Events (alarms and messages). ABB TLE Scalable UL Series UPS

Events (alarms and messages). ABB TLE Scalable UL Series UPS

Add to My manuals
86 Pages

advertisement

Events (alarms and messages). ABB TLE Scalable UL Series UPS | Manualzz

4000

4001

4004

4006

4007

4008

4009

4010

34/86

6.3.1

Events (alarms and messages)

TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B

Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with the software “Data Protection” installed or with the monitoring system “iUPSGuard”.

Alarms and Messages are differently specified because the alarms are indicating an abnormal functioning of the

UPS (which are additionally signaled with the LED ALARM and acoustically with the buzzer ), while the messages indicate the various states of operation of the UPS (stored in the events list, but not activating the LED ALARM and the acoustical alarm).

6.3.2

Alarms list

Code Alarm Description

4011

4012

4013

4100

4102

4103

4104

SETUP VALUES LOST

REGULATION BOARD FAILURE

UPS FAILURE ON PARALLEL SYSTEM

BUS JA CRC FAILURE

BUS JB CRC FAILURE

BUS JA FAILURE

BUS JB FAILURE

CONNECTIVITY BUS FAILURE

EARTH LEAKAGE CURRENT

LOAD GROUND FAULT

CAN BUS FAILURE

RECTIFIER FUSES FAILURE

K4 CLOSING FAILURE

K4 OPENING FAILURE

BATTERY FUSES FAILURE

Parameters are lost and have been replaced with default values.

Please contact your ABB Service Center for intervention.

A blocked DSP on the Control board causes this alarm and consequently the shut-down of Rectifier and Inverter and the opening of K3.

The Master Unit detected the Slave Unit missing on the communication bus even though “Q1 – UPS output switch” is still closed.

The parallel communication bus system is subject to high errors rate on channel JA.

The parallel communication bus system is subject to high errors rate on channel JB.

There is an interruption in the channel JA of the parallel communication bus system.

There is an interruption in the channel JB of the parallel communication bus system.

The connectivity communication bus is faulty or interrupted.

The Unit has detected an earth leakage current above a configured threshold (typically 5% of the maximum rated input current).

Applicable to 3-wire (3ph+PE) distribution only.

The Unit has detected Load ground current above a configured threshold.

Applicable to 3-wire (3ph+PE) distribution only.

The Control Panel communication bus is faulty or interrupted.

The u-switch mounted on the Rectifier input fuses indicates a blown fuse and consequently it is shut down.

Clearance of this condition allows you to restart the

Rectifier.

K4 not closed despite a closing command being issued.

Signaled by auxiliary contact.

Rectifier cannot start.

K4 not open despite an opening command being issued.

Signaled by auxiliary contact.

Utility remains connected to Rectifier bridge.

This function, when enabled on input programmable relays

(“Service Code” required), warns the user about the external Battery Fuses failure or MCB opening, signaled by

NO free contact.

4116

4117

4118

4121

4146

4147

4150

4151

35/86

Code

4105

4106

4110

4115

4125

4126

4130

4140

4141

4142

4143

TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B

Alarm Description

RECTIFIER OVERTEMPERATURE

RECTIFIER TRANSFORMER

OVERTEMPERATURE

RECTIFIER UTILITY OUT OF TOLERANCE

LOW BATTERY VOLTAGE

Temperature sensor indicates a situation of overtemperature on the Rectifier bridge.

Only the alarm is given.

The Rectifier, when in an Off state, cannot start as long as this condition persists.

The temperature sensor inside the input transformer winding indicates overtemperature.

Only the alarm is given.

The Rectifier, when in an Off state, cannot start as long as this condition persists.

Rectifier Input Utility is out of tolerance (voltage, frequency or phase sequence).

The Battery has been discharged and reached “stop operation” time-out (default 3 minutes) and the Inverter will be shut down.

It will restart automatically only when the Battery has recharged enough for a minimum runtime.

HIGH BATTERY VOLTAGE

BATTERY EARTH FAULT

BATTERY FAULT

HIGH DC RIPPLE

Dangerous high DC Voltage caused Inverter shut-down.

Inverter restarts automatically after Battery returns to floating voltage.

A leakage current to earth has been detected on the DC circuit.

During Battery test the voltage falls under the critical level

(depending setting parameters).

