00
898 7.32
913 7.65
927 7.98
941 8.31
954 8.62
-
-
-
-
-
7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)5-hp Standard Motor & High Static Drive
RT-PRC043AC-EN 87
Performance Data
Table 55. Evaporator fan performance 17½ tons with gas heat YSD210/211G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive
5600 434 1.07
472 1.30
504 1.49
533 1.68
560 1.82
585 2.01
611 2.20
634 2.37
655 2.53
676 2.69
6300 478 1.45
514 1.71
546 1.97
571 2.15
598 2.37
622 2.55
645 2.71
668 2.96
691 3.16
711 3.35
7000 522 1.92
556 2.21
587 2.50
615 2.79
636 2.96
660 3.20
683 3.43
703 3.59
724 3.81
745 4.09
7700 568 2.48
599 2.81
628 3.13
655 3.45
680 3.75
699 3.93
720 4.18
742 4.47
761 4.67
779 4.85
8400 614 3.15
643 3.52
671 3.87
696 4.21
720 4.56
742 4.88
760 5.08
780 5.32
799 5.67 818 (a) 5.92
5-hp Standard Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive
5-hp Standard Motor &
High Static Drive
5600 695 2.85
714 3.01
732 3.16
750 3.32
766 3.47
783 3.62
799 3.77
814 3.92
830 4.07
845 4.22
6300 730 3.53
748 3.71
766 3.90
783 4.07
800 4.25
816 4.42
832 4.60
847 4.77
862 4.94
876 5.11
7000 765 4.31
784 4.53
801 4.73
818 4.93
834 5.13
850 5.33
866 5.53
881 5.73
896 5.93
910 6.11
7700 798 5.11
817 5.41
836 5.67
854 5.90
870 6.12
886 6.36
901 6.58
916 6.79
930 7.02
945 7.24
8400 835 6.11
852 6.31
870 6.62
886 6.94
904 7.22
921 7.50
937 7.75
952 8.00
966 8.24
980 8.49
7.5-hp Oversized Motor & Drive 7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)7.5-hp Oversized Motor & Drive
88 RT-PRC043AC-EN
Performance Data
Table 56. Evaporator fan performance 17½ tons with gas heat YSH210/211G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive
5600 479 1.35
523 1.63
560 1.91
584 2.03
607 2.25
630 2.48
651 2.72
671 2.95
690 3.18
709 3.42
6300 531 1.85
566 2.14
604 2.47
637 2.79
655 2.87
677 3.13
697 3.39
716 3.64
735 3.91
753 4.17
7000 583 2.48
613 2.80
649 3.14
678 3.47
709 3.85
726 3.96
744 4.17
763 4.46
780 4.74
798 5.03
7700 636 3.24
662 3.55
692 3.91
726 4.33
750 4.67
779 5.11
795 5.31
810 5.40
827 5.72
844 6.03
8400 687 4.11
713 4.45
739 4.87
768 5.26
798 5.73
819 6.08
846 6.57
864 6.90
875 6.84 891 (a) 7.17
7.5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive
5-hp Standard Motor &
High Static Drive
5600 727 3.66
744 3.91
761 4.15
777 4.39
793 4.65
808 4.88
823 5.13
837 5.39
851 5.64
865 5.90
6300 770 4.44
787 4.70
803 4.96
819 5.23
835 5.51
849 5.78
864 6.06
878 6.33
892 6.61
905 6.88
7000 815 5.33
831 5.62
847 5.91
862 6.20
877 6.50
892 6.80
906 7.10
920 7.41
933 7.70
947 8.01
7700 860 6.35
876 6.67
892 7.00
907 7.31
921 7.63
935 7.95
949 8.27
963 8.60
8400 907 7.52
922 7.86
937 8.21
952 8.56
-
7.5-hp Oversized Motor & High Static Drive
-
-
-
-
-
-
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
(a)7.5-hp Oversized Motor & High Static Drive
RT-PRC043AC-EN 89
Performance Data
Table 57. Evaporator fan performance 20 tons TSD240G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive
6400 473 1.55
504 1.76
533 1.96
560 2.15
585 2.33
609 2.51
633 2.69
656 2.89
677 3.10
699 3.31
7200 525 2.18
553 2.41
579 2.58
605 2.85
628 3.05
651 3.25
673 3.46
694 3.65
715 3.86
735 4.08
8000 577 2.95
603 3.14
627 3.42
651 3.62
674 3.93
695 4.15
715 4.36
735 4.59
755 4.82
774 5.04
8800 629 3.89
653 4.06
676 4.40
698 4.63
719 4.87
740 5.21
759 5.46
778 5.69
796 5.94
814 6.19
9600 682 5.02
704 5.20
726 5.48
747 5.84
766 6.06
785 6.35
805 6.72
823 7.01
840 7.26
857 7.52
7.5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive
6400 721 3.53
742 3.75
762 3.96
782 4.17
802 4.39
819 4.59
837 4.81
855 5.02
872 5.22
889 5.44
7200 754 4.32
774 4.56
793 4.80
813 5.05
832 5.30
850 5.54
868 5.78
884 6.01
902 6.26
918 6.49
8000 793 5.27
810 5.51
828 5.77
845 6.03
862 6.29
881 6.58
898 6.84
916 7.12
932 7.39
948 7.65
8800 832 6.44
849 6.69
866 6.93
883 7.20
899 7.47
915 7.75
930 8.03
947 8.35
9600 873 7.78
889 8.06
905 8.33
-
-
-
-
-
-
-
-
-
7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
90 RT-PRC043AC-EN
Performance Data
Table 58. Evaporator fan performance 20 tons TSH240G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive
6400 503 1.62
541 1.88
570 2.13
611 2.42
635 2.64
658 2.86
680 3.08
701 3.30
721 3.51
740 3.73
7200 555 2.20
590 2.52
620 2.81
648 3.10
685 3.43
707 3.68
729 3.93
749 4.17
768 4.42
786 4.67
8000 607 2.91
642 3.32
673 3.63
695 3.94
722 4.27
757 4.64
778 4.93
797 5.21
816 5.48
834 5.76
8800 660 3.76
695 4.25
721 4.60
748 4.97
768 5.30
793 5.66
826 6.09
847 6.42
865 6.72
883 7.03
9600 714 4.78
747 5.33
773 5.78
798 6.14
821 6.54
838 6.89
861 7.29
892 7.76
916 8.16
932 8.49
7.5-hp Oversized Motor & Drive
7.5-hp Oversized Motor & High Static
Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor &
Drive
5-hp Standard Motor & High Static Drive
6400 759 3.95
776 4.16
794 4.37
810 4.59
826 4.80
843 5.02
858 5.23
873 5.44
887 5.65
902 5.87
7200 805 4.91
822 5.15
838 5.39
855 5.64
871 5.88
886 6.12
901 6.35
916 6.60
931 6.84
944 7.07
8000 851 6.03
868 6.30
885 6.58
900 6.85
916 7.12
931 7.38
945 7.65
960 7.93
974 8.19
988 8.46
8800 899 7.33
916 7.63
932 7.94
947 8.24
962 8.53
-
9600 -
7.5-hp Oversized Motor & High Static Drive
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
RT-PRC043AC-EN 91
Performance Data
Table 59. Evaporator fan performance 20 tons with gas heat YSD240G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive 5-hp Standard Motor & Drive
6400 497 1.73
526 1.90
553 2.11
579 2.29
604 2.47
628 2.65
651 2.85
673 3.06
695 3.27
717 3.49
7200 552 2.39
578 2.58
603 2.82
627 3.04
650 3.24
672 3.45
694 3.65
715 3.86
735 4.09
754 4.32
8000 608 3.21
632 3.46
654 3.67
676 3.95
698 4.18
719 4.41
739 4.64
759 4.87
778 5.09
797 5.32
8800 664 4.20
686 4.52
707 4.71
727 5.00
747 5.30
767 5.56
786 5.80
804 6.06
822 6.31
840 6.56
9600 721 5.39
741 5.76
760 6.00
780 6.24
797 6.57
815 6.90
834 7.17
852 7.44
869 7.72
886 8.00
7.5-hp Oversized Motor & Drive 7.5-hp Oversized Motor &
High Static Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive
6400 739 3.71
759 3.92
779 4.14
798 4.35
817 4.57
835 4.78
852 4.98
869 5.19
887 5.41
903 5.62
7200 774 4.56
794 4.80
814 5.06
833 5.31
851 5.55
869 5.79
886 6.03
902 6.26
919 6.51
935 6.74
8000 815 5.57
832 5.83
849 6.10
868 6.38
886 6.65
903 6.92
920 7.19
937 7.47
953 7.74
969 8.00
8800 858 6.81
875 7.06
891 7.34
907 7.62
922 7.90
938 8.19
955 8.50
9600 902 8.27
918 8.53
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
92 RT-PRC043AC-EN
Performance Data
Table 60. Evaporator fan performance 20 tons with gas heat YSH240G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static 5-hp Standard Motor & Drive
6400 533 1.82
560 2.05
599 2.33
628 2.57
653 2.81
676 3.04
698 3.27
720 3.50
740 3.73
759 3.95
7200 592 2.54
620 2.82
643 3.04
680 3.37
705 3.64
727 3.91
748 4.17
769 4.43
789 4.70
807 4.95
8000 650 3.40
678 3.70
698 3.98
724 4.28
757 4.64
779 4.95
800 5.24
819 5.53
838 5.83
856 6.11
8800 709 4.45
736 4.77
758 5.15
774 5.39
801 5.77
832 6.17
852 6.50
871 6.82
889 7.14
907 7.47
9600 769 5.71
794 6.08
816 6.44
833 6.80
849
7.5-hp Oversized Motor & Standard Drive
7.08
876 7.53
904 7.95
924 8.32
-
7.5-hp Oversized Motor & High Static Drive
-
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive
6400 778 4.18
796 4.40
814 4.63
831 4.85
847 5.08
863 5.30
879 5.53
895 5.76
909 5.97
924 6.20
7200 825 5.21
843 5.46
861 5.72
876 5.96
893 6.22
909 6.48
924 6.74
939 6.99
953 7.23
968 7.49
8000 874 6.40
891 6.69
907 6.97
924 7.26
939 7.54
955 7.82
970 8.11
984 8.38
-
8800 924 7.79
941 8.11
957 8.43
9600 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Oversized Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
9.
For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan Speed” tables to determine operating range.
