Setup Menu. ETC Unison Paradigm P-TS7

Add to My manuals
32 Pages

ETC Unison Paradigm P-TS7 is an advanced touchscreen that integrates with the Paradigm control system to provide intuitive graphics and control options. With a 7" WVGA, 24-bit color display, it offers high-resolution visuals and vibrant colors. The touchscreen supports Hue Saturation and Brightness (HSB) color picker for dynamic selection of color with LED and multi-parameter fixtures. It also allows for Timed Event creation, edit, and override directly from the Setup menu. Built-in proximity and ambient light sensors ensure optimal performance in various lighting conditions.

advertisement

Setup Menu. ETC Unison Paradigm P-TS7 | Manualzz

Setup Menu

On initial power-up, with no ControlDesigner configuration installed or when the touchscreen is not bound / connected to a P-ACP, the touchscreen displays the default splash page which includes the ETC logo and two buttons; {Setup} and {Service Pin}.

7

Pressing the {Setup} button accesses the

Setup

where setup options and technical information are displayed. Pressing the {Service Pin} button issues a service pin request to the Paradigm

Architectural Control Processor over the control network. When the touchscreen is bound/connected to a P-ACP, the configuration file will begin to load.

Setup

Pressing the {Setup} button on the default page displays the

About

page of the touchscreen

Setup menu. Alternatively, you can access the Setup menu by pressing the [Mode] button on the I/O panel. See also

Inputs, Outputs, and Indicators on page 5 .

Each page of the Setup menu displays additional controls and information including {Service

Pin}, Local storage: available/used (read only), {Ok}, and {Cancel}.

P-TS7 User Manual

About

The About page displays read only information pertaining to the touchscreen firmware and operation.

Setup Menu

MAC Address a unique identifier assigned to the touchscreen by ETC for identification over the Paradigm network.

IP Address the current network IP address assigned to the touchscreen. This number can be modified from the

Network on page 25

.

Neuron Id a station specific unique hardware address that is permanent to the touchscreen. This ID is used by the Paradigm Architectural Control Processor to bind/associate (bind) stations within the LightDesigner configuration.

Bootloader the bootloader software version.

Firmware the firmware version loaded onto the touchscreen. Firmware can be updated, reference

System on page 26

for instructions.

Note:

The firmware version in the touchscreen must be compatible with the firmware version in the Paradigm Architectural Control Processor (P-ACP) for the two devices to communicate.

Memory Usage The “Memory Usage” section displays the “Total” memory available, the memory “Used” and the available memory that is “Free” for use.

Boot Reason the last action that caused the touchscreen to boot. Reasons for reboot could be due to a [Reset] button press on the touchscreen I/O panel, power loss, etc.

Watchdogdisplays the status of the Watchdog service.

Note:

Watchdog is a service that monitors touchscreen activity and will automatically reboot the device in the event it would suffer a crash or lockup. Watchdog should be enabled unless instructed otherwise by ETC Technical Services.

8

Screen

9

The Screen page provides user level settings for the touchscreen including:

Backlight Level a level bar is provided to set the relative brightness of the touchscreen backlight. By default, the level is set to full

Note:

When the light sensor is “On”, the Backlight Level sets the maximum level of brightness.

-

-

Backlight Timeout sets the length of inactivity time before the backlight fades to its backlight timeout level. This is separate from any configuration related Inactivity Timeout settings

Level the intensity level the backlight will fade to when its Backlight Timeout has been reached. This level can be set to either “Off” or “Dim”

Light Sensor allows the touchscreen to determine an appropriate backlight level based on ambient light in the space. The internal light sensor measures the ambient light and adjusts the backlight proportionally based on the established backlight level settings. By default, the light sensor is set to Off.

Proximity Sensor when set to On (the default), proximity allows the touchscreen to detect a user’s presence as they approach the touchscreen for use. When proximity is detected, the touchscreen automatically turns on the backlight and displays the inactivity page that was configured in ControlDesigner. Proximity is only supported on the wall-mount P-TS7.

