Measures. ABB TLE Scalable UL Series UPS

Measures. ABB TLE Scalable UL Series UPS

Add to My manuals
86 Pages

advertisement

Measures. ABB TLE Scalable UL Series UPS | Manualzz

28/86

6.2

Measures

TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B

MEASURES

The MEASURES mode is entered any time the

“ MEASURES ” key is pressed.

The LCD screen will indicate a series of screenshots showing the measures of all electric parameters like

AC, DC and various statistics.

In this mode the keys perform the following functions:

Return to HOME screen.

Shows the main screen EVENTS.

See Section 6.3.

Shows the main screen SETUP.

See Section 6.4.

Shows the main screen COMMANDS.

See Section 6.5.

Shows the operating status of the RPA PARALLEL SYSTEM.

See Section 6.6.

Key to reset general alarm and buzzer.

Shows the screen Battery.

Shows the screen Rectifier.

Shows the screen Bypass.

Shows the screen Inverter.

Shows the screen Load.

Shows the screen Booster.

29/86 TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B

Battery screen

Voltage

The Battery voltage.

Current

The Battery current (negative values correspond to the discharge of the Battery).

Temperature

The temperature of the Battery (“XXX” indicates sensor disabled).

Autonomy

The estimated backup time with the present Load.

Note: the backup time is computed given the Unit Load.

Therefore, during IEMi Operation Mode, On-line Units may show a reduced backup time. However, following a power outage, all Inverters are forced on-line.

Therefore, during Battery operation every Unit shows the true Battery autonomy.

Charge level

The Battery charge level.

On battery time

Total operating time of the UPS on Battery (in hours).

BATTERY DISCHARGE COUNTER / Residual Charge Level

The number of discharges combined with the percentage of the available residual Battery capacity at the time

Utility power is restored.

Battery charger status

Battery charge status (Off / Float / Boost).

Rectifier screen

Frequency

The input frequency of the Rectifier.

Voltage L1 / Voltage L2 / Voltage L3

3-phase input Utility voltage PHASE /NEUTRAL.

Voltage DC-link 1

DC-Link 1 voltage.

Voltage DC-link 2

DC-Link 2 voltage.

Main failure count

Total number of times a gap of Utility in the Rectifier has been reordered.

Temperature

Rectifier inlet L1 Coil temperature (Normal / Alarm).

Temperature 1 / 2 / 3

Temperature of the Rectifier bridge (Power Module 1 / 2 / 3).

30/86 TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B

Bypass screen

Frequency

The frequency of the input Utility.

Voltage L1 / Voltage L2 / Voltage L3

3-phase input Utility voltage PHASE /NEUTRAL.

Current L1 / Current L2 / Current L3

Input Utility current for the 3-phases.

Main failure count

The total number of minor Utility faults (Bypass Utility out of tolerance faults).

Number of fast transients

The number of fast transients occurred on the Bypass Utility on the last seven days.

Bypass quality index

The statistic evaluation in % (100= good; 0= bad) of the Bypass utility.

Temperature

The temperature of the SSM - Static Switch Module (°C/ Alarm).

Status

Bypass status: free / blocked.

Temperature

“XXX” indicates disabled function.

Temperature 1 / 2 / 3

Temperature of the Inverter bridge (Power Module 1 / 2 / 3).

Inverter screen

Frequency

The output frequency of the Inverter.

Voltage L1 / Voltage L2 / Voltage L3

3-phase output Utility voltage PHASE/NEUTRAL.

Status

The synchronization status of the Inverter with respect to Utility:

Synchronized.

Not synchronized.

31/86 TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B

Active power

Apparent power

Power factor

Status

Inverter operating time

Apparent power

UPS operation time

Active Power

SEM operation time

Overload counter

IEMi operation time

Load screen

Voltage L1 / L2 / L3

Output voltage PHASE/NEUTRAL for each phase.

Current L1 / L2 / L3

The output current as RMS values for each phase.

Percent load L1 / L2 / L3

The output Load as percentage for each phase.

Load active power (kW) for each phase.

Load apparent power (kVA) for each phase.

Load power factor: (+) inductive Load / (-) capacitive Load

Source of the power supplied to the Load.

Total operating time for the Inverter (in hours).

Total apparent Load power (kVA).

Total operating time for the UPS (in hours).

Total effective Load power (kW).

Total operating time for the UPS in “SEM - Super Eco Mode” Operation Mode (in hours).

Total number of detected output overloads.

Total operating time for the UPS in IEMi Operation Mode (in hours).

This counter is displayed only when IEMi Operation Mode is available (option).

Voltage DC-link 2

Status

Temperature

Temperature 1 / 2 / 3

Booster screen

Battery voltage

The Battery voltage.

Battery current

The Battery current (negative values correspond to the discharge of the Battery).

Voltage DC-link 1

DC-link 1 voltage.

DC-link 2 voltage.

Booster status (Off / Booster / Charger).

“XXX” indicates disabled function.

Temperature of the Booster (Power Module 1 / 2 / 3).