RT-PRC043AC-EN 93
Performance Data
Table 61. Evaporator fan performance 25 tons TSD300/301G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive
7000 532 2.08
559 2.25
588 2.49
612 2.62
637 2.87
662 3.09
686 3.28
708 3.48
729 3.68
750 3.87
7500 566 2.52
593 2.73
618 2.95
642 3.12
665 3.33
689 3.59
712 3.82
734 4.03
755 4.24
775 4.45
8000 600 3.04
626 3.27
648 3.44
674 3.72
694 3.86
717 4.14
739 4.40
760 4.65
781 4.87
800 5.09
8500 635 3.62
659 3.87
680 4.03
705 4.35
725 4.52
745 4.72
766 5.03
787 5.31
807 5.57
826 5.80
9000 670 4.28
692 4.52
713 4.73
734 4.97
757 5.29
775 5.43
794 5.69
814 6.01
834 6.31
853 6.58
9500 705 5.00
725 5.24
747 5.51
764 5.68
787 6.07
806 6.28
823 6.44
842 6.76
861 7.10
880 7.41
10000 740 5.81
758 6.04
781 6.37
797 6.54
816 6.85
838 7.23
854 7.38
871 7.59
889 7.93
907 8.29
10500 775 6.71
793 6.93
813 7.27
831 7.50
847 7.72
868 8.16
886 8.43
902 8.59
-
11000 811 7.69
827 7.93
846 8.25
865 8.56
-
7.5-hp Standard Motor & High Static Drive
-
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
7000 769 4.05
788 4.24
806 4.42
824 4.60
841 4.78
858 4.95
874 5.12
890 5.29
906 5.46
920 5.62
7500 794 4.66
813 4.86
831 5.06
848 5.26
865 5.45
881 5.64
897 5.83
913 6.01
928 6.20
944 6.39
8000 819 5.31
837 5.54
855 5.76
873 5.97
889 6.18
905 6.39
921 6.60
937 6.80
952 7.00
967 7.21
8500 845 6.03
863 6.27
881 6.52
897 6.75
914 6.98
930 7.21
946 7.43
962 7.66
977 7.88
991 8.09
9000 872 6.84
889 7.08
906 7.34
923 7.59
939 7.84
956 8.09
971 8.33
986 8.57
-
9500 898 7.70
915 7.97
932 8.23
949 8.50
10000 925 8.62
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10500
11000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive Accessory
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
94 RT-PRC043AC-EN
Performance Data
Table 62. Evaporator fan performance 25 tons TSH300/301G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive
7000 589 2.44
620 2.65
652 2.96
688 3.30
707 3.52
724 3.73
741 3.94
758 4.15
774 4.36
7500 583 2.57
618 2.85
651 3.18
682 3.56
715 3.78
742 4.12
759 4.35
775 4.58
791 4.80
807 5.03
8000 617 3.09
649 3.33
685 3.79
711 3.99
739 4.37
774 4.75
794 5.04
810 5.29
825 5.53
841 5.77
8500 652 3.67
681 3.92
717 4.39
742 4.65
770 5.10
794 5.31
828 5.79
845 6.08
860 6.33
875 6.60
9000 687 4.33
715 4.60
747 5.00
775 5.44
798 5.65
824 6.18
850 6.42
881 6.94
896 7.23
910 7.50
9500 722 5.05
749 5.34
776 5.66
808 6.26
829 6.49
853 6.92
877 7.32
904 7.67
931 8.20
945 8.48
10000 757 5.86
783 6.17
807 6.45
839 7.06
863 7.48
882 7.66
907 8.36
928 8.58
10500 792 6.75
817 7.08
840 7.37
868 7.87
895 8.50
-
11000 828 7.73
852 8.07
874 8.40
-
-
-
-
7.5-hp Standard Motor & High Static Drive
-
-
-
-
-
-
-
-
-
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
7000 789 4.57
803 4.77
818 4.99
832 5.20
845 5.40
859 5.61
872 5.83
885 6.03
897 6.24
909 6.45
7500 821 5.25
836 5.48
850 5.70
864 5.93
877 6.15
891 6.38
904 6.61
915 6.82
928 7.05
940 7.27
8000 855 6.01
869 6.25
883 6.50
897 6.74
910 6.97
922 7.21
935 7.45
947 7.68
959 7.92
972 8.18
8500 889 6.85
903 7.11
916 7.36
930 7.62
942 7.87
955 8.12
967 8.38
-
9000 924 7.77
937 8.04
950 8.31
963 8.59
-
9500
10000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10500
11000
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive Accessory
-
-
-
-
-
-
-
-
-
-
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC043AC-EN 95
Performance Data
Table 63. Evaporator fan performance 25 tons with gas heat YSD300/301G standard refrigeration system downflow
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive
7000 554 2.22
580 2.43
604 2.56
629 2.79
654 3.02
678 3.22
700 3.41
721 3.61
742 3.80
762 3.98
7500 590 2.72
614 2.90
638 3.10
660 3.28
684 3.54
707 3.77
729 3.98
749 4.19
769 4.40
789 4.60
8000 627 3.28
647 3.44
672 3.71
692 3.84
714 4.10
736 4.37
758 4.62
778 4.84
798 5.06
816 5.28
8500 663 3.90
682 4.05
706 4.37
726 4.53
745 4.73
766 5.03
787 5.31
807 5.56
826 5.80
844 6.03
9000 699 4.60
718 4.77
739 5.06
760 5.31
778 5.45
797 5.74
817 6.05
836 6.34
855 6.62
873 6.86
9500 735 5.37
754 5.58
773 5.82
794 6.17
811 6.32
829 6.53
847 6.85
866 7.18
884 7.49
902 7.77
10000 771 6.23
790 6.47
807 6.67
827 7.06
845 7.29
861 7.44
878 7.73
896 8.08
914 8.42
10500 807 7.17
827 7.46
842 7.63
861 8.00
880 8.36
895 8.52
-
11000 844 8.20
863 8.54
-
7.5-hp Standard Motor & High Static Drive
-
-
-
-
-
-
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
7000 780 4.17
798 4.34
817 4.53
834 4.70
850 4.87
866 5.04
882 5.21
897 5.37
913 5.54
928 5.70
7500 808 4.81
825 5.00
843 5.20
859 5.39
876 5.58
892 5.77
908 5.95
922 6.13
937 6.31
952 6.49
8000 835 5.50
852 5.72
869 5.93
886 6.15
902 6.35
918 6.55
933 6.75
948 6.95
963 7.15
978 7.35
8500 862 6.27
880 6.50
896 6.73
913 6.96
929 7.19
944 7.41
960 7.63
975 7.85
989 8.06
9000 891 7.11
908 7.36
924 7.61
940 7.86
956 8.10
971 8.34
986 8.58
-
9500 919 8.04
936 8.29
952 8.56
10000 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10500
11000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
96 RT-PRC043AC-EN
Performance Data
Table 64. Evaporator fan performance 25 tons with gas heat YSH300/301G standard refrigeration system horizontal
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive 7.5-hp Standard Motor & Drive
7000
7500
8000
8500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
596 2.17
628 2.44
659 2.72
687 2.99
715 3.27
741 3.55
586 2.20
618 2.48
646 2.74
676 3.04
705 3.34
732 3.63
758 3.93
608 2.50
639 2.81
667 3.10
694 3.38
722 3.70
749 4.01
775 4.33
604 2.58
633 2.85
660 3.16
689 3.49
715 3.78
741 4.10
767 4.43
793 4.77
9000 598 2.65
629 2.96
657 3.23
682 3.54
710 3.88
737 4.23
760 4.54
785 4.87
810 5.23
9500 598 2.80
624 3.03
654 3.38
682 3.67
707 3.97
731 4.32
757 4.68
782 5.04
804 5.36
828 5.72
10000 628 3.26
649 3.44
680 3.84
707 4.15
732 4.46
755 4.80
778 5.17
803 5.56
826 5.93
848 6.27
10500 657 3.76
676 3.91
705 4.32
732 4.68
756 4.99
779 5.33
801 5.70
824 6.10
848 6.51
869 6.88
11000 687 4.31
703 4.44
731 4.83
757 5.24
781 5.58
803 5.91
825 6.28
845 6.68
868 7.10
891 7.54
7.5-hp Standard Motor & High Static
Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
7000 766 3.82
789 4.09
812 4.38
834 4.65
856 4.94
877 5.22
897 5.51
916 5.78
936 6.07
954 6.35
7500 782 4.22
806 4.52
829 4.82
851 5.11
872 5.41
893 5.71
913 6.01
933 6.31
952 6.61
969 6.90
8000 800 4.65
823 4.97
845 5.28
867 5.59
889 5.92
909 6.23
929 6.54
948 6.85
967 7.18
985 7.49
8500 817 5.10
840 5.44
862 5.76
884 6.10
905 6.44
926 6.78
945 7.11
965 7.45
983 7.77 1001 8.11
9000 834 5.58
857 5.93
880 6.30
901 6.64
922 6.99
942 7.34
962 7.72
981 8.06 1000 8.42
-
9500 851 6.09
874 6.46
896 6.84
919 7.22
939 7.59
959 7.96
979 8.35
10000 869 6.63
892 7.04
915 7.43
935 7.81
957 8.22
-
-
-
-
-
-
-
-
-
-
-
-
-
10500 889 7.24
910 7.62
932 8.04
953 8.47
11000 911 7.92
930 8.30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
RT-PRC043AC-EN 97
Performance Data
Table 65. Evaporator fan performance—12½ tons—TH*150G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
2500 (a)
4000
-
-
-
-
-
-
-
-
-
-
-
-
370 0.32
417 0.43
458 0.54
496 0.66
531 0.79
564 0.91
593 1.03
623 1.16
386 0.42
430 0.54
472 0.67
508 0.80
543 0.94
576 1.08
606 1.22
635 1.35
360 0.43
404 0.55
447 0.68
486 0.81
522 0.96
556 1.11
588 1.26
619 1.40
647 1.55
387 0.59
426 0.71
465 0.85
502 0.99
537 1.14
570 1.29
602 1.44
631 1.59
660 1.74
4500 377 0.66
417 0.79
452 0.92
486 1.06
521 1.20
555 1.36
586 1.50
617 1.65
645 1.80
673 1.95
5000 409 0.88
448 1.03
481 1.17
512 1.30
542 1.44
573 1.59
604 1.74
633 1.89
662 2.04
688 2.18
5500 441 1.14
479 1.30
510 1.44
539 1.58
567 1.71
594 1.85
624 2.01
652 2.16
679 2.31
705 2.46
6000 474 1.42
510 1.59
540 1.74
568 1.88
594 2.01
620 2.15
645 2.29
671 2.45
698 2.62
724 2.81
3-hp Standard Motor & High Static Drive Accessory (b)
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory
3-hp Standard Motor & High Static Drive Accessory (c)
650 1.28
676 1.40
701 1.52
726 1.64
748 1.76
771 1.87
793 1.98
814 2.09
835 2.21
855 2.32
662 1.48
688 1.61
713 1.74
737 1.86
760 1.98
783 2.11
806 2.23
827 2.36
847 2.48
867 2.61
674 1.69
701 1.82
726 1.96
750 2.09
772 2.22
795 2.35
818 2.49
839 2.64
859 2.78
879 2.96
4000 687 1.89
713 2.04
738 2.18
762 2.32
785 2.47
808 2.62
829 2.79
851 2.97
871 3.17
891 3.40
4500 700 2.10
726 2.26
750 2.41
775 2.58
798 2.75
821 2.95
842 3.15
864 3.41
885 3.71
904 4.06
5000 714 2.34
740 2.50
765 2.68
788 2.87
811 3.09
834 3.36
855 3.66
875 4.02
897 4.49
917 5.04
5500
6000
730
748
2.63
3.02
755
772
2.81
3.26
778
795
3.02
3.54
801
818
3.26
3.89
824
839
3.56
4.32
846
860
3.93
4.85
868
881
5-hp Oversized Motor & Drive
4.40
5.51
889
-
4.96
-
909
-
5.65
-
-
-
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
98 RT-PRC043AC-EN
Performance Data
Table 66. Evaporator fan performance—12½ tons—THD150G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
2500 (a)
4000