The proximity sensor uses active IR to determine proximity to the touchscreen. The sensor has a sensing distance of approximately one foot with a field angle of 15 degrees.

If the sensor registers any moving or stationary objects within this range, it will “wake” the station from its sleeping state and reset the backlight timeout and the station inactivity timer as set in ControlDesigner.

P-TS7 User Manual

Note:

Be aware of stationary objects (such as rack doors) that remain within the sensing range as it may interfere with the function of the sensor. In these applications, it is best practice to disable the proximity sensor.

The proximity sensor is looking for reflected IR; therefore any IR devices (such as alarms or listening assistance systems) within a range of the proximity sensor may prevent the system from sleeping or displaying an inactivity page.

Test Touchscreen

The

Screen

page provides a {Test Touchscreen} button that will launch a tool used to test the touchscreen.

Note:

You can also press and hold the [Mode] button (located on the I/O panel of the touchscreen) for four seconds to launch the Test Touchscreen display.

Complete touchscreen calibration is completed at the factory prior to shipment. This function is provided only to test the touchscreen is working as expected.

If pressing on the screen causes unintended results (such as the press registering elsewhere on the screen), contact ETC Technical Support at an office near you. Reference

Help from ETC

Technical Services

on

page 3

Sound

The Sound page provides a volume control for the master volume level of the touchscreen's built-in speaker.

Setup Menu 10

Protected Pages and Features

The P-TS7 menu features passcode protected pages and features that should be accessed only by trained personnel. Typically, these pages and features are accessed only during system commissioning.

Mobile App Settings

located on the

Comms

page (see

page 12

)

Timed Events

and

Passcodes

located on the

Config

page

Files on page 23

Network on page 25

System on page 26

Timed Events on page 16

Passcodes on page 22

Comms on page 12

Selecting any of the protected pages or selecting a button for a protected feature will display a keypad for passcode entry.

11

Note:

Enter your four digit passcode to access the protected pages. Protected pages and features should be accessed only by trained personnel.

P-TS7 User Manual

Comms

The Comms page provides read-only information about the Paradigm ACP to which the touchscreen is connected (bound to) over the Paradigm control network. This page also provides secured access to the touchscreen Mobile App Settings which allow connection and use of the

ETC Paradigm Touchscreen Remote App.

P-ACP Name: this is the name of the P-ACP the touchscreen is connected (bound) to

Connection Type: this is the type of connection that is made to the P-ACP. Options include “Ethernet” which is NetConnect, or “Lon” which is LinkConnect.

Note:

This information is useful when troubleshooting your communication connection between the P-TS7 and your Paradigm control system.

When a P-TS7 is connected by NetConnect, the IP address of the P-ACP will display.

A Portable LON P-TS7 will indicate the Connector ID of the Portable Connector Station

(UH1RS) it is connected to.

Mobile App Settings

Note:

Mobile App Settings is a protected page. You must enter the Setup passcode to enter the Mobile App Settings page.

The Paradigm Touchscreen Remote App interfaces with the Unison Paradigm control system by connecting over Wi-Fi to your lighting system and an Ethernet (NetConnect) connected P-TS7 touchscreen.

Note:

Touchscreen Remote App connection is incompatible with LON and wireless connected touchscreens.

Setup Menu 12

13

To configure a P-TS7 (Ethernet connected) for use with the Paradigm Touchscreen Remote App, select the {Mobile App Settings} button located on the Comms page.

The Mobile App Settings page provides access to enable the touchscreen for connection via the

Touchscreen Remote App, as well as sets the passcode security and port address for the connection.

When configured and connected, the Paradigm Touchscreen Remote App mimics all current display activity for an online P-TS7 onto the remote mobile device and transmits touch events from the remote mobile device back to the Paradigm system. Each touch event from the mobile device tracks on the P-TS7, and vice versa.

Note:

Only one Paradigm Touchscreen Remote App connection is allowed per P-TS7

Touchscreen at any given time.

Mobile App Connection this setting toggles On or Off the ability for the Paradigm

Touchscreen Remote App to connect to this P-TS7. This setting is Off by default.