Battery test is stopped.

A high ripple is present in the Battery voltage.

Detection of high voltage on the DC-link.

HIGH DC-LINK VOLTAGE

The Rectifier, Booster and Inverter will switch off for protection purposes.

The Rectifier may only be switched on again if the DC-link’s voltage value falls below 430Vdc.

4 th LEG CONTROL SATURATION (Imax) The current in the fourth leg has reached its highest value.

TURN ON RECT. OR SHUTDOWN UPS

RECTIFIER CONTROL FAILURE

ISMAX DETECTION RECTIFIER

RECTIFIER CURRENT MAX

BOOSTER/BATTERY CHARGER

CURRENT MAX

4TH LEG DRIVER FAILURE

BATTERY CHARGER DRIVER FAILURE

BOOSTER OVERTEMPERATURE

4TH LEG OVERTEMPERATURE

Rectifier and Inverter are OFF.

The DC power supply is discharging the Battery.

Rectifier must be restarted, or the Battery must be disconnected in order to avoid damage.

Rectifier Voltage hasn’t reached the set value (probably fault on regulation loop).

LED Rectifier on Control Panel is blinking.

After 3 IS-Max condition within the time frame specified in respective parameter, the Rectifier remains shut-down.

Will cause immediate shut-down of the Rectifier.

Based on the value inserted in the respective parameter.

Detection of maximum current in the Booster/Battery charger.

The Booster/Battery charger and Inverter will switch off for protection purposes.

The Booster’s driver indicates the presence of a defect which switches the power off.

The Battery charger driver indicates a defect, switching it off.

The temperature of the Booster bridge exceeds the machine’s set limit or the coil’s sensor is on.

The temperature of the 4 machine’s set limit. th leg’s bridge exceeds the

36/86

Code Alarm

TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B

4301

4304

4305

4307

4308

4309

4310

4311

4312

4320

4321

4340

4400

4404

4405

4406

4410

4420

INVERTER FUSES

K7 CLOSING FAILURE

K7 OPENING FAILURE

INVERTER TRANSFORMER

OVERTEMPERATURE

DC FUSES FAILURE

DRIVER FAILURE

IGBT RECTIFIER DRIVER FAILURE

BOOSTER DRIVER FAILURE

INVERTER VOLTAGE OUT

OF TOLERANCE

ISMAX DETECTION

HIGH CURRENT SHARING

INVERTER CONTROL FAILURE

BYPASS FUSES FAILURE

K6 CLOSING FAILURE

K6 OPENING FAILURE

SSM FAILURE

BYPASS UTILITY OUT OF TOLERANCE

K3 CLOSING FAILURE

Description

The alarm signals an Inverter outlet fuses fault, causing it to switch off immediately.

It may only be manually switched on after the alarm has ceased.

K7 not closed despite a closing command.

Signaled by auxiliary contact.

Load will be supplied by Utility.

K7 not open despite an opening command.

Signaled by auxiliary contact.

Load will be supplied by Utility.

The temperature sensor of the Inverter Transformer indicates overtemperature.

Elapsed “stop operation” time, Inverter shut-down.

With Utility OK, Load is transferred on Utility.

Blown input DC fuse(s) F1 of the Inverter.

Inverter cannot be started as long as present.

An abnormal condition has been detected on one or more power modules of the Inverter (temperature or overcurrent).

Inverter shut-down and cannot be started as long as the alarm is present.

Indicates a failure on the driver board or the Rectifier IGBT bridge. The Rectifier is shut-down.

Driver Booster error signal.

Inverter Output Voltage is out of the tolerances ( ± 10%).

Inverter is switched OFF.

Detection of Inverter Bridge (Is) current limit causing the

Inverter OFF and automatic re-start.

After 3 times the Inverter switches-Off and it can be restarted manually.

A high exchange current value is detected between the UPS of the RPA Parallel System.

The “Slave” oscillator is not in synchronized with the

Master; thus causing the shut-down of its Inverter.

If after a restart the condition remains, the LED inside the

Inverter symbol on the panel will not light up, indicating that this Inverter cannot supply the Load anymore.

Auxiliary contact signal (normally closed) indicates that one fuse of the Bypass Utility (F16/17/18) is open.

K6 open despite a closing command being issued.

Signaled by auxiliary contact.