—
—
—
—
—
—
—
—
—
—
—
—
369 0.32 416 0.42 458 0.52 496 0.63 530 0.74 561 0.85 591 0.97 618
383 0.41 429 0.52 470 0.64 508 0.76 543 0.88 575 1.01 606 1.13 634
358 0.42 403 0.53 444 0.64 484 0.77 520 0.90 554 1.04 587 1.18 618 1.32 647
386 0.57 424 0.67 464 0.80 500 0.93 535 1.07 569 1.21 600 1.36 629 1.52 658
1.09
1.26
1.47
1.69
4500 375 0.62 415 0.75 450 0.86 484 0.99 519 1.13 552 1.28 583 1.42 615 1.58 644 1.75 671
5000 407 0.82 446 0.97 479 1.09 510 1.22 540 1.37 572 1.53 602 1.69 630 1.84 658 2.01 686
1.92
2.20
5500 440 1.06 477 1.22 508 1.37 537 1.50 565 1.65 592 1.81 621 1.99 650 2.16 676 2.34 701
6000 471 1.34 508 1.52 538 1.69 566 1.84 592 1.99 617 2.15 643 2.32 669 2.51 695 2.71 721
2.51
2.90
3-hp Standard Motor & High Static Drive Accessory (b)
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory (b)
3-hp Standard Motor & High Static Drive Accessory (c)
645 1.22 670 1.35 694 1.48 718 1.61 740 1.75 762 1.88 783 2.02 803 2.17 823 2.31 843
660 1.40 686 1.54 710 1.69 733 1.83 755 1.98 777 2.13 798 2.28 819 2.44 839 2.60 858
674 1.61 700 1.76 725 1.91 749 2.07 771 2.23 793 2.39 814 2.56 834 2.73 854 2.90 873
2.46
2.76
3.07
4000 686 1.85 712 2.02 737 2.18 762 2.35 785 2.51 808 2.68 830 2.86 850 3.04 870 3.22 889
4500 698 2.10 724 2.28 749 2.47 773 2.65 797 2.84 820 3.02 842 3.21 863 3.39 884 3.58 904
5000 712 2.38 737 2.57 762 2.76 785 2.97 809 3.17 831 3.38 853 3.58 875 3.79 895 3.99 916
5500 727 2.70 753 2.90 776 3.10 799 3.31 822 3.52 844 3.74 865 3.96 886 4.19 907 4.42 927
6000 744 3.09 767 3.28 791 3.49 815 3.71 837 3.92 858 4.15 879 4.37 899 4.60 919 4.84 939
5-hp Oversized Motor & Drive
3.41
3.77
4.20
4.64
5.08
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
RT-PRC043AC-EN 99
Performance Data
Table 67. Evaporator fan performance—12½ tons—YH*150G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
5500 462 1.23
496 1.38
525 1.51
553 1.64
582 1.79 610 1.93
638 2.08
666 2.23
692 2.38
718
6000 497 1.53
530 1.69
558 1.83
584 1.96
610 2.09 636 2.24
662 2.39
688 2.56
713 2.73
738
3-hp Standard Motor & High Static Drive Accessory (b)
Continued
External Static Pressure (Inches of Water)
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
2500 (a)
263 0.15
322 0.23
375 0.33
421 0.44
463 0.56 501 0.68
536 0.80
568 0.92
599 1.04
627 1.16
292 0.23
344 0.33
393 0.43
436 0.55
477 0.69 515 0.82
549 0.96
582 1.10
612 1.23
640 1.36
324 0.35
369 0.45
413 0.57
455 0.71
494 0.84 529 0.99
563 1.14
595 1.29
626 1.43
655 1.57
4000 358 0.51
398 0.62
437 0.75
475 0.89
512 1.03 547 1.18
579 1.33
609 1.48
639 1.63
668 1.78
4500 392 0.71
429 0.84
464 0.97
499 1.11
532 1.25 566 1.41
597 1.55
627 1.70
655 1.85
682
5000 427 0.95
462 1.09
493 1.22
525 1.36
556 1.51 587 1.66
617 1.80
645 1.95
673 2.10
700
2.00
2.25
2.54
2.92
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory
3-hp Standard Motor & High Static Drive Accessory (c)
655 1.28
681 1.40
706 1.51
730 1.63
754 1.74 776 1.85
798 1.96
820 2.07
839 2.17
860 2.28
668 1.49
694 1.62
719 1.74
743 1.87
766 1.98 790 2.11
811 2.22
833 2.35
852 2.46
873 2.59
681 1.71
708 1.85
732 1.97
756 2.10
780 2.24 803 2.37
824 2.50
846 2.65
866 2.79
887 2.96
4000 695 1.93
721 2.07
746 2.22
770 2.36
794 2.50 816 2.66
838 2.82
859 3.00
879 3.20
899
4500 708 2.15
735 2.31
760 2.47
784 2.63
807 2.81 830 3.01
852 3.24
873 3.50
893 3.79
913
5000 725 2.41
750 2.57
773 2.75
798 2.97
821 3.20 843 3.47
865 3.81
887 4.22
907 4.71
926
5500 744 2.73
767 2.92
790 3.14
813 3.41
836 3.75 857 4.16
878 4.65
900 5.31
920 6.07
940
6000 761 3.14
786 3.42
809 3.74
831 4.15
852 4.64 873 5.25
894 6.07
913 6.97
934 8.19
954
5-hp Oversized Motor & Drive
3.44
4.18
5.27
7.01
9.61
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
100 RT-PRC043AC-EN
Performance Data
Table 68. Evaporator fan performance—12½ tons—YHD150G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
5500 460 1.15 493 1.30 523 1.44 552 1.58 579 1.73 607 1.90 636 2.08 664 2.26 689 2.43 714
6000 495 1.45 527 1.63 555 1.78 582 1.93 608 2.09 633 2.25 659 2.44 685 2.64 711 2.83 736
3-hp Standard Motor & Drive 3-hp Standard Motor & High Static Drive Accessory (b)
Continued
External Static Pressure (Inches of Water)
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
2500 (a)
—
—
—
—
—
—
—
—
374 0.33 420 0.43 462 0.54 500 0.64 534 0.75 565 0.87 594 0.99 621
391 0.43 436 0.54 476 0.65 513 0.78 548 0.90 580 1.03 610 1.15 638
— — 368 0.44 412 0.55 453 0.67 492 0.79 528 0.93 561 1.07 593 1.21 624 1.36 653
4000 356 0.49 397 0.60 435 0.71 474 0.84 509 0.96 545 1.11 577 1.25 608 1.41 638 1.57 666
1.11
1.29
1.50
1.74
4500 390 0.67 428 0.79 462 0.90 496 1.04 531 1.18 563 1.33 594 1.48 625 1.64 653 1.81 681
5000 425 0.89 460 1.02 492 1.15 522 1.28 554 1.43 585 1.60 614 1.76 642 1.91 671 2.09 698
1.98
2.27
2.61
3.02
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory (b)
3-hp Standard Motor & High Static Drive Accessory (c)
648 1.23 673 1.36 697 1.49 720 1.62 742 1.76 764 1.90 785 2.04 806 2.18 825 2.33 845
664 1.42 689 1.56 713 1.71 737 1.86 759 2.00 781 2.15 802 2.31 822 2.46 842 2.62 861
680 1.64 706 1.79 730 1.94 754 2.10 776 2.27 797 2.43 818 2.60 839 2.77 858 2.94 878
2.47
2.78
3.11
4000 693 1.90 719 2.06 744 2.23 768 2.39 792 2.56 814 2.73 835 2.91 855 3.09 875 3.27 894
4500 707 2.16 733 2.35 758 2.53 782 2.72 805 2.90 827 3.09 849 3.27 870 3.46 891 3.65 911
5000 723 2.46 748 2.65 772 2.85 795 3.05 818 3.26 841 3.47 862 3.67 884 3.88 904 4.08 924
5500 741 2.81 765 3.01 788 3.21 811 3.42 833 3.63 855 3.85 876 4.08 897 4.31 917 4.53 937
6000 758 3.21 782 3.41 806 3.62 829 3.84 850 4.06 871 4.28 892 4.51 912 4.75 932 4.99 951
5-hp Oversized Motor & Drive
3.46
3.84
4.28
4.76
5.24
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
RT-PRC043AC-EN 101
Performance Data
Table 69. Evaporator fan performance—15 tons—TH*180G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
3000 (a)
-
-
-
-
-
-
-
-
369 0.38
411 0.47
448 0.57
483 0.68
514 0.78
543 0.89
570 1.00
596 1.11
391 0.50
429 0.61
465 0.72
499 0.84
530 0.96
560 1.08
587 1.21
614 1.33
378 0.55
416 0.66
451 0.78
485 0.90
516 1.03
547 1.16
575 1.30
603 1.44
629 1.58
4800 370 0.62
408 0.74
443 0.87
476 0.99
507 1.12
537 1.26
565 1.40
593 1.55
619 1.71
645 1.86
5400 405 0.84
439 0.97
472 1.11
502 1.25
532 1.39
560 1.54
587 1.69
613 1.85
638 2.01
662 2.18
6000 440 1.11
472 1.25
502 1.40
531 1.56
558 1.72
584 1.87
610 2.03
635 2.20
659 2.37
682 2.54
6600 476 1.43
505 1.58
533 1.74
560 1.92
586 2.09
611 2.26
635 2.44
659 2.61
682 2.79
704 2.97
7200 512 1.81
539 1.98
565 2.15
590 2.33
615 2.52
639 2.71
661 2.90
683 3.08
706 3.28
727 3.47
3-hp Standard Motor & High Static Drive Accessory (b)
5-hp
Oversized
Motor &
Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory
3HP Standard Motor & High Static Drive Accessory (c)
620 1.23
643 1.35
664 1.47
684 1.59
703 1.72
722 1.86
740 1.99
757 2.13
775 2.27
791 2.41
638 1.46
662 1.59
684 1.73
705 1.86
726 2.00
746 2.14
765 2.28
784 2.42
801 2.57
817 2.72
654 1.73
678 1.87
701 2.02
723 2.17
744 2.32
764 2.47
784 2.62
802 2.78
821 2.94
839 3.10
4800 670 2.02
693 2.18
716 2.34
738 2.51
760 2.67
780 2.84
800 3.01
820 3.18
838 3.35
856 3.52
5400 686 2.35
709 2.52
732 2.70
753 2.88
775 3.06
795 3.24
815 3.42
835 3.61
854 3.80
872 3.98
6000 705 2.73
727 2.91
749 3.10
770 3.29
790 3.48
810 3.68
830 3.88
850 4.08
869 4.28
887 4.48
6600 725 3.16
747 3.35
767 3.55
788 3.75
808 3.96
827 4.17
846 4.37
865 4.59
884 4.80
902 5.02
7200 748 3.66
768 3.86
788 4.07
808 4.28
827 4.49
846 4.71
864 4.93
883 5.15
900 5.38
918 5.61
5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
102 RT-PRC043AC-EN
Performance Data
Table 70. Evaporator fan performance—15 tons—THD180G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
0.80
0.90
1.00
rpm bhp rpm bhp rpm bhp
3000 (a)
—
—
—
3-hp Standard Motor & Low Static Drive Accessory
— — — — — 387 0.49 424 0.61 458 0.72 489
3-hp Standard Motor & Drive
0.84 516 0.96 541 1.08 565 1.20
—
—
— — 367 0.51 407
354 0.54 391 0.67 426
0.63 441
0.80 460
0.76 472
0.94 492
0.89 502
1.08 520
1.02
1.23
532
546
1.16 559
1.38 572
1.30 584
1.54 598
1.44
1.70
4800 — — 383 0.73 418 0.86 449 1.01 480 1.15 510 1.31 540 1.48
5400 371 0.82 412 0.97 446 1.11 476 1.26 504 1.43 531 1.59 558 1.76
567
585
6000 403 1.08 441 1.25 475 1.41 504 1.57 530 1.74 555 1.93 580 2.11 604
6600 435 1.39 472 1.59 504 1.78 532 1.94 558 2.12 582 2.31 605 2.51 628
7200 467 1.75 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97
3-hp Standard Motor & High Static Drive Accessory (b)
653
1.65 591
1.94 611
2.29 629
2.71
1.81 614
2.13 635
2.48 653
672
1.98
2.32
2.69
3.11
3.19 674 3.41 694
5-hp Oversized Motor & Drive
3.62
1.80
rpm
1.90
2.00
bhp rpm bhp rpm bhp
3-hp Standard Motor &
Drive
3-hp Standard Motor & High Static Drive Accessory (b)
3-hp Standard
Motor & High
Static Drive
Accessory (c)
587 1.32 609 1.44 629 1.57 649 1.70 668 1.83 687 1.97 705 2.11