Note:

The following settings are available for configuration when the Mobile App

Connection setting is set to On.

Passcode is a four-digit numeric code used to secure a connection to the touchscreen from the Touchscreen Remote App. On initial setup, the P-TS7 will automatically generate a random four-digit code, alternatively you can choose your own four-digit code, or leave

P-TS7 User Manual

Setup Menu

• the field blank to disable the passcode requirement.

Note:

A passcode may be required when connecting to the P-TS7 using the

Touchscreen Remote App.

Port: UDP port. The port defaults to 49044.

Tip:

When the UDP port is not default (49044), you must specify the port number with the IP address in the Touchscreen Remote App. For example, 10.101.15.101:49045.

Pressing the {Reset to Defaults} button resets the Mobile App Settings to factory defaults:

-

-

-

Toggles the Mobile App Connection Off

Resets the passcode to a new random four-digit code

Resets the Port to 49044.

14

15

Config

The Config page displays the project information that was provided in ControlDesigner, or it displays "Automatic Touchscreen Configuration" if the configuration was generated in

LightDesigner using a standard theme. Project information can only be modified in

ControlDesigner.

Access to 

Timed Events

and the

Passcodes

is also available from this page.

Note:

Timed Events and Passcodes features have protected access. You must enter the setup passcode to view the settings in those screens.

P-TS7 User Manual

Timed Events

Timed Events setup is a passcode protected page. Press the {Timed Events} button on the

Config

page and enter the setup passcode to view and edit timed events.

The Timed Event Setup page allows users to add, edit, and delete timed events. All created timed events are shown.

Note:

ControlDesigner provides a page navigation action to reach a Timed Event configuration directly. ETC recommends that you use this design feature to provide access for end users who wish to edit timed events directly on the touchscreen.

Adding a new event and editing an event are very similar in process.

Setup Menu 16

Add Event

1. Press the {Add} button, the “New Timed Event” wizard displays.

17

2.

Specify the “Start Time”. Press the default {Time of Day} button to display a list of available start times including; “Time of Day”, “Sunrise”, and “Sunset”. Select the option. Depending on the selection, additional options may display:

If “Time of Day” is selected, additional selection for a “Start Time” is required.

If “Sunrise” or “Sunset” are selected, additional selection for an “Offset” is required.

An offset is specified as an additive (press the {+} button) or negative (press the {-} button) hour and minutes setting from the astronomical time.

3.

Specify the “End Time”. The options for “End Time” are similar to the “Start Time” except “Duration” is now an option. When “Duration” is the selected “End Time”, you will also be required to specify the hours and minutes the event should run from its start time.

P-TS7 User Manual

Setup Menu

4.

Press {Next}. Additional options display.

5.

If an override has been created for use with the timed event, select the override from the available options.

Note:

For more information regarding overrides, reference the Paradigm

LightDesigner online help system or contact ETC Technical Services.

6.

To synchronize this timed event when the P-TS7 boots and connects to the Paradigm system, set "Sync at boot" to True.

7.

To run this timed event on protected days, configured in LightDesigner, set the "Allow on

Protected Days" setting to True.

18

19

8.

Press {Next}. Recurrence settings display.

9.

To set the timed event recurrence according to a configured holiday, select the holiday from the drop-down.

10.

Set the recurrence type from the options available in the "Recur" drop-down menu.

P-TS7 User Manual

Example:

Additional settings are provided depending on the selected recurrence type. For example, if “Weekly” is selected, the following options display:

11.

Define the recurrence completely according to the type specified.

12.

Press {Next}, and then set the Recurrence Range options.

13.

Press {Next} to set a Start Action.

Setup Menu 20

21

14.

Click to select actions from the available options in the drop-down menu.

Notice the ability to scroll to more options using the scroll bar on the right. Depending on the selection, more options may display for setting on the “Start Action” page.

Complete the options as required.

15.

Depending on your previous selections, you will either press {Ok} to close the menu, or press {Next} to define an End Action. As needed, complete the selections.

