MAINTENANCE. ABB SG Series 50 - 80kVA UPS

Add to My manuals
82 Pages

advertisement

MAINTENANCE. ABB SG Series 50 - 80kVA UPS | Manualzz

9 MAINTENANCE

WARNING !

All maintenance and service works must be performed by QUALIFIED SERVICE

PERSONNEL.

9.1 MAINTENANCE

A UPS system, like other electrical equipment, needs periodic preventive maintenance.

A regular maintenance check of your installation guarantees higher reliability of your safe critical power supply.

Preventive maintenance work on the UPS can be done only by trained Service technicians.

We therefore recommend you sign a Maintenance and Service contract with GE Global Services @ 1-

800-637-1738

9.1.1 Service check

If this lamp lights up during the normal operation, that means that the unit has not been serviced for the last 20,000 hours by a GE trained technician.

We highly recommend that you contact your Service Centre for preventive maintenance work.

9.1.2 Fans and ventilation

We recommend a periodic cleaning of the ventilation channels and grids on the UPS system, in order to guarantee proper air circulation in the unit and in the Battery .

We recommend replacement of the fans in the units every 20,000 hours .

9.1.3 Other components with limited lifetime

We recommend the replacement of components such as Filter Capacitors and Lithium Battery for the backup of data on the control boards of the units every 50,000 hours .

9.1.4 Battery

We recommend a periodic Manual Battery Test , especially if the Automatic Battery Test is disabled, in order to verify if the Battery can provide the expected backup time in case of Utility Failure .

We recommend this test be performed at least every 3 months , especially if the Battery is not sufficiently discharged during normal operation.

The discharge time you use should be at least half of the Battery runtime.

For Automatic Battery Test setting, a special code is required to enter user set-up parameters.

The start up technician has access to this code and can program this feature during start up.

Please consider that, if you did a full Battery Test to verify the full runtime of the Battery , the charger needs at least 8 hours to recharge the Battery up to 90% of its capacity.

Modifications reserved

OPM_SGS_USM_50K_80K_0US_V030.doc

Page 80/82

Operating Manual SG Series 50 & 80 kVA

9.1.5 Long shut-down periods of the UPS-system

To guarantee that the Battery is fully charged, the UPS system should be in operation for at least 12 hours every 3 months .

If not the Battery may be permanently damaged.

9.1.6 UPS room conditions and temperature

The UPS room and the Battery Room have to be maintained clean and free from dust.

A high temperature of the UPS room and of the Battery Room affect the lifetime of several components inside the equipment.

The Battery is very sensitive to room temperatures above 77°F (25°C).

9.1.7 Long shut-down periods of the UPS-system a) Cleaning, a visual inspection and a mechanical inspection of the UPS modules. b) Replacement of defective parts or the preventive replacement of parts with a defined lifetime c) “Updating” of the equipment (technical improvements subsequent to the delivery). d) Check the calibration of DC voltage and Inverter Output Voltage and Frequency . e) Check of the settings of the electronic regulation, the control and the alarm circuits of the

Rectifier(s) and Inverter(s) . f) Functional checks on Thyristors , Diodes , Transformers , Filter Components , e.g. to ensure that they are operating within the specified design parameters. g) Overall performance test including a Utility Failure simulation with and without the Load . h) Monitoring operation in discharge and recharge mode including any boost charge duties.

Modifications reserved

OPM_SGS_USM_50K_80K_0US_V030.doc

Page 81/82

Operating Manual SG Series 50 & 80 kVA

advertisement

Related manuals

Download PDF

advertisement

Table of contents