608 1.58 629 1.72 650 1.87 670 2.01 689 2.16 708 2.30 725 2.45
723 2.25 740 2.39 758
743 2.61 760 2.76 776
2.54
2.92
623 1.86 647 2.03 669 2.19 690 2.36 709 2.52 728 2.68 746 2.85 764
4800 636 2.16 659 2.34 682 2.52 704 2.71 726 2.90 746 3.09 765 3.28 783
3.01 781
3.46
3.18 797
817
3.35
3.83
5400 656 2.51 677 2.70 698 2.89 717 3.09 738 3.29 758 3.50 778 3.71
6000 676 2.90 698 3.11 718 3.32 737 3.53 756 3.74 774 3.95 792 4.17
6600 694 3.33 716 3.56 737 3.79 758 4.02 777 4.25 795 4.48 812 4.71 829 4.94 846 5.18 862 5.42
7200 715 3.84 735 4.06 755 4.30 775 4.55 795 4.80 814 5.05 833 5.31 849.90 5.56 — — — —
5-hp Oversized Motor & Drive
798
810
3.92 817 4.13 835 4.34
4.40 829 4.63 847 4.86
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
RT-PRC043AC-EN 103
Performance Data
Table 71. Evaporator fan performance—15 tons—YH*180G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory 3-hp Standard Motor & Drive
3000 (a)
-
-
-
-
376 0.39
417 0.49
454 0.59
488 0.69
519 0.80
547 0.91
574 1.02
600 1.13
359 0.42
400 0.52
438 0.63
473 0.75
506 0.87
537 0.99
566 1.11
594 1.24
619 1.36
390 0.59
427 0.70
462 0.81
495 0.94
526 1.07
555 1.21
584 1.34
611 1.48
637 1.63
4800 386 0.66
422 0.79
456 0.92
489 1.04
519 1.18
548 1.32
577 1.46
604 1.61
630 1.77
655 1.92
5400 422 0.90
456 1.04
487 1.18
517 1.32
546 1.47
574 1.62
600 1.77
626 1.93
651 2.09
675 2.26
6000 460 1.19
491 1.34
520 1.50
548 1.66
574 1.81
601 1.97
626 2.14
650 2.30
673 2.48
696 2.66
6600 498 1.54
526 1.70
554 1.87
580 2.05
605 2.22
629 2.39
653 2.57
676 2.75
699 2.93
720 3.11
7200 536 1.96
562 2.13
588 2.31
613 2.50
636 2.69
659 2.88
681 3.07
703 3.26
725 3.45
746 3.65
3-hp Standard Motor & High Static Drive Accessory (b)
5-hp
Oversized
Motor &
Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & High Static Drive Accessory
3HP Standard Motor & High Static Drive Accessory (c)
624 1.25
646 1.36
667 1.49
687 1.62
706 1.74
725 1.88
743 2.01
760 2.15
777 2.29
794 2.43
643 1.49
667 1.62
689 1.76
710 1.89
731 2.03
750 2.17
769 2.31
788 2.45
804 2.60
821 2.76
662 1.77
685 1.92
708 2.07
729 2.21
750 2.37
770 2.52
789 2.67
808 2.83
826 2.99
844 3.14
4800 679 2.08
703 2.24
725 2.41
747 2.57
768 2.74
789 2.91
808 3.08
827 3.25
845 3.42
863 3.59
5400 698 2.44
721 2.61
743 2.79
764 2.97
785 3.15
806 3.33
825 3.52
845 3.70
863 3.89
881 4.08
6000 719 2.84
741 3.03
762 3.22
783 3.41
803 3.61
823 3.80
842 4.00
862 4.20
880 4.40
898 4.61
6600 742 3.30
763 3.50
783 3.70
803 3.91
823 4.11
842 4.32
861 4.54
879 4.75
897 4.97
915 5.19
7200 766 3.84
786 4.05
806 4.26
825 4.47
844 4.68
863
5-hp Oversized Motor & Drive
4.91
881 5.13
899 5.36
916 5.58
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
104 RT-PRC043AC-EN
Performance Data
Table 72. Evaporator fan performance—15 tons—YHD180G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor & Low Static Drive Accessory
3000 (a)
—
—
—
—
—
—
—
—
355 0.40 393 0.51 429 0.63 463 0.74 493
377 0.53 415 0.66 448 0.79 478 0.91 509
— — 366 0.58 402 0.71 436 0.84 470 0.98 501 1.13 528
4800 358 0.66 397 0.78 430 0.92 461 1.07 492 1.21 522 1.38 551
3-hp Standard Motor & Drive
0.86 520 0.98 545 1.10 568
1.05 538 1.19 565 1.33 590
1.28 554 1.43 580 1.59 606
1.54 576 1.71 600 1.88 623
1.22
1.47
1.75
2.05
5400 393 0.90 430 1.04 461 1.19 490 1.35 517 1.51 545 1.67 572
6000 428 1.19 463 1.35 493 1.51 520 1.68 546 1.86 571 2.04 595
1.85 598 2.04 623 2.23 646
2.22 619 2.41 644 2.61 667
2.41
2.82
6600 463 1.54 496 1.73 525 1.90 552 2.07 576 2.26 599 2.46 622
7200 499 1.96 531 2.18 559 2.36 584 2.55 607 2.74 630 2.95 651
2.66 644
3.17 672
3-hp Standard Motor & High Static Drive Accessory (b)
2.86 666
3.38 692
3.06 688
3.60 713
3.27
3.82
5-hp Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor &
Drive
591 1.34 612 1.46 632 1.59 652
3-hp Standard Motor & High Static Drive Accessory
1.72 671 1.86 690 1.99 708
3HP Standard
Motor & High
Static Drive
Accessory (c)
2.13 725 2.27 743 2.42 761 2.56
613 1.61 634 1.76 655 1.90 674 2.04 693 2.19 712 2.34 729
631 1.91 654 2.08 676 2.24 696 2.40 715 2.57 734 2.73 752
2.49 746 2.64 763 2.79 780
2.90 769 3.07 786 3.23 802
2.95
3.41
4800
5400
6000
6600
7200
645 2.23 668
667 2.60 687
690 3.03 711
711 3.50 732
733 4.04 753
2.41 691
2.79 708
3.24 730
3.73 753
4.28 773
2.60 713
2.99 728
3.45 749
3.96 772
4.52 793
2.79 734 2.98 754
3.19 748 3.40 768
3.66 767 3.87 785
4.20 790 4.42 808
4.77 812 5.02 831
5-hp Oversized Motor & Drive
3.16 772
3.60 788
4.09 803
4.66 825
3.35 790 3.54 807 3.72 824
3.81 807 4.03 826 4.24 844
4.31 822 4.54 840 4.77 858
4.88 841 5.12 858 5.36 874
5.28 848.25 5.53 — — — — —
3.91
4.45
5.00
5.60
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Fan Sheave BK110X1 3/16 and 1VP50X7/8 Required.
(c) Fan Sheave BK110X1 3/16 and 1VP56X7/8 Required.
RT-PRC043AC-EN 105
Performance Data
Table 73. Evaporator fan performance— 17½ tons — TH*210G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory
3500 (a)
5600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — 470 0.86 501 1.00 531 1.13 558 1.27 582
462 0.94 494 1.09 521 1.24 547 1.39 573 1.54 599
— — 455 1.06 485 1.20 515 1.36 544 1.53 572 1.70 596 1.88 619
458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643
1.41
1.71
2.05
2.46
6300 — — 459 1.43 492 1.60 520 1.76 546 1.94 570 2.13 594 2.32 618 2.51 641 2.70 664
7000 460 1.65 495 1.86 526 2.07 554 2.24 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689
7700 498 2.13 531 2.38 562 2.62 589 2.82 614 3.02 637 3.22 658 3.44 678 3.66 698 3.90 717
8400 537 2.71 568 2.99 597 3.26 624 3.50 648 3.71 670 3.93 692 4.15 711 4.38 730 4.63 748
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
2.91
3.47
4.13
4.88
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
605 1.54 627 1.68 648 1.82 667 1.96 686 2.11 705 2.25 723 2.40 740 2.55 757 2.70 773
624 1.87 648 2.04 670 2.20 691 2.36 710 2.53 729 2.69 747 2.86 765 3.03 782 3.19 798
641 2.22 663 2.41 686 2.59 708 2.79 729 2.98 750 3.17 769 3.36 788 3.55 805 3.74 822
2.86
3.36
3.93
5600 665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841
6300 687 3.13 709 3.35 730 3.57 750 3.79 768 4.01 786 4.23 804 4.46 821 4.69 838 4.92 856
7000 710 3.68 731 3.91 752 4.15 772 4.40 792 4.64 811 4.89 828 5.14 845 5.38 861 5.62 878
7700 737 4.36 756 4.59 775 4.83 794 5.07 813 5.33 832 5.60 850 5.87 868 6.14 886 6.41 902
8400 767 5.14 784 5.38 802 5.63 820 5.89 837 6.15 854 6.41 872 6.68 889 6.97 907 7.26 924
7.5-hp Oversized Motor & Drive
4.54
5.15
5.87
6.68
7.55
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
106 RT-PRC043AC-EN
Performance Data
Table 74. Evaporator fan performance — 17½ tons — THD210G — dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
— — — — — — — — — —
5HP Standard Motor & Low
Static Drive Accessory
5HP Standard Motor & Drive
470 0.86 501 1.00 531 1.13 558 1.27 582 1.41 3500 (a)
—
—
—
—
—
—
—
—
—
—
—
—
— — 462 0.94 494 1.09 521 1.24 547 1.39 573 1.54 599
455 1.06 485 1.20 515 1.36 544 1.53 572 1.70 596 1.88 619
1.71
2.05
5600 — — — — 458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643
6300 — — 459 1.43 492 1.60 520 1.76 546 1.94 570 2.13 594 2.32 618 2.51 641 2.70 664
7000 460 1.65 495 1.86 526 2.07 554 2.24 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689
7700 498 2.13 531 2.38 562 2.62 589 2.82 614 3.02 637 3.22 658 3.44 678 3.66 698 3.90 717
2.46
2.91
3.47
4.13
8400 537 2.71 568 2.99 597 3.26 624 3.50 648 3.71 670 3.93 692 4.15 711 4.38 730 4.63 748 4.88
5HP Standard Motor & High Static Drive Accessory
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5HP Standard Motor & Drive 5HP Standard Motor & High Static Drive Accessory
605 1.54 627 1.68 648 1.82 667 1.96 686 2.11 705 2.25 723 2.40 740 2.55 757 2.70 773
624 1.87 648 2.04 670 2.20 691 2.36 710 2.53 729 2.69 747 2.86 765 3.03 782 3.19 798
641 2.22 663 2.41 686 2.59 708 2.79 729 2.98 750 3.17 769 3.36 788 3.55 805 3.74 822
5600 665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841
2.86
3.36
3.93
4.54
6300 687 3.13 709 3.35 730 3.57 750 3.79 768 4.01 786 4.23 804 4.46 821 4.69 838 4.92 856
7000 710 3.68 731 3.91 752 4.15 772 4.40 792 4.64 811 4.89 828 5.14 845 5.38 861 5.62 878
7700 737 4.36 756 4.59 775 4.83 794 5.07 813 5.33 832 5.60 850 5.87 868 6.14 886 6.41 902
8400 767 5.14 784 5.38 802 5.63 820 5.89 837 6.15 854 6.41 872 6.68 889 6.97 907 7.26 924
5.15
5.87
6.68
7.55
7.5HP Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC043AC-EN 107
Performance Data
Table 75. Evaporator fan performance—17½ tons—YH*210G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
3500 (a)
4200
4900
5600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — 476 0.89 508 1.02 537 1.16 563 1.30 587 1.43
472 0.99 502 1.14 529 1.28 555 1.43 581 1.59 607 1.76
— — 468 1.12 497 1.27 527 1.43 556 1.60 582 1.78 605 1.95 628 2.12
474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 2.56
