- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- ABB
- TLE Scalable UL Series UPS
- User manual
Events (alarms and messages). ABB TLE Scalable UL Series UPS 86 Pages
Events (alarms and messages). ABB TLE Scalable UL Series UPS
advertisement
4000
4001
4004
4006
4007
4008
4009
4010
34/86
6.3.1
Events (alarms and messages)
TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with the software “Data Protection” installed or with the monitoring system “iUPSGuard”.
Alarms and Messages are differently specified because the alarms are indicating an abnormal functioning of the
UPS (which are additionally signaled with the LED ALARM and acoustically with the buzzer ), while the messages indicate the various states of operation of the UPS (stored in the events list, but not activating the LED ALARM and the acoustical alarm).
6.3.2
Alarms list
Code Alarm Description
4011
4012
4013
4100
4102
4103
4104
SETUP VALUES LOST
REGULATION BOARD FAILURE
UPS FAILURE ON PARALLEL SYSTEM
BUS JA CRC FAILURE
BUS JB CRC FAILURE
BUS JA FAILURE
BUS JB FAILURE
CONNECTIVITY BUS FAILURE
EARTH LEAKAGE CURRENT
LOAD GROUND FAULT
CAN BUS FAILURE
RECTIFIER FUSES FAILURE
K4 CLOSING FAILURE
K4 OPENING FAILURE
BATTERY FUSES FAILURE
Parameters are lost and have been replaced with default values.
Please contact your ABB Service Center for intervention.
A blocked DSP on the Control board causes this alarm and consequently the shut-down of Rectifier and Inverter and the opening of K3.
The Master Unit detected the Slave Unit missing on the communication bus even though “Q1 – UPS output switch” is still closed.
The parallel communication bus system is subject to high errors rate on channel JA.
The parallel communication bus system is subject to high errors rate on channel JB.
There is an interruption in the channel JA of the parallel communication bus system.
There is an interruption in the channel JB of the parallel communication bus system.
The connectivity communication bus is faulty or interrupted.
The Unit has detected an earth leakage current above a configured threshold (typically 5% of the maximum rated input current).
Applicable to 3-wire (3ph+PE) distribution only.
The Unit has detected Load ground current above a configured threshold.
Applicable to 3-wire (3ph+PE) distribution only.
The Control Panel communication bus is faulty or interrupted.
The u-switch mounted on the Rectifier input fuses indicates a blown fuse and consequently it is shut down.
Clearance of this condition allows you to restart the
Rectifier.
K4 not closed despite a closing command being issued.
Signaled by auxiliary contact.
Rectifier cannot start.
K4 not open despite an opening command being issued.
Signaled by auxiliary contact.
Utility remains connected to Rectifier bridge.
This function, when enabled on input programmable relays
(“Service Code” required), warns the user about the external Battery Fuses failure or MCB opening, signaled by
NO free contact.
4116
4117
4118
4121
4146
4147
4150
4151
35/86
Code
4105
4106
4110
4115
4125
4126
4130
4140
4141
4142
4143
TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
Alarm Description
RECTIFIER OVERTEMPERATURE
RECTIFIER TRANSFORMER
OVERTEMPERATURE
RECTIFIER UTILITY OUT OF TOLERANCE
LOW BATTERY VOLTAGE
Temperature sensor indicates a situation of overtemperature on the Rectifier bridge.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start as long as this condition persists.
The temperature sensor inside the input transformer winding indicates overtemperature.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start as long as this condition persists.
Rectifier Input Utility is out of tolerance (voltage, frequency or phase sequence).
The Battery has been discharged and reached “stop operation” time-out (default 3 minutes) and the Inverter will be shut down.
It will restart automatically only when the Battery has recharged enough for a minimum runtime.
HIGH BATTERY VOLTAGE
BATTERY EARTH FAULT
BATTERY FAULT
HIGH DC RIPPLE
Dangerous high DC Voltage caused Inverter shut-down.
Inverter restarts automatically after Battery returns to floating voltage.
A leakage current to earth has been detected on the DC circuit.
During Battery test the voltage falls under the critical level
(depending setting parameters).
Battery test is stopped.
A high ripple is present in the Battery voltage.
Detection of high voltage on the DC-link.
HIGH DC-LINK VOLTAGE
The Rectifier, Booster and Inverter will switch off for protection purposes.
The Rectifier may only be switched on again if the DC-link’s voltage value falls below 430Vdc.
4 th LEG CONTROL SATURATION (Imax) The current in the fourth leg has reached its highest value.
TURN ON RECT. OR SHUTDOWN UPS
RECTIFIER CONTROL FAILURE
ISMAX DETECTION RECTIFIER
RECTIFIER CURRENT MAX
BOOSTER/BATTERY CHARGER
CURRENT MAX
4TH LEG DRIVER FAILURE
BATTERY CHARGER DRIVER FAILURE
BOOSTER OVERTEMPERATURE
4TH LEG OVERTEMPERATURE
Rectifier and Inverter are OFF.
The DC power supply is discharging the Battery.
Rectifier must be restarted, or the Battery must be disconnected in order to avoid damage.
