Standardized configuration. ABB Relion 611 Series, REU611 2.0 IEC, Voltage Protection, Application, Relion, REU611

Standardized configuration. ABB Relion 611 Series, REU611 2.0 IEC, Voltage Protection, Application, Relion, REU611

Add to My manuals
84 Pages

advertisement

Standardized configuration. ABB Relion 611 Series, REU611 2.0 IEC, Voltage Protection, Application, Relion, REU611 | Manualzz

1MRS758335 D

Section 3

REU611 standardized configuration

Section 3 REU611 standardized configuration

3.1

REU611

Application Manual

Standardized configuration

REU611 is available in one configuration.

To increase the user-friendliness of the configuration and to emphasize the simplicity of usage of the relay, only the application-specific parameters need setting within the relay's intended area of application.

The standard signal configuration can be altered by local HMI, Web HMI or optional application functionality of Protection and Control IED Manager PCM600.

Table 9: Standardized configuration

Description

Voltage and frequency protection

Conf.

A

Table 10: Supported functions

Function

Protection

Residual overvoltage protection

Three-phase undervoltage protection

Three-phase overvoltage protection

Positive-sequence undervoltage protection

Negative-sequence overvoltage protection

Frequency protection

Master trip

Control

Circuit-breaker control

Condition monitoring and supervision

Trip circuit supervision

Logging

Disturbance recorder

Fault recorder

Measurement

Three-phase voltage measurement

Sequence voltage measurement

Residual voltage measurement

Table continues on next page

IEC 61850

ROVPTOV

PHPTUV

PHPTOV

PSPTUV

NSPTOV

FRPFRQ

TRPPTRC

CBXCBR

TCSSCBR

RDRE

FLTRFRC

VMMXU

VSMSQI

RESVMMXU

A

3

2

2

2

2

3

3

2

1

1

1

1

1

2

25