6300 — — 482 1.55 512 1.71 538 1.88 563 2.07 587 2.26 610 2.45 634 2.64 657 2.84 680 3.06
7000 490 1.84 522 2.04 550 2.22 576 2.39 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707 3.65
7700 532 2.39 562 2.62 589 2.83 614 3.02 637 3.22 658 3.44 679 3.67 698 3.90 718 4.13 737 4.36
8400 574 3.03 603 3.30 629 3.55 653 3.76 675 3.97 696 4.20 715 4.43 734 4.68 752 4.93 770 5.18
5-hp Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
3500
4200
4900
610 1.57 631 1.71 652 1.85 672 1.99 690 2.14 709 2.28 726 2.43 744 2.58 760 2.73 777 2.89
632 1.92 655 2.09 677 2.25 697 2.41 716 2.58 735 2.74 753 2.91 770 3.08 787 3.24 803 3.42
650 2.30 673 2.48 695 2.67 717 2.86 738 3.06 758 3.25 777 3.44 795 3.63 812 3.82 829 4.01
5600 677 2.76 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65
6300 702 3.28 724 3.50 744 3.72 762 3.94 781 4.17 798 4.39 816 4.61 833 4.84 850 5.08 868 5.32
7000 727 3.88 748 4.11 769 4.36 789 4.60 808 4.85 826 5.10 843 5.34 859 5.59 875 5.83 891 6.08
7700 756 4.59 775 4.83 794 5.08 813 5.34 832 5.60 851 5.87 869 6.15 886 6.41 903 6.69 918 6.96
8400 788 5.44 806 5.69 824 5.95 841 6.21 858 6.46 876 6.74 893 7.03 910 7.32 927 7.61 944 7.91
7.5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
108 RT-PRC043AC-EN
Performance Data
Table 76. Evaporator fan performance — 17½ tons — YHD210G — dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
7700 532 2.39 562 2.62 589 2.83 614 3.02 637 3.22 658 3.44 679 3.67 698 3.90 718 4.13 737
8400 574 3.03 603 3.30 629 3.55 653 3.76 675 3.97 696 4.20 715 4.43 734 4.68 752 4.93 770
5HP Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5HP Standard Motor &
Low Static Drive
Accessory
5HP Standard Motor & Drive
474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 5600 — — — —
6300 — —
1.71 538 1.88 563 2.07 587 2.26 610 2.45 634 2.64 657 2.84 680
7000 490 1.84
(a) 522 2.04 550 2.22 576 2.39 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707
2.56
3.06
3.65
4.36
5.18
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5HP Standard Motor & High Static Drive Accessory
5600 677 2.76
(b) 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65
6300 702 3.28 724 3.50 744 3.72 762 3.94 781 4.17 798 4.39 816 4.61 833 4.84 850 5.08 868 5.32
7000 727 3.88 748 4.11 769 4.36 789 4.60 808 4.85 826 5.10 843 5.34 859 5.59 875 5.83 891 6.08
7700 756 4.59 775 4.83 794 5.08 813 5.34 832 5.60 851 5.87 869 6.15 886 6.41 903 6.69 918 6.96
8400 788 5.44 806 5.69 824 5.95 841 6.21 858 6.46 876 6.74 893 7.03 910 7.32 927 7.61 944
7.5HP Oversized Motor & Drive
7.91
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)5HP Standard Motor & Low Static Drive Accessory
(b)5HP Standard Motor & Drive
RT-PRC043AC-EN 109
Performance Data
Table 77. Evaporator fan performance—20 tons—TH*240G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
4000 (a)
6400
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — 456 0.88 486 1.02 514 1.16 541 1.31 569 1.46 595
451 1.02 481 1.16 512 1.32 541 1.49 568 1.66 592 1.82 615
— — 458 1.21 487 1.37 514 1.54 541 1.71 567 1.88 593 2.07 619 2.26 643
464 1.49 497 1.66 525 1.82 551 2.00 575 2.20 598 2.39 622 2.58 645 2.78 667
1.62
1.99
2.46
2.98
7200 470 1.77 505 2.00 536 2.21 564 2.40 589 2.58 612 2.78 634 3.00 655 3.21 676 3.43 697
8000 514 2.37 547 2.63 577 2.87 603 3.10 628 3.30 651 3.51 672 3.73 692 3.96 711 4.20 730
8800 560 3.10 590 3.38 618 3.65 644 3.92 667 4.16 690 4.39 711 4.61 731 4.84 749 5.09 767
9600 606 3.97 633 4.27 660 4.59 685 4.88 708 5.15 729 5.42 750 5.66 769 5.91 788 6.16 805
5-hp Standard Motor & High Static Drive Accessory
7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)
Continued
External Static Pressure (Inches of Water)
3.65
4.44
5.35
6.42
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
620 1.78 643 1.93 664 2.09 685 2.25 704 2.40 722 2.56 740 2.72 758 2.88 775 3.05 791
638 2.17 661 2.35 684 2.54 706 2.72 727 2.91 747 3.10 767 3.29 785 3.48 802 3.66 819
665 2.65 686 2.85 706 3.05 725 3.25 745 3.45 764 3.66 784 3.88 803 4.09 822 4.31 841
3.21
3.85
4.54
6400 690 3.20 712 3.43 733 3.65 753 3.88 772 4.10 790 4.32 807 4.55 824 4.78 841 5.01 858
7200 717 3.86 737 4.09 758 4.33 778 4.58 798 4.83 817 5.08 835 5.34 852 5.59 868 5.84 885
8000 749 4.68 768 4.92 786 5.16 804 5.41 823 5.66 841 5.93 859 6.20 877 6.48 895 6.76 912
8800 784 5.61 802 5.89
(b) 819 6.15 836 6.41 853 6.67 869 6.95 886 7.21 902 7.49 919 7.78 936
9600 822 6.69 839 6.98 854 7.26 870
7.5-hp Oversized Motor & Drive
7.55 886 7.85 901 8.13 917 8.42 — — —
7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)
— —
5.25
6.10
7.04
8.09
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
8.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
9.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)
(c) Field supplied motor sheave 1VP50 x 1 1/8 required.
110 RT-PRC043AC-EN
Performance Data
Table 78. Evaporator fan performance—20 tons—THD240G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
4000 (a)
6400
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — 454 0.88 485 1.01 513 1.16 540 1.30 568 1.46 594
449 1.01 480 1.15 510 1.31 540 1.48 567 1.65 591 1.81 614
— — 456 1.20 485 1.36 512 1.53 539 1.70 565 1.87 591 2.05 617 2.24 641
461 1.47 494 1.65 523 1.81 549 1.99 573 2.18 596 2.37 619 2.56 642 2.76 665
1.61
1.98
2.44
2.96
7200 467 1.75 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97 653 3.19 674 3.41 694
8000 511 2.35 544 2.60 573 2.85 601 3.08 625 3.28 648 3.48 670 3.70 690 3.93 709 4.16 728
3.62
4.41
8800 556 3.06 586 3.34 614 3.62 640 3.89 664 4.13 687 4.36 708 4.58 728 4.80 746 5.05 764
9600 601 3.91 629 4.22 656 4.53 680 4.82 704 5.12 726 5.38 746 5.62 766 5.87 784 6.10 802
5-hp Standard Motor & High Static Drive Accessory 7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)
5.31
6.37
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Drive 5-hp Standard Motor & High Static Drive Accessory
619 1.77 642 1.93 663 2.08 683 2.24 703 2.39 721 2.55 739 2.71 757 2.87 774 3.04 790
636 2.16 659 2.34 682 2.52 704 2.71 726 2.90 746 3.09 765 3.28 783 3.46 801 3.65 817
663 2.64 684 2.83 704 3.03 724 3.23 743 3.43 763 3.64 782 3.86 802 4.08 821 4.29 839
3.20
3.83
4.51
6400 688 3.18 710 3.40 731 3.63 751 3.85 770 4.08 788 4.30 805 4.52 822 4.75 839 4.98 856
7200 715 3.84 735 4.06 755 4.30 775 4.55 795 4.80 814 5.05 833 5.31 850 5.56 866 5.81 882
8000 747 4.65 765 4.89 784 5.12 802 5.37 820 5.62 838 5.89 856 6.16 874 6.44 892 6.71 909
8800 782 5.57 799 5.84
(c) 816 6.10 833 6.36 850 6.63 866 6.89 883 7.16 899 7.44 916 7.73 933
9600 819 6.64 835 6.92 851 7.21 867 7.49 883 7.79 898
7.5-hp Oversized Motor & Field Supplied Motor Sheave
8.08 914 8.36 —
7.5-hp Oversized Motor & Drive
— — — —
5.22
6.06
7.00
8.03
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Field supplied motor sheave 1VP50 x 1 1/8 required.
(c) 7.5-hp Oversized Motor & Field Supplied Motor Sheave (b)
RT-PRC043AC-EN 111
Performance Data
Table 79. Evaporator fan performance—20 tons—YH*240G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
4000 (a)
—
—
—
—
—
—
—
—
—
—
—
—
— — 465 0.92 494 1.06 522 1.20 549 1.35 576 1.51 602 1.66
463 1.07 493 1.22 524 1.39 552 1.56 578 1.72 601 1.89 624 2.06
— — — — 474 1.29 501 1.46 528 1.63 555 1.80 581 1.98 607 2.17 632 2.37 655 2.56
6400 454 1.43 487 1.61 517 1.77 544 1.95 568 2.14 591 2.33 615 2.52 638 2.72 661 2.92 684 3.14
7200 502 1.98 533 2.19 561 2.38 587 2.56 610 2.76 632 2.97 653 3.19 674 3.41 695 3.63 715
8000 550 2.64 579 2.89 606 3.12 631 3.32 653 3.53 674 3.75 694 3.98 713 4.22 732 4.47 751
8800 599 3.46 627 3.75 652 4.00 675 4.23 697 4.45 718 4.69 737 4.93 755 5.18 773 5.44 790
9600 648 4.44 674 4.74 698 5.04 721 5.33 742 5.56 761 5.80 780 6.05 798 6.30 815 6.58 832
5-hp Standard Motor &
High Static Drive Accessory
7.5-hp Oversized Motor &
Field Supplied Motor Sheave (b)
7.5-hp Oversized
Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
3.84
4.70
5.71
6.86 cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor & High Static Drive Accessory
627 1.82 649 1.98 670 2.13 690 2.29 709 2.45 728 2.61 745 2.77 763 2.93 779 3.09 796 3.26
647 2.24 670 2.42 693 2.61 714 2.80 735 2.99 755 3.18 774 3.36 792 3.55 809 3.74 825 3.92
677 2.76 697 2.96 717 3.15 736 3.36 755 3.56 775 3.78 795 3.99 814 4.21 832 4.43 850 4.65
6400 706 3.36 727 3.58 748 3.81 766 4.03 784 4.26 802 4.48 819 4.71 836 4.94 853 5.18 870 5.42
7200 735 4.07 756 4.31 776 4.56 795 4.80 815 5.06 833 5.31 850 5.57 867 5.81 883 6.06 899
8000 770 4.94 788 5.18 806 5.44 825 5.69 843 5.96 861 6.23 879 6.51 896 6.79 913 7.07 930
8800 807 5.97 825 6.23 841 6.50 858 6.77 875 7.03 891 7.30 908 7.58 925 7.89 941 8.19 958
9600 848 7.14 864 7.43 879 7.73 895 8.01 911 8.30 926 8.59 — — — — — — —
6.32
7.36
8.49
—
7.5-hp Oversized Motor & Drive
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Field supplied motor sheave 1VP50 x 1 1/8 required.