The Load cannot be supplied by Automatic Bypass.

K6 closed despite an opening command being issued.

Signaled by auxiliary contact.

A faulty current has been detected in the static-switch causing the opening of the contactor K6 for 10 seconds.

After 3 times K6 remains definitively open.

Only an ABB Service Technician can reset the alarm.

The Utility Bypass Voltage is out of the tolerances ( ± 10%).

K6 opens, synchronization with Utility is inhibited and transfer to Utility is blocked.

K3 open despite a closing command.

Inverter is switched OFF.

It can be restarted manually after recovery of the alarm condition.

4571

4581

4608

4681

4682

4683

4684

4685

4697

4698

4700

4955

4998

4999

37/86

Code

4421

4520

4522

4530

4531

4563

4570

4701

4702

4900

TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B

Alarm Description

K3 OPENING FAILURE

NO INVERTER POWER

FAN FAILURE

LOAD LOCKED ON UTILITY

LOAD ON UTILITY BY ERROR

DETECTOR

K3 not open despite an opening command.

Be aware the DC Capacitors could remain charged.

The Load supplied by Utility exceeds the Inverter power.

The Load remains supplied by Utility until the alarm stays ON.

The Fan Control Board indicates a malfunction of one or more ventilators.

Load is locked on Utility because 3 transfers on Utility have been detected in a short time (default 30 sec.).

The transfer will be free after a time defined in parameter

(default 30 sec.).

Load is transferred to Utility because the error detector detected a disturbance on the output voltage.

EMERGENCY OFF ACTIVATED

OVERLOAD

OVERLOAD: LOAD ON UTILITY

INVERTER AND UTILITY

NOT SYNCHRONIZED

ECO CONFIG FAILURE

Alarm after detection of an EPO (Emergency Power Off) from an external safety device connected on Customer Interface

Board. Consequently K4, K6, K7 open, Rectifier, Inverter and

SSM are switched Off.

The UPS system is in an overload condition > 105% on

Inverter, or > 150% on Utility.

With Utility unavailable, a sequence of “stop operation” starts. Time out depends on degree of overload.

With Utility Bypass supply available and Load > 115%, the

Load is transferred on Utility. Load will be transferred again automatically on Inverter when Load < 100%.

The voltages of Utility and Inverter are not synchronized, which causes the opening of K6.

The propagation of the eBoost / IEMi configuration to other

Units in an RPA Parallel System failed.

MAIN BOARD BATTERY CHANGE Notice to replace the Lithium Battery located on the Control

NEEDED Board.

DC CAPACITORS CHANGE NEEDED

AC CAPACITORS CHANGE NEEDED

FAN REPLACEMENT NEEDED

SERVICE MAINTENANCE OVERDUE

BATTERY OVERTEMPERATURE

Notice to replace the DC Capacitors.

Notice to replace the AC Capacitors.

Notice to replace the Fans.

Notice to do the Service Maintenance.

Detection of Battery overtemperature condition.

Only an ABB Service Technician can reset the alarm.

BATTERY POWER INSUFFICIENT

DC LOW

POWER SUPPLY BOARD FAILURE

LOSS OF REDUNDANCY

LOAD LOCKED ON INVERTER

OVERTEMPERATURE

LOAD OFF DUE TO EXTENDED

OVERLOAD

LOAD OFF DUE TO LOW BATT. OR

TEMP.

In case of Utility Failure, with the actual Load, the run time would be below stop operation time (default 3 minutes).

Battery voltage is at the lowest limit.

Inverter will remain Off until the Battery voltage reaches the value in parameter.

Detection of a failure on the Power Supply Board, in particular from the DC supply.

Can be enabled or disabled with respective parameter.

A time of lost redundancy superior than specified in respective parameter was detected.

The Load is locked on Inverter after 3 Load transfers within

30 seconds.

After time out (default 30 sec.) Bypass will be free.

An overtemperature condition has been detected on Inverter.

Elapsed “stop operation” time, Inverter shut-down.

With Utility OK, Load is transferred on Utility.

Load Off after time-out of “stop operation” for overload on

Inverter (time depending on the % of overload).

Load Off after time-out of “stop operation” with missing

Utility due to Battery low voltage or overtemperature condition.

advertisement

Related manuals

Download PDF

advertisement

Table of contents