Rectifier Voltage hasn’t reached the set value (probably fault on regulation loop).
LED Rectifier on Control Panel is blinking.
After 3 IS-Max condition within the time frame specified in respective parameter, the Rectifier remains shut-down.
Will cause immediate shut-down of the Rectifier.
Based on the value inserted in the respective parameter.
Detection of maximum current in the Booster/Battery charger.
The Booster/Battery charger and Inverter will switch off for protection purposes.
The Booster’s driver indicates the presence of a defect which switches the power off.
The Battery charger driver indicates a defect, switching it off.
The temperature of the Booster bridge exceeds the machine’s set limit or the coil’s sensor is on.
The temperature of the 4 machine’s set limit. th leg’s bridge exceeds the
36/86
Code Alarm
TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
4301
4304
4305
4307
4308
4309
4310
4311
4312
4320
4321
4340
4400
4404
4405
4406
4410
4420
INVERTER FUSES
K7 CLOSING FAILURE
K7 OPENING FAILURE
INVERTER TRANSFORMER
OVERTEMPERATURE
DC FUSES FAILURE
DRIVER FAILURE
IGBT RECTIFIER DRIVER FAILURE
BOOSTER DRIVER FAILURE
INVERTER VOLTAGE OUT
OF TOLERANCE
ISMAX DETECTION
HIGH CURRENT SHARING
INVERTER CONTROL FAILURE
BYPASS FUSES FAILURE
K6 CLOSING FAILURE
K6 OPENING FAILURE
SSM FAILURE
BYPASS UTILITY OUT OF TOLERANCE
K3 CLOSING FAILURE
Description
The alarm signals an Inverter outlet fuses fault, causing it to switch off immediately.
It may only be manually switched on after the alarm has ceased.
K7 not closed despite a closing command.
Signaled by auxiliary contact.
Load will be supplied by Utility.
K7 not open despite an opening command.
Signaled by auxiliary contact.
Load will be supplied by Utility.
The temperature sensor of the Inverter Transformer indicates overtemperature.
Elapsed “stop operation” time, Inverter shut-down.
With Utility OK, Load is transferred on Utility.
Blown input DC fuse(s) F1 of the Inverter.
Inverter cannot be started as long as present.
An abnormal condition has been detected on one or more power modules of the Inverter (temperature or overcurrent).
Inverter shut-down and cannot be started as long as the alarm is present.
Indicates a failure on the driver board or the Rectifier IGBT bridge. The Rectifier is shut-down.
Driver Booster error signal.
Inverter Output Voltage is out of the tolerances ( ± 10%).
Inverter is switched OFF.
Detection of Inverter Bridge (Is) current limit causing the
Inverter OFF and automatic re-start.
After 3 times the Inverter switches-Off and it can be restarted manually.
A high exchange current value is detected between the UPS of the RPA Parallel System.
The “Slave” oscillator is not in synchronized with the
Master; thus causing the shut-down of its Inverter.
If after a restart the condition remains, the LED inside the
Inverter symbol on the panel will not light up, indicating that this Inverter cannot supply the Load anymore.
Auxiliary contact signal (normally closed) indicates that one fuse of the Bypass Utility (F16/17/18) is open.
K6 open despite a closing command being issued.
Signaled by auxiliary contact.
The Load cannot be supplied by Automatic Bypass.
K6 closed despite an opening command being issued.
Signaled by auxiliary contact.
A faulty current has been detected in the static-switch causing the opening of the contactor K6 for 10 seconds.
After 3 times K6 remains definitively open.
Only an ABB Service Technician can reset the alarm.
The Utility Bypass Voltage is out of the tolerances ( ± 10%).
K6 opens, synchronization with Utility is inhibited and transfer to Utility is blocked.
K3 open despite a closing command.
Inverter is switched OFF.
It can be restarted manually after recovery of the alarm condition.
4571
4581
4608
4681
4682
4683
4684
4685
4697
4698
4700
4955
4998
4999
37/86
Code
4421
4520
4522
4530
4531
4563
4570
4701
4702
4900
TLE Scalable Series 40 to 150 UL S1 UPS User Manual / REV-B
Alarm Description
K3 OPENING FAILURE
NO INVERTER POWER
FAN FAILURE
LOAD LOCKED ON UTILITY
LOAD ON UTILITY BY ERROR
DETECTOR
K3 not open despite an opening command.
Be aware the DC Capacitors could remain charged.
The Load supplied by Utility exceeds the Inverter power.
The Load remains supplied by Utility until the alarm stays ON.
The Fan Control Board indicates a malfunction of one or more ventilators.
Load is locked on Utility because 3 transfers on Utility have been detected in a short time (default 30 sec.).
The transfer will be free after a time defined in parameter
(default 30 sec.).
Load is transferred to Utility because the error detector detected a disturbance on the output voltage.
EMERGENCY OFF ACTIVATED
OVERLOAD
OVERLOAD: LOAD ON UTILITY
INVERTER AND UTILITY
NOT SYNCHRONIZED
ECO CONFIG FAILURE
Alarm after detection of an EPO (Emergency Power Off) from an external safety device connected on Customer Interface
Board. Consequently K4, K6, K7 open, Rectifier, Inverter and
SSM are switched Off.