112 RT-PRC043AC-EN
Performance Data
Table 80. Evaporator fan performance—20 tons—YHD240G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor & Low Static Drive Accessory 5-hp Standard Motor & Drive
4000 (a)
—
—
—
—
—
—
—
—
—
—
—
—
— — 464 0.91 493 1.05 521 1.20 548 1.34 575 1.50 601 1.66
461 1.07 492 1.21 522 1.38 551 1.54 576 1.71 600 1.88 623 2.05
— — — — 472 1.28 500 1.45 527 1.62 553 1.79 579 1.96 605 2.15 630 2.35 654 2.55
6400 451 1.42 485 1.60 515 1.76 541 1.93 566 2.12 589 2.32 613 2.51 636 2.70 658 2.90 681 3.12
7200 499 1.96 531 2.18 559 2.36 584 2.55 607 2.74 630 2.95 651 3.17 672 3.38 692 3.60 713
8000 548 2.64 577 2.88 603 3.10 627 3.29 650 3.50 672 3.72 691 3.95 711 4.19 730 4.43 748
3.82
4.67
8800 596 3.45 623 3.71 649 3.97 672 4.21 694 4.43 715 4.66 734 4.89 752 5.13 770 5.39 787 5.66
(b)
9600 645 4.41 670 4.70 694 4.98 717 5.26 738 5.52 758 5.76 777 6.00 795 6.25 812 6.52 829 6.80
5-hp Standard Motor
& High Static Drive
Accessory
7.5-hp Oversized Motor
& Field Supplied Motor Sheave (c)
7.5-hp Oversized Motor & Drive
Continued
1.10
1.20
1.30
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor & High Static Drive Accessory
626 1.81 648 1.97 669 2.12 689 2.28 708 2.44 726 2.60 744 2.76 762 2.92 778 3.08 795 3.25
645 2.23 668 2.41 691 2.60 713 2.79 734 2.98 754 3.16 772 3.35 790 3.54 807 3.72 824 3.91
675 2.74 695 2.94 715 3.14 734 3.34 753 3.54 773 3.76 793 3.97 812 4.19 831 4.41 849 4.63
6400 704 3.34 725 3.56 746 3.79 764 4.01 783 4.23 800 4.46 817 4.69 834 4.91 851 5.15 868 5.39
7200 733 4.04 753 4.28 773 4.52 793 4.77 812 5.02 831 5.28 848 5.53 865 5.78 881 6.03 896
8000 767 4.91 785 5.15 804 5.40 822 5.65 840 5.92 858 6.19 876 6.46 894 6.75 911 7.03 927
8800 805 5.93
(d) 822 6.19 839 6.45 855 6.72 872 6.99 888 7.25 905 7.54 922 7.83 938 8.13 955
— — — — — — 9600 845 7.09 861 7.38 876 7.67 892 7.96 907 8.24 923 8.52 —
7.5-hp Oversized Motor
& Field Supplied Motor Sheave (c)
7.5-hp Oversized Motor & Drive
6.29
7.31
8.43
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)5-hp Standard Motor & High Static Drive Accessory
(c) Field supplied motor sheave 1VP50 x 1 1/8 required.
(d)7.5-hp Oversized Motor & Field Supplied Motor Sheave (c)
RT-PRC043AC-EN 113
Performance Data
Table 81. Evaporator fan performance—25 tons—TH*300G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
5000 (a)
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — — — 575 1.75 599 1.93 622 2.10
579 2.26 603 2.46 626 2.65 648 2.85 671 3.06
— — 580 2.42 603 2.63 625 2.83 646 3.05 668 3.25 689 3.47
579 2.65 604 2.84 627 3.04 648 3.26 669 3.48 689 3.71 709 3.93
8000
8500
—
—
—
—
— — 577 2.87 603 3.10 628 3.30 651 3.51 672 3.73 692 3.96 711 4.20 730 4.44
574 3.09 602 3.34 628 3.60 653 3.83 675 4.04 696 4.25 716 4.49 735 4.74 753 5.00
9000 572 3.31 600 3.58 628 3.87 654 4.15 678 4.40 700 4.63 720 4.86 740 5.08 759 5.34 777 5.60
9500 600 3.85 628 4.17 655 4.47 680 4.75 703 5.02 724 5.27 745 5.52 764 5.76 783 6.00 801 6.28
10000 627 4.42 656 4.78 681 5.09 705 5.41 728 5.71 749 5.99 770 6.26 789 6.50 807 6.76 825 7.02
10500 657 5.13 683 5.45 708 5.80 731 6.13 753 6.44 775 6.76 794 7.04 813 7.31 831 7.57 849 7.84
11000 685 5.81 711 6.21 735 6.58 758 6.93 778 7.23 800 7.58 819 7.88 838 8.19 856 8.45 —
7.5-hp Standard Motor & High Static Drive Accessory
—
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
644
693
710
2.28 666
3.28 715
3.68 731
2.46 688
3.50 736
3.91 752
2.65 710
3.73 757
4.15 772
2.85 731
3.96 775
4.40 792
3.04
4.19
4.64
729 4.16 748 4.38 768 4.62 787 4.87 807 5.13
8000 749 4.68 768 4.92 786 5.16 804 5.41 823 5.66
8500 771 5.25 789 5.51 806 5.76 824 6.02 841 6.28
9000 794 5.87 811 6.14 827 6.41 844 6.69 861 6.95
9500 817 6.55 834 6.83 850 7.12 866 7.41 882 7.69
10000 841 7.29 857 7.59 873 7.87 888 8.18 904 8.48
10500 865 8.11 881 8.41 —
11000 — — — — —
—
—
—
—
—
—
—
—
7.5-hp Standard Motor & High Static Drive Accessory
—
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
114 RT-PRC043AC-EN
Performance Data
Table 82. Evaporator fan performance—25 tons—THD300G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive
5000 (a)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
602 1.57
633 1.73
661 1.89
688 2.05
587 2.00
614 2.18
640 2.35
665 2.53
690 2.70
714 2.89
739 3.08
588 2.19
616 2.39
641 2.57
666 2.75
690 2.94
713 3.13
736 3.32
759 3.52
593 2.42
620 2.63
645 2.82
670 3.02
693 3.21
716 3.41
738 3.61
760 3.82
782 4.02
8000 597 2.66
625 2.89
650 3.09
674 3.29
698 3.51
722 3.73
743 3.93
765 4.15
785 4.36
806 4.57
8500 632 3.18
658 3.41
683 3.64
706 3.86
728 4.07
750 4.29
771 4.51
792 4.74
812 4.97
832 5.20
9000 666 3.74
692 4.00
714 4.22
737 4.46
757 4.67
779 4.92
799 5.15
819 5.39
839 5.64
858 5.88
9500 701 4.38
726 4.67
746 4.87
769 5.15
788 5.36
808 5.61
828 5.86
847 6.10
866 6.36
885 6.62
10000 737 5.11
760 5.39
778 5.60
800 5.89
819 6.11
838 6.37
858 6.64
876 6.89
895 7.17
913 7.45
10500 766 5.76
792 6.15
813 6.44
832 6.70
851 6.96
869 7.21
888 7.50
905 7.75
923 8.05
941 8.33
11000 806 6.73
824 6.98
844 7.27
864 7.56
883 7.88
900 8.14
918 8.44
7.5-hp Standard Motor & Drive
-
7.5-hp Standard Motor & High Static Drive Accessory
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor &
Low Static Drive
7.5-hp Standard Motor & Drive
712 2.20
736 2.36
758 2.52
779 2.67
799 2.82
763 3.28
787 3.48
810 3.69
833 3.90
855 4.11
782 3.73
805 3.94
827 4.15
849 4.37
871 4.59
803 4.23
825 4.44
846 4.66
867 4.89
888 5.12
8000 826 4.79
846 5.01
867 5.24
886 5.47
906 5.71
8500 851 5.42
870 5.65
889 5.88
908 6.12
927 6.37
9000 876 6.11
895 6.36
913 6.61
931 6.85
949 7.09
9500 903 6.88
921 7.13
938 7.38
955 7.63
973 7.89
10000 930 7.70
947 7.97
964 8.22
981 8.50
-
10500 958 8.60
11000 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive Accessory
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
RT-PRC043AC-EN 115
Performance Data
Table 83. Evaporator fan performance—25 tons—YH*300G
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Drive
5000 (a)
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — — — 586 1.83 609 2.00 632 2.18
596 2.41 619 2.60 642 2.80 664 3.00 687 3.22
— — 599 2.59 621 2.80 643 3.01 665 3.22 686 3.43 707 3.65
603 2.83 626 3.03 648 3.25 668 3.47 688 3.70 708 3.92 728 4.15
8000 — — — — 606 3.12 631 3.32 653 3.53 674 3.75 694 3.98 713 4.22 732 4.47 751
8500 582 3.16 609 3.41 635 3.66 658 3.87 680 4.09 701 4.31 721 4.55 739 4.80 757 5.05 775
9000 611 3.68 639 3.99 664 4.25 687 4.49 708 4.73 728 4.95 748 5.18 766 5.44 783 5.71 800
9500 644 4.36 668 4.60 692 4.89 715 5.16 736 5.41 756 5.66 775 5.89 793 6.15 810 6.43 826
10000 676 5.05 698 5.31 722 5.62 744 5.93 764 6.19 784 6.44 802 6.68 820 6.95 837 7.22 853
10500 703 5.70 728 6.07 752 6.43 772 6.72 792 7.00 811 7.27 829 7.54 847 7.81 864 8.08 880
11000 739 6.65 759 6.93 780 7.27 801 7.58 821 7.92 840 8.23 857 8.48 —
7.5-hp Standard Motor & High Static Drive Accessory
— — — —
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
4.70
5.31
5.98
6.71
7.51
8.38
—
7.5-hp Standard Motor & Drive
653 2.36 675 2.54 697 2.74 719 2.93 740 3.13
709 3.44 731 3.67 751 3.90 770 4.13 788 4.35
727 3.88 748 4.11 769 4.36 789 4.60 808 4.85
748 4.37 767 4.61 787 4.86 806 5.12 825 5.38
8000 770 4.94 788 5.18 806 5.44 825 5.69 843 5.96
8500 793 5.57 811 5.83 828 6.08 845 6.34 862 6.61
9000 817 6.25 834 6.52 851 6.79 867 7.06 884 7.34
9500 843 6.99 858 7.27 875 7.57 890 7.84 906 8.13
10000 869 7.79 884 8.10 899 8.39 — — — —
10500
11000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7.5-hp Standard Motor & High Static Drive Accessory
—
—
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
116 RT-PRC043AC-EN
Performance Data
Table 84. Evaporator fan performance—25 tons—YHD300G—dehumidification (hot gas reheat) option
0.10
0.20
0.30
External Static Pressure (Inches of Water)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor & Low Static Drive Accessory
5000 (a)
-
-
-
-
-
-
-
-
-
-
-
-
584 1.48
613 1.63
642 1.78
670 1.94
696 2.10
606 2.13
633 2.30
658 2.47
683 2.65
708 2.84
732 3.03
756 3.22
585 2.17
612 2.36
637 2.54
662 2.72
686 2.91
710 3.10
733 3.30
756 3.49
779 3.70
593 2.44
618 2.60
645 2.82
668 3.01
692 3.20
716 3.41
737 3.60
760 3.81
781 4.01
803 4.23
8000 626 2.88
654 3.12
677 3.32
700 3.53
723 3.75
745 3.95
767 4.17
788 4.38
808 4.60
829 4.82
8500 665 3.48
688 3.68
711 3.90
733 4.13
755 4.35
776 4.57
797 4.80
816 5.02
836 5.25
855 5.47
9000 702 4.11
723 4.31
745 4.54
766 4.78
787 5.02
807 5.26
827 5.49
846 5.73
865 5.97
884 6.21
9500 734 4.72
758 5.01
780 5.27
799 5.49
820 5.77
838 5.99
858 6.27
876 6.50
895 6.76
913 7.02
10000 771 5.49
796 5.83
815 6.09
835 6.34
852 6.55
871 6.82
889 7.10
907 7.35
925 7.63
942 7.89
10500 814 6.50
831 6.68
848 6.90
869 7.23
886 7.46
903 7.73
921 8.00
939 8.30
956 8.57
-
11000 848 7.34
866 7.61
885
7.5-hp Standard Motor & Drive
7.92
903 8.19
920 8.46
-
7.5-hp Standard Motor & High Static Drive Accessory
-
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
722 2.27
(b) 746
7.5-hp Standard Motor & Drive
2.43
770 2.60
791 2.76
812 2.92
779 3.41
801 3.61
823 3.81
845 4.01
866 4.22
801 3.90
822 4.10
844 4.31
865 4.53
885 4.75
824 4.44
845 4.66
866 4.88
886 5.10
905 5.32
8000 849 5.05
869 5.27
889 5.51
908 5.73
927 5.97
8500 875 5.72
895 5.96
913 6.19
932 6.43
951 6.68
9000 902 6.45
921 6.71
938 6.94
956 7.19
975 7.46
9500 930 7.26
948 7.52
965 7.77
983 8.04
10000 959 8.15
976 8.41
-
-
-
-
-
10500
11000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7.5-hp Standard Motor & High Static Drive Accessory
-
-
Notes:
1.