P-TS7 User Manual

Passcodes

Passcodes are codes that are required to access the passcode protected screens found in the P-

TS7 Setup menu. By default, the Setup passcode is 3031.

Passcodes are created and assigned in the ControlDesigner configuration. This page in the P-TS7 menu displays all Setup Passcodes that have been created and associated to the configuration.

Setup Menu 22

Files

The Files page provides configuration and theme file management, allowing you to load, save, and delete files as needed.

Note:

The Files page is passcode protected. You must enter the setup passcode to display the Files page on this touchscreen.

23

Use the {Load From} and {Save To} features to manage configuration and theme files, transferring from and saving to removable media such as an SD card or USB key.

Note:

If the P-TS7 is already associated with a Paradigm ACP, it will automatically begin retrieving its configuration file when powered.

Some standard ETC themes are loaded for you and will display beneath the “Themes” directory. Themes can be loaded to the touchscreen using removable media.

P-TS7 User Manual

Saving and Loading Files

To begin, you must have a compatible USB drive or SD media card (your choice) inserted into the port receptacle of the touchscreen.

1.

Select either {Config} or {Theme} (whichever file type you want to transfer).

2.

Select an action:

If saving a file to removable media select the file from the list and press {Save To}.

If loading a file from removable media, press {Load From}.

3.

Choose the removable media (SD or USB) you are transferring to/from.

4.

Navigate the file structure of the removable media to select the directory. To return to a previous directory in the removable media, press the {Up} button. Press {Ok} to set the directory location.

Note:

Multiple files can be selected for upload or download by simply touching to select each file. When a file with the same name exists at the save to location or if it already exists on the touchscreen when loading from removable media, you will be prompted to either {Cancel} the action or {Overwrite} the existing conflicting file.

Setup Menu 24

Network

The Network page provides access to view and edit the network address settings for the touchscreen. Factory defaults are displayed in the image below.

25

IP Addressing

Two “IP Addressing” modes are available for use with the touchscreen; Manual and Automatic.

In Manual Mode the IP address and settings are user configured. To change any portion of the address, simply touch inside the field you wish to modify. A numeric keypad will display for edit of the selected field. Make the modifications to the selected field then select another field for edit as necessary.

Note:

When multiple touchscreens are installed into your system, they must each have a unique IP address. For example, 10.101.15.101, 10.101.15.102, etc. Duplicate

IP addresses will cause system communication problems.

In Automatic Mode the touchscreen is configured to obtain an IP address and other network settings automatically from a connected DCHP server. The touchscreen displays the current settings provided from the connected DHCP server but the settings are not user editable. If no DHCP server is present, the touchscreen will assign itself a link-local address in the default 169.254.x.x range. Automatic IP Mode is not recommended for most applications.

Make the mode selection, and then press {Ok} to save your changes. The touchscreen will exit the

Setup , and return the display to your default page (or inactivity page as defined in your

configuration).

P-TS7 User Manual

System

The System page provides read only information regarding the P-TS7 hardware. This page is most helpful when troubleshooting touchscreen issues with ETC Technical Services.

Note:

The System page is passcode protected. You must enter the setup passcode to display the System page on this touchscreen.

Board Revision read only information regarding the touchscreen hardware revision level

{Reload Firmware}: reference

Reload Firmware on page 26

{Reset To Defaults}: reference

Reset to Defaults on page 27

{Event Log}: reference Event Log on page 1

Reload Firmware

Note:

Firmware should only be updated by an authorized technician, or when coordinated with ETC Technical Services.

Note:

The touchscreen firmware file is stored in the LightDesigner installation directory firmware folder (filename PTS_fw_x.y.z.ts7_tfw). Save the file to the root directory of a USB or SD card for loading onto the P-TS7.

1.

Insert the USB key or SD card with the firmware file into the touchscreen I/O port.

2.

Press the {Reload Firmware} button located on the System page.

3.

Select the media (USB or SD) that includes the firmware file from the recognized installed media list.

Setup Menu 26