The UPS system is in an overload condition > 105% on
Inverter, or > 150% on Utility.
With Utility unavailable, a sequence of “stop operation” starts. Time out depends on degree of overload.
With Utility Bypass supply available and Load > 115%, the
Load is transferred on Utility. Load will be transferred again automatically on Inverter when Load < 100%.
The voltages of Utility and Inverter are not synchronized, which causes the opening of K6.
The propagation of the eBoost / IEMi configuration to other
Units in an RPA Parallel System failed.
MAIN BOARD BATTERY CHANGE Notice to replace the Lithium Battery located on the Control
NEEDED Board.
DC CAPACITORS CHANGE NEEDED
AC CAPACITORS CHANGE NEEDED
FAN REPLACEMENT NEEDED
SERVICE MAINTENANCE OVERDUE
BATTERY OVERTEMPERATURE
Notice to replace the DC Capacitors.
Notice to replace the AC Capacitors.
Notice to replace the Fans.
Notice to do the Service Maintenance.
Detection of Battery overtemperature condition.
Only an ABB Service Technician can reset the alarm.
BATTERY POWER INSUFFICIENT
DC LOW
POWER SUPPLY BOARD FAILURE
LOSS OF REDUNDANCY
LOAD LOCKED ON INVERTER
OVERTEMPERATURE
LOAD OFF DUE TO EXTENDED
OVERLOAD
LOAD OFF DUE TO LOW BATT. OR
TEMP.
In case of Utility Failure, with the actual Load, the run time would be below stop operation time (default 3 minutes).
Battery voltage is at the lowest limit.
Inverter will remain Off until the Battery voltage reaches the value in parameter.
Detection of a failure on the Power Supply Board, in particular from the DC supply.
Can be enabled or disabled with respective parameter.
A time of lost redundancy superior than specified in respective parameter was detected.
The Load is locked on Inverter after 3 Load transfers within
30 seconds.
After time out (default 30 sec.) Bypass will be free.
An overtemperature condition has been detected on Inverter.
Elapsed “stop operation” time, Inverter shut-down.
With Utility OK, Load is transferred on Utility.
Load Off after time-out of “stop operation” for overload on
Inverter (time depending on the % of overload).
Load Off after time-out of “stop operation” with missing
Utility due to Battery low voltage or overtemperature condition.
advertisement
Related manuals
advertisement
Table of contents
- 6 Safety rules
- 8 Safety symbols and warnings
- 8 Cyber security
- 9 Layout
- 9 Layout TLE Scalable Series 40 to
- 10 Introduction
- 11 Description
- 12 Block diagram and main elements
- 13 Operation modes
- 13 Normal VFI Operation Mode (Voltage Frequency Independent)
- 13 SEM Operation Mode (Super Eco Mode)
- 14 Utility Failure Operation
- 14 Utility Recovery Operation
- 15 Automatic Bypass
- 16 RPA Parallel System operation
- 16 Introduction to the RPA Parallel System
- 17 Features of RPA Parallel System
- 17 System control
- 17 Synchronization
- 17 Load sharing
- 18 IEMi Operation Mode (option)
- 19 UPS paralleled on the same Battery
- 20 Service and technical support
- 20 Warranty
- 21 Recycling instructions
- 22 Control Panel
- 23 LCD screen
- 23 Home screen
- 24 Description of the selection keys
- 25 Description of the signaling LEDs
- 28 Measures
- 32 Events
- 34 Events (alarms and messages)
- 34 Alarms list
- 38 Messages list
- 41 Setup
- 47 Commands
- 51 RPA Parallel System
- 53 Operation
- 54 Procedures for single TLE Scalable Series 40 to
- 54 Initial start-up of the TLE Scalable Series 40 to
- 58 Complete UPS shut-down
- 59 Restore to normal operation after “System shutdown” with Load not supplied
- 60 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 61 Procedures single TLE Scalable Series 40 to 150 functioning as Frequency Converter
- 61 Initial Start-up of the TLE Scalable Series 40 to 150 as Frequency Converter
- 65 Complete shut-down of the TLE Scalable Series 40 to 150 as Frequency Converter
- 66 Restore to normal operation after “System shutdown” with Load not supplied
- 67 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 68 Procedures for TLE Scalable Series 40 to 150 RPA Parallel System
- 68 TLE Scalable Series 40 to 150 RPA Parallel System start-up
- 73 Separate a UPS Unit from the RPA Parallel System (System Redundancy)
- 75 Reconnect a UPS Unit to RPA Parallel System
- 77 Complete RPA Parallel System shut-down
- 78 Restore to normal operation after “System shutdown” with Load not supplied
- 80 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 82 Options
- 82 Connectivity options
- 82 Options in UPS cabinet
- 82 Options in additional cabinets
- 83 Maintenance
- 83 Service check
- 83 Fans and ventilation
- 83 Other components with limited lifetime
- 84 Battery
- 84 UPS room conditions and temperature
- 84 Preventive maintenance program
- 85 Notes
- 85 Notes Form