For Standard Evaporator Fan Speed (rpm), reference Table 86, p. 118
.
2.
For High Evaporator Fan Speed (rpm), reference
.
3.
For Oversized Evaporator Fan Speed (rpm), reference Table 88, p. 119 .
4.
Fan motor heat (MBh) = 3.15 x Fan bhp.
5.
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6.
For all non-standard sheave combinations, please refer to accessory installer’s guides ACC-SVN34*-EN and ACC-SVN72*-EN.
7.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)7.5-hp Standard Motor & Low Static Drive Accessory.
RT-PRC043AC-EN 117
Performance Data
Table 85. Standard motor and drive/fan speed (rpm)
Tons Unit Model Number
12½
15
T/YS*150G3,4,W,K
T/YH*150G3,4,W
T/YS*180G3,4,W,K
T/YH*180G3,4,W
17½ T/YS*210/211G3,4,W,K
T/YH*210G3,4,W
T/YS*240G3,4,W,K 20
T/YH*240G3,4,W
T/YS*300/301G3,4,W,K
T/YH*300G3,4,W
25
T/YH*300G3,4,W with
Reheat
Note: Factory set at 3 turns open.
6 Turns
Open
605
506
605
506
694
581
642
452
559
452
694
5 Turns
Open
650
544
650
544
731
619
683
485
600
485
739
4 Turns
Open
695
582
695
582
768
657
725
518
642
518
784
3 Turns
Open
740
620
740
620
805
695
766
551
683
551
829
2 Turns
Open
785
658
785
658
842
733
808
584
725
584
874
1 Turn
Open
829
694
829
694
881
769
849
619
766
619
919
Closed
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Table 86. Standard motor and low static fan drive
Tons
12½
15
17½
20
25
Unit Model Number
T/YS*150G3,4,W,K
T/YH*150G3,4,W
T/YS*180G3,4,W,K
T/YH*180G3,4,W
T/YS*210/211G3,4,W,K
T/YH*210G3,4,W
T/YS*240G3,4,W,K
T/YH*240G3,4,W
T/YS*300/301G3,4,W,K
T/YH*300G3,4,W with
Reheat
6 Turns
Open
452
450
506
450
581
351
452
351
506
581
5 Turns
Open
485
480
544
480
619
377
485
377
544
619
4 Turns
Open
518
510
582
510
657
403
518
403
582
657
3 Turns
Open
551
540
620
540
695
429
551
429
620
695
2 Turns
Open
584
570
658
570
733
455
584
455
658
733
1Turn
Open Closed
619 N/A
600
694
600
769
480
619
480
694
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
769 N/A
Table 87. Standard motor and high static drive accessory sheave/fan speed (rpm)
Tons
12½
15
17½
20
25
Unit Model Number
T/YS*150G3,4,W,K
T/YH*150G3,4,W
T/YS*180G3,4,W,K
T/YH*180G3,4,W
T/YS*210/211G3,4,W,K
T/YH*210G3,4,W
T/YS*240G3,4,W,K
T/YH*240G3,4,W
T/YS*300/301G3,4,W,K
T/YH*300G3,4,W
T/YH*300G3,4,W with
Reheat
6 Turns
Open
694
829
694
806
694
766
619
719
619
829
806
5 Turns
Open
731
874
731
844
739
808
652
753
652
874
844
4 Turns
Open
768
919
768
882
784
849
685
786
685
919
882
3 Turns
Open
805
964
805
920
829
891
718
820
718
964
920
2 Turns
Open
842
1009
842
958
874
891
751
853
751
1009
958
1 Turn
Open
881
1053
881
994
919
974
786
887
786
1053
994
Closed
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
118 RT-PRC043AC-EN
Performance Data
Table 88. Oversized motor and drive/fan speed (rpm)
Tons
12½
15
17½
20
Unit Model
Number
T/YS*150G3,4,W,K
T/YH*150G3,4,W
T/YS*180G3,4,W,K
T/YH*180G3,4,W
T/YS*210/211G3,4,W,K
T/YH*210G3,4,W
T/YS*240G3,4,W,K
T/YH*240G3,4,W
6 Turns
Open
863
695
695
695
806
806
806
806
5 Turns
Open
919
747
747
747
844
844
844
844
4 Turns
Open
974
799
799
799
882
882
882
882
3 Turns
Open
1030
851
851
851
920
920
920
920
2 Turns
Open
1085
903
903
903
958
958
958
958
1 Turn
Open Closed
1141 N/A
953
953
953
994
994
N/A
N/A
N/A
N/A
N/A
994
994
N/A
N/A
Table 89. Static pressure drop through accessories (inches water column)
Tons
12½
15
6000
2500
4000
5000
6000
4800
6000
7200
4000
5000
6000
4000
5000
6000
4000
5000
4800
6000
7200
4800
6000
7200
3000
4800
6000
7200
Unit Model
Number cfm (a)
Std
Filters (b)
Through
Reheat
Coil
2”
MERV 8
Filter (c)
2”
MERV 13
Filter
T/YSH150G
T/YSD150G
T/YHH150G
T/YHD150G
T/YSH180G
T/YSD180G
T/YHH180G
T/YHD180G
0.05
0.07
—
—
0.10 —
0.05
—
0.07
—
0.10 —
0.02 —
0.03 —
0.08
0.11
0.15
0.08
0.11
0.15
0.05 —
0.01 0.00 0.01 0.03
0.02 0.01 0.04 0.08
0.03 0.02 0.05 0.11
0.05 0.03 0.07 0.13
0.03 — 0.06
0.09
0.05 —
0.07 —
0.09
0.11
0.13
0.16
0.07
0.11
0.04 —
0.06 —
0.09 —
0.03 —
0.05 —
0.07 —
0.02 0.01
0.04 0.01
0.06 0.02
0.09 0.03
0.13
0.04
0.06
0.08
0.02
0.05
0.06
0.08
0.18
0.06
0.1
0.13
0.03
0.08
0.11
0.14
0.12
0.15
0.19
0.12
0.15
0.19
Std
Economizer with
OA/RA
Dampers (d)
100%
OA
100%
RA
Low Leak
Economizer with
OA/RA
Electric Heater
Accessory (kW)
100%
OA
100%
RA 14–27 36 54
(e)
72
0.33
0.07
0.19
0.26
0.33
0.14
0.19
0.26
0.33
0.19
0.26
0.33
0.19
0.26
0.27
0.14
0.27
0.14
0.27
0.07
0.14
0.2
0.27
0.04
0.01
0.02
0.03
0.04
0.03
0.02
0.03
0.04
0.02
0.03
0.04
0.02
0.03
0.05
0.03
0.05
0.03
0.05
0.03
0.03
0.04
0.05
0.57
0.07
0.16
0.24
0.33
0.36
0.57
0.81
0.27
0.42
0.61
0.27
0.41
0.58
0.25
0.39
0.22
0.33
0.45
0.36
0.57
0.81
0.10
0.22
0.33
0.45
0.10
0.04
0.10
0.16
0.24
0.06
0.10
0.14
0.06
0.10
0.14
0.18
0.29
0.44
0.04
0.07
0.15
0.24
0.35
0.06
0.10
0.14
0.06
0.15
0.24
0.35
0.07
*
0.03
0.05
0.07
0.04
0.07
0.03
0.05
0.07
0.03
0.05
0.07
0.03
0.05
0.06
*
0.03
0.04
0.06
0.04
0.06
0.09
0.03
0.04
0.06
0.03
0.04
0.06
0.03
0.04
0.04
0.06
0.09
0.04
0.06
0.09
*
0.04
0.06
0.09
0.04
0.07
0.04
0.07
*
0.04
0.07
0.1
0.09
*
0.04
0.06
0.09
0.05
0.08
0.04
0.06
0.09
0.04
0.06
0.09
0.04
0.06
0.05
0.08
0.05
0.08
*
0.05
0.08
0.12
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
RT-PRC043AC-EN 119
Performance Data
Table 89. Static pressure drop through accessories (inches water column) (continued)
Tons
17½
20
25
Unit Model
Number cfm (a)
Std
Filters (b)
Through
Reheat
Coil
2”
MERV 8
Filter (c)
2”
MERV 13
Filter (c)
T/YSH210/
211G
T/YSD210/
211G
T/YHH210G
T/YHD210G
T/YSH240G
T/YSD240G
T/YHH240G
T/YHD240G
T/YSH300/
301G
T/YSD300/
301G
T/YHH300G
T/YHD300G
8000
9600
7000
9000
11000
7000
9000
11000
6400
8000
9600
6400
8000
9600
4000
6400
7000
9000
11000
5000
7000
9000
11000
8400
3500
5600
7000
8400
6400
8000
9600
5600
7000
8400
5600
7000
8400
5600
7000
0.05 —
0.07 —
0.10 —
0.06 —
0.09 —
0.12 —
0.03 —
0.05 —
0.07 —
0.01 0.04
0.04 0.10
0.06 0.13
0.08 0.16
0.06 —
0.09 —
0.13 —
0.02 0.04
0.05 0.10
0.08 0.13
0.10 0.16
0.17
0.21
0.07 —
0.11 —
0.16 —
0.04 —
0.06 —
0.09 —
0.02 0.02 0.03 0.06
0.05 0.05 0.08 0.12
0.08 0.07 0.10 0.15
0.11 0.11 0.14 0.19
0.07
0.11
—
—
0.11
0.15
0.15
0.20
0.17
0.09
0.14
0.21
—
—
—
—
0.22
0.13
0.18
0.25
0.26
0.17
0.23
0.32
0.05 —
0.08 —
0.12 —
0.03 0.02
0.06 0.04
0.10 0.06
0.10
0.08
0.04 0.08
0.09 0.13
0.12 0.18
0.17
0.22
Std
Economizer with
OA/RA
Dampers (d)
100%
OA
100%
RA
Low Leak
Economizer with
OA/RA
Dampers (d)
Electric Heater
Accessory (kW)
100%
OA
100%
RA 14–27 36 54
(e)
72
0.32
0.44
0.26
0.4
0.6
0.26
0.4
0.57
0.22
0.32
0.44
0.22
0.32
0.44
0.11
0.22
0.26
0.4
0.6
0.15
0.26
0.4
0.57
0.35
0.09
0.18
0.26
0.35
0.22
0.32
0.44
0.18
0.26
0.35
0.18
0.26
0.35
0.18
0.26
0.05
0.07
0.04
0.07
0.1
0.04
0.07
0.1
0.04
0.05
0.07
0.04
0.05
0.07
0.03
0.04
0.04
0.07
0.1
0.03
0.04
0.07
0.10
0.06
0.03
0.04
0.04
0.06
0.04
0.05
0.07
0.04
0.04
0.06
0.04
0.04
0.06
0.04
0.04
0.54
0.75
0.77
1.27
1.89
0.43
0.67
0.95
0.37
0.54
0.75
0.64
1.0
1.44
0.16
0.37
0.77
1.27
1.89
0.24
0.43
0.67
0.95
1.11
0.13
0.29
0.43
0.59
0.64
1.0
1.44
0.49
0.77
1.11
0.29
0.43
0.59
0.49
0.77
0.43
0.62
0.13
0.21
0.32
0.33
0.55
0.82
0.27
0.43
0.62
0.11
0.17
0.24
0.10
0.27
0.13
0.21
0.32
0.16
0.33
0.55
0.82
0.19
0.08
0.21
0.33
0.48
0.11
0.17
0.24
0.08
0.13
0.19
0.21
0.33
0.48
0.08
0.13
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.08
0.13
0.18
*
0.08
0.13
0.18
0.05
0.08
0.12
0.05
0.08
0.12
0.05
0.08
0.12
*
0.05
0.08
0.13
*
0.06
0.09
0.12
0.06
0.13
0.08
0.10 0.12
0.14
0.17
0.06
0.09
0.13
0.06
0.09
0.13
0.06
0.09
0.06
0.08
0.10 0.12
0.14
0.06
0.17
0.08
0.10 0.12
0.14
0.17
*
0.06
*
0.08
0.10 0.12
0.14
0.17
0.08
0.13
0.14
0.20
0.10 0.11
0.15
0.18
0.18
0.08
0.13
0.18
0.22
0.15
0.22
0.26
0.10 0.11
0.18
0.26
0.09
0.14
0.20
0.09
0.14
0.20
*
0.09
0.10 0.11
0.15
0.18
0.22
*
0.26
*
0.1
0.15
0.22
0.11
0.18
0.26
0.07
0.11
0.16
0.07
0.11
0.16
0.07
0.11
0.16
*
0.07
0.11
0.16
0.09
0.14
0.20
(a)Unit applications below 320 cfm/ton are only applicable to Constant Volume THD models without electric heat and YHD models equipped with modulating gas heat. See below for restrictions:
- Electric heaters on applications below 320 cfm/ton.
- Frostat and Crankcase heaters are required on applications below 320 cfm/ton.
- Multi-speed, single zone VAV or multi-zone VAV applications are capable of running below 320 cfm/ton during low speed airflow operation, but "full" airflow must be set to 320 cfm/ton or higher.
(b)Tested with: 2” filters 12½–25 tons.
(c) Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
(d)OA = Outside Air and RA = Return Air.
(e)Nominal kW ratings at 240, 480, 600 volts.
120 RT-PRC043AC-EN
Performance Data
Table 90. Gas fired heating capacities
Tons Unit Model Number Heating Input MBh (a)
12½
15
17½
YS/H*150G-L1
YS/H*150G-H1
150/100
250/175
YS/H*150G-V1 350/140
YS/H*180G-L1 250/175
YS/H*180G-H1
YS/H*180G-V1
YS/H*210G-L1
YS/H*210G-H1
350/250
350/140
250/175
350/250
120/80
200/140
280/112
200/140
280/200
280/112
200/140
280/200
20
YS/H*210G-V1
YS/H*240G-L1
YS/H*240G-H1
YS/H*240G-V1
350/140
250/175
400/300
350/140
280/112
200/140
320/240
280/112
25
YS/H*300G-L1
YS/H*300G-H1
250/175
400/300
200/140
320/240
YS/H*300G-V1 350/140 280/112
(a)For two stage heaters (input or output), second stage is total heating capacity. Second stage/first stage.
Air Temp. Rise, °F
35–65
15–45
25–55
35–65
15–45
25–55
35–65
10–40
25–55
35–65
25–55
35–65
35–65
25–55
35–65
Table 91. Auxiliary electric heat capacity
Tons Unit Model Number kW
Input
Total (a)
(b)
MBh
Output
No. of
Stages kW
Input
MBh
Output kW
Input
12½–15
TS/H*150G3,4,W
TS/H*180G3,4,W
18.00
27.00
(c)
36.00
54.00
61.47
92.15
122.94
184.41
1
2
2
2
18.00
9.00
18.00
36.00
61.47
30.72
61.47
122.94
—
18.00
18.00
18.00
17½–25
TS/H*210/211G3,4,W
TS/H*240G3,4,W
TS/H*300/301G3,4,W
36.00
54.00
122.94
184.41
2
2
18.00
36.00
61.47
122.94
18.00
18.00
72.00
245.88
2 36.00
122.94
36.00
(a)Heaters are rated at 240V, 380V, 480V, and 600V. For other than rated voltage, CAP = (voltage/rated voltage) 2 x rated cap.
(b)For all input/output categories, does not include fan power or heat.
(c) 27 kW heater can be used with TSD180F4, TSD210F4, TSD240F4, and TSD300F4 only. Cannot be used with oversized motor.
* Indicates both downflow and horizontal units.
MBh
Output
—
61.43
61.47
61.47
61.47
61.47
122.94
RT-PRC043AC-EN 121
Performance Data
Table 92. Electric heater voltage correction factors (applicable to auxiliary heat capacity)
Nominal
Voltage
240
480
600
Distribution
Voltage
208
230
240
440
460
480
540
575
600
Capacity
Multiplier
0.75
0.92
1.00
0.84
0.94
1.00
0.81
0.92
1.00
Table 93. Air temperature rise across electric heaters (°F) kW
9.00
Stages
1
12½ Tons
5000 cfm
Three Phase
TS*150G
TH*150G
—
15 Tons
6000 cfm
Three Phase
TS*180G
TH*180G
—
17½ Tons
7000 cfm
Three Phase
TS*210/211G
TH*210G
—
20 Tons
8000 cfm
Three Phase
TS*240G
TH*240G
—
25 Ton
9000 cfm
Three Phase
TS*300/301G
TH*300G
—
17.30
18.00
27.00
36.00
54.00
72.00
1
1
2
2
2
2
—
11.4
—
22.8
34.1
—
—
9.5
14.2
(a)
19.0
28.5
—
—
—
12.2
16.3
24.4
32.5
—
—
10.7
14.2
21.3
28.5
—
—
9.5
12.6
19.0
25.3
Notes:
1.
For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different airflow, use the following formula:
Temp. rise across Electric Heater = kW x 3414/1.08 x cfm.
2.
*Indicates both downflow and horizontal units.
(a)27 kW heater can be used with TSD180F4, TSD210F4, TSD240F4, and TSD300F4 only. Cannot be used with oversized motor.
Table 94. Hot gas reheat temperature rise (a), (b)
Tons
12½
SCFM
2500
3000
3500
4000
4500
5000
5500
6000
Leaving Evaporator Dry Bulb [°F] (c)
35 40 45 50 55 60 65
30.6 31.8 32.9 33.8 34.7 35.5 36.2
25.7 26.8 27.8 28.7 29.5 30.2 30.8
22.2 23.2 24.1 24.9 25.6 26.3 26.9
19.4 20.4 21.2 22.0 22.6 23.2 23.8
17.3 18.2 19.0 19.7 20.3 20.9 21.5
15.6 16.4 17.2 17.8 18.4 19.0 19.5
14.2 15.0 15.7 16.3 16.9 17.4 17.9
13.0 13.8 14.5 15.1 15.6 16.1 16.5
122 RT-PRC043AC-EN
Performance Data
Table 94. Hot gas reheat temperature rise (a), (b)
Tons SCFM
3000
Leaving Evaporator Dry Bulb [°F] (c)
35 40 45 50 55 60 65
30.4 31.5 32.5 33.3 34.1 34.9 35.5
6400
7200
8000
8800
9600
5000
7000
7700
8400
4000
4800
5600
7200
3500
4200
4900
5600
6300
3600
4200
4800
5400
6000
6600
15
17½
20
25
5800
6600
7400
8000
8800
9600
10400
25.4 26.4 27.3 28.1 28.8 29.4 30.0
21.9 22.8 23.6 24.4 25.1 25.7 26.3
19.1 20.0 20.8 21.5 22.2 22.7 23.3
17.0 17.8 18.6 19.2 19.8 20.4 20.9
15.3 16.1 16.8 17.4 18.0 18.5 19.0
13.9 14.7 15.3 15.9 16.4 16.9 17.4
12.7 13.5 14.1 14.7 15.2 15.6 16.1
34.5 37.9 41.5 45.2 48.5 50.6 50.6
28.0 30.9 33.9 36.8 39.6 42.0 43.8
23.5 26.0 28.6 31.4 34.0 36.2 37.9
20.3 22.4 24.7 27.2 29.7 31.9 33.5
17.9 19.7 21.7 23.8 26.1 28.3 29.9
16.0 17.5 19.3 21.3 23.4 25.3 26.9
14.4 15.8 17.4 19.2 21.1 23.0 24.5
13.2 14.4 15.8 17.4 19.3 21.0 22.5
30.5 31.8 33.0 34.0 35.0 35.8 36.6
25.5 26.7 27.8 28.8 29.6 30.4 31.2
21.8 23.0 24.0 24.9 25.7 26.4 27.1
19.1 20.2 21.1 22.0 22.8 23.4 24.1
17.0 18.0 18.9 19.6 20.3 21.0 21.6
15.3 16.2 17.1 17.8 18.5 19.1 19.6
13.9 14.8 15.6 16.3 16.9 17.5 18.0
12.7 13.6 14.3 15.0 15.6 16.1 16.6
25.5
27.3
29.03
30.4
31.7
32.5
32.4
21.9
19.2
17.1
15.8
14.3
13.1
12.1
23.5
20.7
18.4
17
15.5
14.2
13.1
25.1
22.1
19.7
18.3
16.6
15.2
14
11200
12000
11.2
10.4
12.1
11.2
(a) 70°F OD Ambient Temperature.
(b) For units with the Dehumidification (Hot Gas Reheat) option.
(c) Temperature does not account for indoor fan heat.
13
12.2
26.5
23.4
20.9
19.3
17.6
16.2
14.9
13.9
13
27.5
24.3
21.7
20.3
18.7
17.1
15.8
14.7
13.7
28.4
25.2
22.7
21.1
19.2
17.7
16.4
15.1
14.2
28.8
25.7
23.2
21.6
19.8
18.3
16.9
15.8
14.8
RT-PRC043AC-EN 123
advertisement
Related manuals
advertisement
Table of contents
- 4 Features and Benefits
- 4 Standard Features and Available Options
- 6 Standard Features
- 9 Variety of Options
- 9 Factory Installed Options
- 13 Factory or Field Installed Options
- 14 Field Installed Options
- 16 Other Benefits
- 18 Application Considerations
- 20 Selection Procedure
- 20 Cooling Capacity
- 21 Heating Capacity
- 21 Air Delivery Selection
- 22 Model Number Description
- 23 Model Number Notes
- 24 General Data
- 40 Performance Data
- 124 Controls
- 124 Economizer Controls
- 124 Zone Sensors
- 127 Communication Interfaces
- 128 Electrical Data
- 140 Jobsite Connections
- 141 Dimensional Data
- 150 Weights
- 153 Mechanical Specifications
- 155 Factory Installed Options
- 157 Factory or Field Installed Options
- 159 Field Installed Options